| 1 | Providing and laying in position cement concrete of specified grade excluding the cost of centring and shuttering - All work upto plinth level: 1:1½:3 (1 Cement : 1½ coarse sand : 3 graded stone aggregate 20 mmnominal size). |
| 2 | Supply & Laying following size\" B \" class , G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with accessories like bend, socket etc. for laying earth conductor/ strip / cable in ground/ surface/ recess as required.All as per preapprovedbyEngineerin-charge.(EarthExcavation willbePaid Extra)AllasperpreapprovedbyEngineerin-charge. Foradditional technicalparametersofproducts/work,referAnnexure\"A\"attachedwith this BSR50 mm dia. |
| 3 | Pipe Earthing as per IS:3043- 1987 with 3.0 Mtr. Long, 40 mm dia. \"B \" classG.I.PipeIS:1239(Part-1)2004,EquivalenttoBS:1387 with perforated holes of 12 mm dia ,including all accessories like nut,bolts, reducer, nipple, wire meshed funnel, and Heavy duty weatherproof poly propylene earth pit chamber with lockable Jam free lidsuitable for safe working load 5000 Kg or more of size Top Dia. 225to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm.and embodying the pipe completewithalternatelayerssaltand coke/charcoal,testingofearth resistanceforvalueof5ohmsor lessasrequired&mustrecordby engineerin-chargeduringsite visitandensuretoenterinmeasurment book.Allasperpre approvedbyEngineerin-charge.Foradditional technical parametersofproducts/work,referAnnexure\"A\"attachedwith this BSR . |
| 4 | Supply & Laying following size earth wire in horizontal orvertical run inground/surface/recessincludingriveting,soldering,saddles, making connection with GI/Cu purity purity >95% thimble etc. asrequired. All asperpreapprovedbyEngineerin-charge.For additionaltechnical parametersofproducts/work,referAnnexure \"A\"attachedwiththisBSR . 8 SWG tinned copper Wire |
| 5 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type ofload andsiterequirement)4KVimpulsewithstandvoltage,ISI markedIS 8828(1996) / conforming to IEC 60898-1 2002, IEC60947-2, low watt losses,tripfreemechanisum,energylimitingof class3asperIEC, minimum phase termination capacity of35sq.mm. , conductor line load reversibility , IP 20 contact protectionand fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000upto63A,5000for80 A&aboveratingincludingmaking connections,testingetc.as required.OEMshallhavesubmitNABL/ CPRI/ERDAaccrediated labtypetestreports&Allasperpre approved byEngineer incharge. For additional technical parameters of product/work refer Annexure \"A\" attachedwiththis BSR Single poleMCB (With B/C curve tripping Characteristics0.5 A to 5 A rating |
| 6 | Supplying and drawing FR PVC insulated & unsheathed flexiblecopper conductorasperPWDspecificationforelectricalWorkswith ISI marked(IS:694)andasperIS8130:2013of1.1kVgrade.Wire should be made from 99.90 % purity copper, class 5 stranding inacc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for lesschances of oxidization,insulationPVCtypeA/C/D,flameretardant asperIS 10810-53,betteramperageratingasperIS:3961part5,in existing surfaceorrecessedPVC/MSconduit/casingcapping making connectionswithCopperLugsofsuitablesize, Ferrules,testingetc.as required.OEMMusthaveitsowninhouse NABLlabsetupforall testing facilities for wires. For additionaltechnical parameters of product/ work refer Annexure \"A\" attachedwith this BSR3 x 2.5 sq.mm |
| 7 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Arrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner/ outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware/PVCpipe/openduct/cabletrench/Cabletray(withcable tie) including testing etc. as required of following size. OEM must have it\"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work referAnnexure \"A\" attached with this BSR 16.0 Sq. mm 4 core |
| 8 | Supplying and making end termination with heavy aluminium lugs (Pin / ring type ) confirming to IS 8309 -1993 & IS 8337-1976 dulycrimped withcrimpingtool,PVCtapeetcoffollowingsize.Allasper pre approvedbyEngineerin-charge.Foradditionaltechnicalparametersofproducts/ work , refer Annexure \"A\" attached with this BSR .2.5 Sq.mm |
| 9 | 16.0 Sq.mm |
