Repair/maint of DG Sets, AMF panels, earthing and certain E/M eqpts and plants including misc E/M repairs to installations at AF Station Jodhpur under 32 wing & day to day maintenance of internal electrification, light fittings/fixtures/accessories at certain OTM accns at AFS Mandore under AGE E/M, GE (AF) No.2 Jodhpur; 1 Periodical maintenance and inspection/checking of following size /capacity of DG sets and ensuring smooth functioning of DG sets and replacements of unsv parts of DG sets of following capacities : - Note:- Spare parts required shall be measured and paid separately . 2 15 KVA DG SET 3 20 KVA DG SET 4 35 /40KVA DG SET 5 62.5 KVA DG SET 6 75 KVA DG SET 7 160 KVA DG SET 8 320 KVA DG SET 9 Supply and fixing in Replacement bypass filter element with O ring of Kirloskar /Crompton greeves/Mahindra DG Sets as required at site as per make and modelfor the following capacities of DG Sets :- 10 15 KVA DG SET 11 20 KVA DG SET 12 35/40 KVA DG SET 13 62.5 KVA DG SET 14 75 KVA DG SET 15 160 KVA DG SET 16 320 KVA DG SET 17 Supply and fixing in Replacementluberication oil filter element with O ring of Kirloskar /Crompton greeves/Mahindra DG Sets as required at site as per make and modelfor following capacities of DG Sets:- 18 15 KVA DG SET 19 20 KVA DG SET 20 35 /40KVA DG SET 21 62.5 KVA DG SET 22 75 KVA DG SET 23 160 KVA DG SET 24 320 KVA DG SET 25 Supply and fixing in ReplacementAir filter element inner and outer as requiredfilter element at sitewith O ring ofKirloskar /Crompton greeves/Mahindra DG Sets as required at site as per make and model for following capacities of DG Sets:- 26 15 KVA DG SET 27 20 KVA DG SET 28 35/40 KVA DG SET 29 62.5 KVA DG SET 30 75 KVA DG SET 31 160 KVA DG SET 32 320 KVA DG SET 33 Supply and fixing in Replacementfuel filter element with O ring ofKirloskar /Crompton greeves/Mahindra DG Sets as required at site as per make and model for following capacities of DG Sets:- 34 15 KVA DG SET 35 20 KVA DG SET 36 35/40 KVA DG SET 37 62.5 KVA DG SET 38 75 KVA DG SET 39 160 KVA DG SET 40 320 KVA DG SET 41 Supply and fixing in Replacement of Fan beltofKirloskar /Crompton greeves/Mahindra DG Sets as per given sample for10 kva to 320 KVA DG Sets. 42 Taking of FIPfrom the Engine and Calibration of FIP (Fuel Injection Pump) 35 to 160 KVA DG Set Make : Ashok Leyland /Kirloskar / Cummins/Crompton Greaves Jyoti at admissible pressure including minor spares etc testing and refitting all as specified and directed. 43 Taking of FIPfrom the Engine and Calibration of FIP (Fuel Injection Pump) 320 KVA DG Set Make : Ashok Leyland /Kirloskar / Cummins/Crompton Greaves Jyoti at admissible pressure including minor spares etc testing and refitting all as specified and directed. 44 Supply and fixing in Replacement distilled water to be filled in batteries ,complete all as specified and directed by Engineer-in-charge. 45 Supply and fixing in Replacementignition switch with key in repair for DG sets of any capacities, complete all as specified anddirected by Engineer-in-charge. 46 Material & Labour for replacement of battery cable of size 40 sqmm PVC insulated multi stranded copper conductor singlecore cable with necessary lugs, complete all as specified anddirected by Engineer-in-charge. 47 Supply and filling in Replacementtop up coolent for DG set radiator 48 Supply and fixing in Replacement Water temperature gauge for 320 KVA DG set complete all as specified and as directed. 49 Supply and fixing in Replacement Water temperature gauge for 160 KVA DG set complete all as specified and as directed. 50 Supply and fixing in Replacement oil pressure gauge assembly for 40 KVADG set complete all as specified and as directed. 51 Supply and fixing in Replacement oil temperature gauge for 160 KVA DG set complete all as specified and as directed. 52 Supply and fixing in Replacement cable for Techno meter for 160/320 KVA DG set complete all as specified and as directed. 53 Supply and fixing in Replacement Techno meter assembly for 160/320 KVA DG set complete all as specified and as directed. 54 Supply and fixing in Replacement flexible braided hydraulic hose 5/8 dia x 600 mm length includingsuitable check nuts & washers, complete all as specified anddirected by Engineer-in-charge. 