| 1 | L.T Cables:Supply, installation, testing & commissioning of 1.1 KV grade aluminium/ Cu stranded circular/sector shape core conductor with XLPE insulation, extruded PVC inner sheathed, G.I flat strip/wirearmoured, extruded FRLS grade PVC (ST-2) outer sheathed cable conforming to IS : 1554 Part I / IS7098 Part-I with latest amendments, fixed on wall/column/slab/ false ceiling / existing cable tray/existing hume pipe/trench/shaft/pit/ on 5mm thick M.S. flat /GI spacer/angle/support fixed withcoach screws/grouted in wall/anchor fasteners 2mm. thick G.I. fabricated saddle, all fixingaccessories, etc complete including painting of M.S spacers/angles and saddles or in ground , sandbedding,laying of baked bricks on side & top-, temporary reinstatement, back filling, dewatering,consolidation,disposal of excess earth within the radius of 500 m and making good to the originalfinish etc providing Al cable tag as per enclosed detailed specifications, drawings & asperinstructions of the E-I-C & of the following sizes.NOTE:1) Excavation of earth shall be measured Separetely under relevant item.2) Sealing of hume pipes with wooden bushes after cable laying shall be included in the scope ofwork.3) Clamping of cables on trays including supply of clamping materials as per instruction of EIC shallbeincluded in the scope of work. |
| 2 | 3.5C x 95 sq. mm Al conductor cable |
| 3 | 4C X 2.5 sqmm cu conductor cable |
| 4 | END TERMINATIONProviding end joints of 3.5C x 95 sq. mm cables by crimping with all jointing materials like solderless copper lugs, brass gland, duplicate earthing of gland with brass gland clip, earthing of glands tonearest earthing terminal by using 10SWG/14SWG GI wires etc. all as required & instructed by theEngineer-in-charges. |
| 5 | END TERMINATIONProviding end joints of 4C x 2.5 sq. mm cables by crimping with all jointing materials like solder lesscopper lugs, brass gland, duplicate earthing of gland with brass gland clip, earthing of glands tonearest earthing terminal by using 10SWG/14SWG GI wires etc. all as required & instructed by theEngineer-in-charges. |
| 6 | MCCB/ MCB enclosure:Supply, Installation, Testing & Commissioning of following MCCB/ MCB with suitable IP 65, MSCRCA powder coated enclosure with locks etc along with angle iron framework including minorcivil worksto fix on the wall etc complete and all ncessary and as directed by EIC |
| 7 | 160A, 25 kA FP MCCB thermal magnetic with electronic Earth leakage module |
| 8 | Enclosure for 4P MCCB & 2 Nos of 4P MCB |
| 9 | HDPE pipe:Supply & installation of 50mm dia. HDPE pipe fixed on wall/columns/slab with 4-5 mm thick hotdip G.I. spacer with coach screws/ grouted in wall/anchor fasteners & 2 mm thick G.I. fabricatedsaddle with all fixing accessories OR in ground at a depth of 600 mm below ground level excludingexcavation in all types of soils, all as required & as instructed by EIC. |
| 10 | Excavation |
| 11 | Excavation in soft soil/murum including shorting or dewatering, removing of bricks/tiles etc.,disposing the excess earth within the radius of 3000 m, refilling, consolidation of surface etc. asrequired & as directed by Engineer-in- charge. |
| 12 | Cutting of asphalt road / concrete flooring /drain by using hydraulic drilling machine upto 200mmdepth as required and stacking of rocks, refilling, consolidation of surface, making good to theoriginal finish & Disposing the excess earth within the radius of 3000 m as required & as directed by Engineer-in- charge. |
| 13 | Excavation of hard rock, cutting as required including blasting & chiselling, using compressor,dewatering, back filling, if necessary, disposal of excess earth within the radius of 3000M etc.stacking of rocks at selected places as per instructions of E.I.C. |
| 14 | Removal of paver block / shahbaz stone / existing drain wells & refixing as per original as required& as directed by Engineer-in-charge. |
| 15 | Providing New Points on surface looped from the exisitng points or from the exisitng DB in various school premises: |
| 16 | Supply, installation, testing & commissioning of 4sqmm PVC insulated multistranded cu conductorwires in exiting PVC casing & capping/ Conduits wall, etc.Note: PVC casing & capping/ Conduit is measured separately |
| 17 | Supply, installation, testing & commissioning of 2.5sqmm PVC insulated multistranded cu conductorwires in exiting PVC casing & capping/ conduits/ wall, etc.Note: PVC casing & capping/ Conduit is measured separately |
| 18 | Supply, installation, testing & commissioning of 1.5sqmm PVC insulated multistranded cu conductorwires in exiting PVC casing & capping/ conduits/ wall, etc.Note: PVC casing & capping/ Conduit is measured separately |
| 19 | Supply and installation of PVC casing – capping of 25 x 16mm fixing on wall / slab / beam withnylon plug and wood screw complete with all accessories and at the intervels of 400mm approx. |
| 20 | 25 dia mm rigid HMS LHSFT PVC of conduit with all required accessories like junction box ,bend, etc. on surface of slab / wall / column fixed with PVC spacer saddles , nylon / rawal plug, GI wood screws at the intervals of 300mm as per the instructions of Engineer-in-Charge. |
