| 1 | Charges for dismantling the feeder pillar box after disconnecting all the incoming and outgoing switches, Cable and providing temporary LT panel by MS frame with supply and fixing temporary bus bar of capacity 415 Amp with incoming 250 Amp and 4 nos. 63A.,2 nos. 100A., 2 nos. 32A. and 1 nos. 160Aoutgoing main switches inc. supply and drawing different sizes of cable for making connection with socketing & termination of cable ends to feed power to the building up to 3 days with proper earthing arrangements as required and dismantling the same after completion of Job.(As per direction of EIC) |
| 2 | SITC of outdoor type both sided door feeder pillar box on brick foundation incl. construction of brick foundation of suitable length , width and Height such that there is suitable foundation below the ground level and the feeder pillarbe installed atleast18” height from Gr. Level.Inside the brick pedestal will be filled up by loose sand where the incoming & outgoing cable will be rest The pillar box will be fabricated from 3 mm thick sheet steelwith top cover/canopy being of 5 mm thick sheet steel. The size of the pillar box will be 1800(H) x 2100(W) x 700(D) mm with inner enclosure [size 1500(H) x 1850(W) x 300(D) mm] and 4 nos. angle iron leg & making interconnection by suitable size copper flat / wire. Double Locking arrangement will be made with lock and duplicate keys (7 lever Godrej, navatal lock) with door handle. Two numbers lighting arrangement with control switch to be made inside the box as working light and 1 no. 250V., 5/15 combined plug socket & switch. Painting will be made by synthetic enamelled paint after 2 coats of red led primer. Bricks foundation will be cement, plastering and neat cement finish.(as per direction of EIC) The feeder pillar box comprising the followings. Make- MCCBs/SFUs will be of Legrand/Siemens/ABB/L&T Make. All theother accessories will be Legrand /Siemens/L&T /ABB Make and as per manufacturers standard ]. |
| 3 | INCOMER:-a) 415V.,250A, 4P, 36kA MCCB Thermal Magnetic Releasewith tripping unit, extended rotary handle, both side spreader terminals [Make - L&T, Cat no M98065OOPO+CM92007OOOO+CM98041OOOO] or Similer specification of Legarnd/ABB/Schneider/Siemens,- 1 No. |
| 4 | BUSBAR CHAMBER:-S&F 360 Amp capacity 99.9% - 99.5% electrolytic tinned copper 4 bar bus bar [size of flat 4 x 30 mm x 10 mm] mounted on non-hygroscopic porcelain insulator / hylam sheet having sufficient di-electric strength duly wrapped with colour PVC tapes (Red, yellow, blue & black) for phases & neutral identification & all connection made with required size cu bars - 1set. |
| 5 | OUTGOING:-a)415V, 200 Amp 36 KA 4-Pole MCCB with Thermal Magnetic Releasewith tripping unit, extended rotary handle and both side spreader terminals [Make - L&T, Cat no CM98065OONO + CM92007OOOO+ CM98041OOOO]- 1Nos |
| 6 | b) 415V, 160Amp 36 KA 4-Pole MCCB with Thermal Magnetic Releasewith tripping unit, extended rotary handle and both side spreader terminals [Make - L&T, Cat no CM98065OOMO + CM92007OOOO+ CM98041OOOO ] or Similer specification of Legarnd/ABB/Schneider/Siemens - 2 Nos |
| 7 | c) 415V, 100 Amp 30 KA 4-Pole MCCB with Thermal Magnetic Releasewith tripping unit,, extended rotary handle and both side spreader terminals [Make - L&T, Cat no CM97933OOK2 + CM97921OOOO+ CM97896OOOO ]or Similer specification of Legarnd/ABB/Schneider/Siemens - 4 Nos |
| 8 | d) 415V, 63 Amp 18 KA 4-Pole MCCB with Thermal Magnetic Releasewith tripping unit, extended rotary handle and both side spreader terminals [Make - L&T, Cat no CM97933OOH2 + CM97921OOOO+ CM97896OOOO ] or Similer specification of Legarnd/ABB/Schneider/Siemens- 4 Nos |
| 9 | e) 415V, 32 Amp 18 KA 4-Pole MCCB with Thermal Magnetic Releasewith tripping unit, extended rotary handle and both side spreader terminals[Make - L&T, Cat no CM97933OOF2 + CM97921OOOO+ CM97896OOOO ]or Similer specification of Legarnd/ABB/Schneider/Siemens - 1 Nos |
| 10 | METERING:-(a) 500V., C.T. Coil (C.T. Ratio-500/5A.)- 3 Nos. |
| 11 | (b) LED Indicator lamp (L&T)- 03 nos. |
| 12 | (c) Panel mounted digital Voltmeter in 96x96 mm² (AE/HPL) [0-500V] with VSS - 1 no. |
| 13 | (d) Panel mounted digital Ammeter in 96x96 mm² (AE/HPL) [0-500A] with ASS - 1 no. |
| 14 | (e) Danger Board-01 no. |
