Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | BOQ-A , Extra Low Voltage Works (CCTV & VIDEO CONFERENCING) |
| 2 | Boom Barrier System |
| 3 | SITC of AutomaticElectromechanical BoomBarrierSuitable roadwidthupto 6meterforintensive applications,highspeedwith6 secondopening /closingtimewithAluminiumhousing &aluminium boomwithforkrest, IP67Protectionetc.(forGateEntry/Exit) Safetysensorstobeprovidedfor preventinganyaccidental damagewhileclosing,DriveUnit: Heavy DutyGearMotor. Intelligence: The barriershall useasuitableACDriveforsmoothfunctioning of theequipment.Possibility forintegration viastandarduserinterfaces. Power: 230+/-10%VAC,50Hz. PowerConsumption: Max60Watt, OperatingTemperature:-20Deg to60DegC, Certifications: ISO-9001:2015, CE, IP-67Certification fromGovernmentaccreditedlabetc all complete ApprovedMake:Speedgatz/SynergyAccess /Kaba |
| 4 | SITC of i5InfraredBeam Setetc all complete ApprovedMake:Speedgatz/SynergyAccess /Kaba |
| 5 | SITC of MountingPostforPE Sensoretcallcomplete ApprovedMake:Speedgatz/SynergyAccess /Kaba |
| 6 | SITC of HELIX Receiver,Two Channelsetc all complete ApprovedMake:Speedgatz/SynergyAccess /Kaba |
| 7 | SITC of Transmitter, Silicone2Buttonetcallcomplete ApprovedMake:Speedgatz/SynergyAccess /Kaba |
| 8 | Access Control System |
| 9 | SITC of Multi Modal Face Recognition cum Fingerprint, Smart Card & Password based Reader, 5\" Touch Screen LCD, Android OS, 2GB RAM, 16GB ROM, 256 bit encrypted algorithm to protect important information such as personal info transmitted, Support TLS standard security communication protocols, Live Face Detection with anti-spoofing against 2D photograph, mobile selfie and video, Fake Fingerprint Detection Technology, 20,000 Face Storage capacity (1:N), 50,000 Fingers (1:N) / 2,00,000 Fingers (1:1), 10 million transaction storage, 20,000 Image logs, Onboard Dual Camera, supports Face authentication & verification from up to 3 meters, Communication protocols like TCP/IP, Wiegand Out / IN, RS 485, SD Card, Anti Pass back (Local / Global), Blacklist Employee Management, User wise authentication modes; Built in Lock Control; Mask Detection & Alert (configurable); Thermal Module integration for Body Temperature Detection (Optional), Up to 25,000 lux illumination, UL Listed Power Supply, CE, FCC, RoHS, BIS, WPC certifications etc. suitable for mounting on metal surface/metal frames/ wooden frames / wall / flap barriers or as required based on site conditions including all accessories complete as per specifications. Approved Makes: Secureeye/Essl /Timewatch/HID/ Honeywell/ Smart-I |
| 10 | SITC of Double leaf EM Lock with 1200LBS Collinear Load Test 560 kg,1200 lbs, Operated Voltage 12 / 24 / 48 V DC (optional), MOV Provides Reverse Current Protection, Suitable For Wooden Door, Glass Door, Metal Door, Fireproof Door, Anti-Residual Magnetism Designed High Strength Material, Anodized Aluminum Housing, Design with no Mechanical Bolt, CE Certified capacity etc all complete Approved Makes: Secureeye/Essl /Timewatch/HID/ Honeywell / Smart-I |
| 11 | SITC of EmergencyPushButtonformanual doorreleaseetcall complete ApprovedMakes: Secureeye/Essl /Timewatch/HID/ Honeywell/ Smart-I |
| 12 | SITC of ZLBracketfor600lbs EMLocketcall complete ApprovedMakes: Secureeye/Essl /Timewatch/HID/ Honeywell / Smart-I |
| 13 | Supply and layingof8core1.0mmCable. ApprovedMakes: POLYCAB/FINOLEX/BELDEN |
| 14 | Video Surveillance System (CCTV) |
| 15 | SITC of 5MPVandal-ResistantIR DomeCamerawithHeater,5MP(2592x1944) Resolution, Motorized Vari-focallens (f =3.6-10mm), ApertureF1.8-2.8, Min. [email protected], B/W :0 lux(IRLEDON),Dynamic Range120dB(TrueWDR), IR cutfilterwithautoswitch, IR Distance(LEDs): 30meter,Two-way audio, Alarm in/out, Exposure, WhiteBalance, Self-AdjustingVideo Mode(Sharpness, Contrast,Colors, BrightnessControl),VideoMotionDetection,ActiveTampering Alarm, TripZone,Video CompressionH.265, H.264(MP), M-JPEG, IPCameraProtocol DirectIP2.0, ONVIFProfileS, QuadrupleVideoStreaming, TriggerEvent: MotionDetection, Alarm in, Audio detection, Tampering, TripZone, EventNotificationRemoteS/W, Email (withImage),Micro SD/SDHC /SDXC, SmartFailover(Upto 256GB),IK10Vandal Proof Casing, IP67OutdoorReady, 3-axis mechanical designforinstallation, PowerSource:12VDC, PoE IEEE 802.3af (Class 3), Operating Temperature-40°C~60°C, OperatingHumidity0%~90%, Certification: BIS/UL, FCC,CE approval. MACAddress: TheMAC address of theproposedIPcamerasmustberegisteredinthesamenameof theOEM. TheIPCameraOEM mustconfirm thattheMACaddress of thesurveillancecameras; OUI mustbeinthenameof theOEM.etc all complete ApprovedMake:Mobotix/IDIS/Axis /Avigilon/Sony |
| 16 | SITC of 5MPVandal-ResistantIR BulletCamerawithHeater, 5MP(2592x1944) Resolution, Motorized Vari-focallens (f =3.6-10mm), ApertureF1.8-2.8, Min. [email protected], B/W :0 lux(IRLEDON),Dynamic Range120dB(TrueWDR), IR cutfilterwithautoswitch, IR Distance(LEDs): 30meter,Two-way audio, Alarm in/out, Exposure, WhiteBalance, Self-AdjustingVideo Mode(Sharpness, Contrast,Colors, BrightnessControl),VideoMotionDetection,ActiveTampering Alarm, TripZone,Video CompressionH.265, H.264(MP), M-JPEG, IPCameraProtocol DirectIP2.0, ONVIFProfileS, QuadrupleVideoStreaming, TriggerEvent: MotionDetection, Alarm in, Audio detection, Tampering, TripZone, EventNotificationRemoteS/W, Email (withImage),Micro SD/SDHC /SDXC, SmartFailover(Upto 256GB),IK10Vandal Proof Casing, IP67OutdoorReady, 3-axis mechanical designforinstallation, PowerSource:12VDC, PoE IEEE 802.3af (Class 3), Operating Temperature-40°C~60°C, OperatingHumidity0%~90%, Certification: BIS/UL, FCC,CE approval. MACAddress: TheMAC address of theproposedIPcamerasmustberegisteredinthesamenameof theOEM. TheIPCameraOEM mustconfirm thattheMACaddress of thesurveillancecameras; OUI mustbeinthenameof theOEM.etc all complete ApprovedMake:Mobotix/IDIS/Axis /Avigilon/Sony |
| 17 | SITCof32IPChannel NetworkVideoRecorder, H.2654K Recorder, NDAACompliant, Total incoming throughput370Mbps, SupportedCamera: DirectIP, AXIS, PANASONIC, ONVIF, VideoOutputs 2HDMI, RecordingResolutionUpto12MP(DependingonIPCamera),H.265, H.264VideoCompression, Recording ModeTime-lapse, Event, Pre-event, Panic,TriggerEvent:IDLA(ObjectDetection, Intrusion, Loitering,LineCrossing, FaceDetection),BI(ExceedOccupancyLimit, Social Distancing, MaskRule Violation, QueueCongestion), Motion, Trip-zone, Tampering, VideoLoss, AudioDetection, AlarmIn, NetworkAlarm, Text-in, System etc. SearchModeTime-lapse, EventLog, Text-in,Thumbnail,Metadata, HDD: 6SATA,4eSATA,RAID1Supported, EventNotification, Email (AttachClip(.cbf).MP4), CallbacktoRemoteS/W, PushNotification, Two-way Audio,2USB2.0, USB3.0, Embedded Linux,Built-in16channel PoE Switch,Expandableupto252TBusing eSATAstorage, NDAA Compliance, FCC, UL, CE,CBCertifiedetc all complete ApprovedMake:Mobotix/IDIS/Axis /Avigilon/Sony |
| 18 | SITCofSurvilliance Class harddiskof 6TB HDDetc all complete ApprovedMake:WD/Seagate/Toshiba |
| 19 | SITCofONVIFCompliantS&GVMS,CompatiblewithlinuxOS,VMSshouldhaveAninterfaceto definelayouts andpre-setcameras inmultipleviewmode, Ableto switchbetweendifferentviewpages anddevices, Zoom in/Zoomoutdigitallybymousescroll wheel ,Liveviewwithstream1infull screen modeorstream2inmulti-viewscreenmode(Bitrateadjustable)etc as requiredtocompletethesystem etcallcomplete ApprovedMake:Mobotix/IDIS/Axis /Avigilon/Sony |
| 20 | SITC of 55\"SmartAndroid4K UHDProfessional Display,24x7Operation, 440nits Brightness, Smart AndroidOS,4K UHDResolution, ScreenMirroringthrough, Airplay/Chromecast, DirectLED, 16Gb storage, Wi-Fi, 178DegreeViewing Angle, Landscape/Portrait/TiltInstallation, IP/RS232C Control, 10W+10WSpeakers, 4HDMI2.0, 2USB, PowerScheduling, 1200:1ContrastRatio,ColorGamut(DCI- P3) 92%, HDMIAutoWakeup. 4KHDR Visual Experiencethrough4KHDR ProcessorX1, 4K X-Reality PRO, TriluminosPRO, MotionflowXR,HDR10/HLG/Dolby Visionetc complete ApprovedMake:Sony/Christie/NEC / LG. |
| 21 | SITC of WorkstationwithIntel ProcessorI7orBetter,32GBMemory,400GB SSDforOS, 1TBHDDfor Local Storage, GigabitEthernet, DisplayCard4GB, WindowsOperatingSystem(64bit) withKeyboard, Mouseand21\"Monitordisplay etc complete ApprovedMake:HP/Dell /Lenovo |
| 22 | SITC of Category6UTPCable-LSZH, High-SpeedGigabitEthernetUTP250MHzClass E Cables for Cat6Consists of 23AWGSolidBareElectrolytic GradeCopperConductors,HDPE InsulatedTwisted4 Pair,RipCord, andLSZHOuterJacket, GigabitEthernet(1000Base-T),ULListed,RoHSCertifiedin existing concealed/surfaceconduits /Raceways complete305Mtr. Roll, includingPentaScanning for perCopperconnectitvitywithotherraletedtesting andservices (as peractual)asperspecificationetc. all complete ApprovedMake:Belden/3C3/Commscope/Siemon/ Derwiser/ Legrand |
| 23 | SITC of 19”RackMount, 12PortMulti ModeLIUPanel, preloadedwithapigtails,Splicetray & necessary fibermanagementaccessoriesetc all complete.as perspecificationetc. all complete ApprovedMake:Belden/3C3/Commscope/Siemon/ Derwiser/ Legrand |
| 24 | SITC of SC-LCMMFiberPatchCords( 3Mtr),LSZHjacket, meets IEC-60332-1(LSZH) flameratingfor standardsafety compliantas perspecificationetc. all complete ApprovedMake:Belden/3C3/Commscope/Siemon/ Derwiser/ Legrand |
| 25 | SITC of SC MM Pigtail(1.0Meter), LSZHjacket, meetsIEC-60332(LSZH) flameratingforstandard safetycompliant. as perspecificationetc. all complete ApprovedMake: Belden/3C3/Commscope/Siemon/ Derwiser/ Legrand |
| 26 | SITC of 6CoreMulti ModeOutdoorFiberOpticCable,HighLinkFiberOptic,Armoured,Multi loose Tube, OutdoorCable, Gel filled, CSMFRP,SingleSheathBlackHDPE,OM4,ROHSCertifiedwith OTDRScanningforOFC percoreconnectitvityanduplinktest forPointtoPointwithotherraleted testingandservices (as peractual) as perspecificationetc.all complete ApprovedMake:Belden/3C3/Commscope/Siemon/ Derwiser/ Legrand |
| 27 | SITC of RackMountableLayer2DistributionNetworkSwitch(forIPCCTV) withPOE+withMin24X 10/100/1000Base-T POE ports with2X1Gand2X1/10G(Min) SFP+ports upgradableto4x10G SFP+ports withminPOE budgetof380WorbetterwithFibretransrecievermoduleetc. all complete ApprovedMake:Cisco /Juniper/HP/AlcatelLucent |
| 28 | Supply, installation, testing&commissioningof IP55OutdoorJunctionBoxForFieldDevices at cameraside. JB mustbeofappropriatesizetohousedifferentcomponents asperCCTVsystemdesign confirming. |
| 29 | SITC of 10/100/1000portMulti modeopticalmedia converterasrequiredatsiteetc. all complete ApprovedMake:Cisco /Juniper/HP/AlcatelLucent |
| 30 | SITC of 4PortIndustrial GradeSwitchforPerimeterCamera, AdvancedIndustrial PoE capabilities with supportforHPoE (60W), IEEE 1588v2PTPsupport, Operatesat awidertemperaturerange, withstands greatershock,vibrations,surgeandEMI/EMCvariance,4RJ-4510/100/1000Base-T PoE+ports outof which2ports are60W PoE capable,2100/1000Base-X SFPports, RS-232Console (RJ45) all requiredaccessoriesetc. all complete ApprovedMake:Cisco /Juniper/HP/AlcatelLucent |
| 31 | SITC of 24U(W 600mm/D600mm) Floormountwithfrontglass door,backsteel doorandsidepanels, Accessories of rackWithlock&keyforall sidepanels &door,FanHousingUnitwith4fans, Cable manager4UHorizontal x8, Cantilevertray, ACmainChannel 06points 5Amp(PDU) ,EarthingKit, MountingHardware(Packof 10) as perspecificationetc.all complete ApprovedMake: Valrack/Netrack/CPMG/President/ APW/Poweride/Derwiser |
| 32 | Audio System |
| 33 | SITC of Digital ConferenceSystem:ChairmanDiscussionUnitwith500mm GooseneckMicrophone, built-inDigital Signal Processing, UnitwithPriority andNext-in-LineConfiguration, Priority button silences all delegatemicrophonesandallows onlythechairpersonto speak,Next-in-linebuttongives thefloortothenextspeakerinawaitinglistof speakers whorequestedtospeak, UserButtonwith feedback, High-qualityintegratedloudspeaker, minimum 4W orbetter, Audio quality: 16bitdigital or better,Frequencyresponse: 25Hz-15,000Hzorbetter, 3.5mm stereojacksocketforheadphones outputwithvolumeadjustment,Concealedconferencebus connections,2xRJ45ethernetport (IN/OUT -interchangeable),Loopthrough, daisy-chaincabling(non-proprietary), UnitwithBi colorbar indicator, Compatiblescrewlockmicrophoneconnectivity, Gooseneckmicrophone: Unidirectional, CardioidPolarPattern,Backelectret(condenser), Pressuregradient, MaxSPL@1kHz110dB SPL(1% THD+N),Signaltonoiseratio>67dB(A)Certification: CE; BIS etcallcomplete. ApprovedMake:Televic /Shure/Marconi Technologies. |
