| 1 | Design, Supplying. Fabrication, Erection & Commissioningincluding 3 (three) months TrialRun of 40 m3/hr. capacity Pressure type IRONELIMINATIONPlant with Constructionof Blower room& backwashwater disposal |
| 2 | Supplying, Fabrication, Erection on suitable RCC foundation and Commissioning with 3 (three) months Trial Run (including cost of routine testing of water sample for performance evaluation) of pressure type Iron removal plant as per design norms of the P.H.E. Dte. with necessary accessories viz. MS fabricated shell with minimum 10 mm thick MS plate with 2 (two) coats of anticorrosive paint & minimum 12 mm thick MS media supporting plate fitted with required no. of pot strainer, MS fabricated oxidation chamber with minimum 10 mm thick plate with necessary pipe connection, valves, Gauges & other instruments as required as per departmental approved design & drawing including cost of filter media, Air Compressor & Air blower with motor, starter, main switch etc. of required capacity & approved specification including power connection from main line etc. all complete. (Rate excludes the cost of Concrete Platform & drain, and the cost of Blower Room): 40m³/hr. capacity |
| 3 | Design, Supply, laying, fitting of pipeline from different unit to nearby Drain/ Water body/ Pond/ upto 100m. Length for proper disposal of backwash water. (Payment will be made as per actual length of executed works.) |
| 4 | Earthwork in excavation in foundation trenches or drain in all sorts of soil (including mixed soil but excluding laterite or sandstone) including removing, spreading & stacking the spoil within a lead of 75m as directed. The item includes necessary trimming the sides of trenches. Levelling, dressing and ramming the bottom, bailing out of water as required complete.(a) Depth of excavation not exceeding 1500 mm. |
| 5 | Earthwork in filling in foundation trenches or plinth with good earth, in layers not exceeding 150 mm including watering and ramming etc. layer by layer complete.a) with earth obtainedfrom excavation of foundation. |
| 6 | Filling in foundation or plinth by fine sand in layers not exceeding 150mm as directed and consolidating same by thorough saturation with water ramming complete. Including the cost of supply of sand.( Payment to bemade on measurment of finished quantity ) |
| 7 | Single brick flat soling of picked jhama bricks including ramming and dressing bed to proper level and filling joints with powdered earth or local sand. |
| 8 | Brick work with 1st class Bricksin sand cement Morter (6:1) including raking out joints scaffolding & curing etc. completed as directed by Engineer- in- Charge.a) In foundation and Plinth : |
| 9 | b) In Superstructure : |
| 10 | 40 mm. thick damp proof course with cement concrete(1:1.5:3) (with graded stone chips 20 mm nominal size) with water proofing compound of approved brand @ 0.2% weight of cement including cost of materials over two coats of non toxic acrylic polymer modified cementitious waterproofing slurry coat completed (cost of water proofing compound andnon toxic paint to be paid seperately) for underground water retaining structures. |
| 11 | Ordinary cement concrete ( mix 1:1.5:3 ) with graded stone chips ( nominal 20 mm size) excluding shuttering and reinforcement. If any, Variety |
| 12 | Reinforcement for reinforced concrete work in all sorts of structures including distribution bars, stirrups, binders etc initial straightening and removal of loose rust (if necessary), cutting to requisite length, hooking and bending to correct shape, placing in proper position and binding with 16 gauge black annealed wire at every intersection, complete as per drawing and direction. (a) For works in foundation and upto roof of ground floor/upto 4 m. i) Tor steel/Mild Steel. II. JSW/JSPL/SHYAM/ SRMB/BMASL/ELECROSTEEL/SSL |
| 13 | Hire charges for shuttring with centering and necessary staging upto 4 m. using approved stout props and thick hard wood planks of approved thickness with required bracing for concrete slabs, beam, columns, lintles curved or straight including fitting, fixing and striking out after completion of works.(In all floors).25mm to 30mm thick wooden shuttering as per decision and direction of Engineer-In-Charge. |
| 14 | 125 mmthickBrick work of 1st class bricks with cement morter (1:4). a) in Superstructure. |
| 15 | Plaster to wall, floor etc with sand and cement morter (1:6) including rounding off or champhering corners as directed and racking out joints or roughing of concrete surface including throating, nosing and drip course where necessary (In all floors). a) With 6:1 cement morter.i) 15 mm thick plaster in Ground Floor. |
