| 1 | Supply, erection, embedment testing and commissioning of following size flush mounting new VTPN DB double door enclosure withPhase, Neutral and Earth Bus and interconnecting all wires. The scope of work includes box embedmentby wall cutting, all civil works for neat finishing and as directed by engineer-in-charge. All masonary works shall be neat finishing with existing brick wall. The scope of work includes removal of existing DB\"s, other connectionsand installation of new DB with all masonary works with neat finishing as directed by Engineer In-charge. |
| 2 | Supply and erection of DB TPN - VTPN 6 Way (6 Plus 18) with metal door. Incomer - 1 No, 63A FP MCB out going - 18 nos, 6 - 32A SP MCB. |
| 3 | Removal of existing PDBand embedment, testing and commissioning of existing VTPN DB double door enclosure with phase, Neutral, copper busbars, neutral and earth bus with all terminations and earthing suitable for existing wirings. The scope of work includes removal of existing DB and includes box embedmentby wall cutting, all civil works for neat finishing and as directed by engineer-in-charge. |
| 4 | Supply, embedment testing and commissioning of following size flush mounting new VTPN DB double door enclosure withPhase, Neutral and Earth Bus and interconnecting all wires with necessary civil masonary works as per detailed specifications and as directed by the Engineer-in-charge. All masonary works shall be neat finishing with existing brick wall. The scope of work includes removal of existing DB\"s, other connectionsand installation of new DB with all masonary works with neat finishing as directed by Engineer In-charge. Incomer:1 no , 32 / 40 A , 2 Pole RCBO, 30 mA. Outgoing ; 6A-20A , SPMCB, C series as required -4 no |
| 5 | Removal of existing DB and embedment, testing and commissioning of existing SPN DB 250V, single phase, HORIZONTAL metallic double door DB,copper busbars,neutral link and earth link with all terminations and earthing suitable for existing wirings. The scope of work includes removal of existing DB all connections with all masonary works and includes box embedmentby wall cutting, all civil works for neat finishing and as directed by engineer-in-charge. |
| 6 | Laying, testing and commissioningof1100V gradefollowing sizes HR PVC /XLPE insulated and PVC sheathed Armoured Cu / Alu. UG cables / Armoured jelly filled telephone cables including taking materials from the store,necessary cabling works as specified in section-V. Note: The required cables will be supplied at free of cost. |
| 7 | In build up trenches, on walls with proper clamping on poles and through embedded pipes on floor / trenches including only laying of new cables and fixing of all the material as per the scope of work as directed by Engineer In-charge. (Laying, testing and commissioning charges only) |
| 8 | 3.5C x 70 sq mmALUMINIUMconductorcable |
| 9 | 3.5C x 50 sq mmALUMINIUMconductorcable |
| 10 | 3.5C x 35 sq mmALUMINIUMconductorcable |
| 11 | 3C x 2.5 sq mm COPPERconductor cable |
| 12 | In ground including earth work excavation brick cover on top and sides, sand cushion etc. in all type of soil for cable trenches to lay various size cables. Back filling the same in to original Level, consolidating and removing of excess soil only for laying of new cables as per the specification is included in the scope of works as directed by engineer-in-charge.(Laying, testing and commissioning charges only) |
| 13 | 3.5C x 70 sq mmALUMINIUMconductorcable |
| 14 | 3.5C x 50 sq mmALUMINIUMconductorcable |
| 15 | 3.5C x 35 sq mmALUMINIUMconductorcable |
| 16 | 3C x 2.5 sq mm COPPERconductor cable |
| 17 | Laying, testing and commissioningof1100V gradefollowing sizes HR PVC/XLPE insulated and PVC sheathed flexible Cu cables includingnecessary cabling works. In build up trenches, on walls with proper clamping through embedded pipes on floor / trunches including only laying of new cables for cassette AC units as per the scope of work as directed by Engineer In-charge. Note: The required cables will be supplied at free of cost. |
| 18 | 3C x 4 sq mm COPPER flexible conductor cable |
| 19 | 3C x 2.5 sq mm COPPER flexible conductor cable |