| 34 | SITC of Digital ConferenceSystem:DelegateDiscussionUnitwith400mm GooseneckMicrophone, built-inDigital Signal Processing, UnitwithMicrophoneOn/Off Button, UserButtonwithfeedback, High-qualityintegratedloudspeaker, minimum 4W orbetter, Audio quality: 16bitdigital orbetter, Frequency response: 25Hz-15,000Hzorbetter, 3.5mmstereojacksocketforheadphones outputwith volumeadjustment,Concealedconferencebusconnections, 2xRJ45ethernetport(IN/OUT - interchangeable), Loopthrough, daisy-chaincabling(non-proprietary),UnitwithBi colorbarindicator, Compatiblescrewlockmicrophoneconnectivity,Gooseneckmicrophone:Unidirectional,CardioidPolar Pattern,Backelectret(condenser), Pressuregradient, MaxSPL@1kHz110dB SPL(1%THD+N), Signal to noiseratio>67dB(A) Certification: CE; BIS etc all complete. ApprovedMake:Televic /Shure/Marconi Technologies. |
| 35 | SITC of Digital ConferenceSystem:CentralConferenceControllerwithRecording&WebServer, with built-inDigital Signal Processing, with4Bus Connections(4branches or2closedloops) forredundancymechanism,shouldsupporttotal cablelengthof abranch/loopareupto400M ormore. Themaximam cablelengthbetweenunits orbetweenunits andcentral unitis 80Mormore, 2xUSB ConnectionstoconnectUSBstoragedevicefordirectrecording of themeeting. Recordinginmp3orwav format, seamless takeoverof recordingbetween2USB devices, playbackthroughunits loudspeakers, Maximunnumberofopenmicrophonesatatime-upto8,CameraControl (lookatme) IntegrationCapability, withLCDdisplay toimplementseveral conferencemode: Directaccess, Request, Pushtotalk, FIFO, Voxcontrol, SelectableVoiceActivation, Volumecontrol 0dBto -46dB+“OFF”, Digital Acoustic, FeedbackReduction, Touchsensorbuttontechnology, WithAudioInput&Outputfor connectivity withexternal systemlikeamplifier, wirelessmicrophone&audio/videoconferencesystem, AudioQuality16Bitdigital, Connectivity: BalancedXLR input, 1UnbalancedRCAinput, 2Unbalanced RCAoutputs, 4Bus connections (4branches or2loops), LANconnection, 2USBconnections, 1 LockablePowerconnection,Fan-lessoperation,notgeneratinganynoise,Included48VDC/180W powersupply, comes withabuilt-inindicatorlightonthefront,Certification: CE; BISetcall complete. ApprovedMake:Televic /Shure/Marconi Technologies. |
| 36 | SITC of 20meterConferenceCablefrom sameOEMetc all complete. |
| 37 | SITC of 240WattCommercial MixerAmplifierwith5Inputs, BluetoothStreaming,USBMediaPlayer, Low-Z(4/8Ohm) andHigh-Z(70/100V)operationwithswitchablehigh-passfilter,3mic/lineinputs plus2lineinputs eachwithindividualvolumecontrols andoutputrouting, ImpedanceBalanced mic/line: 20kΩ, UnbalancedlineandRCA:10kΩ,Microphonephantomvoltage48V, Frequency response20Hzto 20kHz,+0.5/-2dB etc all complete. ApprovedMake:Labgruppen,Bose, Powersoft / Extron |
| 38 | SITC of 4\"CoaxialSurface-MountLoudspeaker, 25Watts continuous, 100Wattspeakpower, Frequency response(-3dB) 80Hz-20kHz, System sensitivity (1W@1m) 82±2dB, Dispersion(-6 dB) 107degrees conical averaged1kHz-10kHz, Transformertaps70V - 25W/12.5W/6.3W/ 3.2W/OFFandLOZlowimpedanceoperation, 100V - X /25W/12.5W/6.3W/OFFandLOZ lowimpedanceoperation, UL1480A, EN54-24:2008ratingetc all complete. ApprovedMake Tannoy, QSC, MartinAudio/ Extron |
| 39 | SITC of UHFWireless HandheldMicrophone,Automaticfrequency scanning,10compatibleuser- switchablechannels,TrueDiversity,FM ModulationMode, MaximumDeviation±40kHz, Frequency Response100Hzto15kHz(+1dB, -3dB), Total Harmonic Distortion<1%(at1kHz,±20kHz deviation), DynamiccardioidMicrophoneElement, RFPowerOutputHigh: 30mW; Low: 10mW (switchable), at50ohms, BalancedAudioOutputAttenuator,withTwoflexibleUHFantennas; AC adapter, rack-mountadapters etcall complete. ApprovedMake:AudioTechnica, Shure, DPA. |
| 40 | SITC of 2.5sq.mm X2CoreInstallationSpeakerCable,2.5Sqmm(80/0.20mm) x2corecableATC copperconductorPVC insulated, coretwisted, outerjacketedetcall complete. ApprovedMake:MX,Neutrick, Krystal/MX,Neutrick, Krystal |
| 41 | SITC of XLRMale/Female/AuxCableAdapteretcall complete |
| 42 | SITC of 12U, EquipmentRack, withFront&Sidedoors, 4NoFanAssembly, onTopof theRack,4 Casterwheels, 2no Shelfs to mounttheequipmentswhicharenotrackmounted, 8X2, 5/6Amp. PowerDistributionUnit, CableManager&SufficientRackhardwaresetc all complete. ApprovedMake Valrack, FSS, CPMG/Valrack/ Derwiser |
| 43 | SITC of 3\" In-Ceiling Loudspeaker, 20 Watts continuous, 80Watts peakpower, Frequencyresponse (+3dB, -3dB) 85Hz-19kHz, Sensitivityat1m/1W85dB, Nominal coverageangle130°, Transformer taps 15W/7.5W/3.8W/1.9Wat70V, 15W/7.5W/3.8Wat100VwithMetal grille, cablegland, flex conduit, C-ring,tile-bridgekit, paintmask,cutouttemplate.ApprovedMake: Tannoy,QSC, Martin Audio / Extron |
| 44 | Audio Visual for 11 Seater Conference |
| 45 | SITC of 85\"SmartAndroid4K UHDProfessional Display,440nits Brightness, SmartAndroidOS, 4K UHDResolution,24*7, ScreenMirroringthroughAirplay/Chromecast, DirectLED,16Gbstorage,Wi- Fi, 178DegreeViewingAngle,Landscape/Portrait/TiltInstallation, IP/RS232C Control, 10W+10W Speakers, 4HDMI2.1Inputs, 2USB, PowerScheduling, 1200:1ContrastRatio, ColorGamut(DCI-P3) 92%, HDMIAutoWakeup. 4K HDRVisual Experiencethrough4K HDRProcessorX1, 4KX-Reality PRO, TriluminosPRO, MotionflowXR,HDR10/HLG/Dolby Visionetc all complete. ApprovedMake::Sony/Christie/NEC/Sony/LG/Samsung |
| 46 | SITC of Wireless PresentationPlatformallows simultaneous contentsharing foruptofour1080p presenters, Wireless screencasting withiOS,Android, Mac,Chromebook, andWindows devices throughnativeAirPlay, GoogleCast, orMiracastprotocols, InstructorModeallows ausertomanage content,adjustaudiovolume,uploadandplay mediacontent, streamYouTube,andswitchbetween layouts, Supports YouTubeLivestreaming, Supports cloud-baseddigital signageplatforms, Local storageavailableforplaybackof imagesandvideo etc all complete ApprovedMake:Atlona/PureLink/Extron/WolfVision/Aten / LG / Extron |
| 47 | SITC of CableCubbywithslowmotionflip-opencover, 2Universal Power, 2USB Charger, RJ45 Network, HDMI2.0, madeof aluminumalloy finishing,couldbeflipopenedandclosedetc all complete ApprovedMake:Logic /Kramer/Extron /AMX, Nexxus. |
| 48 | SITC of Full HDUSB PTZCamera, Full HD1080psignal outputformatwithahighframerateof 60 fps, USB 3.0interfacewithHDMIvideooutput,12X OpticalZoom, Horizontal ViewingAngle72°, Vertical ViewingAngle43°, Auto&Manual ExposureControl, Auto&Manual Focus System,128 PresetPositions, CameraControl Protocol VISCA/UVC etc all complete. ApprovedMake::Lumens/Atlona/AMX/Extron/ Avonic. |
| 49 | SITC of 4x4,4K, 18Gbps HDMIMatrixwithScalerandAudioMatrix, Matrixswitchingof4HDMIsignals to4HDMIoutputs, Supports 18Gbps forresolutionsupto4K UltraHD60Hz, Analoganddigital audio de-embedding, integratedaudiomatrix,Downscaling (4K-1080p) on2outputs, 2.5WpowerviaHDMI forAOC, Control viaweb-GUI, CEC,RS232andIR,HDCP2.3compliant, HDRsupportetcallcomplete ApprovedMake::PureLink/Kramer/Extron /AMX/Extron |
| 50 | SITC of Digital ConferenceSystem:CentralConferenceControllerwithRecording&WebServer, with built-inDigital Signal Processing, with4Bus Connections(4branches or2closedloops) forredundancymechanism,shouldsupporttotal cablelengthof abranch/loopareupto400M ormore. Themaximam cablelengthbetweenunits orbetweenunits andcentral unitis 80Mormore, 2xUSB ConnectionstoconnectUSBstoragedevicefordirectrecording of themeeting. Recordinginmp3orwav format, seamless takeoverof recordingbetween2USB devices, playbackthroughunits loudspeakers, Maximunnumberofopenmicrophonesatatime-upto8,CameraControl (lookatme) IntegrationCapability, withLCDdisplay toimplementseveral conferencemode: Directaccess, Request, Pushtotalk, FIFO, Voxcontrol, SelectableVoiceActivation, Volumecontrol 0dBto -46dB+“OFF”, Digital Acoustic, FeedbackReduction, Touchsensorbuttontechnology, WithAudioInput&Outputfor connectivity withexternal systemlikeamplifier, wirelessmicrophone&audio/videoconferencesystem, AudioQuality16Bitdigital, Connectivity: BalancedXLR input, 1UnbalancedRCAinput, 2Unbalanced RCAoutputs, 4Bus connections (4branches or2loops), LANconnection, 2USBconnections, 1 LockablePowerconnection,Fan-lessoperation,notgeneratinganynoise,Included48VDC/180W powersupply, comes withabuilt-inindicatorlightonthefront,Certification: CE; BISetcall complete ApprovedMake::Televic /Shure/Marconi Technologies. |
| 51 | SITC of Digital ConferenceSystem:ChairmanDiscussionUnitwith400mm GooseneckMicrophone, built-inDigital Signal Processing, UnitwithPriority andNext-in-LineConfiguration, Priority button silences all delegatemicrophonesandallows onlythechairpersonto speak,Next-in-linebuttongives thefloortothenextspeakerinawaitinglistof speakers whorequestedtospeak, UserButtonwith feedback, High-qualityintegratedloudspeaker, minimum 4W orbetter, Audio quality: 16bitdigital or better,Frequencyresponse: 25Hz-15,000Hzorbetter, 3.5mm stereojacksocketforheadphones outputwithvolumeadjustment,Concealedconferencebus connections,2xRJ45ethernetport (IN/OUT -interchangeable),Loopthrough, daisy-chaincabling(non-proprietary), UnitwithBi colorbar indicator, Compatiblescrewlockmicrophoneconnectivity, Gooseneckmicrophone:Unidirectional, CardioidPolarPattern,Backelectret(condenser), Pressuregradient, MaxSPL@1kHz110dB SPL(1% THD+N),Signaltonoiseratio>67dB(A)Certification: CE; BIS etcallcomplete. ApprovedMake:Televic /Shure/Marconi Technologies. |
| 52 | SITC of Digital ConferenceSystem:DelegateDiscussionUnitwith400mm GooseneckMicrophone, built-inDigital Signal Processing, UnitwithMicrophoneOn/Off Button, UserButtonwithfeedback, High-qualityintegratedloudspeaker, minimum 4W orbetter, Audio quality: 16bitdigital orbetter, Frequency response: 25Hz-15,000Hzorbetter, 3.5mmstereojacksocketforheadphones outputwith volumeadjustment,Concealedconferencebusconnections, 2xRJ45ethernetport(IN/OUT - interchangeable), Loopthrough, daisy-chaincabling(non-proprietary),UnitwithBi colorbarindicator, Compatiblescrewlockmicrophoneconnectivity,Gooseneckmicrophone:Unidirectional,CardioidPolar Pattern,Backelectret(condenser), Pressuregradient, MaxSPL@1kHz110dB SPL(1%THD+N), Signal to noiseratio>67dB(A) Certification: CE; BIS etc all complete. ApprovedMake:Televic /Shure/Marconi Technologies. |
| 53 | SITC of 20meterConferenceCablefrom sameOEMetc all complete. ApprovedMake:Televic /Shure/Marconi Technologies. |
| 54 | SITC of 2meterConferenceCablefrom sameOEMetc all complete ApprovedMake:Televic /Shure/Marconi Technologies. |
| 55 | SITC of Digital Mixer/Digital Signal Processor,6mic/Lineinputs and1unbalancedstereoinput, 2 balancedoutputs and1unbalancedstereooutput, USB audioinput/output(1stereoinput, 1stereo output), High-performanceechocancelerforeachinputchannel,Noisecancellationthatcanbe assignedtoanyoutputchannel, Built-in12-bandPEQ, compressor, andlimiterforeachoutput channel, PhantomPower+48VDCetc all complete ApprovedMake:QSC /Audio Technica/Shure. |
| 56 | SITC of 4\"CoaxialIn-CeilingLoudspeaker, 30Watts continuous, 120Watts peakpower, Frequency response(-10dB) 70Hz-20kHz, Sensitivityat1m /1W84dB, PeakSPL105dB, 120°Nominal CoverageAngle, Transformertaps 25W/12.5W/6.3W/3.2Wat70V,25W/12.5W/6.3Wat100V withMetal grille, cablegland, flexconduit,C-ring, tile-bridgekit, paintmask, cutouttemplateetc all complete. ApprovedMake:QSC /Tannoy/MatrinAudio /Shure |
| 57 | SITC of 2x60WattCommercial AmplifierwithEnergyStarCertification, Low-Z(4/8Ohm) andHigh-Z (70/100V) operationperoutputwithswitchablehigh-pass filter, Frequency response20Hzto20kHz, +0.5/-1dB,Crosstalk(2channel models) >85dB, Signal-to-noise>97dBA, Thermal protection,over currentprotection,DC protection,highfrequency protection, Controlledstartandshutdown behaviour,DC-faultprotectionetcall complete. ApprovedMake QSC /Labgruppen/MatrinAudio/Shure |