55 Supply and fixing in Replacement RPM metre with cable (0-3000 RPM),, complete all as specified anddirected by Engineer-in-Charge. 56 Supply and filling in Replacement lube oil20 W - 40 for Top up and filling up the oil in the sump after completely flushing the old oil out of the tank and cleaning of the tank for fresh filling, complete all as specified anddirected by Engineer-in-charge.Make : Castrol/Power Supreme 57 Supply and filling in Replacement lube oil SAE 15 W - 40 for Top up and filling up the oil in the sump after completely flushing the old oil out of the tank and cleaning of the tank for fresh filling, complete all as specified anddirected by Engineer-in-charge.Make : Castrol/Power Supreme 58 Supply and fixing in Replacement battery terminal heavy duty as per sample made of brass with bolts and washers all as required at site,, complete all as specified anddirected by Engineer-in-Charge. 59 Supply and fixing in Replacement complete 12 V180 AMPH maintenance free battery and initial charging complete including inbuilt charger including required electrolyte /distilled water etc and fixingas required at site to the concerned DG Set, complete all as specified anddirected by Engineer-in-charge. 60 Supply and fixing in Replacement of self starter assembly for DG set of 40 KVA 12 volts DC including, complete fixing and testing, complete all as specified anddirected by Engineer-in-charge.Make:-Lucas-TVS 61 Supply and fixing in Replacement of self starter assembly for DG set of 160 KVA 12 volts DC including, complete fixing and testing, complete all as specified anddirected by Engineer-in-charge.Make:-Lucas-TVS 62 Supply and fixing in Replacement Rubber hose set for DG set radiator by replacing the unserviceablehose set ,for40 KVA DG setcomplete all as specified as directed by Engineer-in-charge. 63 Supply and fixing in Replacement PLC system for DG sets of 35/40 KVA capacities , complete all as specified as directed by Engineer-in-charge. 64 Supply and fixing in Replacement PLC system for DG sets of 62.5 KVA capacities , complete all as specified as directed by Engineer-in-charge. 65 Taking out the radiator assembly from DG Set of capacity 40 KVA to 160 KVA for cleaning/servicing and cleaning the radiator externally/internally and reinstallation after carrying out the job work:- 66 (a) Externel Cleaning :- Removel of light deposits by using low pressure hot stream jet with addition of detergent and incase stuuborn deposits experienced the radiator to be immersed in a heated Alkali degreasent solution for 30 minutes and then washing off with hot water hose complete all as specified and directed 67 (b) Internel Cleaning:-Internel cleaning be done by prepration of solution of inhivited acidsolvent with fresh waterand circulation of acid solution in radiator for severel times descaling the acid solution by adding 700 gm of soda with 20 ltrs boiling water .Refining be done after pressure check complete all as specified and directed. 68 Supply and fixing in Replacementof turbo charger,160complete all as specified as directed by Engineer-in-charge.Make:- Holest or equivalent as approved. 69 Supply and fixing in Replacementof turbo charger,75complete all as specified as directed by Engineer-in-charge.Make:- Holest or equivalent as approved. 70 Material and labour for dismantling of radiator from engine taking it to work shop repair of leakage pipes, cleaning the radiator with cleaning agents, re-assembling to the engine completely to entingsatisfaction of Engineer-in-Charge 71 Inspection/checking of AMF panelof DG set of capacity 40 KVA to 75 KVA installed at various installations of any make and shape and rectify the defects, replacement of unserviceable part as required at site and cleaning of AMF panel as detecting during inspection or pointed out by users/department and carry outmaintenance , complete all as specified as directed by Engineer-in-charge.Note:- Spare parts required shall be measured and paid separately . 