| 1 | Supply , Installation, Testing and Comissioning of Air Cooled Floor standing Tower type split Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU), R-32/R-410 Green Refrigerant, wireless Remote control, suitable for working between 415 V+/- 10% ,3 phase 50 Hz AC Supplywith low & high voltage cutoff and capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotarycompressor. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . 3.6 TR |
| 2 | Supply , Installation, Testing and Comissioning ofInverter type Air Cooled Hi Wall split type Air conditioners with latest star rating system as per BEE amended upto date complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU), R-32/R-410 Green Refrigerant, wireless Remote control, suitable for working between 230V +/- 10% with low & high voltage cutoff and50 hz , single phaseACsupply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 3 | 2.0 TR ISEER not less then 4.6 |
| 4 | 1.5 TR ISEER not less then 4.6 |
| 5 | Supply & fixing MS powder coated stand suitable for 1.0/1.5/ 2.0 Tr outdoor type of Split AC.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 6 | Supply, installation, testing and comissioning ofinterconnectingcopperrefrigerant pipingof DHE Grade C12200- ASTM B68, B75, chemical composition of copper %- 99.0 Min and Phosphorus %- 0.015 to 0.040 . For Annealed copper tube :- Tensile strength = 210 Mpa wih elongation % = 40 Min . Ink MarkBrand Printing on Hard Tubes should be present. duly insulated with tubular elastomeric nitrile rubber FM/UL approved with high water vapor diffusion resistance and low thermal conductivity should be certified \"Class O\" in Fire Propagationas per BS 476 Part 6 including chase cutting andfilling with mortar, Slotted channel supports mounted on 10 mm threaded rod at suitable spacing the exposed piping shall be wrapped with glass woven cloth and lag coating for vapour barrier and weather protection. Joints shall be covered with nitrile rubber tape of 3 mm thick complete as required of following sizes. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 7 | 22.2 mm O.D., wall thinkness ≥ 1.0mm (insulation – 19 mm thick) |
| 8 | 19.1 mm O.D., wall thinkness ≥ 1.0mm (insulation – 13 mm thick) |
| 9 | Dismentling of splitair conditioner of any capacity/any type including existing indoor unit & outdoor unit , refrigerant piping , connecting cables , drain pipe etc. including shifting of dismentaled material to store completeas required |
| 10 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Un-armoured Coppercable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV withelectrolytic gradeCopper made of copper rodsconfirming to IS 613-1964, of purity >99.7 %,Inner / outer sheath confirming to IS:5831in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray (with cable tie) includingtesting etc. as required of following size. OEM must have it\"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810 For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 11 | 2.5 Sq. mm |
| 12 | 4 core |
| 13 | 6.0 Sq. mm |
| 14 | 4 core |
| 15 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed ArrmouredAluminiumcable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV withH4- Grade electrolyticaluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) includingtesting etc. as required of following size. OEM must have it\"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 16 | 25.0 Sq. mm |
| 17 | 3.5 core |
| 18 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load andsite requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting ofclass 3 as per IEC,minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted inexisting distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above ratingincluding making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 19 | Four pole MCB (With B/C curve tripping Characteristics) |
| 20 | 50/63 A rating |
| 21 | Providing & Fixing of Recessed/surface mounting heavy duty horizontal type Double Door ( Metal / Glazed )Distribution board with Metal end box made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3, powder painted complete with reversible door (for double door DB only )100 amp. insulated copper bus bar/shorting link , copper neutral link, copper earth link , color coded interconnecting wire set of suitable rating and din bar,masking sheet, making internal DB terminations with copper lugs, Ferrules, detachable gland plate, including making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 22 | Metal door (Three phase) IK-09 and IP-43with Metal end box |
| 23 | 8 Way |
| 24 | Providing & Fixing of IS : 4985 - 2000 Class -4 (10 Kgf / Sqcm) UPVC drain water piping withfittings (IS:7834 & 10Kgf/sqcm) like elbow, socket, Tee, solvent cement jointing,support with MS hanger on ceiling or recessed in wallwith chasing & plastering with 6 mmthickclosedcellelastomeric nitrile rubberinsulation including leakage testing etc. as required of following Nominal sizes. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . 32 mm |
| 25 | Supply, Fixing and testing of following capacity ISO certified company made wall mounted stabilizer having output voltage variation from 200 V to 250 V(+/-5%) with input voltage variation from 170 V to 260 V, time delay facility from 2 to 4 minute and high cutoff at 270 V with providing of 16 Amp /20 Amp Industrialplug top making connection etc complete in all respect.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 26 | 4 kVA |
| 27 | 5 kVA |
| 28 | Making hole in stone masonary/ RCC wall/ RCC slab with core cutter for accomodating refrigerant pipe/ drain pipe/ MS pipe/ cables etc of following dia |
| 29 | 50 mm dia per running inch length |
| 30 | 200 mm dia per running inch length |
| 31 | Providing & Fixing ofISI marked (IS:1293) 16 ampunbreakable 3 pin plug top having lamp indicator with CM/L no. printed and made out from industrial grade Polycarbonate or fire resistant ABS material, brass terminal including making connection testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 32 | S&F following sizesof ISI marked ( IS:14927 P - II ) virgin materialUPVC trunking along with accessorieslike coupler, inner, outer, elbow, square box, tee, end cap etc. on surfacewithscrews, expansionfastenersas required. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR. 100 mm x 50 mm |