| 21 | Supply, installation, testing & commissioning of 16 A/6A Socket with shutter along with 16A switchin one box similar to Myrius range of M/s Legrand |
| 22 | Supply, installation, testing & commissioning of 6 A Socket along with 6A switch in one box similarto Myrius range of M/s Legrand |
| 23 | Supply, installation, testing & commissioning of 3 nos of 6 A Socket along with one 6A switch inone box and one dummy switch similar to Myrius range of M/s Legrand (8 Module Box should beHorizontal, Two Nos of 4 Module box vertically aligned is not acceptable) |
| 24 | Supply, installation, testing & commissioning of 25 A 3pin socket outlet with plug(Industrial Type)near split AC unit & 25A DP MCB at operating height on wall, in readymade powder coated MSCRCA box with MS cover and with necessary cutouts,interconnections earthing stud etc . MCB shall be with 10KA breaking capacity. |
| 25 | Supply, Installation, Testing & commissioning of 6A socket near exhaust fan complete with allaccessories as required like connection of the plug top in the exhaust fan etc and as per instruction of EIC |
| 26 | Supply, installation, testing & commissioning of the Controlling switch similar to Myrius range ofM/s Legrand of the above exhaust fans ( Switches should be provided on modular box near entranceor the nearest switchboard already installed):Note: Modular Box is in the scope of work |
| 27 | 2 nos of 6A Switches should be provided in the 2 module Box |
| 28 | 4 nos of 6A Switches should be provided in the 4 module Box |
| 29 | 6 nos of 6A Switches should be provided in the 6 module Box |
| 30 | Installation of the department supplied GI duct and Exhaust Fan |
| 31 | Installation of the department supplied 380 mm GI duct/ 300 mm GI Duct and 380 mm sweep / 300mm sweep Exhaust Fan and minor works of finishing including touch up painting etc as required and as per instruction of EIC |
| 32 | Supply, installation, testing & commissioning of area lighting with 3C X 6 Sqmm complete withtermination and other accessories as required and instructed by EIC. The area light is to be tappedfrom the exisitng DB and is to be looped from the nearest area light termination boxes. |
| 33 | 3C X 6 sqmm Al conductor XLPE insulated cable on wall complete with saddles etc as required |
| 34 | Termination Box:IP66 Halogen free and weather proof cable junction box (without knockouts ) similar to catalogue no.KF2500H of M/s HENSEL make with 4-way terminal block and 0.5 - 4 A, SP, MCB (D-Curve) onDIN channel, 2mm thick removable gland plate of suitable size, and open-able plain cover etc. |
| 35 | Swivelling Bracket:Fabrication, supply & installation of swivelling bracket for area light luminaires with 1500 mm long,25 mm nominal bore dia G.I. pipe (class-B) as per IS 1239 bent into required shape for bracket &fixed in 450 mm long ,32 mm nominal bore dia GI pipe class-B having 3 nos of clamping arrangmentmade up of 300 mm long 40x5 mm G.I. strip, welded suitably to it (32 mm dia G.I. pipe) includingmaking 2 nos of 8mm holes on 32 mm dia G.I. ppe for welding suitable nuts on pipe with requiredbolts for tighting the bracket fixed on surface of wall/slab/beam by 6 nos of minimum 10mm anchorfastners with coach screws,painting of whole bracket with two coats of enamel paint by dippingmethod etc.Note: Scope laso includes providing earthing to bracket by interconnecting with 1.5sqmm wire tojunction/terminal box. |
| 36 | Design, Fabrication, supply of exhaust fan air duct (for 300mm/380mm exhaust fan) fabricated out of20 SWG GI sheet complete with splitters, turning vanes, transition pieces, bends, elbows, reducers,flanged joints with neoprene rubber gaskets, angle stiffeners (wherever required), exhaust duct, cowletc. All hardware like nuts, bolts and washers shall be GI. All flanged joints shall be made reasonablyairtight and all interior surfaces shall be smooth. Bends shall be made with throat radius not less thanone half the dimension of the duct in the direction of turn.Note :1) Scope of work includes breaking of wall & filling the leftover gaps in wall after placing the ductwith cement mortar, bricks etc. finishing by applying white cement & touch up painting of that areaby roller/brush etc. all as instructed by EIC.2) Agency has to made their own arrangement (ladder /scaffolding, zoola, etc.) for working at heightof 5-6 Mtr (approx). |
| 37 | Fabrication, Supply, Installation, Testing & Commissioning of 16 SWG S.S.-304 Bird Screenincluding fixing in front entry of exhaust fan GI duct with all SS hardware as required & asInstructed by E-I-C |
| 38 | Insulating Mat :Supply and fixing in position of \"A\" class ELASTOMER\" \"insulating mat for protection to operatorsfor working voltages upto 3.3 KV as per IS 15652 - 2006 of size 1000mm (W) as per instructions ofEIC. |
| 39 | MS Fabrication :Supply, fabrication and installation of supports using MS channel/angle / flat/ MS rod hangersetc.including cutting, fabrication, welding etc. and painting with two coats of primer and two coats ofenamel/ PU paint of approved shade as per instructions of EIC. |