| 1 | SH-I Replacement of DG sets |
| 2 | Design, Manufacture, Supply, Installation, Testing and Commissioning of 100 kVA diesel generator set with 2 years warranty (as per latest CPCB-IV compliance) comprises of following requirements. (i) 01 No. alternator suitable for generating 100 kVA, 415 V, 3 Phase, 50 Hz, 0.8 PF, 1500 RPM, self ventilated, self regulated, self excited with brushless type conforming to IS 4722, radiator cooled, class-H insulation for windings, performance class of G3 and alternator design as per IEC-60034.(ii) 4 cylinder engine, inline CRDi , 4 stroke, turbo charged diesel engine developing suitable BHP at 1500 RPM suitable for above alternator and complete with all accessories such as base frame, AVM Pads, battery, all types of filters, coupling, starter, residential silencer, lightning arrestor spike, automatic electronic speed governing mechanism,control panel, compact radiatoretc. and conforming to relevant IS with up to date amendments as specified and as required. (iii) 1 No.fuel tank of capacitynot less than 200 ltrs. drawout type or as per OEM for easy maintenance to beprovided inside the Genset.(iv) Genset with powder coated control panel of advanced microprocessor based controller with display indications, bus bar section, MCCB protection etc., |
| 3 | (v) Customised compact modular type acoustic enclosure suitable for the above DG set to limit the noise Level to 75 dB (A) at a distance of 1 mtr., from the enclosure , having insertion loss of standard accoustic enclosure and exhaust muffler with 25 dB (A) , made out of CRCA sheet of 1.6 mm thickness for the outside cover and doors, 0.5 mm thick perforated GI sheet for inside cover, louvers of thickness 1.6 mm CRCA sheet for fresh air and hot air, pretreatment process and UV resistent powder coating of all the parts, neoprene rubber gasket and heavy duty stainless steel locks & hinges.(vi) Acoustic lining made up of high quality rock wool/glass wool/ mineral wool confined to IS-8183 with aluminum cladding, base frame of suitable size channel, provision to accommodate batteries, and support for silencers,provided with 2 Nos. LED fittings and switches and enclosure with high temperature safety device etc., as required. |
| 4 | (vii) Exhaust gas pipingfor above DG of suitable dia. welded black MS B-class pipe confirming to IS:3589 cut to required lengths (Minimium of 10 Mtrs) and installed with necessary bends and clamps, bellows anti-vibration mountings, insulation of exhaust system with mineral wool/ rockwool, 50 mm thick wire mesh & aluminium cladding of 0.6mm thick and provision of suitable exhaust pipe supporting arrangement as per site requirement etc., as required as per specifications.(viii) 1.25 mm thick G.S.S square/rectangular ducting to be fabricated for dissipation of hot air to outside, complete with gaskets, elbows, splitters, vanes, supports, etc as required as per specifications.(ix) DEF tank of suitable capacity to be provided for meeting the emission norms.(x) Complaint to latest emission norms of MoEF/CPCB (i.e., CPCB-IV & Emission Compliant) as specified and as required. (xi) Laying of control cable from AMF panel to DG set, earthing connections, interconnections and adjustment in the chequered plate for cable termination, necessary modifications at site etc., including dismantling of old DG set (of capacity 160kVA ) and shifting the same to location designated by AAI complete as required. (shall be as per IS). |
| 5 | SH:II Supply Items |
| 6 | Supply of 15 Watt, 240V round surface mounted LED Lowbay fixture with THD less than 5%, pressure die-cast aluminum alloyhousing of powder coated,PC diffuser,surge protection of 6 kv, IP65, IK08, 5700K CCT, not less than 120 lm/w luminous efficiency etc., complete as required.(Make:LT, Model No:DISC MIN 15W or equivalent) |
| 7 | Supply of 20 Watt, 240V linear surface mounted LED luminaire with THD less than 5%, extruded aluminium alloy housing & Pressure die-cast end caps of powder coated, Poly carbonate diffuser,surge protection of 20 kv, not less than 130 lm/w luminous efficiency, IP66, IK10, 5700K CCT etc., complete as required.( Make: LT, Model: AMIOT MINI 20W or equivalent) |
