Internal And External Electrical Installation Work For Proposed Giii Storied Handloom Haat Within Contai Municipality Area, Contai, Purba Medinipur.
Tender Value
46.51 Lakhs
Estimated cost
Bid Submission
26 May 2025
0 days left
EMD
93035
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
contai → West Bengal
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Internal And External Electrical Installation Work For Proposed Giii Storied Handloom Haat Within Contai Municipality Area, Contai, Purba Medinipur.
BOQ
| Sl. No. | Item Description |
| 1 | WIRING SYSTEMWiring in 1.5sqmm single core stranded FR PVC insulated & unsheathed single core stranded copper wire(Brand approved by EIC) in 19mm bore, 3mm thick polythin pipe complete with all accessories embedded in wall for one light/fan/bell/exhaust fan point controled by one modular type switch(Brand approved by EIC) fixed on modular GI switch board with top cover plate flushed in wall including mending good damages to original finish (2x1.15 +1x1.5)Average run 6 mtr.(Ref: PWD 2017, SOR-E-20, no.1.i). |
| 2 | Average run 8 mtr.(Ref: PWD 2017,SOR -E-20, no.1.iii) |
| 3 | Wiring in 1.5 sqmm single core stranded FR PVC insulated & unsheathed single core stranded copper wire(Brand approved by EIC) in 19mm bore, 3mm thick polythin pipe complete with all accessories embedded in wall to 240V 6A 5pin plug point incl. supply & fixing of 240V 6A 3pin modular type plug socket & modular type switch(Brand approved by EIC) incl. supply & fixing of earth continuity wire fixed on 4 module GI switch board with 3/4 module top cover plate flushed in wall incl. mending good damages to original finish.one light point controled by one modular type switch(Brand approved by EIC) fixed on modular GI switch board with top cover plate flushed in wall including mending good damages to original finish(2x1.15 +1x1.5)(Ref: PWD 2017, SOR -E-20, no.3)(i) On Board |
| 4 | (v) Average run 4.5 mtr |
| 5 | (v) Average run 6 mtr |
| 6 | Supply and fixing 240V, 16A, 3pin modular type plug socket(Brand approved by EIC), with 16A modular type switch, without plug top on 4 module GI modular type switch board with 3 module top cover plate flushed in wall incl. S & F switch board and cover plate and making necy. connections with PVC copper wire and earth continuity wire etc.(Ref: PWD 2017,SOR -E-18, no.9.b) |
| 7 | Supplying and fixing CRC sheet metal(16 SWG) JB cum switch board of the following size complete with suitable bakelite/Perspex/Coloured perspex(wall matching colour) top cover 3mm thick flushed in wall for housing the board after cutting the brick wall incl. mending good damages to building works.200 mm X 150 mm X 65 mm deep (Ref: PWD 2017, SOR -E-4, no.10.c) |
| 8 | Supply & fixing of 240V, modular type(2 module) fan regulator(step up, brand approved by EIC) on existing modular GI switch board with top cover plate incl. making necessary connection.(Ref: PWD 2017, SOR-E-18, no.10) |
| 9 | Supply & fixing of 240V, 25A, 3pin modular type plug socket(brand approved by EIC)without plug top and switch with 2 module GI modular type switch board with top cover plate flushed in wall and making necy. Connections with PVC cu wire and earth continuity wire etc.(Ref: PWD 2017, SOR-E-17, no.5.a) (For AC point) |
| 10 | Supply & fixing of 240V, 25A, 3pin modular type plug top with indicator (brand approved by EIC) & necy.Connections.(Ref: PWD 2017,SOR -E-17, no.5.b) |
