| 1 | Construction & Commissioning of 2 nos 200 mm dia |
| 2 | Construction of tube well from ground level & up to 100 mtr depth to accommodate housing and assembly pipe of following sizes in all type of alluvium strataunconsolidated formation such as pebbles, boulders etc. by percussion/rotary drilling method as per IS:2800 Part 1: 1991 andIS:2800 Part II: 1979 (both amended up to date) and technical specifications, with gravel as per IS:4097-1967 and it\"s packing as per IS: 2800 (Part I & II) 1979 as amended up to date (the work includes the cost of gravel & it\"s primary packing and packing during development, lowering of housing & strainer assembly pipes with supply and wrapping of coir-rope, wherever necessary for arresting fine sand particles and development work, but excluding the cost of housing and strainer pipe assembly). The work would be completed after obtaining sand free water. |
| 3 | Nominal bore 200 mm dia. |
| 4 | Add 15% extra on above item (Item no 2 for drilling depth beyond 100 mtr and upto 200 mtr, rate shall be applicable for only extra depth beyond 100 mtr and up to 200 mtr. |
| 5 | Construction of tube well after completion of drilling by rotary /percussion method & up to 100 mtr. depthin all type of rocks by DTH systemas per IS:2800 Part 1: 1991 andIS:2800 Part II: 1979 (both amended up to date) and technical specifications. The workshall be deemed completed only after obtaining sand free water. The bore well should have a throughout nominal size bore beyond casing pipe. |
| 6 | Nominal bore 200 mm dia. |
| 7 | Add 15% extra on above item (Item No 2.3.1 to 2.3.2) for drilling depth beyond 100 mtr and up to 200 mtr from ground level, rate shall be applicable for only extra depth beyond 100 mtr and up to 200 mtr. |
| 8 | Add 30% extra on above item(Item No 2.3.1 to 2.3.2) for drilling depth beyond 200 mtr and from ground level, rate shall be applicable for only extra depth beyond 200 mtr . |
| 9 | Supply of ERW M.S. black casing pipe ISI marked (IS: 4270/2001) or amended up to dateoffollowing sizes |
| 10 | 200 mm dia NB (Thickness of pipe 5.4mm & mass of tube 28.46 Kg/m) |
| 11 | Labour charges for making slots on blank pipes made of ERW MS black pipe ISI marked of following sizes, the slotting should be as per IS:8110-1985. |
| 12 | 200 mm dia nominal bore of 5.4mm thickness |
| 13 | Supply & Installation of 3 phase ISI marked submersible motor pump set ofthree star or better rating of BEEand as per IS: 8034-2018 (pump) and IS 9283-2013 (motor) or as amended up to date of approved make of following duty condition with required accessories including making connection suitable for tube well/DCB. The job includes lowering of motor pump, installation of complete fitting & accessories, jointing of electrical cables up to switch board, testing of submersible pump set and interconnection up to water mains, complete in all respect. |
| 14 | 9.3KW (12.5 HP) & head above 120 mtr. |
| 15 | Supply and Fixing of electric control feeder panel comprising of suitable rating MCCB , fully automatic star-delta starter, over load relay,ampere meter with CTs, volt meter, phase preventer, suitable starting capacitors, phase indicators, lighting arrangement etc. complete suitable for three phase pump set. The panel should have space for energy meter ( supplied by DISCOM).All these equipments shall be housed by panel box made out from 18 gauge M.S. Sheet with powder coating. Panel should be ofminimum size 900 x 600 x 450 mm with Stand ( made of angle iron of size 35x35x5mm) duly bolted/screwed with enclosure box having 4 legs, each leg’s length 18\" and double door including in built locking system.The legs should be embedded in M-15 cement concrete plat form. The size of CC platform should be equal or bigger than the base size of panel having height of at least 200 mm from ground level. The panel should have opening of suitable size in front of space for energy meter with glass for meter reading. The operation of panel should be suitable for on 440 Volt AC Supply. |
| 16 | Above 10 HP and up to 15 HP |
| 17 | Supply & Fixing of ISI marked three core PVC flat submersible cableas per IS 694:1990 or amended up to date and conductor as per class 5 of IS 8130:1980including making connection etc. |
| 18 | 3 core 6.0 Sq.mm |
| 19 | Supply & Fixing XLPE insulated / P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor Armoured of IS:7098-I/1554-1 approved makein ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick underlayer ofsand, second Class bricks covering, refilling earth, compaction of earth, making necessary connection, testing etc. as required of size. |
| 20 | 16.0 Sq.mm, 4 core |
| 21 | Supply & Fixing M S clamp set of 50x6 mm flat from iron with nuts and bolts etc for holding the riser pipe assembly of submersible pump set. |
| 22 | Supply & Fixing tube well coverof MS sheet 8mm thick at top & 5mm thick 100mm wide shroud around the edge so as to form a cap on the top end of casing pipe with GI Nipple 45cm long & two GI flanges at both ends in 80mm sizes passing through a hole in the centre of MS sheet. A 25 mm socket with end plug shall also be welded over top plate. A GI nipple having outside thread of size 1/2\" (for installation pressure gauge) shall be provided & welded with 80mm GI nipple near top plate nipple shall be provided with end plug. |
| 23 | 200 mm dia |
| 24 | Providing & Lowering in tube well ISI marked GI Pipe medium duty (“B\" class), Steel tube as per IS:1239 or amended up to date and zinc coating as per IS 4736, threaded and double flanged (welded) on both ends and two number25x3mm MS flat welded on both ends between pipe & flange, rubber washer & nut bolts etc. complete in all respect. |
| 25 | 50 mm dia |
| 26 | Providing & Fixing pump safety cage as per specifications or as directed by Engineer in charge. |
| 27 | Providing & Fixing of double flanged, CI body, ISI marked NRV of approved make of following sizes |
| 28 | 65 mm dia |
| 29 | P, L, J of HDPE/DI Rising /Distribution Main Pipelines complete in all respect. |
| 30 | Providing, lowering, laying and jointing in trenches, standard lengths HDPEISI marked Pipes as per IS-4984: 1995 (amended upto date)with necessary jointing material like mechanical connectors, i.e. thread/ insert joint/ quick release coupler joint/ compression fitting joint or flanged joint and specials jointing pipe byelectro fusion welding method, including all taxes , transportation and freight charges, inspection charges, loading/ unloading charges, stacking of pipes, including cost of labour and material, specials (Tee, bend etc.), satisfactory hydraulic testing, disinfection etc. complete as per technical specifications and direction of Engineer-in-charge of following class and diameter. (excluding earth work) .Note : Providing and fixing of all requisite specials as per drawing, design and layout are inclusive in RM measurement of the item and shall not be paid separately.Supply may be in coil or straight length in 6 M/12 M. |
| 31 | HDPE PE-80 PN-6 |
| 32 | 90 mm. dia. |
| 33 | 110 mm dia |
| 34 | 180 mm dia |
| 35 | Providing, lowering, laying in trenches, aligning, fixing in position and jointingDuctileIron(DI)ISI markedK-7gradeS&Spipesas per IS:8329-2000 (amendedup todate),withinternalcementmortar lining suitable for potablewater with rubber ring (EPDM)joints as per IS: 5382-1985 including all taxes (Central and local), transportation and freight charges, inspection charges, loading/ unloading charges,including cost of labour and material, specials (Tee, bend etc.) satisfactory hydraulic testing, disinfection, commissioning etc. complete as per technical specifications and direction of Engineer-in-charge. (excluding earth work) Note : Providing and fixing of all requisite specials as per drawing, design and layout are inclusive in RM measurement of the item and shall not be paid separately.150MM |
| 36 | Providing & Lowering in tube well ISI marked GI Pipe medium duty (“B\" class), Steel tube as per IS:1239 or amended up to date and zinc coating as per IS 4736, threaded and double flanged (welded) on both ends and two number25x3mm MS flat welded on both ends between pipe & flange, rubber washer & nut bolts etc. complete in all respect. |
| 37 | 80mm dia |
| 38 | Earth work in excavation by mechanical means (Hydraulic Excavator )/ manual means in trenches of required width and gradient for laying and jointing of pipe line including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5 Mtr. including taking out the excavated soil, and then returning the soil as required in layers not exceeding 20cm in depth including consolidating each deposited layer by ramming, watering etc. and disposal of surplus excavated soil as directed within a lead of 50 Mtr. including required all safety provisions etc.:All kinds of soil |
| 39 | Dismantling of cement concrete pavement for pipe line line and chambers by mechanical means using pneumatic tools, cutting the peripheral edge by CC cutter, breaking to pieces not exceeding 0.02 cum in volume and stock piling at designated locations and disposal of dismantled materials up to a lead of 1000 meters. Measurement for dismantled trench to be madeas per standard trench width specified in tender document and no extra payment shall be made be made for trench width more than specified, re-handling of material/earth to complete the tasks as per technical specification and scope of work. |
| 40 | Providing and laying in position cement concrete M10 grade nominal mix 1:3:6 (1 Cement : 3coarse sand : 6 graded stone aggregate 40 mm nominal size) in base course complete including all material, labour, machinery, lighting, guarding for road restoration work in trenches of pipe line and chamber work. Measurement for CC work to be madeas per standard trench width specified in tender document and no extra payment shall be made be made for trench width more than specified,complete work as per technical specification and scope of work. |
| 41 | Providing,lowering, aligning,fixingin positionin pipeline,CID/FSluicevalvesstraight and pocket less body passage of approved make of following Pressure rating & dia complete, confirming to IS:14846 (amended up to date) and of following specifications: Body, Bonnet, Wedge, Gland, Thrust Plate, Cap & Hand wheel of Grey cast iron of IS:210/ FG200Stem - AISI- 410 ,Body Seat ring, Wedge facing ring & Bushes - LTB2/ SS, Face to face dimensions as per IS 14846/2000 (amended up to date) ,Epoxy ( Non-Toxic- suitable for drinking water) applied inside and outside,Flanges Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367/ CS/ galvanised steelInsertion rubber of black EPDM 6mm thick . Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer-in-charge. Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 42 | Manually Operated CI Sluice valve of Class PN-1.0 |
| 43 | 80 mm HW |
| 44 | 100 mm HW |
| 45 | 125 mm HW |
| 46 | 150 mm HW |
| 47 | 200 mm HW |
| 48 | 250 mm HW |
| 49 | Deepeningof existing 6 nos tube well and pump replacement |
| 50 | Deepening of existing tube well by DTH system beyond existing depth up to 100 mtr. and above in all type of rocks including flushing of tube well and obtaining sand free water. |
| 51 | Nominal bore 200 mm dia. |
| 52 | Supply & Installation of 3 phase ISI marked submersible motor pump set ofthree star or better rating of BEEand as per IS: 8034-2018 (pump) and IS 9283-2013 (motor) or as amended up to date of approved make of following duty condition with required accessories including making connection suitable for tube well/DCB. The job includes lowering of motor pump, installation of complete fitting & accessories, jointing of electrical cables up to switch board, testing of submersible pump set and interconnection up to water mains, complete in all respect. |
| 53 | 9.3KW (12.5 HP) & head above 120 mtr. |