72 Inspection/checking of AMF panelof DG set of capacity 160 KVA to 320 KVA installed at various installations of any make and shape and rectify the defects, replacement of unserviceable part as required at site and cleaning of AMF panel as detecting during inspection or pointed out by users/department and carry outmaintenance , complete all as specified as directed by Engineer-in-charge.Note:- Spare parts required shall be measured and paid separately . 73 Supply and fixing in Replacement 4 Pole power contactor with AC coil 160 Amps, 3 phase 415 volt 50 HZ suitable for AMF panelscomplete all as specified as directed by Engr-in-ChargeMake:-Havells model No-IHPAC065500 74 Supply and fixing in Replacement engine start relay 12 volt DC suitable for AMF panels Complete all as specified as directed by Engr-in-ChargeMake:- Eagle Man/PIC 75 Supply and fixing in Replacement frequency meter 45 to 55 HZ AC 415 volt of size Sqmm suitable for AMF panelscomplete all as specified as directed by Engineer-in-Charge.Make:- AE/Premier. 76 Supply and fixing in Replacement selector switch for volt/ampere metre 415 volt four stage suitable for AMF panels Complete all as specified as directed by Engr-in-ChargeMake:- L&T/CONCORD/KAYCEE/C&S 77 Supply and fixing in Replacement cranking relay 12/24 volts DC 8/11 stage suitable for AMF panelscomplete all as specified as directed by Engineer-in-Charge.Make:- Eagle Man or equivalent as approved 78 Supply and fixing in Replacement indicator lamp assembly LED type with red/green/blue for phases R,Y,B suitable for AMF panels complete all as specified as directed by Engineer-in-Charge. 79 Supply and fixing MCCB in replacement of 100 Amps, 3 pole, 415 volts, 50 HZ, rupturing capacity 16KA, connection with proper size of thimbles complete including taking out defective/ unserviceable MCCB all as specified and directed. 80 Supply and fix MCCB in replacement with thermal magnetic release adustable type DN2-250D, 250A, 415 Volts 4 pole 36KA all as specified & directed. 81 Supply and fix MCCB in replacement with thermal magnetic release adustable type DN3-400D, 400A, 415 Volts 4 pole 36KA all as specified & directed. 82 Supply and fixing in replacement of on load change over switch 200 Amps 4 Pole 415 Volts housed in sheet metal enclosure complete all as specified and directed by Engineer-in-Charge. Make-Havelles/standared/Indo Asian. 83 Supply and fixing in replacement of on load change over switch100 Amps 4 Pole 415 Volts housed in sheet metal enclosure complete all as specified and directed by Engineer-in-Charge. Make-Havelles/standared/Indo Asian. 84 Supply and fixing in replacement off load change over switch 200 Amps 4 Pole 415 Volts complete all as specified and directed by Engineer-in-Charge.Make-Havelles/standared/Indo Asian. 85 Supply and fixing in replacement of off load change over switch100 Amps 4 Pole 415 Volts complete all as specified and directed by Engineer-in-Charge. Make-Havelles/standared/Indo Asian. 86 Supply and fixing of battery12 V, 150 AH complete all as specified and directed. Make :- Exide Xpress / Mico or equivalent. 87 M/L for Repairs to out door LTpanel including taking down for repair as follows :-( a )Supply and fixing of MS sheet 16 SWG( 1.6mm ) and fabrication of back side cover of LT panel including cutting to required size and shape fixing in position by bending, welding all as required for proper functioning of LT panel shutters including two coats of coats of synthetic enamel paint over a coat of red oxide.(b ) Supply and fixing of hinges , tee type stove enamelled black medium weight , cold rolled and mild steel 30 mm size and fixed door shutters ( c ) Supply and fixing of locking arrangement with MS sliding door bolts hasp and suitable for use with pad lock of size 200 mm( d ) Mild steel work conforming to Fe-410-0 or Fe-310-0 as in angle iron frame work , cut to size including bending and welding angles as necessary and re -fixing of MS sheet of panel including a shop coat of red oxide prime 88 Supply and fixing of copper thimbles using crimping tool for electrical connections with cable and connecting with suitable size of nuts / bolts and washers of size 120 sqmm to 185 sqmm LT cable size. 89 Supply and fixing of copper thimbles using crimping tool for electrical connections with cable and connecting with suitable size of nuts / bolts and washers of size 25 sqmm to 95 sqmm LT cable size. 90 Supply and fixing in replacementof under ground cable XLPE insulated, 1100 volt grade heavy duty armoured with standed aluminium conductor 4 core 16 sqmm laid in trenches/ duct/ pipe including all electrical connection with required lugs and nuts, bolts complete all as specified and directed by Engr-in-Charge. 