| 16 | b)With 6:1 cement morter.i) 20 mm thick plaster in Ground Floor. (Out side ) |
| 17 | (C) With (4:1) Cement mortar.(i ) 10mm. Thick plaster |
| 18 | Neat cement punning in wall /dado, window sills, floor drains etc. in all floors about 1.5mm thick. |
| 19 | Earth work in filling in compound, tank, low land,ditches etc. with good earth, in layers not exceeding 150 mm. including breaking clods and consolidating the same by ramming and dressing complete. (Payment will be made on profile measurement before and after the work).ii) With carried earth arranged by the contractor within a radius of 3 km. Including cost of carried earth. |
| 20 | Artificial stones in floor, dado, stair case etc. with cement concrete (4:2:1) with stone chips, laid in panels as directed, with topping made with ordinary or white cement (as necessary) and murble dust in proportion (2:1) including smooth finishing and rouding off corners and including application of cement slurry before flooring works, using cement @1.75 kg./sq.m. all complete including all materials and labour. In ground floor.3 mm. thick topping (High polishing grinding on this item is not permitted with ordinary cement).Using grey cement.a) 25mm. Thick. |
| 21 | Wood work in door & window frame fitted & fixed in position complete including a protective coat of painting at the contact surface of the frame.(h) Neem, Jam, Jackfruits. In Ground Floor: |
| 22 | Panel shutters of door & window as per design (each panel consisting of single plank without joint) including fitting & fixing the same in position but excluding the cost of other fittings in G.F. a) 35 mm thick shutter with 19 mm thick panel. (b) Sishu, Gamar, Champ,Badam,Bhola, Mogra, Hallak. |
| 23 | Iron butt hinges of approved quality fitted and fixed with steel screws with I.S.I. Mark(oxidised fitting).(a) 100mm. X 50mm. X 1.25mm. |
| 24 | (b) 75mm. X 40mm. X 1.12mm. |
| 25 | Iron haspbolt of approved quality fitted and fixed complete (oxidised) with 16mm. Dia. rod with centre bolt and round fitting.(a) 300mm. Long. |
| 26 | Iron door ring of approved quality fitted and fixed with nut and washer complete.A) 50 mm dia |
| 27 | Iron door handle of approved quality fitted & fixed complete.(a) 100mm. X 5mm |
| 28 | Anodised aluminium barral/tower/socket bolt (full covered)of approved manufactured from extruded section conforming to I.S.I. specification (I.S.204/74) fitted & fixed with cadmium plated screws.(a)225mm.long x10mm. Dia. Bolt |
| 29 | (b)100mm. Longx 10mm. Dia. Bolt |
| 30 | M.S.clamp for fixing door, windows frame made of flat iron end bifarcated mixed in cement concrete with stone chips(1:2:4) fitted and fixed complete as per direction.(a)40mmx6mm. 200 mm length. |
| 31 | (b)40mmx6mm. 125 mm length. |
| 32 | Supplying anodised aluminium catch hook with eye fitted and fixed to shutter andchowkat complete of best quality:(i) 150mm long. |
| 33 | Supply fitting approved type ventilator in position after cutting holes in walls, setting in cement mortar, mending damages to wall & plaster & two coats of paint of approved brand sandshade, payment of mending two damages of wall plaster and painting to be made separately.a) R.C.C. Ventilator of 20 mmthick.i) upto 0.10 sqm. area. |
| 34 | Supplying fitting & fixing UPVC Pipes A - Type and fittings conforming to IS : 13592-1992 with all necessary clamps nails, including making holes in walls, floor etc. cutting trenches in any soil through masonry concrete structures etc. if necessary and mending good damages including joining with jointing materials (Spun Yarn, Valamoid/Bitumen/M-Seal etc.) complete.a) UPVC Pipe.i) 110 mm dia. |
| 35 | (b) SHOEi) 110 mm dia. |
| 36 | M.S.or W.I. Ornamental grill of approved design joints continuously welded with M.S, W.I. Flats and bars of windows, railing etc. fitted and fixed with necessary screws and lugs in ground floor.(ii) Grill weighing above 16 Kg./sq.mtr and above |
| 37 | White washing with stone lime only including cleaning smoothly surface throughly.(a) Three coats. |
| 38 | Applying Exterior grade Acrylic primer of approved quality and brand on plastered or cencrete surface old or new surface to receive decorative textured(matt finish) or smooth finish acrylic exterior emulsion paint including scraping and preparing the surface throughly, complete as per manufacturer\"s specification and as per direction of the EIC. In Ground Floor:a) One Coat. |
| 39 | Protective and Decorative Acrylic exterior emulsion paint of approved quality, as per manufacturer\"s specification and as per direction of EIC to be applied over acrylic primer as required. The rate includes cost of material, labour, scaffolding and all incidental charges but excluding the cost of primer.In Ground floor (Two Coat).a) Normal Acrylic Emulsion. |
| 40 | (a) Priming one coat on steel or other metal surface with synthetic oil bound primer of approved quality including smoothening surfaces by sand papering etc. |
| 41 | b)Priming one coat on timber or plastered surface with synthetic oil bound primer of approved quality including smoothening surfaces by sand papering etc. |
| 42 | Painting with best quality synthetic enamel paint of approved make and brand including smoothening surface by sand papering etc. including using of approved putty etc. on the surface, if necessary :With super gloss (hi-gloss)a) on Timber or plastersurface. Two coats ( with any shade except white). |
| 43 | b) on steel or other metal surface.iv) Two coats ( with any shade except white). |
| 44 | Supplying, laying, fiting, fixing and jointing of UPVC pipes conforming to IS:4985-2000 with latest revision and amendments, if any, with necessary UPVC/CI specials, CIDF sluice valves, as per relevant I.S. specification including labour charges for earth work in excavation in any kind of soil including mixed soil with boulder ,road sub-grade and its flanks but excluding moorum and laterite or sand stonehard arock including cutting of brick payment without damaging the existing telephone/electrical cable line etc.(in case of damage of any type of cable line during excavation, necessary damaged charges as applicable by the respaective authority will be borne by the agency in his own cost. Loading, unloading, carrying of pipes, specials, valves from the local store to work site and lowering laying of pipes specials valves carefully in trenches maintaining proper levels and alignment ,jointing the pipe and specials including supplying of good quality/approved brand solvent cement (as per IS:14182-1994 including cost of all fabricated PVC fitting i.e. tees,bend, reducers, adopter etc.as per IS:101-1988 and making flange joints including supplying required quantity of nuts, bolts and rubber insertion (CIDF sluice valves will be supplied by the department free of cost) as required at site by adopting suitable method so as to facilate the maintenance of pipe line locally as per conventional method including back filling the trenches with good earth obtained from excavation of trenches including consolidation with watering in layer not exceeding 150mm thk. with maintaining anaverage depth of cushion of 1.10mtr. from the top of pipe line including making interconnection with distribution pipes etc. all complete as per drawing direction and satisfaction of the E.I.C. |
| 45 | N.B. i) Manufacturer’s test certificate for UPVC pipe & specials to be produced before laying of pipe line.ii) 3rd party inspection of UPVC pipe & specials to be done by CEPET or (India) SGS/NTH Kolkata or as per direction of EIC as per approved vender list. iii) No part payment at any stage on account of supply of materials shall be entertained. iv) Payment will be made on actual consumption of materials.v) UPVC pipes for the works to be supplied as per approved vendor list and as per direction & satisfaction of EIC. No pipes will be allowed beyond recommendated vendor list.vi) Submission of drawing of pipe line with statement of materials consumed between node to node points against each R.A. & final bill.if so.vii) Any deviation from required clear cover of 1.10mtr.due to site adverse condition, prior permission is to be obtained from EIC and payment for such work will be made on prorate basis over the rate of entire item. viii) All pipe connection shall be completed in all respect and as per directionof EIC. Decision of EIC in this respect is final & binding. In case of any deviation/or any left out pipe connections an amount of Rs.10,000.00 for each pipe connection will be realized/recovered from the bill.ix) No payment will be made without hydraulic test of the pipe line either part or full |
| 46 | (A) Pressure Rating : Class - III(ii) Laying of pipe line including cost of pipe & fittings /specials but excluding cost of valves. |
| 47 | a) 160mm(OD) |
| 48 | b) 140mm(OD) |
| 49 | c) 110mm(OD) |
| 50 | d) 90mm(OD) |
| 51 | Filling the pipe line with water, testing hydraulically as per I.S 3114-1965 (Article-6) in section of a length not exceeding 500mtr. for head of pressure as per specification including supplying installing and fixing all equipments such as diesel pump set, blank flange, pressure gauge, valve, pressure pump and all other tools and plants including drilling topping and plugging of necessary holes to pipes, blocking ends providing temporary thrust block and subsequent blocking of holes and other jointing materials and dismantling and removal of the same including disposal of water etc. all complete as per specification and direction of EIC. The rate is inclusive of cost of requisite water to be arranged by the contractor (Recovery rate of water @ Rs.10.00/m3, if contractor used water from deptt. source). |
| 52 | a) 160mm(OD) |
| 53 | b) 140mm(OD) |
| 54 | c) 110 mm dia |
| 55 | d) 90 mm dia |
| 56 | Cleaning thoroughly the inner surface of pipe line including specials and valves by flushing with water and subsequently disinfection of the same pipe line by flushing again with water containing bleaching powder resulting in residual chlorine not less than 15mg/ltrs. after 24hrs. of such filling including laboratory testing of water samples obtain from the disinfested pipe line and disposal of water from the pipe line after completion of the work. The rates including of cost of requisite water to be arranged by the contractor) (The rate of water @Rs. 10/m3 may be recovered, if the contractor used water from deptt. source). |
| 57 | a) 160mm(OD) |
| 58 | b) 140mm(OD) |
| 59 | c) 110 mm dia |
| 60 | d) 90 mm dia |
| 61 | HORIZONTAL ROAD CROSSING:Horizontal road crossing by Augor-boring including boring charge, pipe laying and jointing, making baricates, lighting arrangement etc. all complete as per direction of E.I.C. For 80 mm dia. to 200 mm dia. pipes. |
| 62 | Supply and delivery of CIDF sluice valve (Special type) PW-1.00 of different dia make with CI double flanged non rusting spindle sluice valves conforming to IS 14846 -2000 with latest emended having body dome/bonnet and cover of C.I.Gr-F.G 210mtr. spindle of IS-6603 G.R-12/Gr-13 non-magnetic, nuts seat rings are of Gunonetal as per IS:318 LTB-2 flanges and drilled to IS:1538 Part IV & VI valves are suitable for max. working pressure of 10kg/cm2(seat test) and body tested to 15kg/cm2. N.B: The above item should be procured from the reputed manufactures as per deptt. approved vender list. |
| 63 | a) 150 mm dia |
| 64 | Construction of Boundary Wall |
| 65 | Earthwork in excavation in foundation trenches or drain in all sorts of soil (including mixed soil but excluding laterite or sandstone) including removing, spreading & stacking the spoil within a lead of 75m as directed. The item includes necessary trimming the sides of trenches. Levelling, dressing and ramming the bottom, bailing out of water as required complete.(a) Depth of excavation not exceeding 1500 mm. |
| 66 | Earthwork in filling in foundation trenches or plinth with good earth, in layers not exceeding 150 mm including watering and ramming etc. layer by layer complete.a) with earth obtainedfrom excavation of foundation. |
| 67 | Earth work in filling in compound, tank, low land,ditches etc. with good earth, in layers not exceeding 150 mm. including breaking clods and consolidating the same by ramming and dressing complete. (Payment will be made on profile measurement before and after the work) |
| 68 | a) With earth obtained from excavation of fundation |
| 69 | a) With CArried earth arranged by the contractor within a radius of 3 km. including cost of carried earth |
| 70 | Filling in foundation or plinth by fine sand in layers not exceeding 150mm as directed and consolidating same by thorough saturation with water ramming complete. Including the cost of supply of sand.( Payment to bemade on measurment of finished quantity ) |
| 71 | Single brick flat soling of picked jhama bricks including ramming and dressing bed to proper level and filling joints with powdered earth or local sand. |
| 72 | Hire charges for shuttring with centering and necessary staging upto 4 m. using approved stout props and thick hard wood planks of approved thickness with required bracing for concrete slabs, beam, columns, lintles curved or straight including fitting, fixing and striking out after completion of works.(In all floors): 25mm to 30mm thick wooden shuttering as per decision and direction of Engineer-In-Charge.a) 25mm to 30mm thick wooden shuttering without staging in foundation |
| 73 | Cement concrete with graded stone ballast (40 mm size excluding shuttering) In ground floor (A) [Pakur Variety]. (a) 1:3:6 proportion |
| 74 | Ordinary Cement concrete (mix 1:2:4) with graded stone chips (20 mm nominal size) excluding shuttering and reinforcement,if any, in ground floor as per relevant IS codes. |