| 11 | Supply & Fixing 240 V, 25 A, Modular type starter (Brand approved by EIC) with 25A Modular switch type DP MCB (C Curve) and 4 Module GI Modular type switch board with 4 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy.connections with PVC Cu wire and earth continuity wire etc.(Ref: PWD 2017, SOR-E-19, no.17) |
| 12 | SUBMAINS AND CABLESWiring for circuit/ submain wiring alongwith earth wire with the following sizes of FR PVC insulated copper conductor, single core cable in PVC rigid conduit including necessary fittings & connection as required.2 X 2.5 sq. mm + 1 X 1.5 sq. mm earth wire(Ref: PWD 2017, SOR-E-9, no.1.s)[For power Socket & AC] |
| 13 | 4 X 10 sq. mm + 2 X 6 sq. mm earth wire (Ref: PWD2017,SOR -E-9, no.1.d1)[For VTPN to HTPN] |
| 14 | DISTRIBUTION SYSTEMSupplying and fixing double door Vertical type TPN, MCB distribution board for MCCB incomer with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. inter connection with suitable size ofcopper wire and neutral link & provission nfor earthing attachment.Up to 160A(Ref: PWD 2017, SOR-D-11, no.15)4 way (Seimensmake, Enclosure (8GB31571RC) |
| 15 | 6 way (Seimensmake, Enclosure (8GB31572RC) |
| 16 | Supplying and fixing double door horizontal type three pole and neutral, MCB distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. inter connection with suitable size ofcopper wire and neutral link & provision for earthing attachment.(Ref: PWD 2017,SOR -D-10, no.14)8 way (Seimens make, Enclosure (8GB32202RC08) |
| 17 | Supplying and fixing 415 V Four Pole MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing DBs / enclosure and necessary connection 160 Amp Seimens Make(Ref: PWD 2017, SOR-D-8, Item no.10) |
| 18 | Supplying and fixing240/415 V, MCB(Legrand make) of breaking capacity 10 kA, \"C\" characteristics on din rail of the existing DBs and necessary connection.Seimens MakeSP MCB(6-32A) (Ref: PWD 2017, SOR-D-6, no.7) |
| 19 | Four pole(40A)(Ref: PWD 2017, SOR-D-6, no.7) |
| 20 | Four pole(63A)(Ref: PWD 2017,SOR-D-6, no.7) |
| 21 | Supplying and fixing 240/415 V MCB Isolator on din rail of existing DBs and necessary connection.(Ref: PWD 2017,SOR-D-5, no.6)Four Pole Seimens Make(40 Amp) |
| 22 | Four Pole Seimens Make(63 Amp) |
| 23 | EARTHING SYSTEMEarthing with 50 mm dia G.I. pipe 3.64 mm thick x 3.04 metre long and 1x4 SWG GI(Hot dip) wire (4 mtr. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & FR 15mm dia GI pipe protection(i mtr. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 mtr. below the ground level as below.\"By TATA medium GI pipe(Ref: PWD 2017, SOR -G-1, no.2.a) |
| 24 | Supplying and fixing earth busbar of galvanized(Hot dip) MS flat 25mm x 6mm on wall having clearence of 6mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc as required. (Ref: PWD 2017,SOR-G-2, no.4.a) |
| 25 | Connecting the equipments to earth busbar including S & F GI(Hot dip) wire of size as below on wall/floor with staples buried inside wall//floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages.No. 6 SWG (Ref: PWD 2017,SOR-G-2, no.5.a.ii) |
| 26 | No. 12 SWG (Ref: PWD 2017,SOR-G-2, no.5.a.V) |
| 27 | Fitting Fixture FixingFixing only fluorescent light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports incl. S&F EI conduit, ball socket/socket type ceiling plate and connecting the length of PVC insulated wire and painting etc. as required by 2x24/0.20 mm (1.5sqmm) flexible copper wire of 1.10 mt. length. (Ref: PWD 2017,SOR-C-2, 15) |