| 15 | Earthing with 65 mm dia GI pipe (TATA-Medium)x 3.0 Mts. long and 1 No. 50 mm x 6 mm galvanized (Hot Dip) steel strip (4 Mts. long), 20 mm dia x 125 mm long galvanized bolt, double nuts, double washers including finishing both ends by making holes etc. and S & F 65 mm dia GI pipe (ISI-Medium) protection (3 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level to an average depth of 3.65 Mts. |
| 16 | Supply of 1.1 KV grade XLPE/Ar PVC Ar./ Al. Cable Gloster/Polycab/Havells) of following sizes. |
| 17 | 4 core 150 sqmm. |
| 18 | 4 core 50 sqmm. |
| 19 | 4 core 35 sq.mm. |
| 20 | 4 core 25 sq.mm. |
| 21 | Laying only Cable of above 50 sqmm to 150 sqmm through 65mm dia GIpipe incl. supplying and laying of GI pipe. |
| 22 | Laying of one No. cable above 35 sqmm and upto 185 sqmm inunderground trench 460mm wide x 760mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per Mtr. including filling the space between the bricks and cable and also the trench with shifted soil, levelling up and restoringsurface duly rammed. |
| 23 | Laying of one No. cable upto 35 sqmm in underground trench 460mm wide x 760 mm average depth, with brick protection on thetop of the cable with 8 (eight) Nos. bricks per metre, includingfilling the space between the brick & cable and also the trenchwith shifted soil, levelling up and restoring surface duly rammed. |
| 24 | Laying of cable above 3½/4 core 90 sqmm and upto 3½/4 core 150sqmm on wall/surface including S & F MS clams with earthingattachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. asnecy., mending good damages and painting. |
| 25 | Laying of cable from 3½/4 core 35 sqmm to 50 sqmm onwall/surface incl. S & F MS saddles with earthing attachment in 2x 10 SWG GI (Hot Dip) Wire, making holes etc. as necy., mendinggood damages and painting. |
| 26 | Laying of cable upto 4 core 25 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting. |
| 27 | S/F of compression type gland for following 4 core 150 sq.mm PVC/Ar cable & finishing the ends with dowels solderless socket by crimping method as per GS. |
| 28 | S/F of compression type gland for following 4 core 50 sq.mm PVC/Ar cable & finishing the ends with dowels solderless socket by crimping method as per GS. |
| 29 | S/F of compression type gland for following 4 core 35 sq.mm PVC/Ar cable & finishing the ends with dowels solderless socket by crimping method as per GS. |
| 30 | S/F of compression type gland for following 4 core 25 sq.mm PVC/Ar cable & finishing the ends with dowels solderless socket by crimping method as per GS. |
| 31 | Supply & Fixing 415 V, 6 WayDouble Door Vertical TPN DB in S.S enclosure with IP- 42/43 protection on angle iron frame on wall consisting with 1 no. 100 A ,36ka, 4 -pole MCCB as incomer, 6 nos. 63A TP MCBas outgoing with all accessories & interconnection as per GS (Make-Legrand/Schneider/ABB). |
| 32 | Supply & Fixing 415 V, 8 WayDouble Door Vertical TPN DB in S.S enclosure with IP- 42/43 protection on angle iron frame on wall consisting with 1 no. 100 A ,36ka, 4 -pole MCCB as incomer, 8 nos 63A. TP MCB as outgoing with all accessories & interconnection as per GS (Make-Legrand/Schneider/ABB) |
| 33 | Supplying and fixing 415V,16-32A per way, 4 way double door Horizontal TPN MCB Distribution board with IP-42/43 protection, with 4 pole 63 A isolator as incomer and 12 Nos. 6-32A SPMCB\"s (\"C\" curve,10kA) as outgoing concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment (Make-Legrand/ABB/Schneider). |
| 34 | Straight through Jointing of cable of different size by compound jointing kit including S&F ferrule, tapes and jointing materials (Brand approved by EIC |
| 35 | 2 core 4-10 sqmm cable |
| 36 | 3½ / 4 core 25-35 sqmm cable |
| 37 | 3½/ 4 core 50 sqmm cable |
| 38 | 3½/ 4 core 95 sqmm cable |
| 39 | Dismantling R.C. pavement etc. by one\"s own tools and tacklesincluding cutting rods and removing rubbish as directed by EIC . including removal of rubbish ,earth etc from site in all respect and after laying of cables the area must be rectified to original finish as per direction of EIC.Pg 10 Item B/3 and Pg 12 item B/13 of PWD schedule for civil works |
| 40 | Cost for digging out the the soil to find the existing cable route without damaging the cable and replaying the same cables after rectification of the problem along with making good damages to the original finish |
| 41 | Defect Liabibility Period - 1 (One) year |
| 42 | Make & model of each and every material to be approved by EIC |