91 All as per itme No 53.00 above but 4 core 25 Sqmm 92 All as per itme No 53.00 above but 4 core 50 Sqmm 93 All as per itme No 53.00 above but 4 core 70 Sqmm 94 All as per itme No 53.00 above but 4 core 150 Sqmm 95 All as per itme No 53.00 above but 4 core 240 Sqmm 96 All as per itme No 53.00 above but 4 core 300 Sqmm 97 Excavation in trenches in soft/loose soil not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth for route of cable and getting out complete all as specified and as directed by the Engineer-in-Charge. 98 Returning, filling in soft/loose soil including spreading, leveling, watering and well ramming, in layers not exc 25 cm complete all as specified and as directed by the Engineer-in-Charge. 99 Removingof surplus soil to a distance not exc. 50 meter and depositing where directed at a level not exc.1.5 metre above the starting point complete all as specified and as directed by the Engineer-in-Charge. 100 M/&L for stone slab 40 to 50 mm thick rough dressed Jodhpur stone slab cover in trenches for protection of cable 25 to 30 cm wide and not less then 50 cm in length laid dry abutting each other with gap between adjacent slab not exceeding 10 mm over sand cushioning all as specified and directed by Engr-in-Charge. 101 supply and laying of Local tibba dry sand cushioning and cover (8 cmthick layer of sand before laying of cable and 15 cm thick layer of sand after laying of cable)for protection of cable, material and labour complete all as specified and as directed by Engineer-in-Charge. 102 Material and labour in repair for earthing complete with copperplate electrode 60cmx60cmx3.15mm thick, buried directly in ground, vertically to a dpeth not less than 2.25 mtr deep below ground level with top edge of the earth plate at depth not lss than 1.5 mtr below ground level earth plate surrounded by 15 cm thick and packed layers of charcoal, dust and common salt, earth lead copper strip 20 x 3 mm by means of bolts, nuts, check-nuts and wahsers of galvanised iron and thimbles and of earth wire protected by galvanised iron pipe light grade 40mm bore and water pipe 20mm bore GI medium grade with funnel and wire mesh complete 1:3:6 type C-1 using 20mm graded stone aggregate in lieu of CI cover and frame etc all as specified and directed. 103 Dismantling of self starter and remove of defected parts and replace suitable for DG set of 35 to 160 KVA and fixing the same including testing.(Defective spares part to be paid seprately) 104 Supply only Solenoid Switch 105 Supply only Armature 106 Supply only Field coil copper 107 Supply only Carbon Brush 108 S&F fuel pipe from filter to FIP with benzo bolt as per sample suitable for DG sets upto 110 KVA complete all as specified and directed. Make:- Kirloskar, Mico 109 S&F self Starter 12V as per sample suitable for DG set 12v operated. Make:- Kirloskar, Locus. 110 S&F copper strip of size 20 x3 mm as earth continuity conductor buried in ground or fixed to wall/floor/ground provided with porcelain insulators space no less than 0.5 mtrs complete all as specified and directed. 111 Suppyling, installing, testing and commissioning in replacement of outdoor type factory made ,CRCA sheet ,thickness 3.15mm,platform mounted LT panel board to accommodate the following items and built upon angle iron frame suitable size compatmentalized design work ,dully powder coated with gray paint and suitable size of cable glands chromium plated and copper busbars TPN,400 Amps,415V,50Hz complete as following:-(i) MCCB 200 Amps,4 pole,36 Ka -01 (incoming)(ii) MCCB 100 Amps,4 pole,25 Ka -02 (outgoing)(iii) Voltmeter 0-500 V digital type with selector switch - 1 No.(iv) Amp meter 0-200 A digital type with selector switch -1 No.