| 8 | Supply of 30 Watt, 240V linear surface mounted LED luminaire with THD less than 5%, pressure die-cast aluminum housing of powder coated, PC diffuser,surge protection of 6 kv, IP66, IK08, 5700K CCT, not less than 120 lm/w luminous efficiency etc., complete as required. ( Make:LT, Model: Parker V2 surface or Equivalent) |
| 9 | Supply of 35 Watt, 240V LED street light luminaire with THD less than 5%, pressure die-cast aluminum alloy housing of powder coated,Injection moulded special PC compoundlens ,surge protection of 20 kv, IP66, IK08, 5700K CCT, not less than 135 lm/w luminous efficiency etc., complete as required. ( Make:LT, Model: ADORNIS MIN 35W 5700K LED Outdoor Street light or equivalent) |
| 10 | Supply of Dual LED Aviation Obstacle Light Fixture total of 10W, IP66 for both lights, LM-6 Aluminium housing, Lens made of Polycarbonate U.V stabilized optical grade suitable for outdoor/sunlight exposure, PCB\"s of Glass epoxy FR-4 grade with UVLO-94 type,Fixture with Individual solid-state Inbuilt Automatic day/night sensor and low intensity Type-B in accordance with ICAO Annex-14 Volume-I Aerodrome Design & Operations.(Make: RAYDYNAMICS, Model:LIT32-D230-UI or Any Make meeting ICAO requirements) |
| 11 | Supply of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos.blades, 30 cm long down rod, 2 nos. canopies,shackle kit,safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required with 3 years warranty. |
| 12 | Supply of 400 mm sweep 3 blade, BEE 5 star rated, BLDC motor operated pedestal fan of 28 -32 Watt range, 1350 RPM, with air delivery of mim 65 CMM, suitable for 1-Phase, 230V, 50 Hz operation etc., complete as required with 2 years warranty. |
| 13 | Supply of 300 mm sweep, Heavy duty exhaust fan of 90 Watt with 2 years warranty, suitable for 1-Phase, 230V, 50Hz, with air delivery of minimun 1710 CMH, 1400 RPM including provision of louver shutter,powder coated metalic body,motor with copper winding etc., complete as required. |
| 14 | Supply of 380 mm sweep, Heavy duty exhaust fan of 160 Watt with 2 years warranty, suitable for 1-Phase, 230V, 50Hz, with air delivery of minimun 3250 CMH, 1400 RPM including provision of louver shutter,powder coated metalic body,motor with copper winding etc., complete as required. |
| 15 | Provision of Floor mounted water purifier cum dispenser having purification of 50 LPH with RO+UV or RO+ESS purification, stainless steel 304 grade storage tank for Normal/Cold/Hot with each of 20 Ltrs/20 Ltrs/1.1 Ltr storage capacity respectively, dynamic LCD display for monitoring of TDS, Catridge life, Temperature etc., 3 Nos. of stainless steel taps for Normal/Cold/Hot water, suitable for input water TDS of upto 1000 PPM, including with necessary piping arrangements for water intake and drain, operating at 230 V, 1-Phase, AC supply. etc ., complete as required. |
| 16 | Provision of Floor mounted water purifier cum dispenser having purification of 10 LPH with RO+UV or RO+ESS purification, stainless steel 304 grade storage tank for Normal/Cold/Hot with each of 8 Ltrs/3.3 Ltrs/1.1 Ltr storage capacity respectively, dynamic LCD display for monitoring of TDS, Catridge life, Temperature etc., 3 Nos. of stainless steel taps for Normal/Cold/Hot water, suitable for input water TDS of upto 1000 PPM, including with necessary piping arrangements for water intake and drain, operating at 230 V, 1-Phase, AC supply. etc ., complete as required. |
| 17 | Supply of following size XLPE insulated PVC sheathed aluminium conductor armoured power cable of 1.1KV grade confirming to IS 7098 (PART-I) with upto date amendments as required. |
| 18 | 3.5 C X 50 sqmm |
| 19 | 4 C x 16 Sqmm |
| 20 | Supply of 5 Core X 6 sq.mm PVC insulated and PVC sheathed FRLS, 1.1KV garde flexible copper conductor cable as per IS 694 with upto date amendments as required. |
| 21 | SH: III Internal and External Electrical Works |
| 22 | Installation, testing and commissioning of pre-wired LED fittings of all types complete with all accessories etc., directly on ceiling/wall, including connection with 1.5 sq. mm FRLSH PVC insulated, copper conductor, single core cable and earthing, necessary mounting base supports etc., as required |
