| 1 | Supply,Installation,Testing & Commissioning of LT Control Panel board(i) Fabrication with Powder Coating Colour(ii) 250Amps FP MCCB with E/H & S/T - 1 Pc(iii) Volt Meter - 1 Pc(iv) Amps Meter - 5 Pcs(v) Volt Selector Switch - 1 Pc(vi) Amps Selector Switch - 3 Pcs(vii) 250/5 CT - 3 Pcs(viii) 150/5 CT - 6 Pcs(ix) 50/5 CT - 2 Pcs(x) Heat Meter - 1 Pc(xi) Indicator Lamp - 15 Pcs(xii) On/Off Push with Element - 8 Pcs(xiii) On/Off Selector Switch - 2 Pcs(xiv) 160 Amps. TP MCCB with E/W & S/T - 2 Pcs(xv) MNX95 Contactor - 2 Pcs(xvi) 30-50 Overload Relay - 2 Pcs(xvii) 16А ТР МССCB with E/H & S/T - 1 Pc(xviii) 32A TP MCCB with E/H & S/T - 1 Pc(xix) MNX12 Contactor - 1 Pc(xx) MNX25 Contactor - 1 Pc(xxi) 4.5-7.5 Overload Relay - 1 Pc(xxii) 14-23 Overload Relay - 1 Pc(xxiii) 1 No. + 1 Nc Add On Block - 4 Pcs(xxiv) Terminal - 4 PcsRef : Market analysed rate |
| 2 | Repairing,servicing of substation (Transformer, HT & LT OCB) incl supply of Transformer oil150 KVA 6600/435 Volts Tru volt make indoor type transformer thoroughly servicing & all Gaskit packing replace with new packing setting. At the same transformer old condemned oil draned as require new Transformer Oil refilling approx. 290 Ltrs. (1 Barrel) only Labour chargesRef : Market analysed rate |
| 3 | Repairing,servicing of substation (Transformer, HT & LT OCB) incl supply of Transformer oil Supply of new 1 Barrel Transformer OilRef : Market analysed rate |
| 4 | Repairing,servicing of substation (Transformer, HT & LT OCB) incl supply of Transformer oilGaskit, Orring, Silicone GelRef : Market analysed rate |
| 5 | Repairing,servicing of substation (Transformer, HT & LT OCB) incl supply of Transformer oil6.6 KV 400 Amps. H.T. Oil Circuit Breaker \" BECOLORY\" make thoroughly servicing necessary repairing old condemned oil drained & new oil refilling before heating & filtering complete labour charges.Ref : Market analysed rate |
| 6 | Repairing,servicing of substation (Transformer, HT & LT OCB) incl supply of Transformer oilAt the same O.C.B. new oil supply (Make-MEI) Ref : Market analysed rate |
| 7 | Repairing,servicing of substation (Transformer, HT & LT OCB) incl supply of Transformer oil400 Amps. 415 Volts. MEI make L.T. Oil Circuit Breaker thoroughly servicing necessary repairing as required contract blazing old condemned oil refilling before heating & filtering complete labour charges. Ref : Market analysed rate |
| 8 | Repairing,servicing of substation (Transformer, HT & LT OCB) incl supply of Transformer oilNew Transformer Oil SupplyRef : Market analysed rate |
| 9 | (i) Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded \"FR\" PVC insulated & unsheathed copper wire (Brand approved by EIC) in suitable size PVC casing-capping (Precision make) with 1x22/0.3 (1.5 sqmm) single core stranded \"FR\" PVC insulated & unsheathed copper wire for ECC, incl. necy. fittings etc. to light/fan/call bell point with Modular type switch (Brand approved by EIC) fixed on Modular GI / PVC switch board with top cover plate on wall incl. mending good damages to original finish. [PVC casingcapping and Switch board both on surface]Ref : PWD/Elec.Works/2017/Page -E21/ I -1(b). |
| 10 | (ii) Distribution Wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm)single core stranded \"FR\" PVC insulated & unsheathedcopper wire (Brand approved by EIC) in suitable size PVCcasing-capping (Precision make) with 1x22/0.3 (1.5 sqmm)single core stranded \"FR\" PVC insulated & unsheathedcopper wire for ECC, incl. necy. fittings etc. with S & F 6A 5pin Modular type plug socket and switch (Brand approved byEIC) fixed on 4 Module GI switch board with 3/4 Module topcover plate flushed in wall incl. necy. connection makingearthing attachment, painting and mending good damages tobuilding works [PVC casing-capping on surface and Switchboard concealed]Ref : PWD/Elec.Works/2017/Page -E22/ I -6(a). |
| 11 | Wiring in 1.1 KV grade single core stranded \"FR\" PVCinsulated & unsheathed copper wire (Brand approved by EIC)of following sizes in 25mm PVC casing-capping (Precisionmake) incl. necy. PVC clips, fittings etc.2 x 22/0.3 (1.5 sqmm) + 1 x 22/0.3 (1.5 sqmm)Ref : PWD/Elec.Works/2017Page -E11/I- 1. |
| 12 | Wiring in 1.1 KV grade single core stranded \"FR\" PVCinsulated & unsheathed copper wire (Brand approved by EIC)of following sizes in 25mm PVC casing-capping (Precisionmake) incl. necy. PVC clips, fittings etc.2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) Ref : PWD/Elec.Works/2017Page -E11/I- 1. |
