| 1 | WPB (GI) Pole 160x152 (11Mtr.Long,30.44KG/Mtr.)(Total Pole Weight with Base Plate & Stiffner=334.84KG+10.74KG= 345.58KG ) |
| 2 | WPB (GI) Pole 160x152 (13Mtr.Long,30.44KG/Mtr.)- DP (Total Pole Weight with Base Plate & Stiffner=395.72KG+10.74KG=406.46KG ) |
| 3 | Straight Cross Arm 100X50X6mm,9.56KG/Mtr.,each Channel (GI) length1.2mtr., 2no\"s Channel(GI) required=(2x9.56x1.2 |
| 4 | Fish Plate (GI) 50x6mm.,2.36kg/Mtr.,each 0.280 mtr.length, 8no\"s,6 no\"s,6 no\"srequired=(8x2.36x0.280) |
| 5 | Straight Cross Arm 100X50X6mm,9.56KG/Mtr.,each Channel (GI) length 0.306 mtr.,2no\"s Channel (GI)required=(2x9.56x0.306) |
| 6 | DangerPlate,1no\"s.& 2 no\"s |
| 7 | Back Clamp for danger Plate 25X3mm.Flat(GI),0.59Kg/Mtr.Flat(GI)of 0.510 mtr length 1 & 2 no\"s= (1x0.59x0.510) |
| 8 | GI bar bed wire anticlimbing device 3Kg. Per support,2 no\"s qty required = (2x3 kg) |
| 9 | Back Clamp for anticlimbing device 25X3mm.Flat (GI),0.59Kg/Mtr.Flat (GI) of 0.510 mtr length 4no\"s =(4x0.59x0.510) |
| 10 | 11KV pin insulator polymer |
| 11 | HW fitting (B&S) 70KN,3Bolt |
| 12 | Disc insulator(B&S)70KN polymer |
| 13 | Earthing of Support (CoilType) |
| 14 | No-8 GI wire (Dia 4.6mm)0.131KG/Mtr.-2 Mtr.For connecting pole with Coil earthing & lacing |
| 15 | NON METALLIC TIES-11KV 55SQMM CVRD AAAC |
| 16 | IPC for 55sq.mm AAA conductor(For covere dconductor)-11kV |
| 17 | Spike (GI)(using 50 x 6mm Flat(GI)welded with 8mm square bar)(2 No\"s of spike per Set in each Pole) |
| 18 | GI Nut,Bolt & Washer of different sizes(3.55Kg each Cut Pole) & 12.261 kg each dp without AB switch |
| 19 | Black Paint (GIS Numbering & Zebra Stripping) |
| 20 | Yellow Colour Paint(GIS Numbering & Zebra Stripping)for Background |
| 21 | Stock,Storage & Insurance i.e 3% of A |
| 22 | Tools & Plants @2% of C(Except HT Stay Set/GI Pipe earthing) |
| 23 | Transportation @7.5% of C |
| 24 | Erection Charges @5% onTrf/Breaker/WPB/H-Pole |
| 25 | Erection Charges 10% of C (except Trf/Breaker/WPB/H-Pole/Htstay set/GI Pipe/PSC pole/GI Pipe earthing) |
| 26 | Concreting ratio 1:1.5:3(M-20Grade)(500mmX500mmX1800mm)=0.45Cu.mtr(PerPole) |
| 27 | Couping ratio 1:1.5:3(M-20Grade) with dimension (500X500X450)=0.1125 Cumtr (PerPole) |
| 28 | 11KV V Cross Arm (GI) (10.2 Kg each) |
| 29 | Top bracket 100 x 50 x 6 mm GI Channel(GI) (2kg each) |
| 30 | 55 SQ.MM AAACXLPE Covered Conductor |
| 31 | Inspection Fee of Over Head Line (HT)-Rs.375 up to1 km. |
| 32 | Inspection Fee of Drawing Checking and Approval |
| 33 | Top Channel (GI) 100X50X6mm,9.56KG/Mtr.,each Channel (GI)length 2.3mtr., 2no\"s Channe l (GI) required=(2x9.56x2.3) |
| 34 | Double Pole Belting Channel(GI)75X40X4.8mm.,7.14KG/Mtr.,each Channel (GI) length 1.66 Mtr.,4 no\"s Channel (GI) required=(7.14x1.66x4) |
| 35 | 50 x 50 x 6mm. GI Bracing Angle(GI),4.5Kg./mtr.,each Angle (GI) length 2.671 mtr.,4 nos Angle(GI) required=(4.5x2.671x4) |
| 36 | H.T.Stay clamp,50x8mm.Flat (GI),3.14Kg/Mtr.,0.551Mtr.Length,2no\"sqty.required (1Pair) |
| 37 | H.T.Stay set (Complete) |
| 38 | H.T.Stay Insulator Type-C |
| 39 | 7/10 SWG Stay Wire 15kg /stay |
| 40 | GI Pipe Earthing 40mm.3Mtr .Long |