| 28 | Extra for suspension exceeding 25 cm with S&F additional 2 no. 20 mm dia EI conduit (14 SWG) supports & necy. PVC insulated wire and painting etc. as required by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length.(Ref: PWD 2017,SOR-C-2, 16)r |
| 29 | Fixing only single/twin light fitting complete with all accessories directly on wall/ceiling by screws etc.(Ref: (PWD 2017, SOR -C-2, no.14.a) |
| 30 | Fixing only 1No lamp holder on single HW board on wall incl. S&F single HW board(Ref: PWD 2017,SOR-C-2, 9a) |
| 31 | Fixing only lamp(Ref: PWD 2017,SOR-C-2, 11) |
| 32 | Fixing only outdoor / street light type fluorescent light fitting or MV light fitting complete with all accessories to be fixed /projected from the wall of the building incl. making holes/providing clamping arrangement & necy. GI reducer as required. S&F 40 mm GI pipe (ISI-Medium) quality 1.5 mts. average length having suitable bend S&F necy. length of 1.5 sqmm PVC insulated single core stranded annealed copper wire and making connections as required and mending good damages to wall incl. painting etc.(Ref: PWD 2017, SOR-C-3, no.18) |
| 33 | Fixing only exhaust fan after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necessary length of PVC insulated wire and making connection for exhaust of following diameter.23 cm (9\")(Ref: PWD 2017,SOR-C-4, no.28.a) |
| 34 | Supply and fixing the louvers/ shutters on wall with necessary bolts & nuts(6mm dia x 62mm long).For GI 9\" Exhaust fan (Ref: PWD 2017, SOR -D-14, no.32) |
| 35 | Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc including supply & fixing of connecting wire for down rod upto 30cm including painting the rodand making necessary connection as required by 2x1.5sqmm flexible copper wire(Ref: PWD 2017,SOR -C- 3, no.21.a) |
| 36 | LA SYSTEMSupply & fixing of lightning conductor Air-terminals made of 15mm dia 1500mm long GI pipe(ISI Medium) having five prongs of 4 SWG GI(Hot dip)wire at the top with 85mm dia 6mm thick GI base plate at bottom incl. necessary holes etc. duly grouted on the parapet etc in CC mortar(4:2:1)(Ref: PWD 2017, SOR -J-1, no.1) |
| 37 | Supply & fixing of GI(Hot dip) strips 20mm x 3mm thick for horizontal run on the parapet/roof/wall with GI saddle1100mm apart incl. mending good the damages to building works.(Ref: PWD 2017,SOR-J-1, no.9) |
| 38 | Supply & fixing of GI(Hot dip) strips 20mm x 3mm thick for vertical run on the wall with GI saddle with spaced not exceeding 1000mm apart incl. mending good the damages to building works.(Ref: PWD 2017, SOR-J-1, no.11.a) |
| 39 | Making soldered joints between conductors, conductors and air terminals for 4 SWG GI (Hot Dip) wire incl. supply of jointing materials and painting with 2 (two) coats of bituminous pain[WBPWD SOR-2017 Page= J-1, Item no.-5] |
| 40 | Hiring charges for scaffolding arrangement including dismantling at the end of work and carriage for LC installation , per storey of buildingper vertical run.(Ref: PWD 2017,SOR-J-1, no.7) |
| 41 | Earthing with 65mm dia GI pipe(TATA medium) x 3.0 mtr long and 1 no. 50mm x 6mm galvanized(Hot dip) steel strip(4 mtr long), 20mm dia x 125mm long galvanized bolt, double nuts, double washers including finishing both ends by making holes etc and S & F 65 mm dia GI pipe(ISI Medium) protection(3 mtr long) to be filled with bitumen partly under the ground level and partly above the ground level to an average depth of 3.65 mtr.(Ref : PWD SOR 2017 vol-I, Page G-1 No. 2d) |
| 42 | By TATA medium GI pipe (Ref: PWD 2017, SOR -G-1, no.2.a) |