| 58 | SITC of 15Meter4K Premium HighSpeedHDMIAOCFiberOpticCable, Resolutionsupto4K@60Hz 4:4:4incl.HDR 10,HDR 12andDolby Vision, HDMI2.0,HDMI1.xandDVI1.0compliant,HDCP2.2, HDCP1.4compliant, Supports all HDMIaudioformats incl.DolbyTrueHDandDTS-HDMasterAudio, Supports CEC andtransparentEDIDetcall complete. ApprovedMake:PureLink/Lightware/Extron/Belden /Extron |
| 59 | SITC of 1MeterSuperThin4K PremiumHighSpeedHDMICable, HDMIversion2.0–18Gbpsfor resolutions upto4KUltraHD60Hz, GoldplatedprecisioncontactswithSecure-Lock-System, HDMI EthernetChannel andAudioReturnChannel etc all complete ApprovedMake:PureLink/Lightware/Extron/Belden/Extron |
| 60 | SITC of 15MeterUSB3.2Gen2USB-AAOC FiberOptic ExtensionCable,USB3.2(Gen2x1, not backwardcompatiblewithUSB2.0) –10Gbps datatransmission, USB-AmaletoUSB-Afemale,full- metalhousing etc all complete. ApprovedMake:PureLink/Lightware/Extron/Belden /Extron / Workpro |
| 61 | SITC of 2.5sq.mm X2CoreInstallationSpeakerCable,2.5Sqmm(80/0.20mm) x2corecableATC copperconductorPVC insulated, coretwisted, outerjacketedetcall complete. ApprovedMake:Krystal /Belden/Extron/ Workpro |
| 62 | SITC of Category6ACable, 4Pair, S/FTP, PVCjacket(as peractual) etcallcomplete. ApprovedMake:Krystal /Belden/Extron / Workpro |
| 63 | SITC of VariousCables&Connectors etc all complete. ApprovedMake:Krystal /Belden/Extron/Derwiser/ APW/Legrand/ Workpro |
| 64 | SITC of 12U, EquipmentRack, withFront&Sidedoors, 4NoFanAssembly, onTopof theRack,4 Casterwheels, 2no Shelfs to mounttheequipmentswhicharenotrackmounted, 8X2, 5/6Amp. PowerDistributionUnit, CableManager&SufficientRackhardwaresetc all complete. ApprovedMake:CPMG/FSS/Valrack /Derwiser/APW/Legrand |
| 65 | VRV/VRF AC SYSTEM |
| 66 | OUTDOOR UNIT (VRV/VRF) |
| 67 | Supply Installation,Testing & Commissioningof modulartype Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for coolingand heating, having all hermetically sealed inverter type Scroll Compressor(s), minimum two compressors for above 14 HP modules, microprocessor based Controller, top discharge type condensing unit(s), with R 410 A Refrigerant, vibration isolators, with suitable foundation etc. complete as required.The unitshalldeliver the rated capacity at AHRI Conditions and work even at 50°C ambient temperature without tripping. The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required. The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5. DSR-2019 (1) |
| 68 | 16 HP Heating & Cooling |
| 69 | 30 (12+18) Heating & Cooling |
| 70 | INDOOR UNIT-CASSETTE TYPE |
| 71 | Supply, installation, testing and commissioningoffollowing minimum capacity 4-way flow VRV/VRF Cassette Type Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX Copper coil, electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration isolation, cord less remotecontroletc., suitable for operation on single phase 230 V ± 10%, 50Hz AC supply, complete, as required. The unit shall have automatic force shut down provision in case of fire on receiving signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. DSR-2019 (2) |
| 72 | 4 WAY CASSETTE UNITS |
| 73 | 1.2 TR (600 CFM) |
| 74 | 2.0 TR (830 CFM) |
| 75 | 2.4 TR (865 CFM) |
| 76 | INDOOR UNIT-DUCTABLE TYPE |
| 77 | Supply, installation, testing and commissioningoffollowing minimum capacity and external static pressure VRF/VRV ceiling mounted ductable type Indoor unit equipped with washable synthetic media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve, corded remote control, outer cabinet, vibration isolators, drain pan, other necessary supports etc., suitable for operation on single phase AC supply 230 V± 10%, 50 Hz complete as required. The unit shall have automatic force shut down provision in case of fire on receiveing signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. DSR-2019 (4) |
| 78 | Mid Static Ductable units (minimum 45 pascal external static pressure) |
| 79 | 2.6 TR (883 CFM) |
| 80 | COPPER REFRIGERANT PIPING |
| 81 | Supply, Installation, testing and commissioning including vaccumization and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-Oclosedcellelastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Liquid lines, all accessories as per specifications etc. as required : |
| 82 | 6.4 mm dia(OD)(Soft drawn) withtube thickness 1.2 mm with 19 mm thickinsulation |
| 83 | 9.5 mm dia (OD) (Soft drawn) withtube thickness 1.2 mm with 19 mm thickinsulation |
| 84 | 12.7 mm dia (OD) (Soft drawn) withtube thickness 1.2 mm with 19 mm thick insulation |
| 85 | 15.86 mm dia (OD) (Soft drawn) withtube thickness 1.2 mm with 19 mm thick insulation |
| 86 | 19 mm dia (OD) (Hard drawn) withtube thickness 1.2 mm with 19 mm thick insulation |
| 87 | 22.2 mm dia (OD) (Hard drawn) withtube thickness 1.2 mm with 19 mm thick insulation |
| 88 | 28.58 mm dia (OD) (Hard drawn) withtube thickness 1.2 mm with 19 mm thick insulation |
| 89 | 34.9 mm dia (OD) (Hard drawn) withtube thickness 1.62 mm with 19 mm thick insulation |
| 90 | NOTE:-1)The Copper Piping & Piping Circuit should be with Minimum Number of joints, which shall be attained by :(i) Using One End Expanded Tubes(ii) Bending the tubes instead of using elbow joints wherever 90 degree bending is required.(2) Piping should be routed at site in such a manner, that brazed joints in the refrigeration piping are kept to a minimum.(3) The makes of tube fittings shall be same as that of tubes.(4) The thickness of fittings used shall be same as that of the pipe. |
| 91 | Central Remote Controller for VRV/VRF System :- Supplying, fixing, testing and commissioning of Main centralized controller( I- Touch Manager) suitable for groups of indoorunits to be installed for control. (BMS Compatible) |
| 92 | Communication cable and conduit work: :- Supply, laying , testing and commissioning of 2C x 1.5 sq.mm copper conductor shielded cable in conduit. (Communication cable) |
| 93 | Supply, laying and fixing of conduit work including bends, junction boxes, pull wire, surface or concealed conduit work including necessary civil work such as chasing , concealing and making good and or necessary SS clamples, saddles and screws for fixing of conduit: (Conduit for communication cable). :- 25 mm dia 16G MS conduit. |
| 94 | DRAIN PIPES OF INDOOR UNITS: |
| 95 | Supplying, laying, fixing, testing & commissioning of composite UPVC pipes density not less than 10 kg/m3 complete with 9 mm thick nitrile insulation all necessary fittings such as elbows, tees, reducers U-trap, supports, clamps etc. as per specification & drawings. |
| 96 | 25 mm dia |
| 97 | 32 mm dia |
| 98 | VENTILATION SYSTEM |
| 99 | Axial Flow Fan for Normal/Smoke Exhaust |
| 100 | Supply, Loading, Unloading, Lifting, Shifting, installation, testing, commissioning of tube/vane axial flow |fan, consisting of motor, drive arrangement, base frame, supporting arrangement, vibration isolator (Spring |Type), protection mesh (bird screen) and Accessories as per specification & drawings. Motor shall be class \"H\" insulated. The motor shall be suitable for 415+10%, three phase. The motors shall be with Minimum IE-3 Effeciency. The motor shall be suitable for variable speed drive. Fan shall be AMCA certified for Air & Sound. Noise level should not exceed 80 db at 3 m from fan. |
| 101 | The outlet velocity of exhaust fans should not exceed 15 m/s |
| 102 | All fans shall be with fire retardant lexible canvas connection at the inlet and outlet. The cost shall be included. |
| 103 | All fans shall be with gravity louver/non return damper. The cost shall be included. |
| 104 | The complete fan assembly alongwith the motor & drive assembly shall be fire rated i.e. suitable to operate upto 250°C for 2 hours and meet the duty parameters. The fan duty shall be: |
| 105 | Exhaust Air Fan |
| 106 | 30500 CFM; Static Pressure 25 mm of wg; Power 9.3 kW |
| 107 | Fresh Air Fan |
| 108 | 30500 CFM: Static Pressure 25 mm of wg; Power 9.3 kW |
| 109 | DUCTING, INSULATION & AIR DISTRIBUTION SYSTEM |
| 110 | Factory Fabricated Ducting |
| 111 | Supply,installation,balancingandcommissioningoffactory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. Based on DSR-2022(16.12.1) |
| 112 | Thickness 0.63 mm Sheet |
| 113 | Thickness 0.80 mm Sheet |
| 114 | Thickness 1.00 mm Sheet |
| 115 | Volume Control Duct Damper:- Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc, as per specifications. Based on DSR-2022 (16.13) |
| 116 | Supply Air Grills :- Supplying&fixingofpowdercoatedextrudedaluminium Supply Air Grills with aluminium volume control dampers as per specifications.Based on DSR-2022 (16.15) |
| 117 | Return Air Grills :- Supplying&fixingofpowdercoatedextrudedaluminium Return Air Grills with aluminium volume control dampers as per specifications. Based on DSR-2022 (16.16) |
| 118 | Duct Acoustic Lining with Nitrile Rubber foam- Class-1:- Supplying, Fixing,testing and commissioning of Open cell nitrile rubber foam having microban anti-microbial product protection, of 10mm thickness and of 140-180 kg / m³ density cut to required sizes and to be stuck to the inside of duct surfaces with approved adhesive. |
| 119 | Nitrile rubber insulation:- Supplyingandfixingoffollowingthicknessdulylaminated aluminum foilof mat finish closed cell Nitrile rubber (Class \"O\") insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulationcomplete as per specifications and as required. (A) 19mm. |
| 120 | BMS System |
| 121 | SITC of BMS Computer System: i7 Processor, 2.93GHz, 4MB Cache with 8 GB RAM, & 1 TB HDD, 10/100 Mbps Ethernet card, USB connection & internal modem, Microsoft(R) Windows(R) 10 OS Professional Enterprise, 100/1000 Mbps NIC for Network connection and anti virus software with 32\" colour graphics monitor as per Tender Specifications. Accessories included Optical Mouse, Key Pad with the above BMS System configuration. Windows Licensed software compatible with the BMS platform etc. complete as required. Makes (Dell/HP/Samsung/LG) |
| 122 | SITC of the window based graphical software for IBMS system with 3 Nos Client for Operator workstation. The software shall not need additional license for future expansion also. The following software packages shall have below minimum features and compliances. a) 3D & Scalable Vector Graphics (SVG) technology dynamic graphics with Autocad import of plan with Zoom In & Zoom Out facility b) BTL,UL,EN Certified System. c) HTML5 based Web-Server software shall permit use of Standard Web-Browsers such as Microsoft Edge, Google Chrome, Mozilla Firefox, etc d) Cybersecurity TLS 1.3, Seamless integration of Security certificates within customer IT infrastructure, Microsoft’s active directory-based authentication, Use of network infrastructure that supports physical network or VLAN segmentation, End-toend encryption from client to server, End-to-end encryption between servers, Certificate-based data exchange, Encrypted backups |
| 123 | e) Software shall have audit trail feature and Cricital alarms shall be sent over Email. f) Ability to provide data to other systems through MQTT and / Or REST web services interface as an optional feature.( if required in future) g) Reports - Customized reports for Trends and alarm with Graphic screen shots.h) Alarm Escalation: Assisted treatment of alarms which helps in Predefined & fast intervention steps for faster response. Minimum number of active and viewable alarms shall be 10,000. It shall be possible for the user to sort, filter and search on anyavailable criteria such as priority, category, origin, alarm type, etc. On alarm, it shall be possible to notify via email to a preconfigured list of recipients . through a Simple Mail Transfer Protocol (SMTP) or secure email using Simple Mail TransferProtocol Secure (SMTPS). No special software interfaces shall be required and no email client software must be running inorder for email to be distributed.i) The software should natively communicate with three of the most popular standards for buildings: BACnet, LonWorks, and Modbusj) User Intuitive Dashboards. |