| 20 | Endterminationofthefollowing 1100 V grade HR PVC insulated Armoured Copper/ Aluminium conductorUG cables including supply of single compression heavy duty cable gland, crimping lugs and gland earthing etc. as directed by the engineer in charge( Aluminium socket for aluminium cable and copper socket for copper cables ) |
| 21 | 3.5C x 70 sq mmALUMINIUMconductor cable |
| 22 | 3.5C x 50 sq mmALUMINIUMconductor cable |
| 23 | 3.5C x 35 sq mmALUMINIUMconductor cable |
| 24 | 3C x 2.5 sq mm COPPERconductor cable |
| 25 | Earth work excavation in all type of soil for cable trenches to lay various size cables. Back filling the same in to original Level, consolidating and removing of excess soil as per the specifications included in the scope of works as directed by engineer-in-charge. |
| 26 | Supply and fixing of following specified rated MCB breaker and metal sheet enclosures with earthing. The scope of work includes box embedmentby wall cutting, all civil works for neat finishing and as directed by engineer-in-charge. |
| 27 | 63 A, 4 Pole,C Series , 10 KA, 415 V MCB with Metal box enclosure |
| 28 | 32 A, 4 POLE, C Series, 10 KA, 415 V MCB with Metal box enclosure |
| 29 | 32 A, 2 POLE, C Series, 10 KA, 250 V MCB with Metal box enclosure |
| 30 | SITC of Split and Cassette AC units and its copper pipelines |
| 31 | SITC of 2.0Tr capacity, 3 / 4 star rated inverter model Split AC units with indoor and outdoor copper coils ( all copper ), all accessories including outdoor stand, CPVC drain pipe, CU pipe, copper wires and completion of the work including it’s core cutting work suitable for the site condition and as directed by enginner in charge. |
| 32 | SITC of 2.0Tr capacity, 3 / 4 star rated inverter model Cassette AC units with indoor and outdoor copper coils ( all copper ), all accessories including outdoor stand,CPVC drain pipe, CU pipes, copper wires and completion of the work including it’s core cutting work suitable for the site condition in the existing false ceiling and as directed by enginner in charge. |
| 33 | Additional copper pipelines between indoor and outdoor copper coils as directed by Engineer In-charge. |
| 34 | Supply and wiring for lights / fans /sensors / Power point with 1100V grade FRLS insulated copper conductor wires in existing concealed/ ExposedPVC / Metal conduitsas per the detailed scope of work, includingsupply of Wires, switches/ sockets, termination of copper wires at either end by crimping including supply of PVC Sleeves / Ferrules, Copper Crimping Lugs and connecting the wires to various switches, sockets, etc. including testing and commissioning as per the detailed specification as directed by Engineer In-charge. |
| 35 | Wiring for Light/Sensor/Fan Points with 2 Runs of 1.5 Sq.mm (22/0.3) copper wires for Phase & Neutral and 1 Run of 1.5 Sq.mm (36/0.3) copper wire for Earth from switch box to Primary light/sensor/fan point through Control Switch Box including 6A switch as directed by Engineer In-charge. |
| 36 | Wiring for Power point with 3 Runs of 2.5 Sq.mm (36/0.3) Copper wires for Phase & Neutral and Earth from MCB Distribution Board to Power point through Control Switch Box including 2x6A modular switch & 2x5 pin, 6A shuttered type Socket with Modular Plate as directed by Engineer In-charge. |
| 37 | Wiring for AC point with 2 Runs of 4 Sq.mm (56/0.3) Copper wires for Phase & Neutral and 1 Run of 2.5 Sq.mm (36/0.3) copper wire for earth from MCB Distribution Board to AC point including 25A switch as directed by Engineer In-charge. |
| 38 | Supply, laying, connecting and commissioning of following size FRLS copper wires in existing PVC conduits / trunking arrangements with necessary end terminations and earthings in wall / ceiling with necessary supports / clamps and screws etc. from various DB\"s to the eqipments/ power points. The scope of work consist new wiring and termination with existing wires by professinal grade soldering joinds suitable for site condition and as directed by engineer-in-charge. |
| 39 | 2 x 4.0 sqmm + 1 x 2.5 sqmm CU FRLS wires |
| 40 | 2 x 2.5 sqmm + 1 x 1.5 sqmm CU FRLS wires |
| 41 | 2 x 1.5 sqmm + 1 x 1.5 sqmm CU FRLS wires |
| 42 | Supply, wiring and termination of Telephone point with 1 run of 0.5 mm dia, PVC insulated, twin twisted, two pair, tinned copper wire from Telephone krone junction box placed near lift to each room Telephone point sockets in existing open / concealed conduit / PVC Trunking includes supply of new wire and 1 no modular Jack type Telephone Socket cum Shutter with 1/2m metal box and front plate with neat end terminations as directed by Engineer In-charge. |
| 43 | Supply, laying and termination of 1 run of Cat 6 twisted UTP Cable in existing open / concealed PVC Conduits from network switch placed in the Main building hubs to all the rooms communication outlets including terminations, labelling and supply of Cat 6 communication socket (RJ-45) with 2m metal box front plate as directed by engineer in charge. |
| 44 | Supply, Installation, testing and commissioning of approved make modular type metallic boxes, switches, sockets, Step type Fan regulators, base plates, cover-plates, dummy plate etc. as directed by engineer in charge. The removal of existing flush type boxes and other accessories from the wall and supply and fixing of new boxes and accessories with neat finishing suitable for the walls including required civil finishing works are included in the scope of the works. (Refer section-V for more details) as directed by Engineer In-charge. |
| 45 | 6 / 10 A one way Switch |
| 46 | 16A one way switch with indicator |
| 47 | 6 / 10 A two way switch |
| 48 | 6 / 10 A 5 pin Shuttered socketuniversal type |
| 49 | 16 A 5Pin shuttered socket |
| 50 | One module dummy |
| 51 | 2 modular high speed fan regulator |
| 52 | 20A 3pin polycarbonate plug top |
| 53 | MODULAR METAL BOX( GI box 1.2 MM thickness ) |
| 54 | 1 / 2 module modular metal box |
| 55 | 3module modular metal box |
| 56 | 5 / 6module modular metal box |
| 57 | 7 / 8module modular metal box |
| 58 | MODULAR BASE PLATESANDFRONT PLATES |
| 59 | 1 / 2 module modular front plate |
| 60 | 3 module modular front plate |
| 61 | 5 / 6module modular front plate |
| 62 | 7 / 8module modular front plate |
| 63 | Supply and fixing of 1 no 20A 2module starter and 1no 25A switch assembled with 1 no 25A 2module socket assembled with 6 module front plate suitable for split air-conditioners including all end terminations and earthings as directed by engineer-in-charge. |
| 64 | Supply and laying of following size BIS PVC conduits for various wirings, modification including necessary accessories like all bends, junction boxes, elbows and tees etc. and completion of the work as directed by engineer-in-charge including chipping of walls / floors, laying of new conduits and cement plastering for neat workman ship suitable for concealed wiring as directed by Engineer In-charge. |
| 65 | 40/42mm dia Heavy duty Rigid PVC pipes |
| 66 | 32mm dia Heavy duty Rigid PVC pipes |
| 67 | 25mm dia Heavy duty Rigid PVC pipes |
| 68 | 19 / 20 mm dia Heavy duty Rigid PVC pipes |
| 69 | Supply and laying of following size BIS PVC conduits for various wirings, modification including necessary accessories like bend, junction boxes, elbow and tee etc. and completion of work as directed by engineer-in-charge suitable for open wiring as required with neat workman ship as directed by Engineer In-charge. |
| 70 | 40/42mm dia Heavy duty Rigid PVC pipes |
| 71 | 32mm dia Heavy duty Rigid PVC pipes |
| 72 | 25mm dia Heavy duty Rigid PVC pipes |
| 73 | 19 / 20 mm dia Heavy duty Rigid PVC pipes |
| 74 | Supply and laying of 100 mm x50 mm size commercial Dado Trunking PVC for variouswirings, modifications including necessary accessories like bend, elbow, tee and junction etc. and completion of work as directed suitable for open wiring as required. Refer list of preferable make before quote the rates as directed by Engineer In-charge. |
| 75 | LIGHT FITTINGS: Supply, Erection, Testing and commissioning of wall / ceiling / suspendedtype following light fittings, Fans and exhaust fans withnecessary accessories, support, fastners, bolt and nuts from ceiling and as directed by engineer-in-charge. Necessary flexible hose, adopter and enclosed connectors shall be provided to all the light fixtures. |
| 76 | Supply, installation, testing and Commissioning of Recess mounted luminaires. 36W, 3600 lm, 6500 K, Lamp Type LED and as directed by Engineer In-charge. |
| 77 | Supply, installation, testing and Commissioning of light fixtures Lumens ≥2100, Wattage ≤ 20, 6500K LED lamp with individual patti surface mounted luminaires or equivalent Lamp LED and as directed by Engineer In-charge. |
| 78 | Supply, installation, testing and Commissioning of Recess mounted luminaires. 18Watts, 6500K 1800 lumensor equivalent and Lamp Type LED and as directed by Engineer In-charge. |
| 79 | Supply, installation, testing and Commissioning of surface mounted round polycarbonate surface luminaires. 20Watts, 6500K, 1800 lumensor equivalent and Lamp Type LED and as directed by Engineer In-charge. |
| 80 | Supply, installation, testing and Commissioning of Surface mounted luminaires. 12W, 1200 lumens, ≥ 6K or equivalent and Lamp Type LED and as directed by Engineer In-charge. |
| 81 | Supply, installation, testing and Commissioning of 100watts led flood light fitting Weather proof with IP66,Short circuit, open circuit protection,Surge Protection upto 6 Kv, 6500k or equivalent Lamp LED as and directed by Engineer In-charge. |
| 82 | SITC of 35-40 W LED 6500K post top luminaries in the existing pole with clamps, SS bolt, screws, hardware\"s etc., suitable for site condition and as directed by engineer in charge. |
| 83 | SITC of 12W 6500K led Garden lights with its complete set including termination of cable, clamps, SS bolt, screws, hardware\"s etc., suitable for site condition and as directed by engineer in charge. |
| 84 | Supply and fixing of Recess typeHigh dense LED Strip lights, 12 mm wide, 6000 – 6500K, 12 watt / mt assembled in LED Aluminium profile with its all mounted luminaires for the power drives 5 – 6 mt interval suitable for the site condition and as directed by Engineer In-charge. |
| 85 | Supply, installation, testing and Commissioning Recess / surface mounted LED light fixtures Wattage 12W, 6500K false ceiling indirect CAVE LED luminairessuitable for the site condition and as directed by Engineer In-charge. |
| 86 | Supply and fixing of 72 watts, 230Volts rated power drives suitable for 5 – 6 mt interval LED strip lights for the indirect cave lights including necessary wirings and completion of the work suitable for the site condition and as directed by engineer-in-charge. |
| 87 | Supply and fixing of professional grade corporate Chandlier lights medium / High size LED / lamp model luminaires with all fixing accessories suitable for theentrance of thehall with good esthetic. (Reputed and professional grade) and as directed by Engineer In-charge. |
| 88 | Supply, Installation, testing and commissioning of 1200mm sweep, AC high speed, Copper winding corporate model decorative ceiling fan with its complete set including down rod from the roof, required clamps, bolts, screws, hardware\"s etc., as required suitable for the site condition and as directed by engineer-in-charge. |
| 89 | Supply, Installation, testing and commissioning of 400 mm dia decorative corporate model wall fans withON & OFF switch combined regulator with complete set and as directed by Engineer In-charge. |
| 90 | Supply and fixing of MS Grey colour exhaust fan, single phase, Heavy duty, Classic series, 300 – 305 mm dia / square, 1400rpm, including necessary frame work, air louvres, bolt and nuts etc., with neat workmanship and as directed by the engineer in-charge. |
| 91 | Supply and fixing of corporate model Telephone instrument with 16 digit caller id and speaker phone facility as required and as directed by the engineer in-charge. |
| 92 | Supply, Installation, Testing andcommissioning of telephone Krone box made by 16SWG MS with 20+20 krone, metal door and locking facility including necessary end terminations and krone to krone connecting wires and as directed by the engineer in-charge. |
| 93 | Supply and installation of Modular DIN racks forhousingjack panel and computer switching accessories and as directed by Engineer In-charge. |
| 94 | 12U height wall mounting rack |
| 95 | 24 port jack panel |
| 96 | EARTHING |
| 97 | Supply installation and testing of maintenance free earthing system (1x10’ x 5/8” copper bonded steel rod, 22kg Ground enhancing material (GEM) ) as per the IS:3043 including RCC chamber and RCC cover slab. (Refer sec V) and as directed by Engineer In-charge. |
| 98 | Supplying and running of 8 SWG electrolytic grade copper earth conductor for grounding with necessary clamps, bolts,nuts and washers etc., suitable for the site condition and as directed by Engineer In-charge. |
| 99 | 25 x 3mm electrolytic grade tinned copper flat for earthing and as directed by Engineer In-charge. |
| 100 | MS ITEMS : |
| 101 | Supply, Fabrication and Erection of Rust proof, HOT- DIPPED GALVANIZED Fabrication works by using various sizes channels / L angles to reinstall variouselectrical power and lighting main panelsincluding welding works, fasteners worksand painting touch up to lift the panels and as directed by engineer in charge. |
| 102 | Supply and fixing of 3mm thick approved make and colour Hylam sheet switch box cover with neat edge finishing as required and completion of the work with brass cup washers and brass screws and as directed by engineer in charge. |
| 103 | Supply and installation of LT cable routeCEMENT SLAB marker made by RCC masonry works by using Steel rod with size 300 x 75 x 600 mm constructed cement slabwith adequate interval and finishing with all soil removal, yellow paint, letters by red marking and soil filling works including required PCC civil works as directed by Engineer In-charge. |
| 104 | Supply, cleaning the floor, proper pasting and installation of following insulating mat as per specification. (Refer Section-V for more technical details) and as directed by Engineer In-charge. |
| 105 | 2 mm thick Insulating Mat, Proof Voltage Tested upto 10KV, confirming to IEC 61111 |
| 106 | Rewiring of existing wiring: |
| 107 | Re-wiring for Light/Sensor/Fan Points with 2 Runs of 1.5 Sq.mm (22/0.3) with existing copper wires for Phase & Neutral and 1 Run of 1.5 Sq.mm (36/0.3) copper wire as required as per the site conditions and as directed by Engineer In-charge. ( Lot no.1- Admin wing at Ground floor, Lot no.2- Student wing and Director Office at 1st floor, Lot no.3-Student wing West at 1st floor ) |
| 108 | Re-wiring for existing Power point with 3 Runs of 2.5 Sq.mm (36/0.3) with existing Copper wires for Phase & Neutral and Earth from MCB Distribution Board to Power point through Control Switch Box as required as per the site conditions and as directed by Engineer In-charge. |
| 109 | Re-wiring for AC point with 2 Runs of 4 Sq.mm (56/0.3) with existing Copper wires for Phase & Neutral and 1 Run of 2.5 Sq.mm (36/0.3) copper wire for earth from MCB Distribution Board to AC point as required site conditions and as directed by Engineer In-charge |
| 110 | Removal of existing item: The following electrical item placed in Admin building to be removed and as directed by engineer in charge before start the revamp electrical work of this building. This item to be handed over to department before start the electrical work. (Contactors are requested to quote their rates after completion of their site inspection and its compulsory) |
| 111 | Removal of all LDB’s and PDB’s unwanted wires, all modular switch boxes and plug points etc., placed in entire existing building to be reinstalled in the existing place with brick work wall cutting, embedment of DB’s and necessary masonary works suitable for the site condition with neat workmanship and as directed by Engineer In-charge. ( Lot no.1- Admin wing at Ground floor, Lot no.2- Student wing and Director Office at 1st floor, Lot no.3-Student wing West at 1st floor ) |
| 112 | Removal of all electrical light fixtures, AC wirings, fans, conduits casing n’ capping and other all electrical equipments placed in entire Admin building as directed by Engineer In-charge. ( Lot no.1- Admin wing at Ground floor, Lot no.2- Student wing and Director Office at 1st floor, Lot no.3-Student wing West at 1st floor ) |
| 113 | Removal of existing air conditioning items: The following air conditioning item placed in Admin building to be removed and as directed by engineer in charge before start the air conditioning installation work of this building. This items to be handed over to department before start the installation work. (Contractors are requested to quote their rates after completion of their site inspection and its compulsory) |
| 114 | Removal of existing split AC indoors, outdoors, indoor to outdoor electrical control cables, copper pipes with insulation and its outdoor stands and it is including shifting to store room (location: main building ground floor office area, 1st floor East PDF wing, Director’s office and 1st floor JRF/SRF wing) and as directed by Engineer In-charge. |