| 43 | Excavation of soil for installation of Earth Electrode and filling & ramming.(Ref: PWD 2017, SOR-G-1, no.1.a) |
| 44 | Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36cm x 86.36cm x 46 cm deep(below ground level) complete with cement morter(inside) CI hinged inspection cover of size 36.56cm x 36.56cm with locking arrangement. GI reducer including drilling of 46 nos.12 mm dia holes on the G I pipe.(Ref : PWD SOR 2017 vol-I, Page G2 No. 3a) |
| 45 | CABLES (LAYING)Laying in cable Tray/concrete trench clamped to wall with suitable saddles & fixing bolts/in ground including the cost of digging & back filling with sand and brick protection including testing & commissioning of 11KV grade armoured XLPE insulated and sheathed aluminium conductor as required.All cables to be provided with a 1D gap nad shall be properly clamped with cable clamp & ties. Identification tags shall be provided for all cables & route markers for cables in ground.3-1/2 core 300 /240 sq mm XLPE(Ref: DSR 2018 (CPWD), SOR -7, no.7.1.4)(For LT Panel Incomer) |
| 46 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below :Upto 4 core 300 sq mm XLPE(Ref : PWD SOR 2017 vol- I, F-4, no.7(d)) |
| 47 | Upto 4 core 16 sq mm XLPE(Ref : PWD SOR 2017 vol-I, F-4, no.7(d)) |
| 48 | Upto 4 core 70 sq mm XLPE(Ref : PWD SOR 2017 vol-I,F-4, no.7(d)) |
| 49 | Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing material4 core 300 sq mm XLPE (Ref : PWD SOR 2017 vol-I, F- 5, no.8(b)(xxiii) |
| 50 | 4 core 16 sq mm XLPE(Ref : PWD SOR 2017 vol-I, F-5, no.8(b)(xvii) |
| 51 | 4 core 70 sq mm XLPE (Ref : PWD SOR 2017 vol-I, F-5, no.8(b)(xvii) |
| 52 | Laying of cable upto 2 core 25 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting[WBPWD SOR - 2017, Page - F -1, Item No. 2(a) |
| 53 | Laying of cable above 3½ core 50 sqmm and upto 3½ core 90 sqmm on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting[WBPWD SOR - 2017, Page - F -1, Item No. 2(e) |
| 54 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness notless than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.150 mm width X 50 mm depth X 1.6 mm thickness (Ref: DSR 2018(CPWD),SOR -4,no.4.6.2) |
| 55 | Supply and laying of the following size RCChume pipe NP2 class including excavation, refilling as required for cable entry including the cost of sealing the ends asrequired to complete.150mm dia(Ref: DSR 2018(CPWD), SOR -14, no.14.14.2) |
| 56 | CABLESSupply of 1.1KV grade armoured XLPE insulated andsheathed aluminium conductor as following4 core 300 sq mm XLPE Cable. (for panel incomer & DG)Ref: I&W SOR 2022, Page No 101, No.5.3 A2. |
| 57 | 4 core 70 sq mm XLPE Cable. [For Panel to 1st,3rd floor VTPN]Ref: I&W SOR 2022, Page No 101, No.5.3 A2 |
| 58 | 4 core 16 sq mm XLPE Cable. [Panel to Ground floor HTPN]Ref: I&W SOR 2022, Page No 101, No.5.3 A2 |
| 59 | Fitting FixtureSupply TMC 501 conventional industrial batten Philips LED tube, model no TMC 501 P 2xT-LED 22 W P3242 with 2 no mass LED tube 1200 mm 18W865 T-8 I-2100 lm including necessary connection.(only for Sewing area)Ref: I&W SOR 2022, Page No 113, No.5.3 F.20 1st Floor |
| 60 | 2nd Floor |
| 61 | 3rd Floor |
| 62 | Supply of TMC501 Conventional industrial batten Philips LED tube, model no: TMC 501 P 1xT-LED 22 WP3241. Ref: I&W SOR 2022, Page No 113, No.5.3 F.22.Ground Floor |
| 63 | 1st Floor |
| 64 | 2nd Floor |
| 65 | 3rd Floor |
| 66 | Supply of philips make 9 watt bulb Base B22/E27 825 LmRef: I&W SOR 2022, Page No 114, No.5.3 F.27.1Ground Floor |