| 124 | SITC of True IP Based DDC Controllers 32 Bit Intelligent, peer to peer communication, interoperable DDC as per the specification. The compact controller shall have inbuilt 2-portEthernet switch . The controller shall have minimum 12 inputs/outputs inbuilt. The DDC shall have 300 Mhz processor with 128 MByte SDRAM (DDR3) and 32 MByte NOR Flash memory. The controller shall be freely programmable and have System functions (alarming, scheduling, trending, access protection with individually definable user profiles and categories). Note: Comissioning tool should not be dependent on any hardware dongle. The above shall be housed in vandal proof, lockable & secure MS Cabinets to be supplied along with all necessary switchgear protections as required. Number of controllers shall have spare capacity of 15% for future expansion. |
| 125 | a Electrical System |
| 126 | b Plumbing System |
| 127 | SITC of True IP Based BTL & UL Listed for third party integration. The controller shall have 2-port Ethernet switch and WLAN interface. It should have BTL Certified as B-BC and consisiting of dual core CPU 300MHz frequency and are with 512Mb DDR3 SDRAM microprocessor with Storage capacity of 4 GByte. It should support Real Time clock with backup of upto 7 Days using super capacitor. It should Support of the major communication protocols: BACnet,/IP, BACnet MS/TP, Modbus IP and Modbus RTU upto 2000 points. Note: 3rd party make integrator is not acceptable. |
| 128 | VRV ODU |
| 129 | DG |
| 130 | Field instruments |
| 131 | Supplying, installing, testing and commissioning of the following sensors / transducers / transmitters. The DDC shall support sensor with DC 0...20 mA or 4...20 mA, DC 0 ... 10 V, Pt 1000 , NTC 10k, NTC 20k, NTC 1.8K, PT 100 Ohm. All sensors should be UL Listed., Water Tank Level Switch |
| 132 | Cable & Conduits |
| 133 | Supplying, laying, termination, testing and commissioning of Communication cables. (2 core x 1.5 Sq.mm), PVC insulated, shielded twisted copper conductor Armoured cable. |
| 134 | Supplying, laying, termination, testing and commissioning of signal cables. (2 core x 1.5 Sq.mm), PVC insulated, shielded twisted copper conductor Armoured cable |
| 135 | Supplying, laying, termination, testing and commissioning of power cables. (3 core x 1.5 Sq.mm), PVC insulated, shielded twisted copper conductor Armoured cable. |
| 136 | Supplying, laying, termination, testing and commissioning of CAT6 Armoured cable |
| 137 | Network Switches |
| 138 | Supply, installation, testing and commissioning of Layer 2/3 switch with 24 ports (RJ-45) including SFP modules, rack mountable, SMPS power supply & other termination accessories (Like Pigtails/LIUs/ Convertors/Splicing equipment ,Patch panel, Patch Cord, Etc) complete as per specifications and as required for BMS DDC Panel Networking. The switch to switch distance shall not exceed beyond 80 meters. (Make:-Dlink/ Cisco / HP / Avaya/ Tyco / Panduit / Molex ) |
| 139 | SUB HEAD I- 500kVA Compact Sub-Station |
| 140 | Supply, Installation, testing, commissioning and transportation at site ofOutdoor Package type substation comprisingof distribution transformer, RMU, LT switchgear with internal lighting, earthing, padlocking etc. without oil pits. The enclosure shall have modular construction using GI sheets and shall be painted with polyurethane paint from exterior. Connection between RMU and Transformer shall be by Aluminium XLPE HT Cable including the cable termination/alluminium bus bar and from transformer to LT ACB shall be by alluminium bus bar. Two nos. copper & two nos GI links to be provided for neutral & body earthing.The substation shall have following equipments. |
| 141 | HTRMU UNIT SECTION |
| 142 | 11 kV, indoornon extensible Load Break/VCB Panel, 11kV SF6 insulated compact switchgear having metal enclosed robotically sealed / welded stainless steel tank comprising 2nos630 Load Break Isolator and one no 200 amp VCB in SF6 enclosure with self powered numerical overcurrent, short circuit and earth fault relay for Transformercomplete as per specification as required. |
| 143 | TRANSFORMER SECTION |
| 144 | 500 KVA 11KV/433 volts, Delta/Star, vector group DYN11,oil cooled ONAN transformer with OFF Load Tap Changers suitable for incoming voltage variation of +5.0% to -10% in equal steps of 2.5% to give a constant secondary voltage. The transformer shall be provided with fittings, accessories, protection, first filing of oil etc. including Buchholz relay oil/winding temperature, alarm/trip protection, surge arrestor, complete as per specifications and as required.The Losses shall be as per IS 1180 Level -I as per latest Amendment complete as required. |
| 145 | LT SECTION |
| 146 | INCOMING |
| 147 | 1 no. -800 Amps 660 volt 4 pole EDO type ACB complete with: |
| 148 | 4 nos - Cast resin current transformers of 800/5 ratio Class 1.0 for metering |
| 149 | 1 no. Multifuction Meter |
| 150 | 1 no. - Red/Green/AMBER ON/OFF/TRIP indicating lamps |
| 151 | A Sets of Phase Indicating Lamp |
| 152 | 1 no - Microprocessor based release with protection functions-overcurrent 40%-100% with time setting,selective short circuit 100%-1000% with time setting ,instantaneous short circuit 150%-1500%and earth fault releases. |
| 153 | The compact substation shall be complete with all interconnections, labels wiring, etc as required |
| 154 | SUB HEAD II- DG Set and Associates Work |
| 155 | Installation, testing & commissioning of Diesel Engine Set Silent type with 415volts at 1500 RPM,0.8 lagging power factor at 415 volts suitable for 50Hz, 3 phase system and for 0.80 load factor and consisting of following rating for site conditions, complete with base frame, lube oil system, Radiator Cooled, required batteries, electronic governor, instrumentation, day service fuel tank of 990 liters for each DG set, residential type exhaust silencers, alarms, engine mounted control panel, Resistoflex make anti vibration pads, Alternator (Stamford/AVK SEGC) direct coupled to Engine along with static excitation system and AVR panel and all required accessories complete as required and as per specifications. Power cabling, earthing, DG Panel and any other associated electrical work shall be carried out by Electrical contractor and hence is not included in the scope of this work. However the required coordination with Electrical Contractor is in the scope of work. |
| 156 | Diesel Engine |
| 157 | Diesel Engine radiator cooled electronic start of suitable BHP at 1500 RPM suitable for above output of alternator at 40 degree C,50% RH at 1000metre MSL and confirming to BS 5514,BS 649,IS 10000,capable of taking 10% over loading for one hour after 12 hours of continuous operations. The engine will be fitted complite with all the required accessories. |
| 158 | Digital Display for the following |
| 159 | Start & Stop switch with Key |
| 160 | Water temperature indication |
| 161 | Lubrication oil pressure indication |
| 162 | Lubrication oil temperature indication |
| 163 | Batterycharging indication |
| 164 | RPM indication |
| 165 | Over speed indication |
| 166 | Low lube oil trip indication |
| 167 | Ingine hours indication |
| 168 | Alternator |
| 169 | Synchronous alternatorfollowing rating suitable for 415 volts at 1500 RPM 3 phase 50 Hz, AC supply with 0.8 lagging power factor at 40 Degree C 50% RH and at 1000 meter MSL. The alternator shall be having SPDP enclosure,brushless,continuous duty,self excited and self regulated through AVR confirming to IS 4722/BS 2613 suitable for tropical conditions and with class H insulation. |
| 170 | Base Frame and Foundation |
| 171 | Both the engine and alternator shall be mounted on suitable base frame made of MS channel with necessary reinforcement which shall be installed on suitable cement concrete foundation and vibration isolation arrangements as per recommandation of manufacturer. |
| 172 | Exhaust System |
| 173 | Dry exhaust mainfold with hospital exhaust silencer. |
| 174 | Fuel Tank |
| 175 | Daily service fuel tank of 990 ltr capacity fabricated out of 2mm thick MS sheet complite with all standard accessories and fuel piping between fuel tank and diesel ingine with MS class C pipes of suitable dia,complite with valves,level indications and accessories as required as per specifications. |
| 176 | Starting System |
| 177 | 12V/24V DC starting system comprising of starter motors voltage regulator and arrangements for initial excitation complite with suitable nos. of batteries (25 plates,360/180 AH capacity lead acid type) as required as per specification |
| 178 | Accoustic and weather proof enclosure with arrangements for fresh air intake for cooling of the engine and alternator,extraction,discharging hot air into the atmosphere as per specifications. |
| 179 | The D.G. sets shall be inclusive of but not limited to the following standard accessories: |
| 180 | Radiator cooled system . |
| 181 | Fly Wheel to suit flexible/rigid coupling. |
| 182 | Fly wheel housing complete with starter gear ringand coupling. |
| 183 | Fuel hoses. |
| 184 | Electronic Governor. |
| 185 | Air Cleaner with Vacuum Indicator. |
| 186 | Fuel and Lube Oil Filter. |
| 187 | By pass filter |
| 188 | Corrosion inhibitor coolant. |
| 189 | Fuel Pump PT Type. |
| 190 | Water Pump. |
| 191 | Lube Oil Pump. |
| 192 | Electric Starter 24 Volts DC. |
| 193 | Battery Charging Alternator with Built-in-regulator - 24 Volts, 30 Amps. |
| 194 | Residential Silencer including baffle plates and 75mm thick LRB rock wool (64 Kg/m3 density) insulation clad with 26 SWG aluminium sheet cladding. |
| 195 | Expansion below |
| 196 | Flue pipe of required size from DG set FLUE OUTLET upto Silencer. |
| 197 | Safety Control against low Lube oil pressure, over speed and high cooling water temperature along with tripping. |
| 198 | Lube Oil Cooler. |
| 199 | Flexible Pipe joints for Silencer. |
| 200 | Vibration Damper. |
| 201 | Anti Vibration Pads. |
| 202 | Rating of DG Sets as Follows :- |
| 203 | 400 kVA Silent Type |
| 204 | DG Setrs shall be suitable for Auto ON/OFF incase of Failure and Interlocking with PLC in the Panel LT Panel |
| 205 | D.G. panel described as above, complete as required and as per specifications. |
| 206 | Supply, erection, testing and commissioning of exhaust piping Min. 5mm Thick of following sizes with welding joint including bends, MS pipe supports, clamps, dash fastener, nuts, bolts etc., withminimum 50mm thick rockwooll (150Kg/Cub Mtr.) covered with26 SWG aluminium sheet claddings etc. complete as required and as per specifications. insluding Structure along with DG Sets |
| 207 | 250 mm dia. NB |
| 208 | SS Bellows |
| 209 | MS Support structure |
| 210 | Control Cable : |
| 211 | Supply, laying, testing and commissioning of the following sizes of 1.1 KV grade XLPE insulated and PVC sheathed copper conductor armoured stranded control cable conforming latest IS complete as required. |
| 212 | 4 Core x 2.5 Sq.mm Cable |
| 213 | 8 Core x 2.5 Sq.mm Cable |
| 214 | Control Cables termination: |
| 215 | Supplying of all materials and making terminations ofcontrol cable terminations for control cables as per item 3.0 above complete with single brass compression glands, copper lugs etc. as required: |
| 216 | 2 Core x 2.5 Sq.mm Cable |
| 217 | 4 Core x 2.5 Sq.mm Cable |
| 218 | Supply, installation, testing and commissioning of 990 litres capacity day oil storage tank fabricated from 2 mm thick MS plates. Tank shall include 450 mm ID manhole cover, level indicator and flanged connection for inlet, outlet, overflow drain and probe provision for level controller. Tank shall be mounted on 2 m high structure support with access ladder (painted with 2 coats of red oxide primer). (Day oil Tank) |
| 219 | Providing & fixing M.S. class ‘C’ (heavy duty) pipe & fittings like tees, elbows, junctions, unions, bends, plugs etc. Including a coat of Synthetic enamel paint over two coats of primer complete as required. |
| 220 | 25 mm dia |
