| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 10-05-2025 | BoQ Corrigendum | BOQ | 24-05-2025 |
| Sl. No. | Item Description |
| 1 | M&L for disconnecting carefully electrical connection from bothLT (Incomer & Outgoing) sides of the voltage stabilizer, keeping them at safe side and taking out the Voltage stabiliser of capacity250 to 150 KVA of any make for carrying out complete overhauling which shall comprise of the following:-a) M&L for lifting, transporting, handling, the voltage stabilizer to workshop and opening top cover of the voltage stabilizer by unscrewing nuts, bolts, washers etc. including disconnecting core assembly from LT bushing and lifting the same gently and taking out from the shell (container/ body) of the voltage stabilizer. b) M&L for draining out oil from the above said voltage stabilizer in the suitable capacity of container /drums and keeping it in safe custody for reuse. |
| 2 | c) M&L for cleaning the voltage stabilizer body from inside, removing deposited dirt/ sludge/ foreign particles etc. from the bottom/ body of the transformer and drying up the shell from inside before refilling of the transformer oil.d) M&L for cleaning and washing thoroughly core and windings of the voltage stabilizer by hosting down with clean dry oil( without moisture) conforming to IS 335/1983, removing deposited dirt/sludge/foreign particles from the windings/ core, thorough inspection of windings, providing insulations to leads and terminals, heating/ drying/ baking complete carefully and thoroughly inside the heating chamber at suitable temperature to obtain required value of insulation resistance etc. all as directed by Engr-in- charge. e) Lifting and refixing core assembly inside the voltage stabilizer shell gently and carefully, connecting primary/ secondary/ Neutral connections to the bushings assembly including tightening of nuts, bolts, washers of the coreto reduce humming noise all as directed.f) Refilling the filtered transformer oil in the shell of voltage stabilizer complete.g) Refixing the top cover including replacement of cork sheet/ gasket, tightening of nuts/ bolts/ washers etc.complete all as directed by Engr-in charge |
| 3 | h) Lifting/ shifting to the place from where removed or to any location as directed and re-installing the voltage stabilizer including connecting incoming/ outgoing/ neutral and earthing connections etc. all as directed by Engr-in-Charge. j) The inspection of voltage stabilizer shall involve:-i) Checking of all clamps, nuts, bolts including core bolts & cover fixing bolts.Ii) Checking all brazings, joints, tap heads and connection joints.iii) Checking all jumpers, terminations/ connections inside the voltage stabilizer.iv) Inspection of tap changer and servo motor for smooth operation, checking the moving and fixed contacts for contact wear and connection to winding.k) Conducting the tests on core and windings as per IS like ratio, magnetic imbalance, short circuit etc. in presence of Engr-in-Charge and test results shall be signed both by the contractor and Engineer -in-Charge and kept on record. |
| 4 | k) Conducting the tests on core and windings as per IS like ratio, magnetic imbalance, short circuit etc. in presence of Engr-in-Charge and test results shall be signed both by the contractor and Engineer -in-Charge and kept on record.Note:- (i)Any damage to insulators/ bushes/ windings etc. while in the custody of the contractor shall be made good at no extra cost to Department. The serviceability of the voltage stabilizer shall be checked and confirmed by the contractor before taking into his custody.(ii) M&L for rewinding/ re-insulation of LT (primary/ secondary) coils, new transformer oil and dehydration of transformer oil shall be measured and paid separately. |
| 5 | All as per Item No-1.00 herein before but voltage stabiliser of capacity 75 KVA to 25 KVA |
| 6 | M & L for Filtration of transformer oil of servo controlled voltage stabilisers installed at various locations to achieve di-electric strength not less than 60 KV at 2.5mm gap as per relevant IS with portable filtration plant, testing of the oil for the di-electric strength before filtration and after filtration and submit the same signed by both contractor and Engineer in Charge and kept on record complete all as directed. |
| 7 | Supply and topping up of transformer oil with di-electric strength not less than 60 KV in to the Voltage Stabilizers at various locations complete all as specified and as directed. [Make: Poweroil/ Transol/ Sabitha Chemicals] |
| 8 | M&L for rewinding of servo controlled voltage stabilizers of capacity ( 25 KVA to 250 KVA)by winding the defective coils with new copper wire as per I.S. of same gauge and existing size together with new insulated materials/ bracings before placing in to the transformer and assembling the coil with new insulation and fitting the coils in the chamber, testing and commissioning the transformer and recording the test results complete all as directed.[Note: M&L for re-insulation of serviceable coils will be measured & paid separately under relevant items.] |
| 9 | M&L for re-insulating windings of servo controlled voltage stabilizers of capacity ( 25 KVA to 250 KVA) by strip opening of coils (i.e. Primary/ secondary coils) from core assembly safely, unwinding the coils (i.e. Primary/ secondary coils) complete, removing the old defective insulation paper and replacing with newDPC insulation to the copper conductor, re-varnishing of the windings with super varnish including heating/ drying/ backing complete carefully and thoroughly inside the heating chamber at suitable temperature to obtain required value of insulation resistance etc. all as per IS 1986-87 complete all as specified and as directed. |
| 10 | M&L for preparation of old painted surfaces of voltage stabilizers with coarse cloth/ brush and painting throughout externally on exposed surfaces with two coats of smoke grey colour synthetic enamel paint or as approved colour complete all as specified and directed for the following capacity:- |
| 11 | (a) 250 to 150 KVA |
| 12 | (b) 75 to 50 KVA |
| 13 | (c) 25 KVA |
| 14 | Supply & fix as in repair, testing and commissioning of single phase, 240 volts AC servo motor with rated torque not less than 10 Kg/cm, suitable for operation of 75-250 KVA servo voltage stabilizerscomplete all as specified and as directed. |
| 15 | Supply & fix as in repair, testing and commissioning of single phase, 240 volts AC servo motor with rated torque not less than 3 Kg/cm, suitable for operation of 25-50 KVA servo voltage stabilizers complete all as specified and as directed. |
| 16 | Supply & fix as in repair control cards of voltage stabilizers suitable for 250 KVA to 25 KVA of volina Make voltage stabilizers complete all as specified and as directed by Engineer in Charge |
| 17 | Supply & fix as in repair 3 way operating handle switch with connectors for voltage stabilizer of following capacities complete all as specified and as directed. |
| 18 | (i) 250 KVA - 150 KVA |
| 19 | (ii) 75 KVA - 50 KVA |
| 20 | (iii) 25 KVA |
| 21 | M&L for carrying out inspection, checking, repair, maintenance and attending breakdowns for IGBT based UPS of capacity 60 KVA at INHS Dhanvantari comprising of the following outlined services:- (a) The Contractors technical team shall visit the installation site for periodic preventive maintenance check up of the UPS system and the batteries for every 2 months other than breakdown job . During this the system shall be cleaned and general performance will be checked including inspection of all spare parts such as iGBT, Drive cards, relay cards, AC capcitors, inverter cooling fan, ceramic fuses and including replacing the defective spares if any complete, re-assembling, calibration of UPS complete and testing & commissioning complete all as specified and as directed.(b) DC back up source will be maintained by applying white petrolium jelly, checking/ servicing of batteries etc as applicable.(c) Apart from the periodic preventive maintenance visits, all break down calls on the systems covered under contract shall be attended. |
| 22 | (d) Cost of all the spares except Charger card, Power card, Driver card, AC/DC capacitors, IGBT, feed back / isolation transformer, replacement of Batteries to put the UPS in working condition shall be born by the contractor during the contract period.(e) Response time during normal working hours shall be 4 Hrs from the time of receipt of complaint and the resolution time shall bemaximum 48 hrs, based on the nature of complaint and replacement of components and boards. (f) Major Spares such as Charger card, Power card, Driver card, AC/DC capacitors, IGBT, feed back/ isolation transformer, replacement of Batteries required will be measured & paid separately under relevant Schedule. All other spares required for rectifier & inverter section such as other connecting cards, Input fuses, SCR, Inverter cooling fan etc for keeping the UPS in operational state are deemed to be included in the quoted rate.(g) In addition to the above the contractor shall attend and rectify all types of defects arised during the contract period, to keep the UPS system in operational condition.(h) Each UPS will be measured as one Job and any breakdown will be measured seperately. |
| 23 | All as per Item No-12.00 herein before but IGBT based UPS of capacity 05/ 06 KVA at INHS Dhanvantari/ other OTM locations at Minnie Bay. |
| 24 | All as per Item No-12.00 herein before but IGBT based UPS of capacity 80 KVA at INHS Dhanvantari/ other OTM locations at Minnie Bay. |
| 25 | Supply only the following spares for carrying out repairs to UPS of capacity60 KVAunder item Noabove :- |
| 26 | a) Charger Card |
| 27 | b) Power Card / Mother board |
| 28 | c) Capacitor |
| 29 | d)IGBT |
| 30 | e) Isolation/ feed back transformer |
| 31 | f) Driver card |
| 32 | Supply only the following spares for carrying out repairs to UPS of capacity5/ 6 KVA under item No.above :- |
| 33 | a) Charger Card |
| 34 | b)Power Card / Mother board |
| 35 | c) Driver Card |
| 36 | d) Capacitor |
| 37 | e)IGBT |
| 38 | f) Isolation/ feed back transformer |
| 39 | Supply only the following spares for carrying out repairs to UPS of capacity80 KVA under item No.above :- |
| 40 | a) Charger Card |
| 41 | b)Power Card / Mother board |
| 42 | c) Driver Card |
| 43 | d) Capacitor |
| 44 | e)IGBT |
| 45 | f) Isolation/ feed back transformer |
| 46 | Disconnecting & removing existing unserviceable battery and S&F 12 V, 26 AH SMF batteries including terminal clamps, copper lead of suitable length and size including testing and commissioning all as directed. |
| 47 | Disconnecting & removing existing unserviceable battery and S&F 12 V, 42 AH SMF batteries including terminal clamps, copper lead of suitable length and size including testing and commissioning all as directed. |
| 48 | Disconnecting & removing existing unserviceable battery and S&F 12 V, 100 AH SMF batteries including terminal clamps, copper lead of suitable length and size including testing and commissioning all as directed. |
| 49 | Disconnecting & removing existing unserviceable battery and S&F 12V, 200 AH tubular battery including terminal clamps, copper lead of suitable length and size including testing and commissioning all as directed. |
| 50 | Disconnecting & removing existing unserviceable battery and S&F 12V, 150 AH tubular battery including terminal clamps, copper lead of suitable length and size including testing and commissioning all as directed. |
| 51 | Supply and topping up of distilled water in to the tubular batteries upto the marking level complete all as specified and as directed. |
| 52 | Supply, installation, testing & Commissioning ofonline, double conversion IGBT based technology UPS of capacity 5/6 KVA with 3 phase AC input 300 to 450V and 3 phase AC output 415 ± 1%, 50 Hz, pure sine wave with inbuilt isolation transformer necessary protection against short circuit, over load inluding taking down existing UPS complete all as specified and as directed.Make: KRYKARD/ Microtek/ Luminous |
| 53 | Supply, installation, testing & Commissioning ofonline, double conversion IGBT based technology UPS of capacity 3 KVA with 1 phase AC input 280 to 160 Volts and 1 phase AC output 230 ± 1%, 50 Hz, pure sine wave with inbuilt isolation transformer necessary protection against short circuit, over load inluding taking down existing UPS complete all as specified and as directed.Make: KRYKARD/ Microtek/ Luminous |
