| 1 | A-SUPPLY PART |
| 2 | NEW33 KV LINE |
| 3 | 11 Mtr. Long ST Pole(For new line) ST-410 SP56 |
| 4 | GI Channel X-arm including clamps and braces |
| 5 | 150 mm² ACSR Conductor |
| 6 | PG Clamps for 200 mm² ACSR Conductor |
| 7 | 33kV Polymeric composite Pin Insulator 36kV, 10kN,Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm |
| 8 | 33kV Polymeric composite Disc Insulator 36kV,min failing load 90kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm with fittings 4 bolts |
| 9 | Galvinized Nuts and Bolts. |
| 10 | Danger Plates with Clamps |
| 11 | Anti-Climbing Device with Clamps |
| 12 | Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip. |
| 13 | Red Oxide |
| 14 | Aluminium Paint |
| 15 | Cement bottoming 1:2:4 mix as per REC standards .6cum /pole |
| 16 | Galvanised Stay Set with 50 x 8 mm stay clamp, guy insulator(2Nos.), anchor plate (300x 300 x 8 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 20 mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete |
| 17 | Guard netting |
| 18 | 33 KV Isolator Without Earthing Blade |
| 19 | SINGLE BUS OUT |
| 20 | 33 KVVCB (36 KV, 1250 A, 26.2 KA, outdoor type) |
| 21 | 33 KV Isolatorwith earthing blade (36 KV ,1250A.Outdoor.3 pole,25KA) |
| 22 | 33 KV Isolatorwithout earthing blade (36 KV ,1250A.Outdoor.3 pole,25KA) |
| 23 | 33 KV Current Transformer (Single Phase,Multi ratio,multi core ,Outdoor) |
| 24 | 30 KV Lightening Arrestor (30KV,10KA,Station Class.ZNO.Polymer) Gapless |
| 25 | 33 KV C&R panel along with O/C, E/F relay (IEC 61850) Mimic diagram, voltmeter, ammeter, annunciation windows with annunciation relays, 3 PHASE Trivector meter DLMS compliant RS 485 port |
| 26 | 33 kv Post Insulators polymer type , 36 kv, 235 kv impulse, creepage distance 1224 mm |
| 27 | 33 KV PT (33KV/110V,1phase,multicore,Outdoor)(1No per phase) |
| 28 | STEEL STRUCTURES |
| 29 | Pipe Nominal bore 200, 5.9 mm thick |
| 30 | Galvanised steel structures |
| 31 | Galvanized nuts and bolts |
| 32 | CONTROL CABLES |
| 33 | 12 core 2.5 mm2, copper armoured, 1.1 kv grade, ISI FRLS |
| 34 | 4 core 2.5 mm2copper armoured, 1.1 kv grade, ISI FRLS |
| 35 | 2 core 2.5 mm2copper armoured, 1.1 kv grade, ISI FRLS |
| 36 | Lugs & Ferrules etc. |
| 37 | CONDUCTOR AND HARDWARE |
| 38 | 200 sqmm ACSR Conductor Panther |
| 39 | T-Clamp |
| 40 | Single Tension Fitting |
| 41 | 33 KV Disc insulator |
| 42 | Earth Wire 7/4.00 sqmm |
| 43 | G.I flat for earthing 50*6mm |
| 44 | SAFETY ITEMS (TO BE HANDED OVER AT DIVISIONAL STORES ) |
| 45 | Al.Ladder Extendable (30\"Long) |
| 46 | Lifting and Pulling machine 5Ton with Ratchet and Pulley for Panther |
| 47 | Helmet |
| 48 | Rubber Gloves for 33 KV Level |
| 49 | Rubber Gloves for 11 KV Level |
| 50 | SafetyBelt |
| 51 | Safety Shoes |
| 52 | Earthing rod (set of 3 rods) |
| 53 | HV Detector all Voltages |
| 54 | XLPE Cable stripping Tool |
| 55 | Tool boxes complete Comprising of D-ring spanners (6 to 32 No sizes),Hammer Wrench,Pliers |
| 56 | B-ERECTION PART |
| 57 | NEW 33 KV LINE |
| 58 | 11 Mtr. Long ST Pole(For new line) ST-410 SP56 |
| 59 | GI Channel X-arm including clamps and braces |
| 60 | 150 mm² ACSR Conductor |
| 61 | PG Clamps for 200 mm² ACSR Conductor |
| 62 | 33kV Polymeric composite Pin Insulator 36kV, 10kN,Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm |
| 63 | 33kV Polymeric composite Disc Insulator 36kV,min failing load 90kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm with fittings 4bolts |
| 64 | Galvinized Nuts and Bolts. |
| 65 | Danger Plates with Clamps |
| 66 | Anti-Climbing Device with Clamps |
| 67 | Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip. |
| 68 | Red Oxide |
| 69 | Aluminium Paint |
| 70 | Cement bottoming 1:2:4 mix as per REC standards .6cum /pole |
| 71 | Galvanised Stay Set with 50 x 8 mm stay clamp, guy insulator(2Nos.), anchor plate (300x 300 x 8 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 20 mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete |
| 72 | Guard netting |
| 73 | 33 KV Isolator Without Earthing Blade |
| 74 | SINGLE BUS OUT |
| 75 | 33 KVVCB (36 KV, 1250 A, 26.2 KA, outdoor type) |
| 76 | 33 KV Isolatorwith earthing blade (36 KV ,1250A.Outdoor.3 pole,25KA) |
| 77 | 33 KV Isolatorwithout earthing blade (36 KV ,1250A.Outdoor.3 pole,25KA) |
| 78 | 33 KV Current Transformer (Single Phase,Multi ratio,multi core ,Outdoor) |
| 79 | 30 KV Lightening Arrestor (30KV,10KA,Station Class.ZNO.Polymer) Gapless |
| 80 | 33 KV C&R panel along with O/C, E/F relay (IEC 61850) Mimic diagram, voltmeter, ammeter, annunciation windows with annunciation relays, 3 PHASE Trivector meter DLMS compliant RS 485 port |
| 81 | 33 kv Post Insulators polymer type , 36 kv, 235 kv impulse, creepage distance 1224 mm |
| 82 | 33 KV PT (33KV/110V,1phase,multicore,Outdoor)(1No per phase) |
| 83 | STEEL STRUCTURES |
| 84 | Pipe Nominal bore 200, 5.9 mm thick |
| 85 | Galvanised steel structures |
| 86 | Galvanized nuts and bolts |
| 87 | CONTROL CABLES |
| 88 | 12 core 2.5 mm2, copper armoured, 1.1 kv grade, ISI FRLS |
| 89 | 4 core 2.5 mm2copper armoured, 1.1 kv grade, ISI FRLS |
| 90 | 2 core 2.5 mm2copper armoured, 1.1 kv grade, ISI FRLS |
| 91 | Lugs & Ferrules etc. |
| 92 | CONDUCTOR AND HARDWARE |
| 93 | 200 sqmm ACSR Conductor Panther |
| 94 | T-Clamp |
| 95 | Single Tension Fitting |
| 96 | 33 KV Disc insulator |
| 97 | Earth Wire 7/4.00 sqmm |
| 98 | G.I flat for earthing 50*6mm |