| 1 | Supply, erection, testing and commissioning of HOT dip galvanized octagonal steel pole of 11 mtr. height and made out of 4 mm thick sheet, PCD 320 mm having bottom 200 mm A/F & top 100 mm A/F with built in connector box of size 500 mm x 120 mm with a ring of minimum 250 mm width made of 3 mm thick galvanized MS Sheet on window cover for anti-theft arrangement at 2500 mm height from base plate, MS base plate of size 320 mm x 320 mm x 20 mm thick on existing RCC foundation, making connections, interconnections with suitable size of copper wire with thimble/lugs in the connector box, earthing, marking, numbering of pole etc. complete as per drawing & technical specifications attached including following accessories mounted on inbuilt control box having flush cover with 2 Nos. mounting strips with tapped holes:-(a) 6 mm thick phenolic laminated sheet/bakelite sheet inside the window mounted on the existing mounting strips inside the flush door.(b) Supply & fixing 63 Amp terminal block suitable for 16 sq. mm conductor- 4 Nos. & shorting links-5 Nos. on DIN Channel i/c providing and fixing DIN channel of suitable length- 2 Nos. on existing laminated sheet.(c) Terminal suitable for 6 SWG GI Wire/1.5 sq. mm wire.(d) 6 Amp, SP MCB, 10 KA, ‘C’ Series-3 Nos. including mounting on DIN channel, earth stud 2 Nos. welded at suitable height i/c washers & nuts etc.(e)Suitablearrangementforsaddlingofincoming/outgoingcablesi/clugs/thimblesetc.asrequired.(f)Supplyandfixingof1500mmlongSingleOverhangGIbracketmadeof3.60mmthickM.Spipe,B-classwithtopgalvanizedM.Stubeofsuitabledia.toaccommodatethefittingsonpole(tobeinstalledat11mtr.height).(g)ConnectorboxGICoverwithlockingarrangementandGIroundsleeveweldedaroundcoverbox.NOTE:- Embosing / Laser printing of DDA Credentials as approved by Engineer-in-charge shall also be provided on the Octagonal Pole. |
| 2 | Providing and laying in position, M25 reinforced cement concrete foundation of size 750 mm long x 750 mm wide and 1800 mm deep i/c excavation of earth, refilling, providing cutting, bending and placing in position reinforcement of cold twisted bar of 12 mm dia. 1900 mm long (approx.)-8 Nos. and reinforcement ring of cold twisted bar of 8 mm dia. 2900 mm long (approx.)-10 Nos. (With 150 mm spacing) with supply of 4 Nos. M-24 x 750 mm long plus 100 mm bent (150 mm top threaded portion) GI foundation bolts (L Type) & nuts (EN 8-grade) 3 Nos. and 2 Nos. washer per bolt,along with 2 Nos. templates/anchor plate of size 320 mm x 320 mm x 4 mm thick having 4 Nos. 26 mm dia. holes to match with PCD of pole and base plate including centering & shuttering as required positioning of foundation bolts and providing 63 mm (OD)-2 Nos. DWC pipe 1 mtr. long each for cable entry and exit etc. complete as required. |
| 3 | Supply, installation, testing and commissioning of LED street light fitting of following rating made up of pressure die cast aluminium housing (IP-66 protection) with embossing / laser printing of DDA Credentials as approved by Engineer-in-charge in front of LED fittingwith all accessories including making connection etc. complete as required and as per technical specification attached. |
| 4 | LED street light fixture of 170 watt with lumens output not less than 20400 rating. |
| 5 | Supplying of following sizes of XLPE aluminum conductor armoured power cable of 1.1 KV grade i/c connection & testing etc. as required and as per technical specification enclosed. |
| 6 | 4 x 16 Sq.mm |
| 7 | 4 x 35 Sq.mm |
| 8 | 4 x 50 Sq.mm |
| 9 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. |
| 10 | 63 mm dia (OD-63 mm & ID-51 mm nominal) (DSR (E & M) 2022- 14.15.1). |
| 11 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. |
| 12 | Upto 35 Sq. mm (DSR (E & M) 2022- 7.5.1). |
| 13 | Supply, boring and laying of HDPEpipe (ISI) marked of the 90 mm OD size confirming to IS:4984 with pressure rating of 6KG/Sq.cm by trench less technology with no dig. Method by making bore hole in horizontal direction across the road with boring equipment i/c jointing, cleaning, rodding of pipe performing mandrel test providing suitable covers on mouth of pipes, excavation of pits of required size & depth and laying of cables in the pipe. etc. complete as required. |
| 14 | 90 mm OD |
| 15 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavatgion, sand cushioning, protective covering and refilling the trench etc as required. |
| 16 | Upto 35 Sq. mm (DSR (E & M) 2022- 7.1.1). |
| 17 | Above 35 sq.mm and upto95 Sq.mm(DSR (E & M) 2022- 7.1.2). |
| 18 | Supplying and drawing of 3 x 1.5 sq. mm size of 1.1 KV grade FRLS PVC insulated copper conductor single core cable in the existing surface/recessed steel conduit as required (DSR (E & M) 2022- 1.17.3). |