| 54 | M&L for sub main wiring with 4 runs of 25 Sqmm single core, PVC insulated, PVC innersheathed, unarmoured 1100 Volts grade, multi-stranded, copper conductor cables (FRLSH quality) drawn through PVC casing capping/ conduit/ flexible pipe as per site site requirement with fitting/accessories, fixed on, walls, ceiling etc. as required including 25 Sqmm PVC insulated, unsheathed, multistranded, copper conductor, single core cable as earth continuity wire complete as specified and directed.(i) Four runs of cables, one run of earth wire and one run of rigid PVC conduit shall be measured as one run length.(ii) The quoted rate is deemed to be inclusive of necessary copper lugs for termination of cable. |
| 55 | Supply and fix sheet metal enclosure of thickness not less than 1.6 mm with, 2 pole DC MCCB of rating 320 Amps, thermal magnetic type complete all as specified and as directed. |
| 56 | Supply and fix sheet metal enclosure of thickness not less than 1.6 mm with, 2 pole DC MCCB of rating 32 Amps, thermal magnetic type complete all as specified and as directed. |
| 57 | Supply & fix as in repair sheet metal enclosure of thickness not less than 1.6 mm with IP-42 protection along with 415 Volts, 50 Hz, 4P, 125 Amps Bypass switch including indicating lamps complete all as specified and as directed. |
| 58 | M & L for sub-main wiring with 10 Sq.mm (nominal area) PVC unsheathed multi strandard copper conductor PVC insulated 1100 volt grade4 runs of single core cable drawn through and including rigid PVC conduit medium grade minimum 25 mm size / casing capping as per site requirement and its accessories complete along with one single core PVC insulated unsheathed multistranded copper conductor cable green colour of size 10 Sqmm as continuous earthing wire and connecting to common earth dolly completely concealed in walls/ceiling/roofs all as directed and specified. Note : Five runs of PVC copper cable and one run of PVC conduit will be measured as one RM. |
| 59 | Supply & fixing IP 65 / 66thermoplastic-polycarbonate cable junction box of size 155X210X92which is totally shock proof, water proof, halogen free, silica and having internally embedded gasket technology fixing on surface / framewith the helpofrequired size / self drill screw complete all as specified and as directed by Engineer-in -charge. |
| 60 | Supply, fabricate and fix cross arms any size along with, brackets, clamps, bolts, nuts, washers, bracers etc including drilling holes, cold/hot complete to accommodate UPS batteries, including one primer coat and one under and finishing coat of paint complete all as specified and as directed by Engineer in Charge. |
| 61 | M & L for servicing, maintenance, repair & attending break down calls of M/s STERIS make surgical OT lights by authorized rep of OEM by inspecting parts / spares for general repairs / servicing as per the following scope of work given below for smooth and trouble free operation of equipment to the entire satisfaction of user / department all as specified and as directed.Scope of Work:(i) Wiring inspection: Switch OFF, strip opening of OT light covers. Inspection of wiring in suspension from control board for loose connections, pitted terminals, peeled of insulation and rectifing all defectsMechanical connections: Inspecting movements of all arms for smooth functioning including lubrication and replacement of defective parts complete. Adjustment/ replacement of tension springs, inspecting all screws, yoke load supports, securing keys and other connected accessories complete as per OEM instructional manual and rectifying the defects inclusing replacement of defective parts for ensuring smooth operation of all mechanicla connections |
| 62 | (iii) Lightheads: Restore power supply, verify that the sterile handle seats firmly and latches securely on the mount, check condition of lens for scratches, cracks, turn on light and increase to maximum intensity, verify smooth rotation of the pattern size change system, verify all LEDs lit. Trouble shoot if observe any modules having unlit LEDs.(iv) Control: Connect with service software to analyse data synchronization, run hour, LED Module mA measurement, digital live voltage measurement and observe current levels when on maximum intensity. Calibrate only if lights are not maintaining at or near target/ rated current. Turn on light and verify light operation through all intensities.(v) Articulations: Fully articulate suspension about each pivot point. verify range of motion, ease of movement, and that light/ display does not flicker. Check thet light/ monitor does not drift when positioned. Tighten and/or replace brake screws as required and adjust tension as required and verify over all condition of arms for smooth movement. Re-install covers and inspect all arms for missing or loose screws all per OEM instructional manual and recommendation. |
| 63 | Note:(a) The rep of OEM shall visit the installation site for periodic preventive maintenance check up of the OT surgical lights for every 3 months other than breakdown job.(b) Apart from the periodic preventive maintenance visits, all break down calls shall be measured seperately.(c) The quoted rate is deemed to be inclusive of repair/ replacement of defective Power supply board, Master control board, Light head board, wall control interface board, minor parts such as nuts, bolts, grease etc.(d) The spare parts such as LED module, Light head intensity keypad,Main suspension break screw, Spring arm break screw, dome break screw, spring arm cover, rear cover, wall control membrane switch, and light head cover shall be measured and piad seperately under relevant items.(e) In addition to the above the contractor shall deploy rep of OEM to rectify any type of defects arised during the contract period, to keep the OT lights in operational condition. |
| 64 | (a) OT 1 Lights |
| 65 | (b) OT 2 Lights |
| 66 | (c) OT 3 Lights |
| 67 | (d) Minor OT Lights |
| 68 | Supply only the following spares for carrying out repairs to OT surgical lights under item No. 8 above :- |
| 69 | (a) LED Module |
| 70 | (b) Light head instensity keypad |
| 71 | (c) Main suspension break screw |
| 72 | (d) Spring arm break screw |
| 73 | (e) Dome break screw |
| 74 | (f) Spring arm cover |
| 75 | (g) Rear cover |
| 76 | (h) Light head cover |
