| 1 | SCHEDULE \"A\" PART -I Taking down carefully unserviceable aluminium point wiring (light, fan, socket bell or power) complete, (fittings such as switches, ceiling rose lamp holder, regulators, sockets, pendants) stackingat site and keeping in safe custody for taking credit complete all as specified & directed |
| 2 | Taking down ceiling fan any sweep, removing blades ,cleaning the fan completely for dust and dirt and hanging the same back to its original positions including connecting with three core flexible copper wire to ceiling rose etc after the completion of the point wiring including replacement of old unserviceable fan hook, rubber pad, nut bolts and washers etc, complete all as specified and directed |
| 3 | Taking down existing energy meters, keeping aside safely & refixing the same in its original position after making functional & after completion of point wiring/sub main wiring, complete all as specified & directedNote:- Small items required for fixing the electric energy meter at site shall be provided by the contractor and cost for the same shall be deemed to be included in the quoted rates. |
| 4 | Taking down existing electric water heater, keeping aside safely & refixing the same to its original position afterservicing of the whole geyser/making functional and after completion of wiring work, complete all as specified & directed.Note: If any part found unserviceable during the refixing of water heater at site shall be provided by the contractor and cost for the same shall be deemed to be included in the quoted rates. |
| 5 | M&L for point wiring with PVC insulated sheathed 1100 volt grade FRLS cable with multi stranded copper conductor of size 1.5 Sq mm (Nominal area) drawn through and in existing PVC conduit of any size, fixing acessories inculding sunken anodised pressed terminal box not less than 1.2 mm thick covered with3 mm thick bakelite laminated sheet cover of suitable size with suitable size screws for mounting switches, sockets, regulators with and including 1.5 sqmm FRLS multi stranded copper conductordrawing as continuous earth wire connected to main earth and earth dollyforOne light/fan point /bell point controlled by one switchswitches/sockets/regulators complete all as specified & directed. |
| 6 | All as per Srl item N0 05 above but for one socket out let 5 Amp controlled by one switch on same board with other switch complete all as spd & directed |
| 7 | All as per Srl item N0 05 above for one socket out let 5 Amp controlled by one switch on independent board with other switchcomplete all as specified and directed |
| 8 | M&L for point wiring with PVC insulated sheathed 1100 volt grade FRLS cable with multi stranded copper conductor of size 1.5 Sq mm (Nominal area) drawn through and including non metallic rigid PVC conduit medium grade ISI markednot less than 20 mm dia ,concealed in wall and surface on ceiling with all conduit fittings & fixing acessories inculding sunken anodised pressed terminal box not less than 1.2 mm thick covered with3 mm thick bakelite laminated sheet cover of suitable size with suitable size screws for mounting switches, sockets, regulators with and including 1.5 sqmm FRLS multi stranded copper conductordrawing as continuous earth wire connected to main earth and earth dollyforOne light/fan point /bell point controlled by one switchswitches/sockets/regulators complete all as specified & directed. |
| 9 | All as per Srl item N0 08 above but for one socket out let 5 Amp controlled by one switch on same board with other switch complete all as spd & directed |
| 10 | All as per Srl item N0 08 above for one socket out let 5 Amp controlled by one switch on independent board with other switchcomplete all as spd & directed |
| 11 | S&Fswitch piano flush type 5 Amps single pole one way complete all as specified & directed. |
| 12 | S&F switch socket combination 2 in 1, 3 pin, 5 Amp flush type complete all as specified & directed. |
| 13 | S&Fswitch socket combination 2 in 1 5 pin 5 /15 Amps flush type complete all as specified & directed. |
| 14 | S&F of ceiling rose surface type 65mm x 50mm 2 to 3 terminal complete all as specified & directed. |
| 15 | S&F Step type fan regulator 300 watt, 230 volts, 50 HZ, AC. Supply complete all as specified & directed. |
| 16 | S&Fbell pushpiano type 5 Amps complete all as specified & directed. |
| 17 | S&F electric bell ding dong230 volt AC complete all as specified & directed. |
| 18 | M&L for Concealed Point wiring using FRLS PVC insulated sheathed multi strand copper conductor cable 1100 volt garde1.5 Sqmm FRLS PVC insulated sheathed multi strand copper conductorearth wire drawn IN and including PVC conduit ISI marked not less than 20 mm dia concealed in wall & surface on ceiling with all conduit fittings etc incl testing and making good to disturbed surface to match existing surface forOne light/fan point /bell pointcomplete all as specified &directed. (Note :- cost of modular boxes, Suitable modular switch base, frame & cover is included in quoted rate.) |