| 221 | Providing & fixing CI ball valves of the following sizes suitable for pressure of 10 kg/sqcm complete with all necessary fittings |
| 222 | 25 mm dia |
| 223 | Providing and fixing gun metal flot valve with necessary fittings complete as required. |
| 224 | 25 mm dia |
| 225 | Providing \"No smoking and Flammable\" sign boars as per requirements of Petrolium Rules as required. |
| 226 | Supply and installation of 4 nos. fire bucket with sand with suitable bracket complite as required. |
| 227 | Supply and fixing of 9 kg foam type fire extinguisher complite as required. |
| 228 | 11 KVSwitchgear Panels |
| 229 | Design, Manufacture, Supply, delivery & Coordination with Contractor forInstallation , Testing and commisssioningof following panel totally enclosed with CRCA sheet steel clad floor, mounting, epoxy based powder coating vermin proof, fully interlocked horizontal isolation, and extensible, horizontal draw out, vacuum insulated, metal clad switch board having single/double isolation features complete with circuits as detailed below. The switch board would be complete with necessary insulation – silicon based Raychem or equivalent insulated copper bursars, earthing switch/Truck, Wiring, labels, cable eyes, cable termination to receive XLPE cables, foundation bolts and suitable for operation on 11 KV 3 phase, 50 cycle, earthed system with a rupturing capacity of 350 MVA at 11 KV for 3 seconds. |
| 230 | Incoming 11 KV Panel Board |
| 231 | 1 – Air insulated metal clad housing |
| 232 | 1 – Set of 3 phase, insulated copper bus bars 630 amps rating. |
| 233 | 6 – Single pole cluster type isolating contacts i.e. plug and switches. |
| 234 | 1 – Triple pole draw out trolly mounted 11 KV 350 MVA, 630 AmpsVacuum circuit breaker fitted with arc control devices. |
| 235 | 1 – Trip free 240 V AC, motor charged spring release closing mechanism complete with necessary auxiliary switches, emergency hand trip device and mechanical ‘OFF’ & ‘ON’ indicators. |
| 236 | 6 nos NO/NC contacts |
| 237 | 1 – 24 Volt DC shunt trip coil & closing coil. |
| 238 | 3 – Dual core dual ratio cast resin current transformers of ratio 250-125/5 Class 5P10 and Class 1.0, 15 VA burden for protection & metering. |
| 239 | 1-3 Phase cast resin horizontal draw out bus potential transformer ratio 11 KV / √3 : 110 / √3 Volt, class 1.0, 100 VA, connected star/star with H.V and L.V. connections, H.V. fuses and LV MCB of adequate rating to withstand fault level in P.T circuit, isolating plugs for H.V. and L.V. connection. |
| 240 | 1- common Hooter |
| 241 | 1 – Strip heater to prevent absorption of moisture. |
| 242 | The instrument and relay panel fitted with followings |
| 243 | 1 – Digital voltmeter0 – 12 KV with 3 way and OFF selection facility. |
| 244 | 1 – Digital Ammeter (0-250) amps with 3 way and OFF selection facility. |
| 245 | 1 no.Multi function Meter (MFM-1) with RS 485of 1.0 accuracy to measure voltage, current, power factor, frequency, KW , KVA, KWH, KVAh. |
| 246 | 1 – no. circuit breaker control switch for electrical (T/N/C) |
| 247 | 1 – Triple pole numerical I.D.M.T. over current & earth fault relay with two outer elements connected for over current protection and the middle element for earth fault protection over current setting 50% - 200% Earth fault setting 20% - 80% (51 and 51N) |
| 248 | 1 – Master trip relay (86) |
| 249 | 1 – Trip circuit Supervision relay.(95) |
| 250 | 1 – Anti pumping relay (94) |
| 251 | 1 – Over Voltagerelay (59) |
| 252 | 1 – Set of red / green indicating lamps for close and open position with MCB. |
| 253 | 1 – Amber indicting lamp for auto trip with MCB |
| 254 | 1 – Clear indicating lamp for trip circuit healthy with MCB |
| 255 | 1 – Set of RYB Phase indicating lamps one per phase with MCB |
| 256 | 1 - Blue indicating lamp for spring charged.with MCB |
| 257 | 1 – Push button on front door for emergency trip. |
| 258 | 1 – Cable end box suitable forcable termination to receive 11 KV3 core 240 sq.mm XLPE cable. |
| 259 | 11KV, 1No Incoming Panel board as described above & as per specification including Power Pack for Auxiliary Services |
| 260 | 415 Volts Panel |
| 261 | Design, manufacture, supplying, erection, testing and commissioning of the following front operated front access 2mm thick steel enclosure free standing, outdoor type, dust and vermin proof, Panel with IP42 Protection & Feeder PIllar with IP 55 whether proof protection with hinged and lockable doors complete with interconnections, electrolytic aluminium crimping lugs, brass glands, bonding to earth and painting,, suitable for use at 415 volts, 3 phase 4 wire 50 Hertz system, and with 25 MVA rupturing capacity at 415 volts. |
| 262 | Note : The following provisions shall be required to be made in the switchboard detailed below: |
| 263 | The switchboard shall be have provision for entry of all cables / bus duct from the top / bottom as required. |
| 264 | All live accessible parts shall be shrounded and all equipment shall be finger touch proof.The busbar insulation shall be with heat shrinkable sleeves. SMC/DMC shrounds and bus bar supports shall be used. |
| 265 | Suitable tinned copper extension links for incoming / outgoing cables shall be provided wherever required. |
| 266 | Control circuits includes breaker control switch, auto manual selector switch, spring charging trip indication Timer, control wiring, Auxiliary contactors MCB\" as required at site. |
| 267 | All the incomers breakers shall be interlocked to avoid parallel operation. |
| 268 | All ACB, fault level breaking capacity indicates Ics value at 415 volts. (Ics = Icu = Icw = 100%) for 1 sec. |
| 269 | MCCB\"s in the MAIN LT Panel shall be with inbuilt Microprocessor based overload and short circuit & Earth fault release as per BOQ . |
| 270 | Link and drops from ACB / MCCB shall be designed for full rated current of ACB / MCCB rating at same amount of current density as of main bus bar. |
| 271 | Space heater / light / air filter/exhaust fan shall be provided for each vertical compartment. |
| 272 | All CT\"s shall have same fault level rating as their respective circuit breaker. |
| 273 | Bus bar size/rating, type of insulator, size of insulator, support for insulator, spacing of busbar support shall be as per CPRI approved design. |
| 274 | MAIN LT PANEL ( IP 42 PROTECTION) |
| 275 | INCOMER -I & II (500 KVA CSS 1W/1S) |
| 276 | 2 nos -800 Amps 415 volt 50 KA 4 pole EDO ACBwith Microprocessor based release with protection functions-overcurrent 40%-100% with time setting,selective short circuit 60%-1000% with time setting ,instantaneous short circuit 150%-1500%and earth faultsetting 20% - 100%releases. complete with: |
| 277 | 4 nos - Cast resin current transformers of 800/5 ratio Class 1.0 for metering |
| 278 | 1 - Digital Ammeter scaled 0-800 amps with 3 way and OFF selector switch |
| 279 | 1 - Voltmeter scaled 0-500 volts with 3 way and Off selector switch |
| 280 | 1 no.Multi function Meter (MFM-1) with RS 485of 1.0 accuracy to measure voltage, current, power factor, frequency, KW , KVA, KWH, KVAh. |
| 281 | Red/Green ON/OFF indicating lamps |
| 282 | 1 set of three RYBphase indicating lamps |
| 283 | 1- Amber indicating lamp for auto trip |
| 284 | 1- Blue indicating lamp for spring charged |
| 285 | Motor wound Springclosing meachanism |
| 286 | 1 no Reverse Power Relay (32) |
| 287 | Suitable for 3 nos 3.5C240 sqmm Al XLPE Cable |
| 288 | INCOMER -I & II (400 KVA DG SET 1W) |
| 289 | 1 nos -800 Amps 415 volt 50 KA 4 pole EDO ACBwith Microprocessor based release with protection functions-overcurrent 40%-100% with time setting,selective short circuit 60%-1000% with time setting ,instantaneous short circuit 150%-1500%and earth faultsetting 20% - 100%releases. complete with: |
| 290 | 4 nos - Cast resin current transformers of 800/5 ratio Class 1.0 for metering |
| 291 | 1 - Digital Ammeter scaled 0-800 amps with 3 way and OFF selector switch |
| 292 | 1 - Voltmeter scaled 0-500 volts with 3 way and Off selector switch |
| 293 | 1 no.Multi function Meter (MFM-1) with RS 485of 1.0 accuracy to measure voltage, current, power factor, frequency, KW , KVA, KWH, KVAh. |
| 294 | Red/Green ON/OFF indicating lamps |
| 295 | 1 set of three RYBphase indicating lamps |
| 296 | 1- Amber indicating lamp for auto trip |
| 297 | 1- Blue indicating lamp for spring charged |
| 298 | Motor wound Springclosing meachanism |
| 299 | 1 no Reverse Power Relay (32) |
| 300 | Suitable for 2 nos 3.5C300 sqmm Al XLPE Cable |
| 301 | BUS COUPLER |
| 302 | 1 nos -800 Amps 415 volt 50 KA 4 pole EDO ACBwith complete with: |
| 303 | Red/Green ON/OFF indicating lamps |
| 304 | BUS BAR SECTION -I&II |
| 305 | Electrolytic high conductivity aluminium three phase and neutral busbars rated at 1000 amps having a minimum current density of 1.0 amp per sq mmand suitable to with stand symmetrical fault level of 35 kA at 415 volts. The neutral busbar is to be of 50% capacity. |
| 306 | OUT GOING SECTION -I |
| 307 | 2 nos. 400 amps 35 kA 415 volt TPN MCCB with Microprocessor based release with protection functions-overcurrent 40%-100% with time setting,selective short circuit 60%-1000% with time setting ,instantaneous short circuit 150%-1200% completewith : |
| 308 | 3 nos - Cast resin current transformers of 400/5 ratio Class 1.0 for metering |
| 309 | 1 - Digital Ammeter scaled 0-400 amps with 3 way and OFF selector switch |
| 310 | Red/Green ON/OFF indicating lamps |
| 311 | 2 nos. 250 amps 35 kA 415 volt TPN MCCB with Microprocessor based release with protection functions-overcurrent 40%-100% with time setting,selective short circuit 60%-1000% with time setting ,instantaneous short circuit 150%-1200% completewith : |
| 312 | 3 nos - Cast resin current transformers of 80/5 ratio Class 1.0 for metering |
| 313 | 1 - Digital Ammeter scaled 0-80 amps with 3 way and OFF selector switch |
| 314 | Red/Green ON/OFF indicating lamps |
| 315 | 3 nos. 100 amps 35 kA 415 volt TPN MCCB with Thermal Magnetic based release with protection functions-overcurrent 40%-100% with time setting,selective short circuit 60%-1000% with time setting ,instantaneous short circuit 150%-1200% completewith : |
| 316 | 3 nos - Cast resin current transformers of 100/5 ratio Class 1.0 for metering |
| 317 | 1 - Digital Ammeter scaled 0-100 amps with 3 way and OFF selector switch |
| 318 | Red/Green ON/OFF indicating lamps |
| 319 | OUT GOING SECTION -II |
| 320 | 2 nos. 400 amps 35 kA 415 volt TPN MCCB with Microprocessor based release with protection functions-overcurrent 40%-100% with time setting,selective short circuit 60%-1000% with time setting ,instantaneous short circuit 150%-1200% completewith : |
| 321 | 3 nos - Cast resin current transformers of 400/5 ratio Class 1.0 for metering |
| 322 | 1 - Digital Ammeter scaled 0-400 amps with 3 way and OFF selector switch |
| 323 | Red/Green ON/OFF indicating lamps |
| 324 | 2 nos. 250 amps 35 kA 415 volt TPN MCCB with Microprocessor based release with protection functions-overcurrent 40%-100% with time setting,selective short circuit 60%-1000% with time setting ,instantaneous short circuit 150%-1200% completewith : |
| 325 | 3 nos - Cast resin current transformers of 250/5 ratio Class 1.0 for metering |
| 326 | 1 - Digital Ammeter scaled 0-250 amps with 3 way and OFF selector switch |
| 327 | Red/Green ON/OFF indicating lamps |
| 328 | 1 nos. 200 amps 35 kA 415 volt TPN MCCB with Microprocessor based release with protection functions-overcurrent 40%-100% with time setting,selective short circuit 60%-1000% with time setting ,instantaneous short circuit 150%-1200% completewith : |
| 329 | 3 nos - Cast resin current transformers of 200/5 ratio Class 1.0 for metering |
| 330 | 1 - Digital Ammeter scaled 0-200 amps with 3 way and OFF selector switch |
| 331 | Red/Green ON/OFF indicating lamps |
| 332 | 2 nos. 100 amps 35 kA 415 volt TPN MCCB with Thermal Magnetic based release with protection functions-overcurrent 40%-100% with time setting,selective short circuit 60%-1000% with time setting ,instantaneous short circuit 150%-1200% completewith : |