| 77 | M & L for cleaning of semi underground static water tank of capacity 1.65 lakh ltrs by the following method :-(a) The inner surface of the walls of the tank shall be cleaned with wire brush after emptying the water in the tank to adjacent tank.(b)After thorough cleaning of the tank, the cleaning water and sludge is to be removed by using pump and the sludge has to be disposed off at a place as directed.(c)After removing the sludge from tank, the tank shall be cleaned with anti bacterial agents.(d) Applying water proofing compound to arrest leakages and seal the cracks on walls.(e) After complete treatment, writing of \"Tank capacity\" \"Date of cleaning and due date of cleaning\" on wall including applying two coats of white washing to external surfaces complete all as specified and as directed |
| 78 | All as per item No 35.00 above here-in-before but of semi underground sump capacity 60000 Liters complete all as directed. |
| 79 | M/L for Inspection, maintenance and servicing of (60-105) HP Deisel Engine pump for \"B\" check once in a 03 month or 250 hrs whichever is earlier of the engine for smooth functioning and carrying out the complete checks as per the manufacturers instructions all as specified and directed by the Engineer-in-Charge:-(a)Replace the lubricating oil.(b)Replace lubricating oil filter element.(c)Replace lubricating oil by pass filter element.(d)Replace the fuel filter element.(e)Check engine coolent.(f)Check the crank case breather.(g)Check turbo charger (for turbo fitted engine).(h)Draining out unserviceable engine oil from sump.(i)Checking & adjusting fan belts.Note.replacement of engine oil & radiator coolant are included in the rate quoted. |
| 80 | M & L for dismantling the pump of following capacity, isolating suction / delivery line connections, checkingthe worn out parts like impeller, shaft, stuffing box, shaft sleeve using Micrometer and transporting to workshop for repairs, check for condition of bearings, removing scales from impeller and pump housing, building the worn out metal of transmission shaft to required level, machining to the required size on lathe machine, grinding and finishing to match the sleeve, and fixing into the housing, re-assembling, transport back to the installation, installing in position, check for alignment with dial gauge, inserting shims where necessary, refixing with coupling, tightening with torque wrench to required level, re-connecting the flanged pipe connections of suction/ delivery, greasing for bearings including replacement of rubber insertion etc complete.Note :- Spares will be measured and paid separately under relevant schedule. |
| 81 | (a) 60 HP - 40 HP |
| 82 | (b) 12.5 HP / 10 HP |
| 83 | Supply only for incorporating of pumpset repair work for pumpset of capacity 60 HP - 40 HP :- |
| 84 | a)Shaft bushes with check nuts (stainless steel) for above pumpset. |
| 85 | b)Ball bearings suitable for above pump. Make : NBC / SKF. |
| 86 | c)Metal Coupling for above pumpset. |
| 87 | d) Mechanical shaft seal |
| 88 | Supply only for incorporating of pumpset repair work for pumpset of capacity 12.5 HP / 10 HP :- |
| 89 | a)Shaft bushes with check nuts (stainless steel) for above pumpset. |
| 90 | b)Ball bearings suitable for above pump. Make : NBC / SKF. |
| 91 | c)Metal Coupling for above pumpset. |
| 92 | d) Gland packing end cover (Stainless steel of suitable grade)as per existing size |
| 93 | M & L for dismantling the defective induction motor of any capacity/make/class of insulation from foundation bed, disconnecting all electric supply connections, duly coupled with pump/compressor, trasnporting to workshop removing burnt out widing from stator/rotor, rewinding with suitable gauge of super enamelled copper wire and replacing DE /NDE bearings, insulation materials, varnishing , heating, greasing of bearings etc complete, re-assembling, testing and commissioning of following capacity motors all as directed.Note : Terminal block, Bearings of motorif required will be measured & paid separately under relevant schedule items. |
| 94 | (a) 60 HP - 40 HP |
| 95 | (b) 12.5 HP / 10 HP |
| 96 | M & L for dismantling of motor of following capacities pumpset from installed position after disconnecting the coupling and electric connections and transporting the motor to the work shop, strip opening of the motor complete incl dismanlting stator,rotor assembly and cleaning the complete assemblies by taking out perished glass sleeve of connecting leads from common termination to terminal block,and washing with carbon tetra chloride, decarbonising and cleaningthe rotor with CTCsolution.Replacing the glass sleeve of connecting leads from common termination to terminal block, binding the loose coils with binding cloth, varnishing the coils complete and applyng bectol on the excitor coils, stator coils and heating complete, reassembling the unit and testing with megger for insualtion value and re-assembling, aligning with pump, re-inserting shims where necessary, refixing with coupling, tightening with torque wrench to required level, re-connecting the electric cable etc and check for drawing current testing, commissioning etc all as directed. |
| 97 | (a) 60 HP - 40 HP |
| 98 | (b) 12.5 HP / 10 HP |
| 99 | Renewal of rubber bush coupling for the following capacities of pumpsets complete all as directed:- |
| 100 | (a) 60 HP to 40 HP |
| 101 | (b) 12.5 HP / 10 HP |
| 102 | Supply only following bearings required during rewinding / varnishing of motors all as directed:- |
| 103 | (a)DE/NDE bearings suitable for 40 to 60 HPmotor |
| 104 | (b)DE/NDE bearings suitable for 12.5 / 10 HP motor. |
| 105 | Supply only terminal block complete with hardware of following capacity motors:- |
| 106 | (a) 60 HP to 40 HP |
| 107 | (b) 12.5 HP / 10 HP |
| 108 | Taking down unserviceable pressure guage of any size complete all as specified and as directed. |
| 109 | Supply and fixing of pressure gauge0-12 kg/cm² complete with necessary fittings incl disamntling old oneall as directed. |
| 110 | Servicing/ attending break down complaints/ cleaning the motor starter panel of following size, replacing defective control wiring of starter/MCCB/contactor/meters/indicator lamps/electronic timer/relay/connecting cooper wires, tightening the cable end terminals with bus bar/ connector links/ MCCB/ MCB/ contactor/ relay and timer end terminals with proper torque for avoiding loose connections complete all as specified and as directed for the following capacity of pumps:Note: a) Spare parts such as MCCB, MCB, contactor, meters, indicator lamps, copper wire of size greter than 10 Sqmm shall be measured and paid seperately under relevant items as supply only.b) Apart from the servicing maintenance visits, all break down calls shall be measured seperately. |