| 23 | Installation, testing & commisioning of pre-wiredLED street light fixtures on wall clamped by providing 40mm dia of B-class GI pipe, 1.5 mtr long GI arm bracket including connection with 1.5 sq. mm FRLSH PVC insulated, copper conductor single core cable and earthing etc., complete as required |
| 24 | Installation, testing and commissioning of 10 Watt dual LED aviation obstruction light over 1.5 mtr height painted MS angle iron frame work at the top of 30 mtr heigh tower building with necessary electrical connections, i/c fabricating supply & fixing of hot dip galvanised 1.5 mtr heigh angle iron stand for installing twin dome aviation obstruction lights with necessary drilling, angle fastener, etc complete as required. |
| 25 | Supplying and laying of following size OD HDPE Pipe of PE 80 PN 6 ISI Marked along with all accessories conforming to IS 4984complete with fitting and cutting, jointing etc.,direct in ground (0.75 Mtr below the ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., as required. |
| 26 | 40 mm |
| 27 | 75 mm |
| 28 | Laying of one number XLPE insulated and PVC sheathed power cable of 1.1 KV grade of following size in the existing RCC/HUME/METAL Pipe/HDPE Pipe as required. |
| 29 | Upto35 Sq.mm |
| 30 | Above 35 sq. mm and upto 95 sq. mm |
| 31 | Laying of one number XLPE insulated and PVC sheathed power cable of 1.1 KV grade of following size in the existing masonry open duct as required. |
| 32 | Upto35 Sq.mm |
| 33 | Above 35 sq. mm and upto 95 sq. mm |
| 34 | Laying and fixing of one number XLPE insulated and PVC sheathed power cable of 1.1 KV grade of following size on wall surface as required. |
| 35 | Upto35 Sq.mm (clamped with 1mm Thick Saddle) |
| 36 | Above 35 Sq.mm and upto 95 Sq.mm(clamped with 1mm Thick Saddle) |
| 37 | Laying of one number XLPE insulated and PVC sheathed power cable of 1.1 KV grade of following size on existing cable tray as required. |
| 38 | Upto35 Sq.mm |
| 39 | Above 35 sq. mm and upto 95 sq. mm |
| 40 | Supply & installing 150mm width x 50mm depth x 1.6mm thickness size of perforated hot dip galvanised iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with GI suspenders including GI bolts & nuts etc as required |
| 41 | Supply & installing 150mm width x 50mm depth x 1.6mm thickness size of perforated hot dip galvanised iron cable tray \"bends\" (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with GI suspenders including GI bolts & nuts etc as required |
| 42 | Supply and erection of 6 Mtr height Octagonal Hot Dip GI street light pole upto 1 mtr long single arm bracket suitable for mounting single street light luminarie complete with base plate,J foundation bolts with template, washer nuts, anchor plates, earthing stud, 6 Amps MCB along with connector terminal including providing suitable RCC (1:3:6) pole foundation as per standards/OEM specification, 40mm dia HDPE pipe in foundation for cable entry and exitetc., complete as required. |
| 43 | Supply and fixing of polycarbonate IP-66 box of suitable size loop in -loop out box for street light poles along with 6 Amps MCB, 16 Sq.mm, 4 Pole connector terminal of 20 Amps capacity, including 16 Sq.mm cable terminations, lugs, glands, clamps for fixing on poles etc., as required. |
| 44 | Supplying and errection ofLoop-inLoop-outBox Outdoor type(Doouble door with hinged type outdoor and key lock) made out of 3mm thick CRCA sheet steel for outer Shell (width not less than 450 mm) with canopy and 2mm thick CRCA sheet steel for inner partition, 3 mm thick for gland plates, dust tight, vermin proof, totally enclosed, cubicle type, floor mounting, free standing, extensible on both sides, painting with 7 tank process for powder coating in approved shade and also includes provision of necessary supporting arrangement with MS \"C\" channel with 100A copper busbar for three Phase & One Neutral, Gland&connectionProvisionforoneincomer (3.5 Cx50 sq mm)and 3 outgoings , earthconnection and suitable forthree PhaseACsupply, with suitable RCC foundation (1:3:6) as per E-I-Cetccompleteasrequired. |
| 45 | Supplying and making indoor end termination with brass compression gland and aluminium lugs for following size of XLPE insulated and PVC sheathed aluminium conductor cable of1.1 KV grade as required. |
| 46 | 3.5 X 50 SQ.MM |
| 47 | 4 X 16 SQ.MM |
| 48 | SH-IV Lightning Protection & Earthing |