(v) fully automatic star delta starter suitable for 12 HP -02(vi) Indicating lamp LED RYB set of three with colour coding -1 No. 112 Routine maintenance of DG set of capacity 35 KVA to 320 KVA by carrying out the test check for belt tensioin,adjustment of valve clearance with clearance gap o 0.4 mm for both inlet and exhaust valve and adjustment of tapped with filer gauge,replacement of changing gear and Flywheel and oil,cleaning of injector/Nozzles and spray check,servicing of self starter by replacement of carbon bushes,Terminal wires including cleaning with vaccum cleaner to wipe out unwanted materials/dust from alternator and other minor repairs/servicing of Emgine complete all as specified and directed by Engineer-in-Charge. ( Make of engine Kirloskar/Greaves). 113 Taking down copper/aluminium point wiring for (light, fan, bell, socket power socket etc )complete including fixture and fittings such as switches,sockets lamp holder bracket light fittings tube light fittings, regulators, ceiling rose , mirror light fitting , ceiling light fitting, fancy light fitting , fall ceiling light fitting bell/ buzzerand removing materials to store for keeping in safe custody or for taking credit ( credit for above items should be made as per condition separately) and making good disturbed surfaces of wall floor etc. 114 M&LPoint wiring complete with 1.5 Sqmm single core multi standard copper conductor PVC FLRS insulated unsheathed cable in and incl PVC casing capping / PVC Conduit with accessories existing pressed steel terminal boxes (sunk in wall) including new 3.00 mm thick plastic laminated sheet top cover with 1.50 Sqmm insulated unsheathed PVC covered copper conductor for common earth and connecting to earth dolly for :- 115 One light point controlled by one one way switch 116 One fan point controlled by one one way switch 117 One bell point controlled by one bell push switch 118 One socket out let 5 Amps on the same board 119 One socket out 3 pin 5 Amps on the independentboard. 120 All as per item No77.00 above but with 2.5 Sq mm single core multi standard copper conductor cable for 6 pin 15 Amps socket out let on independent board. 121 S&F switch flush type 5 Amp, 240 V single pole one way ISI Marked. 122 S&F switch socket combination 2 in 1,5 Amps flush type 123 S&F switch socket combination outlet 6 pin ,6/16 Amps flush type 124 S&F ceiling rose, 3 Terminal Point/PVC/polycarbonate, isolated body. 125 S&F lamp holder , PVC /Polycarbonate type with back plate suitable for batten fitting complete with necessary wire connection etc. 126 S & F in replacementfor sheet metal enclosures distribution board where MCB to be used with 200 Amps rated bus bar CL-IP-43 240 V, 8 way single pole & neutral link 127 All as per itme No 84.00 abovebut 12 way 240 V, 128 All as per item No 84.00 above but 4 way 240 V, 129 M&L in replacement for MCB single pole 6-32Amps, 240 V . 130 M&L in replacement for MCB single pole & neutral 32 to 63 Amps, 240 V . 131 M&L in replacement for MCB triple pole & neutral 63 Amps, 240 V 132 S&F in replacement 20 W LED batten (1.2 m) made of CRCA sheet housing with a PC glossy diffuser and mounting accessories duly prewired connection having a nominal system lumen output of 2000 lumens at a minimum system efficacy of 105 lumens per watt and total power consumption not more than 19 watt including driver. It has a rated system life time of 40000 burning hours at L70 and should have a color temperature of 6500K, CRI>80, THD < 10% and PF > 0.95complete. Make - Crompton Cat No LCTLN-20-WW or equivalent in Philips/Wipro. 133 S&F in replacement LED Recessed full it luminaire with glare free uniform illumination with longer life and less maintance wattages in 2 ft x 2 ft not less then 100 lumen /watt complete all as specified and as directed. temperature of 6500K, CRI>80, THD < 10% and PF > 0.95complete. Make - Crompton Cat No LCTLRNE -36-FO-CDLor equivalent in Philips/Wipro. 134 S&F in replacement LED StudBulk Head 10 wattfixture perfect interior and exterier application within carparks, walkway, stairwells, carridoors, local authorities and housing accosiation as well ascommercial building including connectioncompleteall as specified and directed by Engineer in Charge. 