| 111 | a) Motor starter of capacity 60 HP |
| 112 | b) Motor starter of capacity 40 HP |
| 113 | c) Motor starter of capacity 12.5/ 10 HP |
| 114 | Supply only MCCB 3 Pole 250 A, 25 KA breaking capacity,Ics=100% Icu, thermal magnetic release type complete. |
| 115 | Supply only 3 pole power contactor with AC3 duty current rating not less than 70 Amps, conforming to IEC 60947-4-1 complete all as specified.Make: MNX 70 of L&T/ LC1D503 of C&S/ equivalent model in Indo Asian/ Schneider. |
| 116 | Supply only 3 pole power contactor with AC3 duty current rating not less than 50 Amps, conforming to IEC 60947-4-1 complete all as specified.Make: MNX 50 of L&T/ LC1D403 of C&S/ equivalent model in Indo Asian/ Schneider. |
| 117 | Supply only electronic timer with adjustable timer setting complete all as specified. |
| 118 | Supply only thermal overload relay range 45 Amps to 75 Amps of 160A max complete all as specified. |
| 119 | Supply only thermal overload relay range 30 Amps to 50 Amps of 125A max complete all as specified. |
| 120 | Supply only indiactor lamps complete all as specified. |
| 121 | Supply only PVC insulated, single core, multistrand, 1100 Volts grade copper cable of size 25 Sqmm complete all as specified .Make: Polycab/ Havells/ Gloster/ RR Kabel |
| 122 | Supply only PVC insulated, single core, multistrand, 1100 Volts grade copper cable of size 16 Sqmm complete all as specified .Make: Polycab/ Havells/ Gloster/ RR Kabel |
| 123 | Supply and fixing as in repair DOL starterthree phase, 415 Volt with over load relay suitable for 10/12.5 HP capacity with sheet steel enclosure complete all as directed. |
| 124 | Material and labour for preparation/cleaning of outer surface by scrapping with emery paper or other means and painting of fire fighting pump motor of following sizes with two coat of synthetic enamel paint red colour all as specified and as directed. |
| 125 | (a) 60 Hp |
| 126 | (b) 40 HP |
| 127 | (c) 12.5 / 10 HP |
| 128 | M& L for preparation to external old steel surface of fire fighting pipe line and connected fittings of various sizes n. exc 60 cm girth including holderbats, distance pieces, etc. (length measured over bends, branches etc) upto Ground floor level height/ pipe line on terrace by scraping and applying two coats of synthetic enamal paint over a coat of red oxide primer complete all as specified and as directed.Note :- (i) Colour of paint will be decided by Engr-in-Charge.(iii) Contractor shall made good all disturbed surfaces and quoted rate deemed to be inclusive for the same. |
| 129 | M& L for preparation to external old steel surface of fire fighting pipe line and connected fittings of various sizes n. exc 60 cm girth including holderbats, distance pieces, etc. (length measured over bends, branches etc) upto height G+3/ terrace level by scraping and applying two coats of synthetic enamal paint over a coat of red oxide primer complete all as specified and as directed.Note :- (i) Colour of paint will be decided by Engr-in-Charge.(ii) Scaffolding and other safety precution equipment will be arranged by the contractor for the pipes which are upto G+3 floor/ terrace height and cost for the same shall be deemed to be included in the quoted rate.(iii) Contractor shall made good all disturbed surfaces and quoted rate deemed to be inclusive for the same. |
| 130 | Taking down old unserviceable MS pipe of any class and any size complete all as specified and as directed. |
| 131 | Supply and lay as in repairof MS pipe ERW Heavy (IS1239) errect, jointing complete of 150 mm dia with necessary supports and specials such as tees, bends, reducers etc including consumables and making good the disturbed surfaces of wall/ ceiling etc and taking down old unserviceable MS pipe complete all as specified and asdirected. |
| 132 | All as per item srl No 63.00 here-in-before but of 100 mm dia complete all as specified and as directed. |
| 133 | All as per item srl No 63.00 here-in-before but of 80 mm dia complete all as specified and as directed. |
| 134 | All as per item srl No 63.00 here-in-before but of 50 mm dia complete all as specified and as directed. |
| 135 | All as per item srl No 63.00 here-in-before but of 25 mm dia complete all as specified and as directed.Note : for item Nos. 62.00 to 67.00(i) The excavation earth work measured and paid seperately under relevant item.(ii) Flanges & gaskets at both ends of each pipe shall be included in the quoted rate.(iii) The quoted rates also include for cutting of existing pipe for insertion offittings / new branch pipe.(iv) Painting to the new pipe including applying primer shall be measured and paid seperately. |
| 136 | M& L for preparation to external new steel surface of fire fighting pipe line and connected fittings of various sizes n. exc 60 cm girth including holderbats, distance pieces, etc. (length measured over bends, branches etc) upto Ground floor level height/ pipe line on terrace by scraping and applying two coats of synthetic enamal paint over a coat of red oxide primer complete all as specified and as directed.Note :- (i) Colour of paint will be decided by Engr-in-Charge.(iii) Contractor shall made good all disturbed surfaces and quoted rate deemed to be inclusive for the same. |
| 137 | M& L for preparation to external old steel surface of hose box/door/panel boardand connected accessories of various sizes by scraping and applying two coats of synthetic enamal paint over a coat of red oxide primer complete all as specified and as directed.Note :- (i) Colour of paint will be decided by Engr-in-Charge.(ii) Contractor shall made good all disturbed surfaces and quoted rate deemed to be inclusive for the same. |
| 138 | M&L for sprinkler testing by applying fire with proper arrangements to drain the water and replace the blown sprinkler with new sprinkler glass bulb type (Standard response) as per IS:15106/TAC guidelines 68 degree temperature rating pendent type by using teflon tape to arrest water leakage and resolving any issues raised in pipe during the testing complete all as specified and as directed.Note: 1) The quoted rate is inclusive of replacement of sprinkler during testing.2) The quoted rate is not inclusive of replacement of damaged sprinkles other than testing period and replacement of pipe line.3) Testing of each sprinkler shall be measured as one Job. |
| 139 | S&F as in repair Sprinkler glass bulb type (Standard response) as per IS:15106/TAC guidelines 68 degree temperature rating pendent type complete all as specified and directed. |
| 140 | Taking down old unserviceable valves of any type and any size complete all as specified and as directed. |
| 141 | S&F ball type foot valve flanged type with CI body of size 200 mm dia along with cast iron body strainer, nitrile rubber coated ball with suitable gasket, nut, bolts including suitable flange to match with the holes of foot valve to make the connection with the existing suction pipe line and necessary welding work complete all as specified and as directed.Make: Normex/ Audco/ Intervalve or equivalent make approved by GE. |
| 142 | S&F butterfly valve with CI body of size 100 mm dia with suitable gasket, nut & bolts including necessary welding works as required complete all as specified and as directed.Make: Audco/ Intervalve/Upadhyay/ Leader |
| 143 | S&F butterfly valve with CI body of size 150 mm dia with suitable gaskit, nut & bolts including necessary welding works as required complete all as specified and as directed.Make: Audco/ Intervalve/ Upadhyay |
| 144 | S&F butterfly valve with CI body of size 80 mm dia with suitable gaskit, nut & bolts including necessary welding works as required complete all as specified and as directed.Make: Audco/ Intervalve/ Upadhyay/ Leader |
| 145 | S&F ball valve of size 25 mm dia with necessary welding works as required complete all as specified and as directed |
| 146 | Supply and fixing cast Iron Non return valve, short body type, flanged ends heavy duty as per IS 5312, PN 1.6 of size 150 mm dia including 6mm thick rubber insertion ring complete all as specified and as directed.Make: Audco/ Intervalve/ Upadhyay/ Leader |
| 147 | Supply and fixing cast Iron Non return valve, short body type, flanged ends heavy duty as per IS 5312, PN 1.6 of size 80 mm dia including 6mm thick rubber insertion ring complete all as specified and as directed.Make: Audco/ Intervalve/ Upadhyay/ Leader |
| 148 | Taking down old unserviceable yard hydrant post of any type and any size complete all as specified and as directed. |
| 149 | M & L for yard hydrant post 80 mm dia MS of flange type complete all as specified and as directed.Make: Getech/ Newage or equivalent make |
| 150 | M & L for servicing of 26 No fire hydrant posts for arresting any leakage, replacing damaged O rings, lock plugs, end caps with chain complete all as specified and as directed.Note: (i) lock plugs shall be measured and paid seperately under relevant item as supply only. |
| 151 | Supply only lock plugs for fire hydrant posts complete |
| 152 | M & L for servicing, maintenance, repair & attending break down calls of M/s Edwards/ M/s Apollo make fire alarm panel as per OEM instructions which includes preventive maintenance schedule of fire alarm panel and connected items, cleaning of panel and all connected items, checking the functionality of all modules, checking for any malfunction of the system and rectifying the same, replacing any damaged wire / comminication cable, checking for receiving the notofications properly and if not rectifying the same and changing the mapping location with the item as per site requirement complete all as specified and as directed.Note:(a) The rep of service engineer with proficiency in above OEM panel shall visit the installation site for periodic preventive maintenance check up of fire alarm system for every 6 months other than breakdown job.(b) Apart from the periodic preventive maintenance visits, all break down calls shall be measured seperately(c) The quoted rate is inclusive of minor parts only and all major parts like control module, monitor module, power supply board, loop card, mother board and display board shall be measured and paid seperately under supply item only.(d) In addition to the above the contractor shall deploy service engineer to rectify any type of defects arised during the contract period, to keep the fire alarm system in operational condition.(e) The quoted rates are inclusive of boarding/ lodging/ transportation of service engineer along with T&P & necessary software. |
| 153 | Supply only control module suitable for the existing fire alarm panel complete all as specified and as directed. |
| 154 | Supply only monitor module suitable for the existing fire alarm panel complete all as specified and as directed. |
| 155 | Supply only power supply control board suitable for the existing fire alarm panel complete all as specified and as directed. |
| 156 | Supply only mother board suitable for existing fire alarm panel complete all a s specified and as directed. |
| 157 | M & L for servicing, maintenance, repair & checking functionality of Heat & Smoke detectors of make M/s EDWARDS/ M/s Apollo by zone wise with all connected items (isolators/ manual call points/ response indicators/ Hooter cum strobe etc) connected through wires which includes cleaning of Heat & Smoke detectors with blower and all connected items, checking the functionality of all modules, checking for any malfunction of the detectors and rectify/ replace the same, replacing any damaged wire complete all as specified and as directed.Note:(a) The periodic preventive maintenance check up of fire detection system shall be carried for every 3 months other than breakdown job.(b) servicing/ maintenance/ repair & checking functionality of Heat & Smoke detector of each zone shall be measured as one Job. Apart from the maintenance visits, all break down calls shall be measured seperately.(c) The quoted rate is inclusive of minor parts only and all major parts like Heat & semoke detecors, manual call point, response indicators and hooter cum strobe shall be measured and paid seperately under supply item only.(d) servicing/ maintenance/ repair & checking functionality of Heat & Smoke detector of each zone shall be measured as one Job.(e) The quoted rates are inclusive of boarding/ lodging/ transportation of service engineer along with T&P. |
| 158 | Supply only Heat & smoke detectors addressable type compatible for EDWARDS EST 3X/ Apollo make fire alarm panel complete all as specified. |
