| 1 | Supply installation testing and commissioning of single girder 3 Ton EOT crane( lift upto 6 Mtr. & Span upto 6 Mtr.). Make - DJB approved. |
| 2 | Revival of HT Panel (11 KV ,800A ) atV-7 & V13 Ranney wells |
| 3 | Reinstate including dehydration of Transformer at V-7 & V13 Ranney wells (250 KVA Transformer Each site) |
| 4 | Providing GI pipe 200 mm dia size ,medium class with GI flange welded in both sides 3 Mtr long with MS bracket duly welded on each side of pipe each flange should be 8 holes and cut for cables. Make :- Jindal / TATA. |
| 5 | Providing G.I required off size threaded heavy duty nut-bolts of good quality. |
| 6 | Providingsubmersible cable with copper conductor having three core sizes 16 sq. mm working on 1100V. Make:-Finolex/Plaza/Unistar or any other make approved by DJB. |
| 7 | ProvidingGI reducer 200 mm x250 mm dia. Double flange. Heavy class Make: - Ganesh/ ISI |
| 8 | ProvidingGI bend 200 mm dia 90deg. Double flange. Heavy class Make: - Ganesh/ ISI |
| 9 | Making and supply of MS clamp of 700 mm long x 75 mm width x12 mm thick complete with nut and bolts and washers for holding the 200 mm dia pipe including bending and shaping etc. as required. |
| 10 | Providing neoprene rubber sheet having 50% neoprene, 3 mm thick Make Jyoti/Worth/DJB approved |
| 11 | ProvidingofMS chequered sheet(3MM) |
| 12 | Providing CIDF non risingspindle sluice valve 250MM, PN 1.0 Make-Kirloskar/IVC/DJB approved make(4.33.8) |
| 13 | Providing CIDF non risingspindle sluice valve 450MM, PN 1.0 Make-Kirloskar/IVC/DJB approved make(4.33.12) |
| 14 | Providing CIDF Swing type Non return valve 250MM, , PN 1.0Make-Kirloskar/IVC/DJB approved make(4.34.8) |
| 15 | Providing and Laying of HT cable of suitable size as per site condition XLPE 120 SQ MM Armored aluminum HT 3 Core Cable. Make -Havells/ DJB approved. |
| 16 | Providing and Laying of LT cable of suitable size as per site condition XLPE 240 SQ MM Armored aluminum LT 3.5 Core Cable Make -Havells/ DJB approved. |
| 17 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required.DJB Approved (35.1.4) |
| 18 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.Djb Approved (35.1.15) |
| 19 | Electrification work for Ranneywells and Systemization of Electrical installation for Energization of Tubewells at Okhla WTP Complex including Testing and commissioning. (Refer detailed breakup) |
| 20 | Lowering & Fixing of pumpsets & with proper connecting with delivery line complete with other allied works with the help of, Fitter, Welder, Cutter, Helper, Beldar, Supervisor, Electrician, chowkidar and material used like pipe, bend, reducer, other T&P complete required etc at site of work. (3 nos pumpset for each site) |
| 21 | Testing of Pumpsets and delivery pipe line with pressure as per requirement of site |