135 S&Fin replacement elect bell AC 230 V single pole ISI Marked. 136 S&F in replacementsub main wiring with 2 run of 6 Sq mm single core copper conductor cable drawn through in rigid PVC conduit ISI marked with fitting and 6.0 Sq mm single core copper conductor cable for continues earth wire all as directed. 137 M& L in repairs for Earthing complete with galvanised steel earth plate electrode60×60cm.× 6mm thick, burieddirectly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate notlessthan 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion complete all as specified and as directed. 138 S&F in replacementmirror light fitting LED of 10 Watt 2 feet long complete 230V, 6000k rated CCT energy efficient with automatic ballast pen holders stsrters blocks ,diffusers complete with all accessories including tube internally prewired and including connecting with twin core twisted flexible copper cable complete all as specified and as directed.Make -orient model no-LBLN-10-C /bajaj/crompton. 139 Supply and fixing in replacement fan electronic regulator 300w step type all as specified and as directed by Engr-in-Charge. 140 M&L for taking down ceiling fan and refixing the same after repair replacement of unserviceable other parts like clamps, nut, bolt, washer and locking arrangement, rubber reel,flexible wire, canopy, shaft, capacitor etc. testing complete all as specified and directed by Engineer-in Charge .Note:- Replacement of unserviceable other parts like clamps, nut, bolt, washer and locking arrangement, rubber reel,flexible wire, canopy, shaft, capacitor etc. shall be measured & paid for separately. 141 1200 mm (48) sweep. 142 1400 mm (56) sweep. 143 All as per item No. 98.00 above but exhaust fans of following sizes:- 144 230 mm (9) sweep 145 300mm (12) sweep 146 380/400mm (12) sweep 147 Supply and fixingGun metal bush of ceiling fans any type of any sweep including cutting of grooves for fixing of bearing instead of bush any type/any size. 148 M & L for rewindingof burntCeiling fan by opening covers of ceiling fan ,remove the burnt winding ,cleaning the slots and rewinding the fan with super enammeled copper wire of same wire gauge,warnishing after windingall as directed by Engineer-in-charge . 149 M & L of rewinding of burnt Exhaust fan motor size of 300/400 mm sweep fans by opening covers by unscrewing nuts/screws ,cleaning the slots and rewinding the fan with super enammled copper wire of same wire gauge complete call as directed by Engineer-in-charge . 150 Supply and fixingball bearing of 1200 mm (48)/1400mm sweep make: NBC/SKF/National suitable for ceiling fan. 151 Supply and fixingball bearing of make: NBC/SKF/National any sweep suitable for exhaust fans/pedestal fans of any make & size. 152 Supply and fixing aluminumblades of 1200/1400 mm celingfans of complete all as specified and directed. 153 Supply and fixingoil type condenser of Usha/Bajaj/Unistar Make, 230 volts AC including necessary soldering of capacity 2.5 MFD. 154 All as per item No. 106.00 above but capacity 4 MFD for exhaust fans/pedestal fans.Make: Jamco/GEC/Crompton 155 M&L for disconnecting, taking down and refixing the same after repair the geyser of any cap including striping, cutting the existing copper inner tankafter welding, brazing and tightening the hold fast ,nuts, bolts, washer etc complete and including making good to disturbed existing surface with plastering all as dircted by Engr-in-Charge 156 Supply and fixing in replacement heating element of Geysers of 2 KW rating required at site including rubber washers.Make – Theeta/ Recold/Bajaj (ISI Marked) 157 Supply and fixingin replacement thermostat for the Geyser of 25/50 ltrcapacity ISI marked 158 Supply and fixing in replacement PVC heavy duty hot type connecting pieces nylon braided with brass adopters 600 mm/450 mmlong and fixing in position suitable for Geyser of25/50 Litre capacity 159 Supply and fixing in replacement copper connection heavy duty hot type connecting with 02 Nos brass adopters and washer of size 600 mm/450 mm long and fixing in position suitable for geyser of 25/50 litre capacity 160 Supply and fixingin replacement geyser indicator lamp square type/round type