| 49 | Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc., complete as required. |
| 50 | Jointing copper tape (with another Copper tape, base of the finial or any other metallic object) by riveting / nut bolting / sweating and soldering etc., as required. |
| 51 | Providing and fixing copper tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required. (For horizontal run) |
| 52 | Supply and laying of single core 70 sq.mm size FR PVC insulated unarmoured copper cable of 1.1 KV grade Green color for earth connection on wall surface as required.(For vertical run) |
| 53 | Providing and fixing testing joint, made of 20 mm X 3 mm thick copper strip, 125 mm long, with 4 Nos. of Brass bolts, nuts, chuck nuts and spring washers etc., complete as required. |
| 54 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal / coke and salt as required |
| 55 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required |
| 56 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal / coke and salt as required |
| 57 | Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/terminating with brass nut, bolt, spring, washer etc., as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 58 | Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer,excavation and re-filling etc. as required |
| 59 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required |
| 60 | Supply and fixing of Fibre glass hallow supporting poles having height of 9 Meter for providing and termination of horizontal air terminalswith moulded metalic base with stainless steel bolt nuts and the supporting pole shall be fixed on the roof over 30 meter height tower building. |
| 61 | Providing and fixing 6 SWG dia G.I wire on surface or in recess for loop earthing as reqired. |
| 62 | Providing and fixing 4 mm dia copper wire on surface or in recess for loop earthing on wall/existing GI pipe etc., as required. |
| 63 | Providing,fixing and laying of following sizes Unplasticized Polyvinyl Chloride (UPVC) pipes at 0.5 Mtr below direct in ground, including all UPVC plain & brass threaded fittings this includes jointing of pipes & fittings with one step UPVC solvent cement, trenching, refilling & testing of joints complete etc., as required. |
| 64 | 32mm nominal dia |
| 65 | 25mm nominal dia |
| 66 | SH:VFIRE ALARM WORKS. |
| 67 | SITC of UL ListedIntellegent Addressable type Optical Smoke cum Heat Detector complete with all accessories like base, base box etc., to be installed under/above false ceiling - roof/concealed space etc.,including interconnecting with loop cable complete as required. |
| 68 | Supply and fixing of UL Listed Addressable Hooter cum Strobe complete with address switch including base plate, box, necessary accessories etc., as required. |
| 69 | SITC of UL Listed Addressable type Manual Call Point (Pull Station Type) complete with Input Module, Push Botton, enclosed in box with provision for cable or conduit coupling, painted as required. |
| 70 | SITC of UL ListedIntelligent Analogue addressable Control Relay Module suitable for Single output activation complete with termination etc., as required. |
| 71 | SITC ofUL Listed Intelligent Analogue addressable Hooter Control Module suitable for Single output activation complete with termination etc. as required. |
| 72 | SITC of UL Listed Addressable Loop/Fault Isolator with base with termination etc. as required. |
| 73 | Providing & fixing of First Aid Box as approved by St. John Ambulance Brigade/ Indian Red Cross conforming to IS 2217-1963 as required |
| 74 | Supplying & laying of 2Cx1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required. |
| 75 | Supplying and laying of \"B\" Class G.I pipe of following dia, i/c excavation of bituminous/ concrete road/ pavement, excavation of soil to maximum depth of 0.75 Mtrs from ground refilling the soil and with CC of ratio 1:3:6 on top for 0.15 Mtrs after laying Pipe and plastering, making good thesame etc., as required. |
| 76 | 40 mm dia |
| 77 | 80 mm dia |
| 78 | Charges for Re-programming the existing Fire Alarm Control Panel to install the new / additional addressable type equipments like, Optical Smoke cum Heat Detectors, Hooters, MCPs, Control relay modules, Repeater Panel, etc. |