| 159 | Supply only addressable Manual call point resettable type compatible for EDWARDS EST 3X/ Apollo make fire alarm panel complete all as specified. |
| 160 | Supply only Fire Alarm Sounder cum strobe shall have audibility level not less than 85 DB measured at 1 Mtr, strobe shall have not less than 75 cd flashing at 1 Hz for visual indication with control module, operating voltage 24 volts DC the sounder cum strobe shall be integrated with control modules of existing FACP complete all as specified. |
| 161 | Supply only response indicators complete all as specified and as directed. |
| 162 | Taking down old unserviceable hydrant valve of any type any size complete all as specified and as directed. |
| 163 | Supply and fixing fire hydrant valve, single headed including required washer and fittings completeall as specified and directed. |
| 164 | Supply and fixing fire hydrant valve, double headed including required washer and fittings completeall as specified and directed. |
| 165 | Taking down old unserviceable Hose pipe of any length complete all as specified and as directed. |
| 166 | Supply and fix C P Hose of 15 m length complete all as specified and as directed. |
| 167 | Taking down old unserviceable gun metal branch pipe of any size complete all as specified and as directed. |
| 168 | Supply and fix branch pipe gun metal 63 mm inlet made threaded outlet 15 mm bore nozzle short complete all as specified and as directed. |
| 169 | Taking down old unserviceable hose box of any type and any size complete all as specified and as directed. |
| 170 | M & L forhose box of any description and providing new hose box made of 18 gauge MS sheet 800x600x250mm with double door with 4mm thick glass and door frame made of 16 gauge MS sheet painted fire red outside and brilliant white inside yardincluding taking down unserviceable hose box complete all as specified and as directed. |
| 171 | Taking down old unserviceable hose reel drum of any type and any size complete all as specified and as directed. |
| 172 | Supply and fix Hose reel Drum including 30 m long and 20 mm dia high pressure hose reel and taking down unserviceable hose reel drum complete all as specified and as directed. |
| 173 | Supply and fix as in repair of transparent acrylic sheet thickness of minimum 3 mmfor hose boxcomplete all as specified and as directed. |
| 174 | Excavation in trenches of soft/loose soil not exc 1.5 mtr wide and not exc 1.5 mtr in depth for foundation, pipe, laying of cable etc not exc 10 Sqmtr on plan and not exc 1.5 mtr in depth and getting out complete all as specified and as directed |
| 175 | Returning filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25 cm in soft/loose soil all as specified and as directed by Engineer-in -charge. |
| 176 | Removing excavated materials (soil) to a distance not exceeding 50 meters and depositing where directed at a level not exceeding 1.5 meters above the starting point all as specified and as directed by Engineer-in -charge. |
| 177 | M & L for Cutting the tarmac / hard standings and excavating in trenches across the road for laying pipe including making good the excavated portion by means of PCC 1:3:6, type C2 matching with the surroundings all as directed. |
| 178 | Demolition of brick work or stone boulder masonry, built in cement mortar complete all as specified and as directed. |
| 179 | M&L for brick work in valve chamber or support baseor straight or curved on plan with sub class \"B\" bricks in cement mortar 1:6 complete at various locations all as specified and directed |
| 180 | Demolition of cement concrete of any description and in any position not otherwise specifically provided complete all as specified and as directed. |
| 181 | M&L for cement concrete in foundations, filling and mass concrete type D2 1:4:8( 40 mm graded aggregate) complete all as directed. |
| 182 | M & L for carrying out repair, maintenanace, servicing and attending breakdown of oil fired incinerator of Make HATT, includinginspecting all parts, control circuit wiring and control circuit boards / mother board for general repairs / servicing / over hauling as per OEM instructions for ensuring smooth and trouble free operation of equipment to the entire satisfaction of user / department all as specified and as directed :(a) The rep of OEM shall visit the installation site for periodic preventive maintenance check up of the Fire incinerator system for every 6 months other than breakdown job . During this the system shall be cleaned and general performance will be checked including inspection of all spare parts such as fuel injection pump, primary burner system, secondary burner system, operation of hydraulic doors, ID fan, FD fan, entire control circuit wiring, PCB board / control circuit board and all other connected items for functioning of the fire incinerator and repairing the same if found defective and testing & commissioning after rectifying defect complete all as specified and as directed.Note:(i) All spare parts such as nozzle assembly, photo cell light detector, fuel pump, solenoid switch,ignition electrode, thermocouple, control circuit borad / mother board / PCB, burners, hydraulic oil shall be measured and paid seperately. (ii) The quoted rate inclusive of cleaning of Fire incinerator and connected system as per OEM instructions.(iii) The charges for fixing, commissioning, testing of new spares including diamantling old units is included in the quoted rate.(Each job per incinerator is for 04 months and breakdown call will be measured and paid seperately).(iv) The quoted rates are inclusive of boarding/ lodging/ transportation of service engineer along with T&P. |
| 183 | Supply only following spares for carrying out repairs / maintenance / servicing under item No 114.00 |
| 184 | (a) Supply only Nozzle assembly |
| 185 | (b) Supply only Photocell Light detector |
| 186 | (c) Supply only control circuit board / mother board |
| 187 | (d) Supply only hydraulic oil |
| 188 | (e) Supply only Fuel pump BFP 41L3 |
| 189 | (f) Supply only Solenoid switch |
| 190 | (g) Supply only Ignition electrode |
| 191 | M & L for carrying out repair, maintenanace and attending breakdown calls of chemical desiccant dehumidifier of capacity 600 cmh (FFB - 600),including strip opening of dehumidifier inspecting parts / spares for general repairs / servicing / over hauling as per the following scope of work given below for ensuring smooth and trouble free operation of equipment to the entire satisfaction of user / department all as specified and as directed: |