| 333 | 3 nos - Cast resin current transformers of 100/5 ratio Class 1.0 for metering |
| 334 | 1 - Digital Ammeter scaled 0-100 amps with 3 way and OFF selector switch |
| 335 | Red/Green ON/OFF indicating lamps |
| 336 | 3 nos. 63 amps 35 kA 415 volt TPN MCCB with Thermal Magnetic based release with protection functions-overcurrent 40%-100% with time setting,selective short circuit 60%-1000% with time setting ,instantaneous short circuit 150%-1200% completewith : |
| 337 | 3 nos - Cast resin current transformers of 60/5 ratio Class 1.0 for metering |
| 338 | 1 - Digital Ammeter scaled 0-60 amps with 3 way and OFF selector switch |
| 339 | Red/Green ON/OFF indicating lamps |
| 340 | Electrically Mechanically Interlocked Incomer, Buscoupler & Busbar |
| 341 | The Panel shall be complete with all interconnections, labels wiring, etc as required |
| 342 | CAPACITOR PANEL I&II (125 KVAR) ( IP 42 PROTECTION) |
| 343 | INCOMER |
| 344 | 1 no.- 250 amps 35 kA 415 volt 4P MCCB with Microprocessor based release with protection functions-overcurrent 40%-100% with time setting,selective short circuit 60%-1000% with time setting ,instantaneous short circuit 150%-1200% |
| 345 | 3 nos - Cast resin current transformers of 250/5 ratio Class 1.0 for metering |
| 346 | 1 - Digital Ammeter scaled 0-250 amps with 3 way and OFF selector switch |
| 347 | 1 - Voltmeter scaled 0-250 volts with 3 way and Off selector switch |
| 348 | 5 step automatic power factor correction relay to sense and monitor the system power factor and provide impulses for operation of 6 capacitor circuits as below. |
| 349 | 1 set of three RYBphase indicating lamps |
| 350 | Suitable for 1 nos 3.5C240 sqmm Al XLPE Cable |
| 351 | BUS BAR |
| 352 | Electrolytic high conductivity aluminium three phase and neutral busbars rated at 300 amps having a minimum current density of 1.0 amp per sq mmand suitable to with stand symmetrical fault level of 35 kA at 415 volts. The neutral busbar is to be of 50% capacity. |
| 353 | OUT GOINGS |
| 354 | 1 nos. 125 amp TPN 35 kA MCCB with thermal over load andmagnetic short circuit release and each complete with followings |
| 355 | 3 pole capacitor grade contactor suitable for automatic switching of 50 kVAR capacitor bank |
| 356 | Red/Green ON/OFF indicating lamps |
| 357 | Auto/Manual Selector Switch |
| 358 | ON/OFF Push Button |
| 359 | 50 kVAr hermetically sealed metallized polypropylene capacitor units complete with fuse protection, discharge resistors, interconnections etc complete as required . |
| 360 | 2 nos. 63 amp TPN 35 kA MCCB with thermal over load andmagnetic short circuit release and each complete with followings |
| 361 | 3 pole capacitor grade contactor suitable for automatic switching of 25 kVAR capacitor bank |
| 362 | Red/Green ON/OFF indicating lamps |
| 363 | Auto/Manual Selector Switch |
| 364 | ON/OFF Push Button |
| 365 | 25 kVAr hermetically sealed metallized polypropylene capacitor units complete with fuse protection, discharge resistors, interconnections etc complete as required . |
| 366 | 2 nos. 32 amp TPN 35 kA MCCB with thermal over load andmagnetic short circuit release and each complete with followings |
| 367 | 3 pole capacitor grade contactor suitable for automatic switching of 12.5 kVAR capacitor bank |
| 368 | Red/Green ON/OFF indicating lamps |
| 369 | Auto/Manual Selector Switch |
| 370 | ON/OFF Push Button |
| 371 | 12.5 kVAr hermetically sealed metallized polypropylene capacitor units complete with fuse protection, discharge resistors, interconnections etc complete as required . |
| 372 | The Capacitor Panel shall be complete with all interconnections, labels wiring, etc as required |
| 373 | GROUND FLOOR PANEL ( IP 42 PROTECTION -INDOOR DUTY) |
| 374 | INCOMER |
| 375 | 1 no.- 400 amps 25 kA 415 volt 4P MCCB with Microprocessor based release complete with |
| 376 | 3 nos - Cast resin current transformers of 400/5 ratio Class 1.0 for metering |
| 377 | 1 - Digital Ammeter scaled 0-400 amps with 3 way and OFF selector switch |
| 378 | 1 - Voltmeter scaled 0-500 volts with 3 way and Off selector switch |
| 379 | BUS BAR |
| 380 | Electrolytic high conductivity aluminium three phase and neutral busbars rated at 500 amps having a minimum current density of 1.0 amp per sq mmand suitable to with stand symmetrical fault level of 25 kA at 415 volts. The neutral busbar is to be of 50% capacity. |
| 381 | OUT GOINGS |
| 382 | 18 nos. 63 amp 4P 10 kA MCB with thermal over load andmagnetic short circuit release |
| 383 | The Panel shall be complete with all interconnections, labels wiring, etc as required |
| 384 | FIRST FLOOR PANEL ( IP 42 PROTECTION -INDOOR DUTY) |
| 385 | INCOMER |
| 386 | 1 no.- 400 amps 25 kA 415 volt 4P MCCB with Microprocessor based release complete with |
| 387 | 3 nos - Cast resin current transformers of 400/5 ratio Class 1.0 for metering |
| 388 | 1 - Digital Ammeter scaled 0-400 amps with 3 way and OFF selector switch |
| 389 | 1 - Voltmeter scaled 0-500 volts with 3 way and Off selector switch |
| 390 | BUS BAR |
| 391 | Electrolytic high conductivity aluminium three phase and neutral busbars rated at 500 amps having a minimum current density of 1.0 amp per sq mmand suitable to with stand symmetrical fault level of 25 kA at 415 volts. The neutral busbar is to be of 50% capacity. |
| 392 | OUT GOINGS |
| 393 | 15 nos. 63 amp 4P 10 kA MCB with thermal over load andmagnetic short circuit release |
| 394 | 1 nos. 40 amp DP 10 kA MCB with thermal over load andmagnetic short circuit release |
| 395 | The Panel shall be complete with all interconnections, labels wiring, etc as required |
| 396 | UPS PANEL ( IP 42 PROTECTION -INDOOR DUTY) |
| 397 | INCOMER |
| 398 | 1 no.- 80 amps 25 kA 415 volt 4P MCCB with Thermal over load and Magnetic short circuit relase complete with |
| 399 | 3 nos - Cast resin current transformers of 80/5 ratio Class 1.0 for metering |
| 400 | 1 - Digital Ammeter scaled 0-80 amps with 3 way and OFF selector switch |
| 401 | 1 - Voltmeter scaled 0-500 volts with 3 way and Off selector switch |
| 402 | BUS BAR |
| 403 | Electrolytic high conductivity aluminium three phase and neutral busbars rated at 100 amps having a minimum current density of 1.0 amp per sq mmand suitable to with stand symmetrical fault level of 25 kA at 415 volts. The neutral busbar is to be of 50% capacity. |
| 404 | OUT GOINGS |
| 405 | 2 nos. 40 amp 4P 10 kA MCB with thermal over load andmagnetic short circuit release |
| 406 | 4 nos. 40 amp DP 10 kA MCB with thermal over load andmagnetic short circuit release |
| 407 | The Panel shall be complete with all interconnections, labels wiring, etc as required |
| 408 | TERRACE PANEL ( IP 42 PROTECTION -INDOOR DUTY) |
| 409 | INCOMER |
| 410 | 1 no.- 200 amps 25 kA 415 volt 4P MCCB with Thermal over load and Magnetic short circuit relase complete with |
| 411 | 3 nos - Cast resin current transformers of 200/5 ratio Class 1.0 for metering |
| 412 | 1 - Digital Ammeter scaled 0-200 amps with 3 way and OFF selector switch |
| 413 | 1 - Voltmeter scaled 0-500 volts with 3 way and Off selector switch |
| 414 | BUS BAR |
| 415 | Electrolytic high conductivity aluminium three phase and neutral busbars rated at 250 amps having a minimum current density of 1.0 amp per sq mmand suitable to with stand symmetrical fault level of 25 kA at 415 volts. The neutral busbar is to be of 50% capacity. |
| 416 | OUT GOINGS |
| 417 | 9 nos. 63 amp 4P 10 kA MCB with thermal over load andmagnetic short circuit release |
| 418 | 2 nos. 40 amp 4P 10 kA MCB with thermal over load andmagnetic short circuit release |
| 419 | The Panel shall be complete with all interconnections, labels wiring, etc as required |
| 420 | Cable& Termination |
| 421 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. UPPWD-501 |
| 422 | 3.5 core 300 sq mm |
| 423 | 3.5 core 240 sq mm |
| 424 | 3.5 core 150 sq mm |
| 425 | 4 core 25 sq mm |
| 426 | 4 core 16 sq mm |
| 427 | 4 core 10 sq mm |
| 428 | 4 core 6 sq mm |
| 429 | 3 core 6 sq mm |
| 430 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVCinsulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. Based on DSR-9.1 |
| 431 | 3.5 core 185 sq mm . Based on DSR-9.1.27 |
| 432 | 4 core 25 sq mm. Based on DSR-9.1.34 |
| 433 | 4 core 16 sq mm. Based on DSR-9.1.33 |
| 434 | 4 core 10 sq mm. Based on DSR-9.1.32 |
| 435 | 4 core 6 sq mm. Based on DSR-9.1.31 |
| 436 | 3 core 6 sq mm. Based on DSR-9.1.31 |
| 437 | S/L of 90mm dia. DWC pipe for drawing of power cable across the road by drilling of 120mm dia. at 1mtr. Work should be done by manual Trenchless method. Complete in all respect per direction of Engineer-in-charge YEIDA SOR-12 |
| 438 | S/L of 120mm dia. DWC pipe for drawing of power cable across the road by drilling of 150mm dia. at 1mtr. Below the road level the work should be done by manual Trenchless method. Complete in all respect per direction of Engineer-in-charge YEIDA SOR-13 |
| 439 | S/L of 160mm dia. DWC pipe for drawing of power cable across the road by drilling of 190mm dia. at 1mtr. Below the road level the work should be done by manual Trenchless method. Complete in all respect per direction of Engineer-in-charge YEIDA SOR-14 |
| 440 | S/L of 200mm dia. DWC pipe for drawing of power cable across the road by driling of 230mm dia. at 1mtr. Below the road level the work should be done by manual Trenchless method. Complete in all respect per direction of Engineer-in-charge YEIDA SOR-15 |
| 441 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. Based on DSR-4.1. |
| 442 | 100 mm width X 50 mm depth X 1.6 mm thickness. Based on DSR-4.1.1 |
| 443 | 150 mm width X 50 mm depth X 1.6 mm thickness. Based on DSR-4.1.2 |
| 444 | 200 mm width X 50 mm depth X 1.6 mm thickness. Based on DSR-4.1.3 |
| 445 | 300 mm width X 50 mm depth X 1.6 mm thickness. Based on DSR-4.1.4 |
| 446 | Providing, laying and fixing following dia RCC pipe NP2 class (light duly)in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement: 2 fine sand) including trenching (75 cm deep) and refilling etc as required. Based on DSR-14.14. |
| 447 | 100 MM DIA. Based on DSR-14.14.1 |
| 448 | 150 MM DIA. Based on DSR-14.14.2 |
| 449 | 250 MM DIA. Based on DSR-14.14.3 |
| 450 | 300 MM DIA. Based on DSR-14.14.4 |
| 451 | Constructing masonry Chamber 60x60x75 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box 100mm top diameter, 160 mm bottom diameter and 180 mm deep (inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size), including necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design : With bricks of class designation-150 - \"UPPWD/SOR-2020/DAR/17.33.1 |
| 452 | Earthing |
| 453 | Supply and burying of 40mm dia x 4.5 metres long G.I. Pipe vertically for earthing having 12mm dia. Holes spaced 75mm apart drilled up to 2 metre from the bottom complete with earthing lead of No. 6 to 8SWG GI wire in G.I. Pipe up to appron (and from appron to switch board the cost of G.I. wire and pipe will be extra) upto switch board, 30cm square C.I. box with hinged cover masonary enclosure, funnel at top, alternate layers of charcoal/coke and salt at least 150mm thick alround etc. as per directions of Engineer-in-charge complete in all respects as per drawing. UPPWD-701 |
| 454 | Supply and burying of G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. UPPWD-703 |
| 455 | Supply and burying of copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. UPPWD-705 |
| 456 | Supply and laying of 32mm x 6mm copper strip from earth electrode directly in the ground as required complete in all respect. UPPWD-718 |
| 457 | Supply and laying of 32 mm x 6 mm G.I. strip from earth electrode directly in the ground as required complete in all respect. UPPWD-717 |
| 458 | Supply and laying of 25mm x 5mm G.I. strip from earth electrode directly in the ground as required complete in all respect. UPPWD-716 |