| 10 | P / L of Double wall corrugated HDPE pipe confirming to IS : 16205 P- 24,StiffnessClass750N,Externallycorrugatedandhavingsmooth surface inside with HDPE Coupler, Elbow, Tee at required Depth below the ground for laying cable of following Nominal Outer dia.MFR Test report from NABL accrediated is to be submitted.(Excavation of Earth & Back filling with compaction is to be Paid Extra)All as per pre approved byEngineer in-charge.For additionaltechnicalparametersofproducts/work , refer Annexure \"A\" attached with this BSR .50 mm |
| 11 | Providing & Fixing of IK08 IP-66 protected high power LED flood light system with single piece Pressure diecast aluminium housing, toughened glassdiffuserwithsuitablelensesonLEDtoachievevariousbeam angles, of high power LED of 3 to 5 watt each . Integrated potted driver asauniqueBISRnumberhavingefficiencymorethan85%andin compliance to BIS certified and Trade mark certificate. The System level Luminaire efficacy >=125 lm/ wt. LED driver Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety.PowerFactor>0.95,THD(I)<10%,drivercurrent<=750mA. driver should be Phase to phase protection of 440 V for 4 Hrs. Electrical Connector,SurgeProtectionMin>=4KVinternaland10KVexternal but inside driver compartment, System life of 50000 Burning hours with 70%ofInitialLumensmaintained,CRI>70andCCT5700K±355K. ManufacturesWordMark/NameEngraved/Embossing/Screenprinting on die cast housing to allow traceability/authenticity. Fixture shall be IS 10322 Complianced.OEM Must have its own in house NABL lab setup foralltestingfacilitiesforLEDfixtures.(LM79/LM80)Certificate/ reportwithliablewarrantyofproduct/accessoriesfromOEMshallbe submitted. All as per pre approved by Engineer in-charge. For additional technicalparametersofproducts/work,referAnnexure\"A\"attached withthisBSR.HighPowerLEDFloodLightMinimumlumenoutput25000 lm |
| 12 | SITCof IP55protecteddoubledoor3phasestreetlighttimerpanel (Minimum size 600mm X300mmX250mm) dust and vermin proof compartmentalisedcubicalpanelmadeoutofCRCAsheet,required hardware,duly paintedby twocoatsofzinc/redoxideprimerfolledby coated / epoxy / PU painted with phosphatisation in grey required shade aftersining.ThepanelhavingPU/Neoprenerubbergasketofnotless than 3mm thickness ,seprate detchable , gland plate M.S base channel , hinged door with lockingarrangement forrequirment /switchgear. Thickness of sheet not be less than1.6mm upto 600mm length /width of any compartment and be of 2.0mm above 600mm. Load bearing stracture shall be of 2.0mm thick sheet supported by base M.S channel if required sidewallsandcablealleycompartmentshavingboltedtypedoorwuth detachableextensiontypestruthavingfollowingcomponentsonDIN rails complete with copper wiring (minimum 4 sq mm).Lug and aluminium busbar of suitable rating and as per suitable rating as paer the instructionsofEngineerinchargeonsuitableironangleframewith properfoundation.1)1No.95Ampere 4 pole AC1 rating contactor make - Schinder.2)3No.32amp.MCBintheincomingcircuit.3) 3No.32amp.MCBintheoutgoingcircuit.4)1No.byepassMCB.5) 1No.MechnicaltimerMake:-Hager.6)3Nos100Ampere,230VporcelainkitkatfuseconformingtoIS: 2086,1983inthe incomer connection before the meter.7)Spaceprovisionandmountingarrangementforthreephaseenergy meter provided by DISCOMS. |
| 13 | ProvidingandLayingRCCFoundationforOctagonal/ConicalStreet Lightpoles,HighmastPolesasperDrawingattachatTableP-4with Following Procedure& Allasper preapproved by Engineer in-charge. Foradditionaltechnicalparametersofproducts/work,referAnnexure \"A\" attached with this BSR .A)ExcavationofPitforFoundationSizeuptorequireddepthfrom Ground levelB) Dressing of Pit and Dry stone pitching 200 mm thick including supply of stones and preparing surface complete.C) Providing and laying in position cement concrete of M-10 grade of 75 mm thicknessD)ReinforcementforR.C.C.workwithTMTbarsincluding straightening, cutting, bending, placing in position and binding all complete.E) Centring and shuttering including strutting , propping etc. and removal of form work for Footing and PedestalF)Providing&Fixingof2no.RequiredSizePLBHDPEPipe& Foundation Bolt with template as per OEM Recommendations.G)ProvidingandLayingReinforcecementConcreteofM-25gradein Footing and Pedestal including Curing the foundation for 7 days.H) Providing and Fixing Nosing Angle 40 mm x 40 mm x 6mm with 2 no. 100 mm long, 10 mm dia. Lugs on each face.Pole Foundation for Octagonal pole from 7 Mtr. To 9 Mtr. |
| 14 | in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \"A\" attached with this BSR . |