| 13 | Wiring in 1.1 KV grade single core stranded \"FR\" PVCinsulated & unsheathed copper wire (Brand approved by EIC)of following sizes in 25mm PVC casing-capping (Precisionmake) incl. necy. PVC clips, fittings etc. 2 x 56/0.3 (4 sqmm) + 1 x 36/0.3 (2.5 sqmm)Ref : PWD/Elec.Works/2017Page -E11/I- 1. |
| 14 | Supplying & Fixing GI Modular Switch Board of the followingsizes complete with three no. suitable size Copper bar withholes (for Ph, N & E) fixed on bakelite/Hard Rubber insulatorover the MS welded chairs incl. top cover flushed in wall forhousing the board after cutting the brick wall incl. makingearthing attachment, painting and mending good damages tobuilding works(i) 12 Module Ref : PWD/Elec.Works/2017/Page -E-17/ I -1(d). |
| 15 | Supplying & Fixing GI Modular Switch Board of the followingsizes complete with three no. suitable size Copper bar withholes (for Ph, N & E) fixed on bakelite/Hard Rubber insulatorover the MS welded chairs incl. top cover flushed in wall forhousing the board after cutting the brick wall incl. makingearthing attachment, painting and mending good damages tobuilding works(ii) 6 Module Ref : PWD/Elec.Works/2017/Page -E-17/ I -1(d). |
| 16 | (i) Supply & Fixing 240 V 6 A Modular type switch (Brandapproved by EIC) on existing GI Modular type switchboard having top cover plate and making necessaryconnections as requiredRef : PWD/Elec.Works/2017/Page -E-17/ I -3(a) |
| 17 | (i) Supply & Fixing 240 V, 6A, 5 pin Modular type plugsocket (Brand approved by EIC), without switch & plugtop, on existing GI Modular type switch board with topcover plate and making necy. connections with PVC Cuwire and earth continuity wire etc.Ref : PWD/Elec.Works/2017/Page -E-17/ I -4(a) |
| 18 | Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts.long and 1 x 4 SWG GI (hot Dip) wire (4 Mts.long), 13 mmdia x 80 mm long GI bolts, double nuts,double washers incl. S&F 15 mm dia GI pipe protection (1 Mt.long)to be filled with bitumen partly under the ground level and partly above groung level driven to an average depth of 3.65 Mts.below the ground level. By ISI-Medium G.I Pipe. Ref: PWD/Elec.works/2017/P-G-1/I-2(a) |
| 19 | Connecting the equipments body to earth busbar including S&F 20 mm x 3 mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipments incl. drilling holes, with bolts, nuts, washers etc. Ref: PWD/Elec.works/2017/P-G-3/I-5(c) |
| 20 | Supply and Installationof Split type room air conditioning machine of following tonnage capacity 3 star rating fifled with rotary crompresser and cooling capacity min. 6000 k cal/Hr., minimum discharge air flow 800cum mtr, 800EER ( W/W) 2.7-2.89. (Rates are inclusive of extra refrigerant pipe drain pipe connecting cable) up to the satisfaction of the EIC.1.5 Ton (Make : Hitachi) 3 star non-inverter type Ref : Irrigation & Waterways/Mech Elec. Works/2022/P-118/I-5.3 H.8.0.3 |
| 21 | Supply & Fixing 240 V, 25 A, Modular type starter (Brand approved by EIC) with 25A Modular switch type DP MCB (CCurve) and 4 Module GI Modular type switch board with 4 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cuwire and earth continuity wire etc. Ref : PWD/Elec. Works/2017/Page - E-19/ I -17. |
| 22 | Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good thedamages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment (i) 8 wayEnclosure (LTTD08N)Make: L&TRef: PWD/ Elec. works/ 2017/P-D10/I-14 |
| 23 | Supplyinstallationtestingandcommissioningof following capacity geyser 5 star rated storage water heater with advanced 3 level safety For 15L-capacity Ref : Irrigation & Waterways/Mech Elec. Works/2022/P-118/I-5.3 H.6.2 |
| 24 | Supply of 1.1 KV Grade , PVC insulatedarmoured cable with AL conductor as perIS-7098(PART-1)/1988Cable size(4 c x 16 sqmm)Make:Havells/Gloster/Polycab or equivalent Ref: UD&MA/ Elec.-Mech works/ 2018/P-11/I-B1 |
| 25 | Laying of cable on wall/surface including S & F MS clams with earthingattachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. asnecy., mending good damages and painting.Cable size(4 c x 16 sqmm) Ref: PWD/ Elec.works/ 2017/P-F1/I-2(b) |
| 26 | Supplying and fixing compression type gland complete with brassgland, brass ring & rubber ring for dust & moisture-proof entry ofXLPE/PVC armoured cable. Cable size(4 c x 16 sqmm) Ref: PWD/ Elec.works/ 2017/P-F4/I-7© |
| 27 | Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materialsCable size(4 c x 16 sqmm)Ref: PWD/ Elec. works/ 2017/P-F5/I-8(b)(xii) |
| 28 | Add @ 18% GST |
| 29 | Add @ 1% Labour Cess |