| 1 | Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc. removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as perconditions separately) and making good disturbed surfaces of walls, floors, etc.complete all as specified and as directed by Engr-in-Charge. |
| 2 | Taking down of MCB DB any type including MCB SP/SPN and making good to existing surfacecomplete all as specified and as directed by Engr-in-Charge. |
| 3 | M&L Point wiring with 1.5 Sqmm (nominal area) copper conductor FRLS cable (multi-stranded) PVC insulated and unsheathed electric cable 1100 volts drawn through PVC casing and caping of suitable size (as per conductor run) with all fittings and accessories and including PVC insulated unsheathed electric cable 1100 volts 1.5 Sqmm (multi-stranded) copper conductor single core (green colour) as continuous earth wire connected to common earth dolly including 50mm deep box made out of 2nd class hard wood board of suitable size and shape and other boxes for mounting light fittings etc covered with 3mm thick plastic laminated Hylum ISI marked for followingcomplete all as specified and as directed by Engr-in-Charge.Note:- Screw used for fixing TW baords, casing and caping ceiling rose, square blocks etc should be nickel cadmium screws. |
| 4 | One light point controlled by one 5 Amps one way switch |
| 5 | One 3 pin socket outlet 5 Amps on same board |
| 6 | All as per item No 3 above but for one 3 pin socket outlet 15 Ampsindependent with cable of size 2.5 Sqmm for point wiring and 1.5 sqmm in continuous earth wire complete all as specified and as directed by Engr-in-Charge. |
| 7 | S & F Switch piano flush button single pole one way 5 Amps, 240 Voltscomplete all as specified and as directed by Engr-in-Charge. |
| 8 | S&F socket outlet 3 pin, 5 Amps, 1 flush type suitable for 2 pin / 3 pin plugcomplete all as specified and as directed by Engr-in-Charge. |
| 9 | S&F switch socket combination 2 in 1, 3 pin, 15 Amps, flush type (multipurpose) complete all as specified and as directed by Engr-in-Charge. |
| 10 | S&F Ceiling rose surface backelite ISI marked with 3 terminalincluding connecting and testingcomplete all as specified and as directed by Engr-in-Charge. |
| 11 | S & F in repair lamp holder, PVC/polycarbonate type with back plate straight or angular suitable for batten fittingscomplete all as specified and as directed by Engr-in-Charge. |
| 12 | S & F in repair PVC rectangular block for mounting of switches, socket with 3 mm thick plastic laminated sheet cover of size 200x150x50mmcomplete all as specified and as directed by Engr-in-Charge. |
| 13 | Submain wiring with two single core PVC insulated unsheated FRLS flexible copper conductor cable of size 6 Sqmm and one single core PVC insulated unsheated (FRLS) flexible copper conductor cable of size 6 Sqmm as earth lead in and including PVC casing capingof size 25mm, ISI marked and making good the disturbed surfacecomplete all as specified and as directed by Engr-in-Charge. (Note : Two runs of 6 Sqmm cable, one run of 6 Sqmm earth cable and PVC conduit all one RM length each shall be measured together as one unit of one RunningMetre.) |
| 14 | S&F MCB DB sheet enclosure,Double door type, single pole and neutral 240V with 200 Amp rated bus bar suitable size plate and common neutral link all enclosed in standard steel sheet flush mounting type factory fabricated complete confirming to IP 42/43 without MCB and with enclosure blank plates for unusedway suitable for 8 waycomplete all as specified and as directed by Engr-in-Charge. |
| 15 | Supply and fixing 240V, 10 KA \"B\" curve miniature circuit breaker (MCB) of single poles and current carrying capacity 5 to 32 AMP, in the MCB DB Complete with connection testing and commissioningcomplete all as specified and as directed by Engr-in-Charge. |
| 16 | Supply and fixing MCB SPN240V, 10KA \"C\" curve (40-63) Amp current carrying capacity in the MCB DB complete with connection testing and commissioningcomplete all as specified and as directed by Engr-in-Charge. |
| 17 | Supply and fixing in repair Rechargeable LED Bulb energy saver9 W ,B22 (220-240 V) 50 hz, 6500k, fast charging 2200 mAH battery inbuild ,white colorcomplete all as specified and as directed by Engr-in-Charge. |
| 18 | Supply & Fixing in repair LED light fitting 1X10W bulkhead luminaires including LED light and driver holder connecting up with three core flexible copper conductor cable of suitable sizecomplete all as specified and as directed by Engr-in-Charge. |
| 19 | S&F in repair LED Light fitting mirror type with high output diffuser 2 feet, 10 watt 220 V AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and as directed by Engr-in-Charge. |
| 20 | S&F in repair exhaust fan made of sturdy Engineering plastic complete with louvers shutter, voltage 230V,50Hz RPM 1200 copper winding of sweep 300mcomplete all as specified and as directed by Engr-in-Charge. |
| 21 | S&F in repair surface and wall mounted LED batten with polycarbonate housing and integrated electronic driver tube light fitting 20W, 4 ft long, 220 Volts , and connecting to ceiling rose with three core twisted flexible copper cable of suitable sizecomplete all as specified and as directed by Engr-in-Charge. |
| 22 | M&L in replacement earthing complete with galvanized steel earth plate electrode 600 x 600 x 6mm thick burried directly in ground not less than 2.25m deep below normal ground level (with the top edge of the plate not less than 1.50 m below the normal ground level) connected to GI earth wire 4 mm by means of GI bolts, nuts, check nuts and washers of GI all as shown in electrical plate No.3 of SSR Part-I connected to earthing test point with and including necessary excavation and earth work in any strata PCC pit 1:3:6 type C-1, 20mm bore medium grade GI pipe for watering 15mm bore light grade pipe for GI wire protection and funnel including 40mm thick RCC slab cover and testing on completion,complete all as specified and as directed by Engr-in-Charge. (Make :-TERRAFILL/ SAFE/ ASHLOK) |
| 23 | Supply and fixing in repair LED street light fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete making all necessary connection with suitable capacity of 3 core circular cable complete all as specified and as directed by Engr-in-Charge. |
| 24 | M & L in repair GIPipe (medium grade,ISI Marked) 32 mm dia ,1.5 mtr long ,bend to shape for street light fitting bracket ,with 2x pairs of MS clamps of suitable length of size 40x5 mm of MS flat iron with nuts bolts and washer and taking out old one including connection with street light complete all as specified and as directed by Engr-in-Charge. |