| 41 | 50 x 6 mm Flat (GI) for earthing ,2.36kg/mtr., (2.5mtr.For mesh formation and 2.5mtr.For raising)= 5x2.36 & (10.7 mtr for raising )=10.7 x 2.36 |
| 42 | Concreting ratio 1:1.5:3(M-20Grade)(500mmX500mmX2200 mm)=0.55Cu.mtr (Per Pole) |
| 43 | Fixing of complete 11KV line Complete stay set includes1) Turn BuckleAssembly2) StayRod& Stay plate3) Stay Insulator4) Stay Wire.5) Stay clamps with Nuts & bolts BA will do the excvation including excvation, supply of 0.5 Cum cement concrete foundation 1:2:4 size (500 mm x 500 mm x 800mm ) using 20 mm BHG metal with all labour and material as per TPCODL Drawing & Standard. |
| 44 | Provide necessary civil material for construction of Earthing chamber, excavation & installation of incuding earthing pipe dia up to 100 mm dia for length of 3Mtr. Scope also includes necessary nut bolt,25Kg Bentonide Power,connection & welding within coming earth Flat(GI). The work to be executed as per TPCODL drawing & design |
| 45 | Guarding Channel (GI) 75x40x4.8 mm,7.14KG/Mtr.,each Channel (GI) length 3.5mtr.,4 no\"s Channel (GI) required=(4 x 7.14x3.5)(For Double Pole) |
| 46 | No-6 GI wire (0.192kg/mtr.)for Main String |
| 47 | Construction Earthing chamber including installation of earthing pipe.Making earthing chamber including excavation , soil treatment with bentonide powder , calculation of earth resistance, including Installation of 3Mtr GI Pipe 40mm/50mm including welding of Flat (GI) around pipe . |
| 48 | IPC for 80 sq.mm AAA conductor(For covere dconductor)-11kV |
| 49 | 55 SQ.MM AAACXLPE Covered Conductor |
| 50 | Guarding Channel (GI) 75x40x4.8 mm,7.14KG/Mtr.,each Channel (GI) length 2.2 mtr.,4 no\"s Channel (GI) required=(4 x 7.14x2.2)(For Single Pole) |
| 51 | Eye Bolt (236 mm, 16 mm dia, 1.577 kg/mtr) |
| 52 | GI Nut,Bolt & Washer of different sizes (0.5 Kg/Pole) |
| 53 | 9 Mtr. Long 300Kg. PSC Pole |
| 54 | LT Stay set Complete |
| 55 | 7/12 SWG GI stay wire,Grade-2 |
| 56 | LT stay Clamp (1.40 Kg/pair) |
| 57 | LT Stay insulator |
| 58 | Pole clamp for EYE hook for (XLPE Aerial bunched Cable) |
| 59 | EYE hook for XLPE Aerial bunched Cable |
| 60 | Dead End Clamp suitable for messenger XLPE Aerial bunched Cable |
| 61 | 4C × 35 mm² (P)+1C×35mm² (M)(LTAB Cable ) Without Street Light Core |
| 62 | Insulated piercing connector.Type-B-main 25 to 150 sq.mm & Tap-6 to 35 sq.mm |
| 63 | Coil Earthing |
| 64 | Dangerplate(LT) |
| 65 | Erection Charges 20% of Cof PSC pole -Not to be used for 33 kv |
| 66 | Fixing of LTComplete stay set includes1) Turn Buckle Assembly2) Stay Rod & Stay plate 3) Stay Insulator4)StayWire. 5)Stay clamps with Nuts & bolts, including excvation,supply of 0.5 Cum cement concrete foundation 1:2:4 size (500 mm x500 mm x800 mm)using 20 mm BHG metal with all labour and material (Excavation of earth will be done of size 500X500X1500 mm.) |
| 67 | Concreting ratio 1:1.5:3 (M-20 Grade) (500 mm X500 mm X 1500 mm ) =0.375Cu.mtr (PerPole) |
| 68 | Dismantling of 11/13Mtr.Joist/WPB Pole- 150 X 150 mm/ 160 X 160 mm |
| 69 | Dismantling of 9/8 Mtr. PCC/Joist Pole |
| 70 | Dismantling of ACSR /AAAC34/ 55 mm2 from overhead line |
| 71 | Dismantling of ACSR/AAAC80/100 mm2 from overhead line |
| 72 | Dismantling of varous size of LT AB Cable |