| 192 | Scope of work:(i) Filters: Check for physical status of filters, cleaning the both process and reactivation air filters by racking out filters from dehumidifiers and clean both the filters with compressed air or wash with warm soap solution and refix both the filters in their location. If the filters are damaged replace the filters of OEM recommended make.(ii) Desiccant Rotor: Check the desiccant rotor for smooth operation, no sign of discoloration, pits, cracks due to dirt, dust or other foreign material. The desiccant rotor should be removed for cleaning from its position safely as per OEM instaructions. Cleaning the rotor by dry vaccum and dusting brush with attachment with soft bristle brush and vaccum both the surfaces of rotor or by applying moisture free compressed air of pressure rating less than 2 Kg/sqcm on one side at lease 250mm away from rotor surface and vaccum on other side, refix the rotor in its original position. The cleaning of desiccant rotor is upto full satisfaction of Engineer in charge and if the rotor replacement is inevetable due to poor performance of rotor the same should be replaced with new desiccant rotor of OEMmake complete all as directed.(iii) Seals: Check the seals for any wear and tear and air leakge, the same should be replaced with high performing silicone seals complete all as directed.(iv) Reactivation air heater: Check the heater element complete all as directed.(v) Fan Motors: Check for any abnormal sound from the motors and clean both the process and reactive motors by removing from their original postion, remove the impeller and clean the fan impeller throughly and refix the same in original location.(vi) Bed drive unit: Disconnect the bed drive motor supply check for any wear and tear of bed drive timing belt and replace the same if damaged and care should be taken for to avoid revese rotation of motor while refixing.(vii) Electric circuit: Tighten all connections by applying proper torque . |
| 193 | (viii) Attending complaints of Dehumidifier of following capacity, checking for control circuit and power circuit connections from MCB TPN / SPN plug socket control point to dehumidier, healthiness of process fan & react fan motor winding, functionality of the contactors, over load relay, differential pressure switch, delay timer, heater coil, thermostat, limit switches, illuminating switches,rotation of dessicant rotor / bed drive reduction unit, complete as per nature of complaint and rectify the defect by replacing concerned material / rewinding of fan motors complete to make the dehumidifier operational all as specified and as directed.Note:(i) The quoted rate is inclusive of control wiring.(ii) Each complaint / servicing attended shall be measured as one job through job card.(iii) All spare parts incorporated should be as per OEM recommendation only.(iv)Sapres like control wiring, nuts / bolts / washers etc, T&P for servicing are deemed to be included in the quoted rate.(v) Replacement of spares such as filters, desiccant rotor, bed drive unit, Bed drive timing belt limit switch, thermostat, seal group, heater coil, LED lamp, switches, contactors, relays, MCBs, rewinding of fan motor will be measured and paid separately under relevant items. |
| 194 | (vi) It is responsibility of contractor to engage required manpower as per requirement and take necessary measures to run the equipment in event of breakdown to the satisfaction of user and as directed. Considering the sensitive nature of installation the contractor shall always be in a position to make alternate standby arrangement in case of break down. Contractor shall keep his spares ready in advance for carrying out repairs without any delay. Any break down shall be attended within 2 Hrs and defects shall be rectified within 24 Hrs of time otherwise a recovery of Rs 2000/Hr along with cost of perished storage products due to non-functional of equipment shall be attributed to contractor without any further claim. The cost for same is deemed to be included in scope of item. The labour charges for fixing, commissioning, testing of new spares including diamantling old units is included in the quoted rate.(Each job per each dehumidifier unit for 04 months and breakdown call will be measured and paid seperately). |
| 195 | Supply only following spares for carrying out repairs / maintenance / servicing under item No 116.00 |
| 196 | Supply only react air filter of size 280 x 160 x 25 mm for FFB 600 model. |
| 197 | Supply only process air filter of size 350 x 160 x 38 mm for FFB 600 model. |
| 198 | Supply only Desiccant rotor of OEM make for FFB 600 model. |
| 199 | Supply only seal group of OEM make for FFB 600 model. |
| 200 | Supply only bed drive timing belt of OEM make for FFB 600 model. |
| 201 | Supply only MCB TPN, 415 Volts, 32 Amps 10 KA complete |
| 202 | Supply only power contactor 3 phase, operated by 230 volts complete. Cat Part No. 10919 |
| 203 | supply only Thermal overload relay complete Cat part No. 10968 |
| 204 | Supply only differential pressure switch complete Cat part No. 11065 |
| 205 | Supply only delay timer 0-10 (s/m/h) range Cat Part No. 11093 |
| 206 | Supply only heater coil 2.4 KW,230 Volts AC tubular type complete Cat Part No. 11168 |
| 207 | Supply only thermostat of range 50-300º C complete Cat Part No. 11089 |
| 208 | Supply only bed failure limit switch SPDT Cat part No. 11067 |
| 209 | Supply only illuminating switch Cat Part No. 11077 |
| 210 | Supply only bed drive reduction unit with gear motor of capacity 0.34 HP, 230 volts complete. Cat part No. 10682 |
| 211 | Rewinding of process / React fan motors of capacity 0.5 HP, 3 phase 415 volts complete |
| 212 | Supply only MCB SPN 230 Volts, 25/32 Amps 10 KA complete |
| 213 | Taking down MCB of any type and any size complete all as specified and as directed. |
| 214 | Supply and fix MCB TPN 40-63 A, 10 KA breaking capacity including taking out old unserviceable MCB complete all as specified and as directed. |
| 215 | Disconnecting and removing existing unserviceable battery and S&F maintenance free battery 12V 180 AH including terminal clamps, copper lead of suitable length including testing and commissioning all as directed. |