| 1 | SECTION A :- EARTHING Earthing with GI earth pipe 2 mts long 40 mm dia medium class with ISI mark, of approved brands including accessories and providing masonry enclosure with CI/RCC coverhaving locking /Lifting arrangement and watering pipe etc. (but without charcoal or coke and salt) as required as per the Earthing Drawing provided by the Engineer-Incharge.The scope of work includes the following: a) Excavation ofpit of sizenot less than 1.0x1.0x 2.0 mtrs(min) and disposal of excavated soil. b) Class B GI pipe, 40mm diameter as per specifications. c)Charcoal/salt as per specs ( paid seperately). d) Refilling the pit of size not less than 1.0x1.0x 2.0 mtrs(min) with soft black soil of minimum resistivity i/c transportation. e)Masonary chamber with proper foundation, cover plate and locking arrangement. f) Testing of earth value with earth megger and certifications of its value. Aluminium tag with embossed earthing value to be attached to the pipe. g)watering arrangement(plumbing will be paid seperately).(a) In soily strata |
| 2 | Extra for using salt and charcoal for pipe earth electrode as required( 65 Kgs of Charcoal and 5 Kgs of Salt). |
| 3 | Supplying and laying 8 SWG copper wire at 0.5 m below ground level for conductor earth electrode including soldering etc. as required |
| 4 | SECTION B :- CABLE SUPPLY Supply of3 1/2 core armoured PVC/XLPE insulated, PVC sheathed aluminium conductor cable of 1.1 KV grade with ISI mark conforming to IS:1554(Part I) ,IS:7098(Part I) with latest amendments of following size. |
| 5 | 3 1/2 Core 25 sq.mm armoured cable |
| 6 | 3 1/2 Core 35 sq.mm armoured cable |
| 7 | Supply of4 core armoured PVC/XLPE insulated, PVC sheathed copper conductor cable of 1.1 KV grade with ISI markconforming to IS:1554(Part I) ,IS:7098(Part I) with latest amendments of following size. |
| 8 | 4 Core 2.5 sq.mm armoured cable |
| 9 | 4 Core 4 sq.mm armoured cable |
| 10 | SECTION C :- CABLE LAYING IN TRENCH FORMATE Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of size not exceeding 25 sq.mm direct in ground including excavation in the form of a trench as per Cable Trench Drawing provided by the Engineer-Incharge,sand cushioning with screened sand bed of 20mm thick , protective covering with bricks placed breadth-wise on top of cable all over the run( the brick protection shall cover the cable and project atleast 5 cms over the sides of the cable) and backfilling the excavated earth without stones or hard material and making the surface proper with 15 cm crown on the top complete as required. |
| 11 | (a) In soily strata |
| 12 | Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of size exceeding 25 sq.mm but not exceeding 120 sq.mm direct in ground including excavation in the form of a trench as per Cable Trench Drawing provided by the Engineer-Incharge,sand cushioning with screened sand bed of 20mm thick , protective covering with bricks placed breadth-wise on top of cable all over the run( the brick protection shall cover the cable and project atleast 5 cms over the sides of the cable) and backfilling the excavated earth without stones or hard material and making the surface proper with 15 cm crown on the top complete as required. |
| 13 | (a) In soily strata |
| 14 | Laying of one number additional PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of size not exceeding 25 sq.mm direct in ground in the same trench in one tier horizontal formation including excavation in the form of a trench as per Cable Trench Drawing provided by the Engineer-Incharge,sand cushioning with screened sand bed of 20mm thick , protective covering with bricks placed breadth-wise on top of cable all over the run( the brick protection shall cover the cable and project atleast 5 cms over the sides of the cable) and backfilling the excavated earth without stones or hard material and making the surface proper with 15 cm crown on the top complete as required. |
| 15 | (a) In soily strata |
| 16 | SECTION D :- CABLE TERMINATION Supplying and making cable end terminations with brass compression gland and aluminium lugs for folowing sizes of 3 1/2 Core PVC insulated PVC sheathed/XLPE aluminium conductor cable of 1.1 KV grade, completeas required. |
| 17 | (1) 3 1/2x 25 Sq. mm. armoured Cable |
| 18 | (2) 3 1/2x 35 Sq. mm. armoured Cable |
| 19 | Supplying and making cable end terminations with brass compression gland and copper lugs for folowing sizes of 4 Core PVC insulated PVC sheathed/XLPE aluminium conductor cable of 1.1 KV grade, completeas required. |
| 20 | (1) 4 x 1.5/2.5 Sq. mm. armoured Cable |
| 21 | (2) 4 x 4 Sq. mm. armoured cable |
| 22 | SECTION E:- LIGHT FITTINGS Supply and installation of Outdoor Bollard Luminaire Power : 15 Watts CRI 90Ra , Beam angle : 126°CCT : 3000 KDiffuser : Opal PCHousing : Die Cast AluminiumIP 65 |
| 23 | Supply and installation of Outdoor Surface Light Luminaire Power : 12 Watts CRI 90Ra , Beam angle : 26°CCT : 3000 KDiffuser : LensHousing : Die Cast Aluminium IP 65 |
| 24 | Supply and installation of Outdoor Surface Light Luminaire Power : 30 WattsCRI 90Ra , Beam angle : 46°CCT : 3000 KDiffuser : LensHousing : Die Cast Aluminium IP 65 |
| 25 | Supply and installation of GI Pole With mounting accessoriesupto 5mtr |
| 26 | Supply and installation of Outdoor Gate Light Luminaire Power : 50 WattsCRI 90Ra , Beam angle : NACCT : 3000 KDiffuser : OpalHousing : Die Cast Aluminium IP 65 |
| 27 | Supply and installation of Linear Corner Profile with LED Luminaire Power : 12 WattsCRI 90Ra , Beam angle : NACCT : 3000 KDiffuser : OpalHousing : Aluminium IP 67 |
| 28 | Supply and installation of Constant Voltage Driver Power : 100W IP 67 |
| 29 | SECTION F:- LV PANELSSupply and installation of Outdoor type LV panels with timer as per the specifications |
| 30 | Supply and installation of Outdoor type main LV panel with timer as per the specifications |
| 31 | Earthwork in excavation by mechanical means (hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sq.m on plan) including disposal of excavated earth lead upto 50 m and lift upto 1.5m disposed earth to be leveled and neatly dressed including providing barricading, danger lighting guarding as directed in : All kinds of soil |
| 32 | Rubble packing with hard laterite stone under floors including watering ramming and consolidating etc. in pipeline trenches and other foundations complete. |
| 33 | Providing & laying cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded granitic or basaltic stone aggrt. 40 mm. nominal size) excluding cost of centering, shuttering and finishing in: All works upto plinth level |
| 34 | Centering & shuttering including Strutting, Propping & removal of forms for : Foundations, footings, bases for columns andmass concrete. |
| 35 | Providing and laying in position (1:11/2:3) Reinforced cement conrete excluding the cost of centering, shuttering, finishing and reinfrocement (1 cement: 1½ coarse sand:3 graded stone agg 20mm nominal size), a) All Works Upto Plinth Level. |
| 36 | Refilling the pipeline/foundation trenches plinthsides, foundation etc. with available excavated earth in layers not exceeding 20 cm depth consolidating each layer ramming and watering lead upto 50 M and all lifts and disposal of surplus earth as directed by Engineer in Charge. |
| 37 | TRANSPORTATION AND CARRIAGE OF MATERIALS (A) By tipper truck including loading,unloading and stacking |
| 38 | ( ii ) Earth |
| 39 | PVC fexible 25mm pipe-medium |