| 67 | 1st Floor |
| 68 | 2nd Floor |
| 69 | 3rd Floor |
| 70 | Supplying of approved make high speed ceiling fan (ISI marked) of following sizes having double ball bearing complete with standard down rod, canmopy, hanging shackle, Aluminium blades, without regulator, A.C. 230- 250 vilts of 1200mm sweep ceiling mounted white colour high speed fan. 900mm/1050mm/1200mmRef: I&W SOR 2022, Page No 115, No.5.3 G.1.1 Ground Floor |
| 71 | 1st Floor |
| 72 | 2nd Floor |
| 73 | 3rd Floor |
| 74 | Supply and delivery of 230V,50Hz Heavy duty Metal 9\"exhuast fan.UD & MA Mech-Elect SOR-2018, Page- 14, Item- 5 Ground Floor |
| 75 | 1st Floor |
| 76 | 2nd Floor |
| 77 | 3rd Floor |
| 78 | Supply and delivery & installation at site of 100 Watt Flood light.Philips make(Model-BVP192 LED 110 CW HO NB FG GR PSU)(For compounding lighting)(MED Section Rate) |
| 79 | FIRE EXTINGUISHERISI marked Powder type fire extinguisher for class ‘B’ & ‘C’ fire 6 Kg. capacity fitted with forged brass squeeze lever discharge valve conforming to IS:15683:2006 complete with initial refill consisting of ISI marked Co2 gas cartridge of 120 grams capacity conforming to IS:4947 and ISI marked sodium base dry chemical powder conforming to IS:4308, suitable for operating between (-) 30ºC to (+)55ºC.Fire rating -13B.(UDMA Page - 25, Item - 79(D) |
| 80 | ISI marked Powder type fire Engine 25 Kg. capacity conforming to IS:10658 fitted with gun metal cap, high pressure discharge hose with nozzle, mounted on trolley wheels complete with initial refill consisting of Co2 cylinder of 1 Kg.capacity with ISI marked controlled valve conforming to IS:3224 and ISI marked sodium base dry chemical powder conforming to IS:4308.(UDMA Page-25; Item-79;D) |
| 81 | 415 VOLT LT PANELSSupply,fixing, testing and commissioning of Indoor type, compartmentalized, floor mounted, single front LT Panel primer coated with powder coated paint & provided with required gasket for dust/vermin proof with degree of protection IP54 suitable for 415volt, 3phase,50Hz, 4wire system fabricated out of CRCA sheet upto 2mm thick(1.6mm for doors) duly compertmentalized for incomer, bussection, outgoings, cable alleys & CT, PT, ampere, volt selector switches, frequency, phase indicating lamp, energy meter complete including cost of busbar supports, detachable cable gland plates, 2 earthing terminals, internal wiring & fixing of seperately supplied MCBs, MCCBs, panel mounted changeover switch/SFUs etc. as required but excluding cost of busbar strips, Ammeter, Voltmeter, selector switch as per approved design & specification. Approx size- (2175 x 3800 x 900)mm(Make- Royco, RNR, Sellwin, Electrocon) |
| 82 | Supply ofKVA (CPCB IV+) Silent DG set comprising ofEngine 156BHP@NTP, 1500.00 RPM, coupled to 125KVA alternenater approved by EIC.Three phase 415V, 50 Hzalternator mounted on a common Base frame along with other accessories i.e., Fuel tank, with STD panel, Battery with leads and acoustic enclosure. & battery charger\"s first fill of tube oil & AVM pad as per Technical Specification.(MAke- Kriloskar, Jakson, Mahindra, Tata)Unloading,shifting installation andcommissioning charge ofon above cost |
| 83 | Add 18% GST (Sl No. 1 to 55) |
| 84 | Add 1% Welfare Cess |
AI Tender Summary
Tender Timeline
May 09, 2025
11:30 IST
Tender Published
Tender notice published.
CompletedMay 26, 2025
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
CompletedMay 29, 2025
Bid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender