| 1 | Safe loading Carriage & unloading of following material from store centre to pit site/JE dump store. |
| 2 | 3core standerd aluminium conductor PVCinsulaed armoured served sheathed cables 1100 Volts grade size of 240 sq.mm 3-1/2 core |
| 3 | 3core standerd aluminium conductor PVCinsulaed armoured served sheathed cables 1100 Volts grade size of 150 sq.mm 3-1/2 core |
| 4 | 3 core 300 sq.mm standerd aluminium conductor XLPE (Cross linked polyethylene)insulaed PVC bedded |
| 5 | straight through joint kit of size 31/2 X 300 sq.mm with heatshrinkable kit including ferrulcs and other jointing materials. |
| 6 | Work |
| 7 | Laying of3core standerd aluminium conductor PVCinsulaed armoured served sheathed cables 1100 Volts grade size of 240 sq.mm & 150 sq.mm 3-1/2 core at a depth of 750mm below ground level over a cushion of 75 mm. thick sand all around and protected with burrnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer- Incharge, complete in respect. the armouring of the cable shall be properly connected with the earth conductor by clamps etc. |
| 8 | Laying of3 core 300 sq.mm standerd aluminium conductor XLPE (Cross linked polyethylene)insulaed PVC bedded, Galvanised flat steel strip armoured cables confirming to I.S. 7098 (Part-II with latest amendments) 33 KV grade at a depth of 900 mm below B9ground level over a cushion of 100 mm thick fine river sand all around and protected with well burnt bricks on sides and on top put across. The armouring of cable shall be properly connected with earth conductor by clamps etc. |
| 9 | Fixing and making straight through joint kit of size 31/2 X 300 sq.mm with heatshrinkable kit including ferrulcs and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminum conductor cable of 33 KV grade as requied. |
| 10 | Supply & fixing with decentralized material which is arranged by the contractor at his own cost |
| 11 | Supply & Installation with Testing and Commissioning of Schneider Make 33kV 800 Amps Indoor type VCB Panel, STC 25kA/ 3Sec Cu Bus Bar 3 Incomer 1 Bus Couplar 3 Outgoing |
| 12 | Supply & Installation with Testing and Commissioning of Schneider Make 1250kVA 33/0.433kV Level-1 Losses as per IS:1180 Latest, OLTC Transformer with RTCC & AVR Having Cable Box termination in each side |
| 13 | 500 kVAr APFC Panel with Partial IGBT based intelligent Hybrid PEC (HyPEC) with below specification |
| 14 | SITC of factory fabrication & wired, metal clad dust & vermin proof, floor mounting type 500 kVAr IGBT based intellrgent Hybrid PFC (HyPFC) Panel fabricated out of 2 mm thick CRCS sheet bsteel & MS channal base of 100 X 50 X 6 mm. The instrument chamber shall be seperate & shall comprise of flush type digital metering systemwith selector swithches for phase to phase & phase to neutral voltage, line current with OFF with CTs for different redings, backup protection MCBs, phase indicating LED Lights etc. The panel board shall have suitable capacity of electrolytic & electrical grade Aluminium Bus Bars insulated with PVC heat shrink sleeves & mounted on NON Hygroscopic SMC / DMC supports. No cable shall be terminated directely on to the switchgear terminal for which necessary arrangement should be made with bus bar extensions / connectors including hardwares for cable jointing. The panel board shall be compartmentalized & shall have FRP sheetprotection where ever bus bar crosses from one compartment to other. the panel shall have the following feature: |
| 15 | 1.Nominal voltage : 440 V (+/- 10%) 2. Thyristor Switching Module and IGBT fired circuit for Active filler integrated Thyristor Modules with Heat Sink, Firing Board Circuit 3.Speed <0.2 milli second4. Efficiency >98%5.Current Injecting - Stepless Current Compensation 6. Effectivness - effective with high fluctation load 7. Reactive Power Compensation Capability - Both Leading & Lagging PF / inductive and capacitive reactive power compensation8. Load Balancing - Negative sequencecurrent injection to balance grid current.9. Harmonic mitigation - Harmonic compensation 10. Neutral Compensation 11. Ventilation Through Axial Flow Fan with Thermostat 12. Capacitors Bank Super Heavy Duty Series at 525V 50/60Hz |
| 16 | SITC of L.T. Control Panel, indoor Cubical type dust & vermin proof floor mounting typs, dead front construction, made of 2 mm thick CRCA sheet duly Powder Coated and complete with the following switchgears, meters & accessories of L&T or equivalent make including connections & intreconnections etc. complete in all respects. |
| 17 | INCOMING :2000 A, FP Air Circuit Braker EDO MP Release with necessary protection devices- 3 Sets.BUS COUPLER:2500 A, FP Air Cirucut Breaker EDO MP Release- 2 Sets. INTERLOCKIG: All incooming ACBs & Bus Coupler shall be electrically interlocked BUS BARS : 2400 A. TPN Aluminium Bas Bars with PVC heat shrink sleeves and mounted on Non hygroscopic DMC supports - 1 SetDIGITAL METERING : Multi Function Meter with RS485 Communication -3 SetsDigital VM ,AM,VSS,ASS,CTs, Phase Indicating Lights &Control MCBs-3 Sets OUTGOING : 1250A, 4P Air Circuit Breaker MDO with amperemeter, selector switch , CTs & ON indicators - 3 Sets 800 A, 4P Air Circuit Breaker MDO With amperemeter ,Selector switch, CTs & ON indicators -3 Sets630 A, 4P MCCB with S/L, ROHM, amperemeter, |
| 18 | Selector switch, CTs. &ON indicators -6 Set.400 A, 4P MCCB with S/L, ROHM, ampermeter, Selector switch,CTS.&ON indicators-6 Sets250A, 4P MCCB with S/L ROHM, ampermeter,Selector switch,CTS.&ON indicators-6 Sets 125 A, TP MCCB with S/L ROHM, ampermeter,Selector switch,CTS.&ON indicators-3 Sets |
| 19 | EMERGENCY L.T. PANEL: INCOMING: 1600 A, FP Air Circuit Breker EDOMP Rrlease with necessary protection devices- 1 Sets BUS-BARS:2000 A, TPN Aluminium Bus Bars with PVC heat shrink sleeves and mounted on Non hygroscopic DMC supports -1 Set.DIGITAL METERING: MILTI Function Meter with RS 485 Communication- 1SetsDigital VM,AM,VSS, ASS,CTs, Phase Indicating Lights & Control MCBs-1 Sets OUTGOING 630 A, 4P MCCB with S/L,ROHM ampermeter, Selector switch, CTs& ON indications- 2 Sets 400 A, 4P MCCB with S/L,ROHM, ampermeter,Selector switch, CTs& ON indications- 2 Sets 250 A, 4P MCCB with S/L,ROHM, ampermeter,Selector switch, CTs& ON indications- 4 Sets 125 A, TP MCCB with S/L,ROHM, ampermeter, Selector switch, CTs& ON indications- 2 Sets |
| 20 | SITC of L.T Control Panel, indoor cubical type dust& vermin proof, floor mounting type, dead frount construction, made of 2 mm thickCRCA sheet steel duly powder Coated and complete with the following switchgears, meter & accessories of L&T orequivalent Make including connection & interconnection etc.comlete in all respects. |
| 21 | SYNCRONIZING OF 2 Nos. DG Sets Through 2 Sets Of Panels all together consisting of INCOMING :800 A, FP EDO Air Circuit Breaker MP REL. with closing trip preventer,230 V Closing Coil, 24 V DC Shurt Trip Coil & 415 VAc Under Voltage Release Aux & Trip Cotact Block- 2 SetsDIGITAL METERING: Multi Function Meter with RS485 Comminication Port CTs. Indicating Lightswith Backup Protection MCBs - 2 setsBus-BARS (Main Horizontal) 2000 A. TPN Aluminium Bus Bars with PVC heat shrink sleeves and mounted on Non hygroscopic DMC supprots CONTROL INSTRUMENTS : PLCwith HMI display - 1 Sets.Resin cast CTs 800/5A 15VA with Shorting terminals- 2 Sets.Status Indicating Lights 24V DC- 2 Sets.Phase Indicating Lights 230v AC (R.Y.B)- 2 Sets.Auto / Manual Selector Switch 2P 2W - 1 Set. |
| 22 | Power Switch Scoket 15 A- 1 Set.Push Button with NO / NC Contacts (For Start)- 2 Sets.Push Button with NO / NC Contacts (For Stop) - 2 Sets.Push Button with NO / NC Contacts (For Fault Accept) - 2 Sets. Push Button with NO / NC Contacts (For Reset)- 2 Sets.Push Button with NO / NC Contacts (For Emergency Stop)- 2 Sets.ON / OFF Selector Switch for battery charger- 2 Sets.SMPS Battery Charger - 2 Sets. DC VM Analog type 30 V - 2 Sets.DC AM Analog type 30 V- 2 Sets.SP Control MCB\"s- 2 SetsDP Control MCB\"s- 2 Sets.FP Control MCB\"s- 2 Sets.Control Relays 4CO 24V DC- 2 Sets.Control Relays 4CO 230V AC- 2 Sets.Control Contactors 24V DC- 2 Sets. Control Contactors 230V AC- 2 Sets. Control Contactors- 2 Sets. Protection Relay if requird other than incorporated in DG Controller - 2 Sets. RelayBoard 24V DC- 2 Sets. Power Supply 24V DC 5A - 2 Sets. Hooter 24V DC- 2 Sets. Cooling Fan 230V AC - 2 Sets. Breaker Control Switch 25A (TNC) - 2 Sets. |
| 23 | Space heater with thermostat - 2 Sets. 24V 20A rectifier with Heat Sink- 2 Sets. Control Terminal Block 4 Sq.mm - 2 Set.UPS - 2 Sets.OUTGOING : 1600 A, FP EDOAir Circuit Breaker MP REL. with closing trip preventer, 230V Closing Closing Coil, 24V DC Shunt Trip Coil & 415 V AC Under Voltage Release Aux. & Trip Contact Block- 1 Set. |
| 24 | Supply and laying of3core standerd aluminium conductor PVCinsulaed armoured served sheathed cables 1100 Volts grade at a depth of 750mm below ground level over a cushion of 75 mm. thick sand all around and protected with burrnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer- Incharge, complete in respect. the armouring of the cable shall be properly connected with the earth conductor by clamps etc. |
| 25 | 400 sq.mm 3-1/2 core |
| 26 | 300 sq.mm 3-1/2 core |
| 27 | 50 sq.mm 3-1/2 core |
| 28 | 35 sq.mm 3-1/2 core |
| 29 | Supply and fixing of brass nickle plated compression gland for PVC insulated & armourd served sheathed, underground cable including rubber ring etc. complete in all respect. The armouring of the cable shall be properly connected with the earth as per direction of Engineer-Incharge. |
| 30 | 35 sq.mm 3-1/2 core |
| 31 | 50 sq.mm 3-1/2 core |
| 32 | 150 sq.mm 3-1/2 core |
| 33 | 240 sq.mm 3-1/2 core |
| 34 | 300 sq.mm 3-1/2 core |
| 35 | 400 sq.mm 3-1/2 core |
| 36 | Supply and fixing of plain or pin type copper tin plated cable socket (lug) to the cable leads, insulating with tape and making connection etc. complete in all respect as per direction of the Engineer-Incharge. |
| 37 | 35 sq.mm |
| 38 | 50 sq.mm |
| 39 | 150 sq.mm |
| 40 | 240 sq.mm |
| 41 | 300 sq.mm |
| 42 | 400 sq.mm |
| 43 | Supply and burying of 600mm x 600mm x 3mm copper plate vertically for earthing with its top at least 3 meters below ground level complete with 20mm dia G.I. pipe and funnel for watering and one earthing lead of one no. 8 to 10 SWG copper wire in 15mm dia G.I. pipe up to switch board ( from appron to switch board the cost of G.I. pipe and copper wire will be extra) 30cm square C.I. frame with hinged cover mesonry housing alternate layers of charcoal/coke and salt at least 150mm thick alround etc. complete in all respect. |
| 44 | Supply and burying of 600mm x 600mm x 6mm G.I. plate vertically for earthing with its top at least 3 meters below ground level complete with 20mm dia G.I. pipe and funnel for Watering and one earthing lead of two no. 8 to 10 SWG G.I. wire in 15mm dia G.I. pipe up to switch board ( from appron to switch board the cost of G.I. pipe and G.I. wire will be extra) 30cm square C.I. frame with hinged cover mesonry housing alternate layers of charcoal/coke and salt at least 150mm thick alround etc. as per direction of the Engineer-In-charge complete in all respect. |
| 45 | Supply and laying of 32mm x 6mm copper strip from earth electrode directly in the ground as required complete in all respect. |
| 46 | Supply and laying of 32mm x 6mm G.I. strip from earth electrode directly in the ground as required complete in all respect. |
| 47 | Supply and fixing of the fire extinguisher, ABC Type 6.00 kg. capacity (ISI Marked IS: 15683 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. |
| 48 | Supply and fixing of C02 type fire extinguisher 4.5 kg. capacity (ISI Marked IS : 2878 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. |
| 49 | Supply and fixing of shock treatment chart (prescribrd under l.E. rules) duly framed with glass and supported from back with hard board or soft board with supply of all material labour T&P for proper completion of work. |
| 50 | Supply and laying of 1800mm X 900mm x 12mm thick chequered rubbbber matting of tested quality. |
| 51 | Supply and erection of factory fabricated and wired metal clad dust and vermin proof Feeder Pillar Panel TPN switch board complete with the following HRC Type heavy duty TPN fuse switches with fuses and instrument chamber etc. complete in all respects. The instrument chamber shall be separate and shall comprise of flush typs ammeter, voltmeter, selector switches for ammeter, instrument fuses, current transormer etc. The board shall have suitable capacity electroytic alumininum busbars as per IS8623 istulate with heat shrink sleeving and mountend on non hygroscpic supports such as CMC/DMC support with deteachable side covers and shall be suitable for extension on the sides. The switches shall be complete with suitable cable end boxes, reverse entery boxes in case of pedestaal type, cable sockets, compression glands and indicating lamp on incoming etc. The job includes the grounting of the board as per direction of Engineer-in charge. |
| 52 | INCOMING |
| 53 | 800 Amp/415Volt ACB-1No |
| 54 | OUTGOING |
| 55 | 630 Amp,ACB-1 No,100 Amp MCCB-2 Nos.& 63 AmpMCCB-1 No |
| 56 | Cat.B Pannel Cubicle Type |
| 57 | INCOMING |
| 58 | 1600 Amp/415Volt ACB-1 No |
| 59 | OUTGOING |
| 60 | 800 Amp ACB- 2 Nos |
| 61 | Cat.B Pannel Cubicle Type |
| 62 | Supplying, installation, testing and commissioning of silent type DG sets, AMF Panel, bus ducting/ cables from DG sets to essential panel, synchronizing panel where required, DG set enclosure room sound insulation/ventiation/smoke exhaust as required earthing of DG set system, control. cabling, fuel tank/piping DG set exhaust piping / exhaust chimney as per CPCB norms,civil works connected with DG sets including foundation as required. (500 KVA * 2 Nos.) |
| 63 | Regular Operation and Maintenance Technical Staff for25000/ month per opertor total opertor 5 no. and rs 15000/ per month helper total no. 5 , 4 no. operator and helper for operation duty and 1 technition and 1 helper (Total man power 10 nos)engage maintination work for 36 month. |