| 19 | All as per Srl item N0 18 above but for one socket out let 5 Amp controlled by one switch on same board with other switch complete all as spd & directed |
| 20 | All as per Srl item N0 18 above for one socket out let 5 Amp controlled by one switch on independent board with other switch complete all as spd & directed. |
| 21 | All as per item No 14 here in before but point wiring with 2.5sqmm FRLS multi stranded copper conductor cable for main circuit and 2.5sqmm cable as earth continuity conductor for one 15Amp socket out let controlled by one 15Amp switch on independat board complete all as specified & directed. |
| 22 | All as per item No 14 here in before but point wiring with 4 sqmm FRLS multi stranded copper conductor cable for main circuit and 4 sqmm cable as earth continuity conductor for controlled by two pin and earth plug and socket complete all as specified & directed. |
| 23 | S & F Modular snap switch SP one way 5/6 Amps suitable for 1 Module complete all as specified & directed. |
| 24 | S & F ModularBell push ,SP5/6 Asuitable for 1 Module complete all as specified & directed. |
| 25 | S & F Modular socket 5 pin 5/6 Amps suitable for 2 Module complete all as specified & directed. |
| 26 | S & F Modular snap switch SP one way 15/16 Amps suitable for 1 Module complete all as specified & directed. |
| 27 | S & F Modular socket 5/6 pin 15/16 Amps suitable for 2 Module complete all as specified & directed. |
| 28 | S & F Modular Fan step Regulator electronic, 120 watts 2 Module complete all as specified & directed. |
| 29 | S & F Modular blanking plates 1 module complete all as specified & directed. |
| 30 | S&F electric bell ding dong230 volt AC complete all as specified & directed. |
| 31 | S&F of ceiling rose 3 terminal complete PVC/Polycarbonate isolated boly complete all as specified and directed. |
| 32 | Supply in replacement,white / warm / cool white PVC LED fitting 1x20 watt complete with all accessories 230V 50 Hz complete as specified and directed. |
| 33 | Supply in replacement, white / warm / cool white LED channel of 5W, 230V frequency 50/60 Hzintegral sleek extruded polycarbonate LED channel with white acrylic cover, Power Factor not less then 0.9 as complete as specified and directed. |
| 34 | M&L LED light fitting white / warm / cool white 1x9W bulk head luminaries IP 65 complete with all accessories includingLED lamp 9 watt , connecting up with twin core twisted flexible copper conductor cable with suitable size of 230V 50 Hz complete as specified and directed. |
| 35 | S&F decorative wallmounted luminairein white / warm / cool white with & including 9 Watt LEDlamp complete all as specified and directed. |
| 36 | S &FLED white / warm / cool white sleek surface round ceiling mounteddecorative down lightfitting with PC cover suitable for 1x15 watt complete all as specified and directed. Cat Part No HPLLEDRB15 (CW)S |
| 37 | S&F for lamp holder PVC/polycarbonate type with back plate incl 7 Watt LED Bulb suitable for batten fittings complete all as specified and directed. |
| 38 | Supply & fixing of LED Bulb warm / white / cool whtie 9 Watt complete all as specified and directed |
| 39 | Supply and fixing swing typewall mounting fan 400 mm sweep single phaseAC 230/240V complete for wall mounting incl grouting, holding down bolts, nuts, andprovision of flexible copper conductor cable 3 core 23/0.0076 size from ceiling rose to fan. complete all as specified and directed |
| 40 | Supply & fixing PVC Exhaust fan 250/300 mmsweep single phaseAC 230/240V complete with louvers complete all as specified and directed |
| 41 | Supply & fixing Steel Body Exhaust fan 300 mmsweep single phaseAC 230/240V complete with louver, complete all as specified & directed. |
| 42 | Supply and fix house service static electronic temper proof energy meter ACsingle phase static energy meter of accuracy class 1.0 rating 10-60 A, 240 V ,50 Hz static watthour meter, complete all as specified & directed. |
| 43 | S&F MCB single pole 5 to 32 Amps 10 KA 240 volts \"C\" series complete all as specified & directed. |
| 44 | S&F MCBSPN 40 A to 63 A 10 KA 240 volts \"C\" series complete all as specified & directed. |
| 45 | S&F MCB single pole 40/63 Amps 10 KA 230 volts \"C\" series complete all as specified & directed. |
| 46 | S&FTPN 40 to 100 Amp 4Pole 16KA415 Volt with fixed magnetic and fixed thermal setting complete all as specified & directed. |
| 47 | S&F sheet metal enclosuredistribution board SPN 12 way230 V, 50 Hz double doorwith neutral, Earthing bar and din rail complete incl taking out existing UNSV DB with MCBs complete all as specified & directed. |
| 48 | S&F sheet metal enclosuredistribution board SPN 8 way230 V, 50 Hz double doorwith neutral, Earthing bar and din rail complete incl taking out existing UNSV DB with MCBs complete all as specified & directed. |
| 49 | S&F sheet metal enclosuredistribution board SPN 4 way230 V, 50 Hz double doorwith neutral, Earthing bar and din rail complete incl taking out existing UNSV DB with MCBs complete all as specified & directed. |
| 50 | S&FMCCB 125A 4Pole 16KA415 Volt with fixed magnetic and fixed thermal setting complete all as specified & directed. |
| 51 | S&FMCCB 100A 4Pole 16KA415 Volt with fixed magnetic and fixed thermal setting complete all as specified & directed. |
| 52 | S&F sheet metal enclosure double door for distribution board factory made for MCB DB load link TPN 4 way (when MCB\"s are to be used) with suitable size of busbar including complete,fixed flush in wall including chases wall for fixing DB and making goodthe distributed wall surfaces to match with existing specification including taking down all as directedby Engr-in-Charge at site incl taking out of exsing UNSV DB with MCBs. |
| 53 | Supply and fix electric water heater, storage type steel body with stainless steel inner tank and heating element upto 2 KW capacity 25 litre, BEE 5 Star rated complete with all accessories such as safety valve, thermostate, NRV, connection piece etc. complete all as specified & directed. |
| 54 | S&F sheet metal enclosure double door for distribution board factory made for MCB DB load link Vertical TPN 4 way including MCCB 125 Amps, 16 KA 230 V suitable for MCCB as incomer, 125 Amp,4 pole. (when MCB\"s are to be used) with suitable size of busbar including 125 A MCCB as incomer 16 KA complete,fixed flush in wall including chases wall for fixing DB and making goodthe distributed wall surfaces to match with existing specification including taking down all as directedby Engr-in-Charge at site incl taking out of exsing UNSV DB with MCBs, complete all as specified & directed. |
| 55 | M&L in replacement of sub main wiring with two single core FRLSPVC insulated unsheathed 1100 volts grade cable with stranded copper conductor of size 6 Sq mm drawing through and includingconcealed rigid non metallic PVC conduit medium grade ISI marked minimum 20 mm dia including one single core FRLS PVC insulated unsheathed 1100 volts grade cable with stranded copper conductor of size 6 sq mmas earth continuity conductorconnected to commen earth and earth dolly complete including taking down existing UNSV complete all as specified & directed. |
| 56 | M&L in replacement of sub main wiring with two single core FRLSPVC insulated unsheathed 1100 volts grade cable with stranded copper conductor of size 10 Sq mm drawing through and includingconcealed rigid non metallic PVC conduit medium grade ISI marked minimum 20 mm dia including one single core FRLS PVC insulated unsheathed 1100 volts grade cable with stranded copper conductor of size 10 sq mmas earth continuity conductorconnected to commen earth and earth dolly complete including taking down existing UNSV complete all as specified & directed. |
| 57 | S&F building security lightluminaries eenergy saving and envirnment friendly long life LED light of 25W made up of pressure die cast aluminium housing with acrylic cover as diffuser with IP66 protection and Impact resistanve of IK07, including MS Bracket light grade 25 mm dia, 1.2 m long bend in shape fixed on wall having an angle120 degree, fixed with and suitable size nuts, bolts and washers etc including taking down of existing light fitting and complete all as specified and directed. |
| 58 | M&L for earthing complete for bldgwith galvanized mild steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 meters below ground level) with top edge of earth plate not less than 1.5 meters below ground level connected to galvanized earth wire 4.00 mm diaby means of nuts, bolts, thimbles, chuck nuts, washers of GI or steel,PCC (concrete chamber of size 300 mm x 300 mm x 300 mm inside dimension) shall be PCC 1:3:6 type C-1 using 20mm graded stone aggregate with fair finish ,internal surface of concrete chamber shall be given 15mm thick plaster in CM 1:4, funnel with wire mesh of 22 gauge,80 mm thick PCC pit cover 320 mm x 320 mm of RCC 1:2:4 type B-1 using 20 mm graded stone aggregate reinforced with XPM, JALLI pit shall be filled withcharcoal dust and common salt all as shown in electrical plate No 3 of MES SSR Part-I (2009) as specified includingprovision of 15mm dia medium grade GI pipe for earth wire protection and 20 mm dia for watering complete ,all excavation andearth work & connecting the earthing to an earthing test point / main switch board as specified and testing on completion complete all as specified & directed. |