| 54 | Supply and Fixing of electric control feeder panel comprising of suitable rating MCCB , fully automatic star-delta starter, over load relay,ampere meter with CTs, volt meter, phase preventer, suitable starting capacitors, phase indicators, lighting arrangement etc. complete suitable for three phase pump set. The panel should have space for energy meter ( supplied by DISCOM).All these equipments shall be housed by panel box made out from 18 gauge M.S. Sheet with powder coating. Panel should be ofminimum size 900 x 600 x 450 mm with Stand ( made of angle iron of size 35x35x5mm) duly bolted/screwed with enclosure box having 4 legs, each leg’s length 18\" and double door including in built locking system.The legs should be embedded in M-15 cement concrete plat form. The size of CC platform should be equal or bigger than the base size of panel having height of at least 200 mm from ground level. The panel should have opening of suitable size in front of space for energy meter with glass for meter reading. The operation of panel should be suitable for on 440 Volt AC Supply. |
| 55 | Above 10 HP and up to 15 HP |
| 56 | Supply & Fixing of ISI marked three core PVC flat submersible cableas per IS 694:1990 or amended up to date and conductor as per class 5 of IS 8130:1980including making connection etc. |
| 57 | 3 core 6.0 Sq.mm |
| 58 | Providing & Lowering in tube well ISI marked GI Pipe medium duty (“B\" class), Steel tube as per IS:1239 or amended up to date and zinc coating as per IS 4736, threaded and double flanged (welded) on both ends and two number25x3mm MS flat welded on both ends between pipe & flange, rubber washer & nut bolts etc. complete in all respect. |
| 59 | 50 mm dia |
| 60 | Replacement of Centrifugal Monoblock & Horizontal Centrifugal Split Casting pump sets at existing pumphouse |
| 61 | Providing and fixingat site with necessary packing,Horizontal Centrifugal Split Casting pumps with 4 poleinduction motor operating at synchronised speed of speed 1500 RPM as per IS 12615: 2011 or amended up to date , CI casing and casing ring, SS 316 impeller, SS 410 Shaft and shaft sleeve, coupling guard, common base plate, foundation bolts, Cement concrete foundation etc. complete with all respect as per the specification and scope of work and direction of Engineer in Charge of following range of duty conditions.Note: Duty condition of required pump shall also be mentioned in BoQ. |
| 62 | Discharge 20 to 30 LPS and head 41 to 50 M |
| 63 | Discharge 51 to 60 LPS and head 71 to 80 M |
| 64 | Supply and Fixing of electric control feeder panel comprising of suitable rating MCCB , fully automatic star-delta starter, over load relay,ampere meter with CTs, volt meter, phase preventer, suitable starting capacitors, phase indicators, lighting arrangement etc. complete suitable for three phase pump set. The panel should have space for energy meter ( supplied by DISCOM).All these equipments shall be housed by panel box made out from 18 gauge M.S. Sheet with powder coating. Panel should be ofminimum size 900 x 600 x 450 mm with Stand ( made of angle iron of size 35x35x5mm) duly bolted/screwed with enclosure box having 4 legs, each leg’s length 18\" and double door including in built locking system.The legs should be embedded in M-15 cement concrete plat form. The size of CC platform should be equal or bigger than the base size of panel having height of at least 200 mm from ground level. The panel should have opening of suitable size in front of space for energy meter with glass for meter reading. The operation of panel should be suitable for on 440 Volt AC Supply. |
| 65 | Above 20 HP and up to 30 HP |
| 66 | S & F of Star delta Starter with MCB, Main and Aux Contactor, O/L Relay, L/R Selector Switch,3 Indicating lamps, Start-Stop PushButton ,Control MCB with panel with all accessories with following rating. |
| 67 | Removing of existing CI/ DI Double flange sluice valves, non return valves, butter fly valves etc. in existing Distribution/ Rising Main/ Transmission Main pipe line of following sizes, works include de-jointing of valve, dewatering, taking it out of the pit with adequate safety arrangement at site and then refill the pit from excavated sand by ramming it at sides of pipe & up to ground level. Work shall be done as per specification, scope of work and direction of Engineer-in-charge. All old material shall be removed safely & all old material shall be deposited in Divisional Store.Note: Rates are exclusive of earth work and road cutting. |
| 68 | 200 mm |
| 69 | Providing,lowering, aligning,fixingin positionin pipeline,CID/FSluicevalvesstraight and pocket less body passage of approved make of following Pressure rating & dia complete, confirming to IS:14846 (amended up to date) and of following specifications: Body, Bonnet, Wedge, Gland, Thrust Plate, Cap & Hand wheel of Grey cast iron of IS:210/ FG200Stem - AISI- 410 ,Body Seat ring, Wedge facing ring & Bushes - LTB2/ SS, Face to face dimensions as per IS 14846/2000 (amended up to date) ,Epoxy ( Non-Toxic- suitable for drinking water) applied inside and outside,Flanges Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367/ CS/ galvanised steelInsertion rubber of black EPDM 6mm thick . Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer-in-charge. Note: Rates are exclusive of tail piece/ dismantling joints and earth work. |
| 70 | 200 mm |
| 71 | Repairs to plaster of thickness 12mm to 20mm in patches of area 2.5 sq. metres and under including cutting the patch in proper shape, raking out joints and preparing and plastering the surface of the walls complete including disposal of rubbish to the dumping ground within 50 m lead With cement mortar 1 :4 ( 1 cement : 4 coarse sand) |
| 72 | Dismantling old plaster or skirting, raking out joints and cleaning the surface for plaster including disposal of rubbish to the dumping ground within 50 meter lead. |
| 73 | Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade including all scaffolding:Old work (one or more coats) including scrapping surface andnecessaryrepairs. |
| 74 | Same colour |
| 75 | Painting exterior surface ofWallwith 100% acrylic exterior paint of approved brand and manufacture to give an even shade with two or more coats including prepartion of base with sand papering, primer, putty,etc complete in all respect including scaffolding and safety provision |
| 76 | New Work |
| 77 | Old Work |
| 78 | Providing and fixing steel gate, grating , and grills made of angles, tees, square bars, flats,or black pipe with holdfast and fittings complete as per design and drawing including cutting welding and fabrication with priming coat of red oxide |
| 79 | Providing and fixing of flanged/ plain ended MS Specials made from MS sheet strips of relevant IS specification of approved thickness by welding,lowering,laying,aligning,fixinginpositionatalllevel/ depths in trenches complete includingall taxes, material,labour, inside lining, outside coating, testingandcommissioning alongwithpipelineaspertechnicalspecifications anddirection of Engineer-in-charge.MS pipespecialsup to600mmdia (withminimum5mmthickness sheet) |
| 80 | Demolishing stone rubble masonry manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge:In cement mortar. |
| 81 | Providing and laying in position cement concrete including curing, compaction etc. complete in specified grade excluding the cost of centering and shuttering - All work up to plinth level. M15 grade Nominal Mix 1: 2: 4 (1 cement : 2 coarse sand : 4 graded stoneaggregate 20mm nominal size). |
| 82 | Repair to brick masonary in cement sand mortar 1:6 withnew brick. |
| 83 | De-jointing and removing of already laidCI/DI pipes of following diameters in excavated trenches with care, without damaging pipes, CID joints, valves, specials etc. and other materials and then refilling of soil after de-laying and de-jointing of pipelines with proper compaction and disposing of all surplus soil as directed with in a lead of 30 mtr. This also include stacking the pipes with care and transporting the same to div./sub div. store or as directed by EIC with in the division. (Rates are Exclusive of Earth Work) 100mm |
| 84 | Laying, Jointing, Testing and Commissioningof Ductile Iron (DI) Pipes of any class in assorted length with specials, valves etc. including local handling and transportation from PHED store and then refilling of soil with proper compaction and disposing of all surplus soil as directed with in a lead of 30 mtr as per satisfaction of EIC. (Rates are Exclusive of Earth Work and jointing materials) |