| 75 | Reinforcement for reinforced work in all sorts of structures including distribution bars, stirrups, binders etc intial straightening and removal of loose rust (if necessary), cutting to requisite length, hooking and bending to correct shape, placing in proper position and binding with 16 gauge black annealed wire at every inersection, complete as per drawing and direction.(Rate Analysis).(i) Other than SAIL/TATA/RINL (a) For works in foundation, basement and upto roof of ground floor/upto 4 m.(i) Tor steel/Mild Steeel. |
| 76 | Brick work with 1st class Bricksin sand cement Morter (6:1) including raking out joints scaffolding & curing etc. completed as directed by Engineer- in- Charge. |
| 77 | a) In foundation and Plinth : |
| 78 | 125 mmthickBrick work of 1st class bricks with cement morter (1:4). in Ground Floor. |
| 79 | Plaster to wall, floor etc with sand and cement morter (1:6) including rounding off or champhering corners as directed and racking out joints or roughing of concrete surface including throating, nosing and drip course where necessary (In all floors). |
| 80 | b)With 6:1 cement morter.(i) 20 mm thick plaster in Ground Floor. |
| 81 | Neat cement punning in wall /dado, window sills, floor drains etc. in all floors about 1.5mm thick. |
| 82 | Applying Exterior grade Acrylic primer of approved quality and brand on plastered or cencrete surface old or new surface to receive decorative textured(matt finish) or smooth finish acrylic exterior emulsion paint including scraping and preparing the surface throughly, complete as per manufacturer\"s specification and as per direction of the EIC. In Ground Floor:a) One Coat. |
| 83 | Protective and Decorative Acrylic exterior emulsion paint of approved quality, as per manufacturer\"s specification and as per direction of EIC to be applied over acrylic primer as required. The rate includes cost of material, labour, scaffolding and all incidental charges but excluding the cost of primer.In Ground floor (Two Coat)a) Normal Acrylic Emulsion |
| 84 | M.S.or W.I. Ornamental grill of approved design joints continuously welded with M.S, W.I. Flats and bars of windows, railing etc. fitted and fixed with necessary screws and lugs in ground floor. (ii) Grill weighing above 16 Kg./sq.mtr and above. |
| 85 | Extra for work in grill gate: For hanging and locking arrangements including supply of materials and labour complete. |
| 86 | Priming one coat on steel or other metal surface with synthetic oil bound primer of approved quality including smoothening surfaces by sand papering etc. |
| 87 | Painting with best quality synthetic enamel paint of approved make and brand including smoothening surface by sand papering etc. including using of approved putty etc. on the surface, if necessary :With super gloss (hi-gloss): on steel or other metal surface. With super gloss (hi-gloss):Two coats ( with any shade except white). |
| 88 | Approach Road |
| 89 | Box cutting or filling in Road embankment in all sorts of soil including spreading the soils properly over the flank as necessary or on berm to approximate grade & camber and rolling the sub-grade with power roller to proper camber and grade as per direction and satisfaction of Engineer-in-charge including uprooting and removing plants and jungles when and where necessary.: Depth up to 150 mm. |
| 90 | Single brick flat soling of picked jhama bricks including ramming and dressing bed to proper level and filling joints with powdered earth or local sand. |
| 91 | Supplying and laying Polythene Sheet (150gm / sq.m.) over damp proof course or below flooring or roof terracing or in foundation or in foundation trenches. |
| 92 | Hire charges for shuttring with centering and necessary staging upto 4 m. using approved stout props and thick hard wood planks of approved thickness with required bracing for concrete slabs, beam, columns, lintles curved or straight including fitting, fixing and striking out after completion of works.(In all floors): 25mm to 30mm thick wooden shuttering as per decision and direction of Engineer-In-Charge.a) 25mm to 30mm thick wooden shuttering without staging in foundation |
| 93 | Ordinary Cement concrete (mix 1:1.5:3) with graded stone chips (20 mm nominal size) excluding shuttering and reinforcement if any, in ground floor as per relevant IS codes. (i) Pakur Variety.(Ref: P-26, It-10i PWD SOR) 3rd Corrigendum, Pg-13, it-33.i |
| 94 | Earth work in filling in compound, tank, low land,ditches etc. with good earth, in layers not exceeding 150 mm. including breaking clods and consolidating the same by ramming and dressing complete. (Payment will be made on profile measurement before and after the work): With carried earth arranged by the contractor within a radius of 3 km. Including cost of carried earth. |