| 459 | Supply and fixing of one number 8 SWG G.I. wire in 15mm dia. G.I. pipe for earthing, laid in ground or in wall duly concealed including the cost of cement, sand, labour, T&P other material required for proper completion of the work as directed at site. UPPWD-721 |
| 460 | Lightning Conductor |
| 461 | Providing and fixing of lightning conductor finial, made of 25 mm dia 300mm long, G.I. tube, having single prong at top, with 85mm dia 6mm thick G.I. base plate i ncluding holes etc. complete as required. Based on DSR-6.2 |
| 462 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required. (For horizontal run). Based on DSR-6.7 |
| 463 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run) . Based on DSR-6.8 |
| 464 | Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required. Based on DSR-6.12 |
| 465 | Earthing with G.I earth Plate 600 x 600 x 6 mm thick including accessories and providing mansory enlsoure with cover plate having locking arrangment and watering pipe of 2.7 metre long, with charcoal /coke and salt as required. Based on DSR-5.2 |
| 466 | Jointing copper /G.I. tape (with another copper/ GI tape, base of the finial or any other metallie object) by riveting /nut bolting/sweating and soldering etc as required. Based on DSR-6.4 |
| 467 | Providing and laying G.I. tape 32 mm X 6 mm from earth electrode directly in ground as required. Based on DSR-6.14 |
| 468 | External Lighting & Poles |
| 469 | Supply & fixing of 7 mtr GI Octagonal Pole of approved make (top dia 70mm, Bottom dia 130mm and base plate 12mm thik) having 3mm thikness with single arm bracket (1 Mtr length) on RCC foundation including the cost of foundation, foundation bolts, excavation & back filling and Required T&P completee in all respect. UPPWD-641 |
| 470 | Supply & fixing of 7 mtr GI Octagonal Pole of approved make (top dia 70mm, Bottom dia 130 mm and base plate 12mm thik) having 3mm thikness with Double arm bracket (1 Mtr length) on RCC foundation including the cost of foundation, foundation bolts, excavation & back filling and Required T&P completee in all respect. UPPWD-642 |
| 471 | Supply and fixing of LED Street light Fitting having die cast aluminium body and diffuser with driver set suitable for 45 watt to 50 Watt. Confirming to IP 66 protection complete in all respect. UPPWD-1421 CAT- AAA |
| 472 | Supply and fixing of decorative 8 to 16 Watt LED bollard luminaire with driver set confirming to IP 65 protection complete in all respect. UPPWD-1442 CAT- AAA |
| 473 | Supply & Fixing of XLPE insulated, Copper un-armoured Control cable 1100V grade etc.(A) 3 x 4 sq. mm. Based on DSR - 9.1.7 |
| 474 | Supply & Fixing of XLPE insulated Aluminium un-armoured Cable. (A) 3 x 6 sq. mm. UPPWD-501 |
| 475 | Supply & Fixing of XLPE insulated Aluminium un-armoured Cable. (A) 4A x 2.5 sq. mm. YEIDA SOR-1( C) |
| 476 | UPS SYSTEM |
| 477 | Supply ,installation, testing and commissioningof IGBT Rectifier & Inverter basedUPS system comprising of 1 no 40 kVA units with batterybank backup of 20 minutes duration for full load with all standards fittings, accessories, protection, instruments, indications and controls including but not restricted to transformer, rectifire, inverter, SMF battery with float cum boost battery charger, static bypass switch, maintenance bypass, output isolation transformer, interconnections etc.including warranty and free all inclusive comprehensive maintenance services for two years for UPS and battery bank after the date of handing over complete as per specification and as required. |
| 478 | Pumps & Allied Equipment |
| 479 | Providing, fixing, testing & Commissioning of Sump Pumps for lifting water from UGT sumps located @ site level to fill the OHT of CSF-07 |
| 480 | Submersible single stage single entry pumps with CI body and two vane enclosed type SS impeller connected to TEFC submersible motor for 415 volts, 3 phase, 50 cycles including MCC panel with level controllers, auto control, sequential change over facility with one proper working at low level & two proper working at high level with an audible alarm, solid handling upto 20 mm including all interconnectivity cables, with both pumps connected to common outlet header including valves, non return valves, lifting chains etc. complete in all respect. |
| 481 | The above pump sets must be supplied complete with following accessories. |
| 482 | Complete piping 65 mm dia common delivery upto 20 m as per enclosed tentative layout. (The pipe should be preferably heavy duty G.I) -- 1 Set |
| 483 | 50mm dia Butterfly valve.-- 2 Nos |
| 484 | 50 mm dia NRV valve.-- 2 Nos |
| 485 | 15m flexible copper cable of rated size from pump set to control panel (position of panel marked in enclosed layout in plant room).-- 1 Set |
| 486 | Electrical DOL Starter panel having suitable ratingof Incoming and outgoing MCB to Starter along with all necessary accessories & safety devices such asSingle phasing preventer, Overload relay, dry run protection, On/Off/Trip indicating LED type indication,level controller with operational mode (2 nos Pumps) as one working and one standbyat low levels and both working at high level and cut-off at dry level, working/standby selection and with provision for remote Push Button control (Panels with sump pumps near each sump as per site conditions). (AR-68) |
| 487 | Automatic built-up water level controller with necessary length of cable upto control panel. |
| 488 | Motor rating - 1 HP |
| 489 | Discharge-max. 1.8 m3/hr. |
| 490 | Total head- 25-30 m (Approx.) |
| 491 | Make -KSB |
| 492 | (Complete set as above with 2 nos. pumps) |
| 493 | Providing, fixing, testing & Commissioning of Sump Pumps for lifting water from drainage sumps in plant room. |
| 494 | Submersible single stage single entry pumps with CI body and two vane enclosed type SS impeller connected to TEFC submersible motor for 415 volts, 3 phase, 50 cycles including MCC panel with level controllers, auto control, sequential change over facility with one proper working at low level & two proper working at high level with an audible alarm, solid handling upto 20 mm including all interconnectivity cables, with both pumps connected to common outlet header including valves, non return valves, lifting chains etc. complete in all respect. |
| 495 | The above pump sets must be supplied complete with following accessories. |
| 496 | Complete piping 65 mm dia common delivery upto 20 m as per enclosed tentative layout. (The pipe should be preferably heavy duty G.I) -- 1 Set |
| 497 | 50mm dia Butterfly valve. 2 Nos |
| 498 | 50 mm dia NRV valve.-- 2 Nos |
| 499 | 15m flexible copper cable of rated size from pump set to control panel (position of panel marked in enclosed layout in plant room).-- 1 Set |
| 500 | Electrical DOL Starter panel having suitable ratingof Incoming and outgoing MCB to Starter along with all necessary accessories & safety devices such asSingle phasing preventer, Overload relay, dry run protection, On/Off/Trip indicating LED type indication,level controller with operational mode (2 nos Pumps) as one working and one standbyat low levels and both working at high level and cut-off at dry level, working/standby selection and with provision for remote Push Button control (Panels with sump pumps near each sump as per site conditions). (AR-68) |
| 501 | Automatic built-up water level controller with necessary length of cable upto control panel. |
| 502 | Motor rating - 1 HP |
| 503 | Discharge-max. 9 m3/hr. |
| 504 | Total head- 10-15 m (Approx.) |
| 505 | Make -KSB |
| 506 | (Complete set as above with 2 nos. pumps) |
| 507 | ProvidingandfixingManholeCoverforU.G&O.H.Tanks- Providing and fixing extra heavy duty 560mm dia, double seal, water tight DI manhole cover and frame for placing over the underground water tanks with lifting and locking arrangements as per approved sample, complete in all respect including fixing in PCC as per site requirement. (Note:- Manhole covers for U.G & O.H. Tanks) |
| 508 | Supply, Installation, Testing and commissioning of Electrical Motor Driven Hydrant Fire Pump Set (Factory Fitted) suitable for automatic operation consisting of the following as per the specifications. specification as per fire fighting requirements and on the pattern of TAC OR LOCAL AUTHORITY APPROVAL) as per following specifications: |
| 509 | Providing and fixing horizontal End Suction multi stage, single outlet factory fitted pumping set with bronze impeller with gland capable of delivering 2280 LPM against a total head of 75 M with CI body and connected by a flexible coupling to a totally enclosed fan cooled induction motor mounted on a common structural baseplates with all pump accessories complete as per specifications including pressure gauge with gunmetal isolation valves and anti vibration pump, motor to be suitable for 415 volts, 3 phase, 50cycles A.C. supply( specification as per fire fighting requirements and on the pattern of TAC OR LOCAL AUTHORITY APPROVAL) as per instruction of following specifications: |
| 510 | b) Squirrel cage induction motor totally enclosed fan cooled type suitable for 415 volts ±15%, 3 phase, 50 Hz AC supply of suitable capacity(approximate 50 KW) for the above pump coupled with flexible coupling including earthing as per relevant Indian standard & specifications. |
| 511 | c) Common bed plate for mounting pump and motor fabricatedfrom suitable MS Channel asper manufacturer\"s recommendations. |
| 512 | d) Suitable RCC pump-foundations as per manufacturer\"s design and 4 nos. dunlop (cushy foot) heavy duty antivibration mounting pads. (AR-46.02) |
| 513 | Supply, Installation, Testing and commissioning of Diesel Engine Driven Fire Pumping set (Factory Fitted) suitable for automatic operation consisting of the following as per the specifications. specification as per fire fighting requirements and on the pattern of TAC OR LOCAL AUTHORITY APPROVAL) as per following specifications: |
| 514 | Providing and fixing horizontal split casing multi stage, single outlet pumping set with CI body and bronze impeller & with gland capable of delivering 2280 LPM against a total head of 75 M connected by means of a flexible coupling to a water cooleddiesel engine mounted on a common structural base plate with antivibration pads and and foundation complete with electric panel, battery (including one spare battery), utomatic starting arrangement exhaust pipe of required length to discharge outside building with muffer, day oil tank mounted on suitaible structural supports complete in all respects as per specifications ready for use and as per latest requirement of fire autority regularities. |
| 515 | b) Water cooled TAC approved Diesel Engine suitable for developing at least 70 BHP at 2800 RPM) compatible for above pump complete with automatic starting mechanism, batteries, automatic battery charger unit, flexible coupling with the pump, fuel tank, silencer, exhaust pipe with insulation approx. 25m length & all standard accessoriesas required as per TAC rules including earthing, mandatory spares and tool kit. |
| 516 | c) Common bed plate for mounting pump and engine fabricated from suitable MS Channel as per manufacturer\"s recommendations. |
| 517 | d) Suitable RCC pump foundations as per manufacturer\"s design 8 Nos Dunlop Anti-vibration (cushy foot) heavy duty mounting pads. (AR-47.02) |
| 518 | Supply, Installation, Testing and commissioning of ElectricalMotor Driven Automatic pressurisation (Jockey) pumping set (Factory Fitted) suitable for automatic operation consisting of the following as per the specifications. specification as per fire fighting requirements and on the pattern of TAC OR LOCAL AUTHORITY APPROVAL) as per following specifications: |
