Tender For Work Of Installing Lighting Around 07 Ponds In The Authority Area In The City. - Providing & Fixing ofIK08 IP-66 protected high power LED flood light system with single piece Pressure diecast aluminium housing, toughened glass diffuser with suitable lenses on LED to achieve various beam angles,of high power LED of 3 to 5 watt each . Integrated potted driver as a unique BIS R numberhaving efficiency more than 85 % and in compliance to BIS certified and Trade markcertificate. The System level Luminaire efficacy >=125 lm/ wt. LED driver Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety .Power Factor >0.95 , THD(I) <10%, driver current <=750mA. driver should be Phase to phase protection of 440 V for 4 Hrs. Electrical Connector , Surge Protection Min >=4KV internal and 10KV external but inside driver compartment, System life of 50000 Burning hours with 70% of Initial Lumens maintained, CRI>70 and CCT 5700K±355K.Manufactures Word Mark/Name Engraved/Embossing/Screen printing on die cast housing to allow traceability/authenticity. Fixture shall be IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities forLED fixtures.(LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . High Power LED Flood Light Minimum lumen output 25000 lm 2 Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Un-ArrmouredAluminiumcable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV withH4- Grade electrolyticaluminium conductor confirming to IS 8130 of purity >99.6 %,Inner / outer sheath confirming to IS:5831in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray (with cable tie) includingtesting etc. as required of following size. OEM must have its own in house NABL accrediated Laboratory for testing procedure as per IS:10810. For additional technical parameters of product / work refer Annexure A attached with this BSR 25.0 Sq. mm 3.5 core 3 Supplying and makingend termination with heavy aluminiumlugs ( Pin / ring type )confirming to IS 8309 -1993 & IS 8337-1976 duly crimped with crimping tool, PVC tape etc of following size.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 25.0 Sq.mm 4 Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from99.90 % purity copper, class 5 stranding in acc. to IS:8130/IEC 60228 forlower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5,in existingsurface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of product / work refer Annexure A attached with this BSR, 2 x 1.5 sq.mm 5 Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load andsite requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting ofclass 3 as per IEC,minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted inexisting distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above ratingincluding making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure A attached with this BSR, Single pole MCB (With B/C curve tripping Characteristics),6 A to 32 A rating 6 Providing & Fixing of Recessed/surface mounting heavy duty horizontal type Double Door ( Metal / Glazed )Distribution board with Metal end box made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3, powder painted complete with reversible door (for double door DB only )100 amp. insulated copper bus bar/shorting link , copper neutral link, copper earth link , color coded interconnecting wire set of suitable rating and din bar,masking sheet, making internal DB terminations with copper lugs, Ferrules, detachable gland plate, including making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure A attached with this BSR, Metal door (single phase) IK-09 and IP-43 with Metal end box, 16 Way (16+2) 7 Pipe Earthingas per IS:3043- 1987 with 3.0 Mtr. Long, 40 mm dia. B class G.I. Pipe IS: 1239 (Part-1) 2004, Equivalent to BS : 1387 with perforated holes of 12 mm dia ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height250 to 300 mm. and embodying the pipecomplete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or lessas required & must record by engineer in charge during site visit and ensure to enter in measurment book.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 8 Providing & Fixing of IK08IP65 protected Top/Bottom mounted LED Post top Luminarie made of single piece constructionpowder coated die cast alluminium housing with UV stabalized Clear / frosted Polycarbonate diffuser andAluminium anodised with sand blast reflector. The System level Luminous efficacy ≥100 Lumen/W. SMD LEDs is to be used, System CRI>70, CCT: 3000/4000/6500 K. The integral electronic driver must be potted & has a unique BIS R number must be potted & has a unique BIS R number constant current and Internal/external surge protection device of min. 4KV(L-N)and efficiency > 85%, PF>0.9, THD<10% and input Voltage range of 140-270V AC at 50Hz. System life of 50000 Burning hours with 70% of Initial Lumens maintained . Driver current <750mA.Fixture must be in compliance with BIS Standards and Trade mark Certificate complete in all respect.OEM Must have its own in house NABL lab setup for all testing facilities forLED fixtures.(LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . Minimum lumen output 4000 lm Post top Luminarie 9 Supply, Installation, Testing and Commissioning of Spike Light with 10 Degree Beam Deflection and 3000 K CCT,6 Watt(RUIDP Sor 2023) 10 Decorative haritage pole in 4 Meter height. Pole upper section of length 3mtr is of dia 76mm and 1 meter bottom section of dia 114mm with decorative casting with base plate as per drawing. Provision for inside termination box with 4way connector & 1nos 6 AMPS MCB for local isolation with cover.Complete in all aspects with foundation bolts. (RUIDP Sor 2023) 11 Providing and Laying RCC Foundation for Octagonal / Conical Street Light poles, High mast Poles as perDrawing attach at Table P-4 with Following Procedure & All as per pre approved by Engineer in charge.For additional technical parameters of products/ work , refer Annexure A attached with this BSR .A) Excavation of Pit for Foundation Size upto required depth from Ground levelB) Dressing of Pit and Dry stone pitching 200 mm thick including supply of stones and preparing surfacecomplete.C) Providing and laying in position cement concrete of M-10 grade of 75 mm thicknessD) Reinforcement for R.C.C. work with TMT bars including straightening, cutting, bending, placing inposition and binding all complete.E) Centring and shuttering including strutting , propping etc. and removal of form work for Footing andPedestalF) Providing & Fixing of 2 no. Required Size PLB HDPE Pipe & Foundation Bolt with template as per OEM Recommen dations.G) Providing and Laying Reinforce cement Concrete of M-25 grade in Footing and Pedestal includingCuring the foundation for 7 days.H) Providing and Fixing Nosing Angle 40 mm x 40 mm x 6mm with 2 no. 100 mm long, 10 mm dia. Lugs oneach face. Pole Foundation for Octagonal pole from 3 Mtr. To 6 Mtr. 12 P / L of Double wall corrugated HDPE pipe confirming to IS : 16205 P-24,Stiffness Class 750 N, Externally corrugated and having smooth surface insidewith HDPE Coupler, Elbow, Tee at required Depth below the ground for layingcable of following Nominal Outer dia. MFR Test report from NABL accrediatedis to be submitted.(Excavation of Earth & Back filling with compaction is to bePaid Extra)All as per pre approved by Engineer in charge. For additionaltechnical parameters of products/ work , refer annexure A attached withthis BSR .50 mm 13 SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/ freestanding floor mounted dust and vermin proof compartmentalised cubical panelas specifications and Other parameters required as per point (a) ,(b), (c),(d), (e),(f), (g), (h) as below:-(a)Thickness of CRCA sheet shall be 2.0 mm, cable alley compartments havingconcealed hinged type doors with key type lock with / without detachableextension type structure. Removable 3 mm. thick sheet steel gland plates withappropriate size of knockouts for cables shall be provided(b)complete panel shall undergo a process of degreasing, Water rinsing,Activation, derusting, pickling in acid bath, phosphatising & shall be subjecmicrons on both side of panel. The panel having PE foam/ Neoprene rubbergasket of not less than 3mm thickness ,required hardware , concealed hingeddoor with key type locking arrangement for equipment/switchgear earthed with2.5 sq.mm braided copper wire.[c) Interconnection between bus bar and switchgears /cable shall be rigidlysupported and made out by flexible copper wires (up to 63 amp ) and by solid busbar (>63 amp ) . control wiring will be carried out with 1.5 Sq.mm, Earth wire with2.5 Sq.mm and CT with 2.5 sq.mm flexible copper wire only. All joints /interconnections of copper bus bar shall be dully tinned . Clearance betweenmain bus bar and risers / metal parts shall be at least 10 mm additional to widthleeves . Earth and Neutral busbar shall be half of the size of phase bus bar. ( Cost of Bus bar / Flexible wire forInterconnection between Main busbar and Switchgear is to be Paid Extra )(d)Wiring between components within switchgear and Incoming / outgoing cableshall be done through the terminal block only. Direct connection shall not bepermitted. Each terminal block shall be one piece moulded, barrier type, 650 voltgrade, complete with washers, heads, studs with two nuts and identification stripsand shall have adequate continuous current rating. For tap-offs, adjacentterminals with shorting strips shall be used. 10% Spare terminal blocks shall beprovided. Wire identification on marking strip shall correspond to the designationof the wiring diagrams. All wire terminals on the equipment shall also be markedith designation corresponding to those of the wiring diagram.(e)All wiring shall be enclosed in plastic channels and neatly bunched and closedin metering chamber, Wiring between terminals of various devices shall be ‘pointto point’ (no wire splitting or tee connectons) with wires neatly trucked along theback of the panels, adequately supported to prevent sagging.(f)Floor mounted anel shall be mounted on Base frame of ISMC channel size 100x 50 x 5 mm ( to be paid Extra ) 14 Providing & Fixing of AC operated heavy duty 230 /440 Volt power contactor asper PWD specification for electrical Works, ISI marked IS/IEC 60947-4-1 : 2000having provision of mechanical interlocking, auxilary contacts, Din rail mountingtype including making connections, testing etc. as required. All as per preapproved by Engineer in charge. For additional technical parameters of products/work , refer Annexure A attached with this BSR .4 pole Power contactors with following AC 1 Rating 40 Amp 15 Providing & Fixing of mechanical / digital time switch having following day / weekprogramme and minimum 100 hours reserve and AC1 rating of 16-20 amperesincluding making connection, programming conforming to IEC 60730-1 and 60730-2-7 etc. as required. All as per pre approved by Engineer in charge. For additionaltechnical parameters of products/ work , refer Annexure A attached with thisBSR .One day & week reserve (digital type ) 16 Providing & Fixing of 240/415 V AC MCB with positive isolation of 10kA breaking capacity (B/ C/D tripping characteristic as per type ofload and site requirement) 4 KV impulse withstand voltage, ISImarked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting of class 3as per IEC, minimum phase termination capacity of 35sq.mm.conductor line load reversibility , IP 20 contact protection and fittedin existing distribution board/sheets, minimum electrical operation20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A &above rating including making connections, testing etc. as required.OEM shall have submit NABL / CPRI / ERDA accrediated lab typetest reports & All as per pre approved by Engineer in charge. Foradditional technical parameters of product / work refer AnnexureA attached with this BSRFour pole MCB (With B/C curve tripping Characteristics)50/63 A rating