| 1 | Provision :- Schedule A :- 6.50 KM - 33 KV Line on 280 KG PCC PoleSchedule B :- 07 No. - 33 KV DP StructureSchedule C :- 01 No. - 5 MVA PTRSchedule D :- 07 KM - 11 KV Line on 140 KG PCC PoleSchedule E :- 06 No. - 11 KV TP StructureSchedule F :- 05 No. - 11 KV Road CrossingSchedule G :- 10 No. - 11 KV DP Structure Schedule H :- 01 No. - S/s PTR EarthingSchedule I :-06 No. - 33 KV TP StructureSchedule J :- 03 No. - 33 KV Road Crossing |
| 2 | 280 Kg.,9.1 Mtrs. long PCC pole |
| 3 | Erection Charges for 280 Kg.,9.1 Mtrs. long PCC pole {(including Pit Digging - Base Padding of Pole by Stone Block/Pre Cost Block, Pole Erection, Back Filling/Boulder, Earthing Coil)} (Including with Transportation from Area store Guna/Gwalior/ Bhopal to working Site) |
| 4 | WPB 160x160 MM, 30.44 KG/Mtr 13 Mtr. Long |
| 5 | Erection Charges forWPB 160x160 MM, 30.44 KG/Mtr 13 Mtr. Long {(including Pit Digging - Base Padding of Pole by Stone Block/Pre Cost Block, Pole Erection, Back Filling/Boulder, Earthing Coil)} |
| 6 | Back Clamp for 280 Kg PCC Pole of MS Flat 65x8mm.(Each weight 1.92 Kg) |
| 7 | Earthing Coil of 115 Turns of 50 MM.Dia and 2.5 Mtr. Lead of 4.0 MM G.I Wire |
| 8 | 33 KV Pin Insulator Polymer Composite (10 KN) |
| 9 | Erection charges for Fixing of 33 KV Pin Insulator Polymer Composite (10 KN) |
| 10 | Stay set 20 mm. complete without Stay wire (Painted) |
| 11 | Erection charges for Stay Set 20 MM. Complete including Pit Digging, Binding of Stay wire at Eye bolt, Stay insulator and Anchor Rod & Tigting on pole) |
| 12 | STAY GI WIRE 7/4.00 MM.(7/8 SWG) |
| 13 | Clamp 65X8 MM of MS Flat for pcc Pole 280Kg. (Each weight 3.04 kg ) |
| 14 | Stay Insulators 90X65mm |
| 15 | Back filling of poles with boulders. |
| 16 | Concreting of structures & foundation (1:3:6) |
| 17 | Erection charges for Concreting of structures & foundation (1:3:6) |
| 18 | Red oxide paint |
| 19 | Erection charges for Red oxide paint |
| 20 | Aluminium paint |
| 21 | Erection charges for Aluminium paint |
| 22 | Danger Boards Enamelled 33 KV |
| 23 | Erection charges for Danger Boards Enamelled 33 KV |
| 24 | M.S.Nuts with Bolts |
| 25 | 33 KV V cross-arms 75x75x6 mm angle |
| 26 | Labour Charges for Fixing of 33 KV V cross-arms 75x75x6 mm angle |
| 27 | 33 KV Top Clamp 75x75x6 mm angle |
| 28 | Labour Charges for Fixing of 33 KV Top Clamp |
| 29 | 33 KV Carpet guarding |
| 30 | Erection Charges for 33 KV Carpet guarding |
| 31 | (v) ACSR Dog conductor 0.10 sq. inch (100 sq.mm. Al.Eq.), (6/4.72 + 7/1.57 mm) |
| 32 | Erection Charges for Stringing of (v) ACSR Dog conductor 0.10 sq. inch (100 sq.mm. Al.Eq.), (6/4.72 + 7/1.57 mm) |
| 33 | Anti climbing devices ( Barbed wire 2.24 mm dia, 14 SWG) |
| 34 | Erection Charges for Anti climbing devices ( Barbed wire 2.24 mm dia, 14 SWG) |
| 35 | Back Clamps for H-Beam of MS Flat 65x8mm (Each weight 1.92 Kg) |
| 36 | Clamp 65X8 mm Flat of MS Flat for H-Beam (Each weight 3.2 kg) |
| 37 | 33 KV V cross arm 75X75X6 mm. angle type |
| 38 | Erection Charges for Fixing of 33 KV V cross arm 75X75X6 mm. angle type |
| 39 | 33 KV Top Clamp 75X75X6 mm. angle type |
| 40 | Erection charges for fixing of 33 KV Top Clamp 75X75X6 mm. angle type |