| 519 | Providing and fixing horizontal split casing single/multi stage, single outlet pumping set with bronze impeller & with gland capable of delivering 180 LPM against a total head of 75 M with C.I. body and connected by a flexible coupling to a totally enclosed fan cooled inductionmotor mounted on a commonstructural baseplates with all pump accessories complete as per specifications including pressure gauge with gunmetal isolation valves and anti vibration pump, motor to be suitable for 415 volts, 3 phase, 50cycles AC supply (specification as per fire fighting requirements and on the pattern of TAC OR LOCAL AUTHORITY APPROVAL) as per instruction of following specifications: |
| 520 | b) Squirrel cage induction motor totally enclosed fan cooled type suitable for 415 volts ±15% 3 phase 50 Hz AC supply of suitable capacity(approx. 7.5 KW) for the above pumpwith synchronous speed of 2900 RPM confirming to IS:325 & duly coupled with above pump coupled with flexible coupling including earthling as per relevant Indian Standard and specifications. |
| 521 | c)Common bed plate for mounting pump and motor fabricatedof suitable MS channel as per manufacturer\"s recommendations. |
| 522 | d) Suitable RCC Pump foundations as per manufacturer\"s design 4 Nos Dunlop Anti-vibration (cushy foot) heavy duty mounting pads. (AR-48.02) |
| 523 | Providing, fixing, testing and commissiong of double flanged vertical air vessel fabricated from 10mm MS plate with dished ends from 10mm MS plate, outside with one coat of primer and two coats of synthetic enamel paint of approved shade, complete with approved quality of pressure switches, pressure gauge and all other required accessories to operate commonly main fire pump and Jockey pump at drop of pressure, automatically at required pressure setting :(49.00) |
| 524 | Recommended dia.: 450mm |
| 525 | Height of shell : 2000mm |
| 526 | Working pressure: 14.5 kg/cm2 |
| 527 | Test Pressure :25 kg/cm2 |
| 528 | MCC PANEL (Panel for fire pumps) |
| 529 | Design, manufacture, supply, installation, testing and commissioning of following MV switchgear panels suitable for 415 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be indoor, free standing floor mounted, sheet metal clad, cubicle. |
| 530 | All MCCBs shall be provided with magnetic & adjustable thermal releases for short circuit & overload protection with front drive kit (rotary operating handle). |
| 531 | Fault current wherever mentioned shall be Ics value. (Ics = 100% Icu) |
| 532 | Each Starter shall be provided with Motor Duty MCCB/MCB, suitable for the specified Kw of motor (as per SLD), AC3 power contactors, single phasing preventor, on-off Trip Indication Lamps, start /Stop Push Buttons, Auto Manual selector switch Ammeter with Suitable ratio CTs, Auxillary Contactsand remote control, interlocking etc. |
| 533 | All outgoing terminals (power and control) shall be brought upto cable alley. 10% extra terminals shall be provided. |
| 534 | All meters are digital type. |
| 535 | FIRE FIGHTING MAIN PANEL |
| 536 | INCOMING |
| 537 | 1 no 630 amp 4P 35 KA MCCB with thermal over load and Magnetic short circuit release with |
| 538 | 3 Nos. phase indicating lamps |
| 539 | 1 sets of ON/OFF Indicating Lamps |
| 540 | 1 No. ammeter & voltmeter with selector switches |
| 541 | Set of cast resin CT\"s of 630 / 5A, class 1.0, 5 VA. |
| 542 | BUS BAR |
| 543 | Electrolytic high conductivity aluminium three phase and neutral busbars rated at 800 amps having a maximum current density of 1 amp per sq mm suitable to with stand symmetrical fault level of 35 kA at 415 volts for 1 second. The neutral busbar is to be of 50% capacity. |
| 544 | OUTGOINGS FOR HYDRANT/MAIN PUMPS |
| 545 | MCCB 3 Pole,400A(with adjustable thermal magnetic release and (Ics=Icu=25 KA upto 415 V), with CT operated digital Ammeter (0 - 400 A), with 3 CT\"s of 200/5 A, 10 VA, accuracy 1.0, ASS and coloured LED for on (Red) indication - (1 sets) |
| 546 | Fully Automatic Star Delta Starter suitable for Hydrant Pump motor of minimum 70 HP for each pumpand(as per the recommendation of pump manufacturer) complete with over load protection, current sensing type single phase preventer complete with contactors, push button, indicators LED type Auto/manual selector switches all accessories and FRLS copper conductor wiring etc. as required - (1 sets) |
| 547 | OUTGOINGS FOR JOCKEY PUMPS |
| 548 | MCCB 3 Pole,63A(with adjustable thermal magnetic release and (Ics=Icu=25 KA upto 415 V), with CT operated digital Ammeter (0 - 63 A), with 3 CT\"s of 200/5 A, 10 VA, accuracy 1.0, ASS and coloured LED for on (Red) indication - 1 Sets |
| 549 | Fully Automatic DOL Starter suitable for Jockey Pump motor of minimum 10 HP and(as per the recommendation of pump manufacturer) complete with over load protection, current sensing type single phase preventer complete with contactors, push button, indicators LED type Auto/manual selector switches all accessories and FRLS copper conductor wiring etc. as required - 1 Set |
| 550 | Diesel Engine Control70 HP |
| 551 | Auto / Manual selector switch and 3 attempt Starting device, Electronic timer, Relays, Auxiliary switches, Rotary switches, Tripping relays, Contactors, Push button for manual Start / Stop etc. to make the equipment automatic as per functional requirement. |
| 552 | Battery charging unit suitable for 24 V DC with boost and trickle charger, selector switch, with suitable rating transformer, rectifier, RC filter network, fuses on AC and DC protection, 0 - 30 V DC Digital Volt meter, 0 - 20 A DC Digital Ammeter, the charger should be cut off when the engine is started and the batteries shall be charged from battery charging alternator provided in the engine. |
| 553 | Indication LED\"s for high / low lub, oil pressure, water temperature, engine on indicator, with suitable alarms, acknowledgement button etc. |
| 554 | System Controller |
| 555 | Designing, Supply, Installation, Testing and Commissioning of system controller to control operation of Main Electric Fire Pumps, Diesel Engine Pump, Jockey Pumps in sequence as per specification consisting of relays, timers, sensors, annunciation window for fault indication, complete as per specification. |
| 556 | First Jockey pump will start than Hydrant pump start, in case of failure of power diesel pump will start. |
| 557 | Colour coded internal wiring and connections etc. with suitable size Fire Retardant Low Smoke PVC insulated copper cable / solid aluminium strip / bus bar from incoming to bus bar and from bus bar to switch gears / MCCB, starters, meters, selector switches, indicating LED\"s, interlocking and sequence operation arrangements. |
| 558 | Terminal facility for repeat indicator of various audio and visual indications. |
| 559 | The MCC Panel shall be complete with all interconnections, risers, internal wiring, labels etc complete as required. (AR-51) |
| 560 | Fabricating and Installing following size of perforated Hot dip G.I cable tray including horizontal and vertical bends, reducers, tees, cross members and other accessories as required and duly suspended from the ceiling with MS suspenders and including painting etc. as required. (52) |
| 561 | 300 mm width x 50 mm depth x 1.6 mm thickness |
| 562 | 150 mm width x 50 mm depth x 1.6 mm thickness |
| 563 | Supply, Laying, Fixing, Testing and Commissioning of following sizes of XLPE insulated PVC sheathed armoured Copper / aluminium conductor cable of 1.1 KV grade on existing cable tray / surface as required. (AR-53) |
| 564 | 4 core x 2.5 Sq mm copper conductor armoured control cable. |
| 565 | 3 core x 16 Sq.mm. Aluminium Armoured (Jocky) |
| 566 | 3 core x 95 Sq.mm. Aluminium Armoured (Main Pump) |
| 567 | Supply and making end termination with brass compression gland and copper/aluminium lugs for following size of XLPE insulated and PVC sheathed aluminium conductor cable of 1.1 KV grade as required. (AR-54) |
| 568 | 4 core x 2.5 Sq mm copper conductor armoured control cable. |
| 569 | 3 core x 16 Sq.mm. Aluminium Armoured |
| 570 | 3 core x 95 Sq.mm. Aluminium Armoured |
| 571 | Providing and fixing following size of GI strips/ GI wire etc. on surface or in recess for connections, including GI clamps etc. as required.(AR-55) |
| 572 | 25 mm x 5 mm GI strip |
| 573 | 6 SWG dia G.I. wire |
| 574 | Providing and fixing resilient rubber neoprene lined single arch vibration eliminators suitable for raw water upto 450C temperature working pressure 14.5 kg/cm2 and test pressure 25 kg/cm2 with unit control. (AR-56) |
| 575 | 50 mm dia |
| 576 | 65 mm dia |
| 577 | 80mm dia |
| 578 | 100mm dia |
| 579 | 150 mm dia |
| 580 | 200 mm dia |
| 581 | 250 mm dia |
| 582 | Providing and fixing CI double flanges suction strainer (PN 2.0) “Y” type including, nuts, bolts and 3mm thick rubber insertion complete. (AR-57) |
| 583 | Providing and fixing brass/bronze lever operated ball valve of full flow with stainless steel ball (AISI 304 and spindle AISI 410) with setting and gland of superior quality having minimum working pressure of 20 kg/cm2.(AR-58) |
| 584 | Supply, installation, testing & commissioning of cast iron butterfly valves, wafer end type class PN 1.6 as per IS: 13095-1991 or BS: 5155, including necessary nuts, bolts, gaskets etc. complete.(AR-59) |
| 585 | 50mm dia nominal bore.(without gear box) |
| 586 | 65mm dia nominal bore.(without gear box) |
| 587 | 80mm dia nominal bore.(without gear box) |
| 588 | 100mm dia nominal bore. (without gear box) |
| 589 | 150mm dia nominal bore. (without gear box) |
| 590 | Providing and fixing CI double flanged horizontal/vertical type non-return valve including nuts, bolts, 3mm thick rubber insertions complete to IS:5312, part-I, swing type, class PN 1.6. (AR-59) |
| 591 | 65mm nominal bore |
| 592 | 80mm nominal bore |
| 593 | 100mm nominal bore |
| 594 | 150mm nominal bore |
| 595 | 200mm nominal bore |
| 596 | Providing, fixing, jointing and testing of mild steel black pipe (IS: 1239 Part-1) heavy class including cutting, welding/ screwing etc. and providing all fittings viz. flanges, bends, tees, elbow, reducers etc. includingthe cost of structural work for supports fabricated from standard sections (of required size and thickness) e.g. MS rods, angles channels, slotted angle, etc., cutting to sizes, drilling welding fixing to insert plates, including painting over a coat of primer, cuttingholes and chases in brick or RCC walls/slabs and makinggood the same to the approval of engineer/consultant complete including painting with one coat of primer and twoor more coats of enamel paint of approved make and shade including steel work. Note : Pipes upto and 40 mm dia shall be threaded joints, 50mmand above shall be welded joints. (AR-61) |
| 597 | 25mm dia |
| 598 | 50mm dia |
| 599 | 65mm dia |
| 600 | 80mm dia |
| 601 | 100mm dia |
| 602 | 150mm dia |
| 603 | 200mm dia (IS : 3589 - Thickness : 6.35mm) |
| 604 | 100mm dia(IS : 3589 - Thickness : 6.35mm) |
| 605 | Supply, installation, testing & commissioning of gun metal fire brigade connection consisting of 63 mm dia instantaneous type male coupling with built-in check valves and 150 mm dia. flanged outlet complete with bolts, nuts and rubber insertions as required as per IS:904-1983.(AR-62) |
| 606 | Four Way |
| 607 | Supply, installation, testing & commissioning of gun metal 2 way Fire brigade suction hose coupling (Draw-out Connection) with nut for female coupling as per IS:902-1974 complete with 150 mm dia. GI suction pipe and 150 mm dia. 1 No. CI foot valve flanged (to be connected to static water tank).(AR-63) |
| 608 | Providing and fixing pressure switch (for operation at 0-25 kg/cm2) with required fittings and accessories complete.(AR-64) |
| 609 | Supply, installation, testing & commissioning of pressure gauges with isolation cocks and chrome plated copper pipes as hydrant station to read pressure from 0-25 kg/cm2 complete and of dial dia 150 mm.(AR-65) |
| 610 | Supply, Installation, Testing & Commissioning ofMS pipe class \"C\" deisel engine exhaust pipe 150 mm (including all fittings, clamps, steel support 50 mm thick glass wool insulation with 24 gauge aluminium cladding, bird proof cowl etc.) of suitable dia for ingine. The pipe shall be provided with 12 mm thick supercera ceramic fibre rope. (AR-66) |