| 1 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/ PVC conduit as required. 3 x1.5 sq mm |
| 2 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles intheexistingMCBDBcompletewithconnections,testingand commissioning etc. as required.Single Pole |
| 3 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. Direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc complete as required. (REX Polyextrusion / Jain Irrigation / Duraline / Avadh Polytube/ Gemini make). 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 4 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 5 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 6 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering (i)Upto 35 sq. mm |
| 7 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective coverin . Above 35 sq. mm and upto 95 sq. mm |
| 8 | Laying of one number PVCinsulated andPVC sheathed / XLPE power cable of 1.1KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Upto 35 sq. mm |
| 9 | Laying of one number PVCinsulated andPVC sheathed / XLPE power cable of 1.1KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Above 35 sq. mm and upto 95 sq. mm |
| 10 | Laying of one number PVC insulated andPVC sheathed / XLPE powercableof1.1KVgradeoffollowingsize in the existing masonry open duct / along pole / loose/loop as required. Upto 35 sq. mm |
| 11 | Laying of one number PVC insulated andPVC sheathed / XLPE powercableof1.1KVgradeoffollowingsize in the existing masonry open duct / along pole / loose/loop as required Above 35 sq. mm and upto 95 sq. mm |
| 12 | Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted/welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required. |
| 13 | Supplyingandmakingendterminationwithbrass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1KV grade as required.i) 2 X 16 sq. mm(22 mm) |
| 14 | Supplyingandmakingendterminationwithbrass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1KV grade as required.i) 3.5 x 50 sq. mm (35mm) |
| 15 | Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, for all lift , including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.In all kinds of soil (for foudation of pole) |
| 16 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :Cement concrete 1:3:6 (1 Cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 17 | Centering and shuttering including strutting, propping etc. and removal of form work for :Foundations, footings, bases for columns |
| 18 | Supplying and Errection of 6 Mtrs hight G.I. octagonal pole on the existing foundation with following specifications - Bottom - 130 mm, Top - 70 mm , thick- 3 mm (bottom & top section) hot deep galvanise sheet , Base plate- 220 mm X 220 mm X 12 mm, foundation bolt size - 20 (M20) mm dia, bolt length - 700 mm, Nos of holes - 04 Nos, Foundation Bolt - 04 Nosincluding supply and embedding 2 Nos. 63 mm dia DWC HDPE pipe for cable entry (from bottom of foundation to top of foundationfor cable entry ), with inbuilt resistance,weathproof electrical junction box having terminal blocks for looping in /looping out of cables, din rail,32 Amp connectors etc mounted on bakelite sheet forflush door having locking arrangement etc. as required as per manufacturer specification and as mentioned in the NIT Make -Crompton /Surya/Utkash/Bajaj/jindal |
| 19 | Supplying and Errection of 7 Mtrs hight G.I. octagonal pole on the existing foundation with following specifications - Bottom - 130 mm, Top - 70 mm , thick- 3 mm (bottom & top section) hot deep galvanise sheet , Base plate- 220 mm X 220 mm X 12 mm, foundation bolt size - 20 (M20) mm dia, bolt length - 700 mm, Nos of holes - 04 Nos, Foundation Bolt - 04 Nosincluding supply and embedding 2 Nos. 63 mm dia DWC HDPE pipe for cable entry (from bottom of foundation to top of foundationfor cable entry ), with inbuilt resistance,weathproof electrical junction box having terminal blocks for looping in /looping out of cables, din rail,32 Amp connectors etc mounted on bakelite sheet forflush door having locking arrangement etc. as required as per manufacturer specification and as mentioned in the NIT Make - Crompton /Surya/Utkash/Bajaj/Jindal |
| 20 | S/I/T/C of Single arm bracket having cap made out of 80 mm dia GI pipe (Medium class),300 mm long and arm made out of 40 mm dia GI Pipe (Medium class) , 0.5 Mtr long to be welded with cap including fixing the bracket with 04 Nos GI nut on existing pole including connection testing etc as required as per direction of engg-in-charge. |
| 21 | S/I/T/C of straight arm bracket having cap made out of 80 mm dia GI pipe (Medium class),300 mm long and arm made out of 50 mm X 50 mm X 6 mm angle iron1 Mtr longto be welded on cap including fixing the bracket with 04 Nos GI nut on existing pole including connection testing etc as required as per direction of engg-in-charge. |
| 22 | S/I/T/C of double arm bracket having cap made out of 80 mm dia GI pipe (Medium class),300 mm long and arm made out of 40 mm dia GI Pipe (Medium class) , 0.5 Mtr long one side and .5 Mtr long another side to be welded with cap including fixing the bracket with 04 Nos GI nut on existing pole including connection testing etc as required as per direction of engg-in-charge. |
| 23 | Installation/Testing/Commisioning of LED street lights/secuirity lightsin the existing GI Pole/octagonal poles of length up to 9 Mtr including connection, testing etc as required as per direction of engg-in-charge. |
| 24 | Desigining,Fabrication Supply/ installation/ testing and commissioning of compartmentalised type outdoor feeder piller, double door made out of 2.03 mm thick CRCA powdered coated sheethaving 200 amps, 04 nos insulated aluminium bus bars and to accommodate following accessories, front & back openable door with proper hinges, R-Y-B LED indicators and P & F of internal connection with suitable size of copper wires, following accessories & angle iron frame of suitable size with 600 mm long legs made out of 50 mm x 50 mm x 5 mm thick angle & grouting the same in suitable cement concrete foundation, arrangement for incoming & outgoing cables, cable termination, earthing, locking, interconnection etc. as required. (CPRI Approved builder). The feeder pillar should have Indicating lamp (LED type) 22.5 mm 230 volt AC Red, Yellow and blue make LK/Havells/simens- 03 nos, CT Ratio (Amp) 100/05, accuracy class 1, burden 05 VA - makeLK/AE/Trinity -03 nos, Digital Multifunction meter (VAF + PF) make LK or equivalent in AE/Siemns- 01 No,Earth studs on both side.The feeder pillar should have provision to acccomodate 125 Amp , 4 Pole MCCB-1 No as a incommer and , 100 Amp 4 poleMCCB -01 nos -as spare ,63 Amp , 2 Pole MCCB-03 No as outgoing). The design of the feeder pillar should got approved from Competent Technical authority before fabrication.(The Fp should be of approx size 600 x 600 x 350 mm deep(area of Feeder pillar is taken in sq mm face area). |
| 25 | Providing and fixing of following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. 63 A, 25 KA, 2 Pole MCCB.(Make Havells/C&S/LK) |
| 26 | Providing and fixing of following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. 100 A, 30 KA, 4 -pole MCCB (Make Havells /C& S/LK) |
| 27 | Providing and fixing of following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. 125 A, 30 KA, 4 -pole MCCB (Make Havells /C& S/LK) |
| 28 | Total of MR items ( Items 18 to 27) |
| 29 | Total of Electrical DSR Items 1 to 14 |
| 30 | Add \"GST\" Difference MF (0.0633) on DSR(Elect)-(Sr. no. 01 to 14) On Rs 110544.00 |
| 31 | Total ofCivil DSR items (Sr. no. 15to 17) |
| 32 | Total of ( Electrical items+ MF+ Civil DSR items) |
| 33 | Add \"Multiplying Correction factor (0.973) on TOTAL ( Rs 13,76,664.00 |