| 19 | Supplying,installation,testing&commissioningoffloormountedfreestandingtypeL.T.cubicalMainFeederPillardulycompartmentalized(outdoortype)madeoutof2mmthickMSCRCAsheetwith4nos.x600mmlonglegsmadeofM.Sangleiron ofsize40mmx40mmx5mmthickalongwithframe &legssuitablygroutedinfoundationi/cconnection,interconnectionoftheaccessoriesmountedthereonwithsuitablesizeofcopperwire/stripwiththimble/lugs,earthingthebodyofthefeederpillari/csupplying&fixingofthefollowingitemsandaspertechnicalspecificationenclosed.a)125A,36KA,FPMCCB(Ics=Icu)-1No(incomer).b)63A,16KA,FPMCCB(Outgoingcircuit)(Ics=Icu)-3Nos.c)100A,30KA,FPMCCB(Outgoingcircuit)(Ics=Icu)-1Nos.d)Voltmeter(0-500V)96Sq.mmwithselectorswitch–1Sete)Amp-meter(0-100A)96Sq.mmwithselectorswitch&100/5AmpratioCTS–1Setf)IndicationLamp(RYB)LEDtypewithcontolSPMCB6Amp.-1set.g)TPcontractorofAC-3rating110Amp.1No.h)6AmpsinglepoleMCB-1No.i)Auto/Manualtoggleswitch–1Setj)AstronomicalTimerswitch–1No.k)200amp,4stripaluminiumbusbar–1Setl)Glandplatewithgland–1setm)DangerNoticeplate–1No.n)6pin15Ampswitch/socketoutlet–1Seto)LEDLightinginsidethefeederpillarp)CompartmenthavingspaceforDISCOMenergymeterwith6mmthickbacklitesheetformountingenergymeter.q)SurgeProtectionDevice-1No.Note:Foundationshallbemadeaspersiterequirementforwhichnothingextrashallbepaid.PCC-1:2:4(1cement:2coarsesand:4gradedstone) |
| 20 | Supplying,installation,testing&commissioningoffloormountedfreestandingtypeL.T.cubicalServiceFeederPillardulycompartmentalized(outdoortype)madeoutof2mmthickMSCRCAsheetwith4nos.x600mmlonglegsmadeofM.Sangleiron ofsize40mmx40mmx5mmthickalongwithframe &legssuitablygroutedinfoundationi/cconnection,interconnectionoftheaccessoriesmountedthereonwithsuitablesizeofcopperwire/stripwiththimble/lugs,earthingthebodyofthefeederpillari/csupplying&fixingofthefollowingitemsandaspertechnicalspecificationenclosed.a)100A,30KA,FPMCCB(Ics=Icu)-1No(incomer).b)63A,16KA,FPMCCB(Outgoingcircuit)(Ics=Icu)-3Nos.c)Voltmeter(0-500V)96Sq.mmwithselectorswitch–1Setd)Amp-meter(0-100A)96Sq.mmwithselectorswitch&100/5AmpratioCTS–1Sete)IndicationLamp(RYB)LEDtypewithcontrolSPMCB6Amp.-1set.f)TPcontractorofAC-3rating110Amp.1No.g)6AmpsinglepoleMCB-1No.h)Auto/Manualtoggleswitch–1Seti)AstronomicalTimerswitch–1No.j)200amp,4stripaluminiumbusbar–1Setk)Glandplatewithgland–1setl)DangerNoticeplate–1No.m)6pin15Ampswitch/socketoutlet–1Setn)LEDLightinginsidethefeederpillaro)SurgeProtectionDevice-1No.Note:Foundationshallbemadeaspersiterequirementforwhichnothingextrashallbepaid.PCC-1:2:4(1cement:2coarsesand:4gradedstone). |
| 21 | Fabricating, supplying and fixing of angle iron steel structure frame of suitable size to accomodate Main Feeder Pillar/Service Feedar Pillar fabricated out of 40 mm x 40 mm x 5 mm angle iron, and providing and fixing wire mesh of 8 SWG and shall be fixed and supported with 40 mm x 50 mm M.S. flats and the frame is to be grouted with M.S. angle legs not less than 30 cm in cement concrete 1:2:4 (1 cement :2 course sands and 4 stone aggregate 20 mm nominal size) foundation, painted with two coats of red oxide primer and two coats of synthetic enamel paint, and providing two leaf doors with 12 nos. hinges of size 75mmX60mmX3mm in front with two nos. sliding door bolt of size 30 mm X 16 mm and 2 nos. of godown lock for locking arrangement, complete etc. required. |
| 22 | Providing and fixing following rating and breaking capacity and pole MCCB with themomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. a) 125 A, 36KA, FPMCCB (DSR (E & M) 2022- 2.2.14). |
| 23 | Supply & installation of hot press moulded SMC junction box side hinged door type of minumum inside size 250 x 200 x 105 mm to accommodate 125A FPMCCB. Box should be weatherproof, rustproof, shockproof with provision for 3 phase cable entry & exit from bottom/side, external bracket for fixing on existing surface including drilling holes, making connections, testing etc. complete as required. |
| 24 | Supplying and making End Termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 25 | 4x16 Sq.mm(DSR (E & M) 2022- 9.1.33). |
| 26 | 4x35 Sq.mm(DSR (E & M) 2022- 9.1.35). |
| 27 | 4x 50 Sq.mm(DSR (E & M) 2022- 9.1.36). |
| 28 | Earthing with G.I. earth Pipe 4.5 mtr long, 40 mm dia including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/coke and salt as required (DSR (E & M) 2022- 5.2). |
| 29 | Providing and fixing 25 mm x 5 mm G.I. strip in 40 mm dia GI pipe from earth electrode including connection with GI nut, bolt, spring washer, excavation and refilling etc. as required (DSR (E & M) 2022- 5.11). |
| 30 | Providing and fixing 25 mm x 5 mm G.I. strip on surface or in recess for connection etc. as required (DSR (E & M) 2022- 5.15). |
| 31 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/recessed conduit/sub main wiring/cable as required (DSR (E & M) 2022- 5.18). |
| 32 | Welding of LED lights with bracket for anti theft purpose with MS strip etc. complete as required. |