| 41 | 33 KV (45KN) Composite Polymer Disc Insulators |
| 42 | Erection Charges for 33 KV (45KN) Composite Polymer Disc Insulators with Strain H/W |
| 43 | 33 KV Strain Hardware (T & amp; C type) fittings |
| 44 | MS strain plate 65x8mm 250mm long |
| 45 | Horizontal & Cross Bracing set of MS angle of 50X50X6 mm for 5 ft(1.5 mtr) centre DP |
| 46 | Erection Charges for fixing of 5\" centreHorizonatal and Cross Bracing withsupporting clamps on both the poles. |
| 47 | D.C. Cross arms 5 ft centre to center (100x50x6 mm) Channel along with strain plates, Clamps |
| 48 | Erection charges for fixing of D.C. Cross arms 5 ft centre to center (100x50x6 mm) Channel along with strain plates, Clamps |
| 49 | Crane charges for Handling & installation of 33/11 KV S/S Power Transformer (5 MVA) with fitting of all radiaters, above 50 km. upto 100 Km. from crane availablity location incl all taxes |
| 50 | Transportation charges with Trala For 5 MVA PTR with all radiaters from Area Store Guna to 33/11 KV SubStation. |
| 51 | Yard fencing with chain link mesh over brick wall |
| 52 | MS main and wicket gate on RCC column |
| 53 | MS Sheet Shine Board, bay indication board & RYB phase indication board |
| 54 | Ctrl room & Internal electrification work for Size 6.00 X 11.70 M for rural ar. |
| 55 | Yard leveling and metalling |
| 56 | Laying of Metal in yard:100 mm thick metalling with 40 mm size B.T. |
| 57 | Pro. avoid grass in sub-station yards detailed in (e-1) and (e-2) in Civil Stock |
| 58 | App road(RCC 1:2:4)main gate to power xmer found size(20x3M)Black soil |
| 59 | App road 60mm thick concr paver block M-30 grade along trench upto various equip |
| 60 | ADD DIGGING 150 MM DIA TUBE WELL, CASING BEYOND 60 MTR |
| 61 | 1000L P/F Sintex OH tank & GI pipe fitting,water tap near X-mer neutral earthing |
| 62 | Providing and fixing 5HP submersible pump |
| 63 | P&F perfo cable tray 300 wide,2 thick fix 45x45x5 MS angle grouted CC 1:24 |
| 64 | ing brick massonery 0.6x0.6M inner,flag stone cover:18 no. earth pit |
| 65 | Fire extinguisher cartridge CO2 10 kgs |
| 66 | 33 KV VCB, Outdoor Porcelain clad type with complete structure and accessories excluding CT & pannel |
| 67 | Erection Charges for Handling & Installation of 33 KV VCB, Outdoor Porcelain clad type with complete structure and accessories excluding CT & pannel |
| 68 | 33 KV CTs.Outdoor Oil immersed type 200-100/5 Amps |
| 69 | Erection Charges for Handling & Installation of 33 KV CTs.Outdoor Oil immersed type 200-100/5 Amps |
| 70 | 33 KV control & relay panel with numerical static relay for Feeder protection |
| 71 | Erection Charges for Handling & Installation of 33 KV control & relay panel with numerical static relay for Feeder protection |
| 72 | 33KV Transformer Control & Relay Panel with diffrential protections for 8MVA Power transformer with Numerical relay |
| 73 | Erection Charges for Handling & Installation of 33KV Transformer Control & Relay Panel with diffrential protections for 8MVA Power transformer with Numerical relay |
| 74 | 11 KV VCB, Outdoor Porcelain clad type with complete structure and accessories excluding CT & pannel |
| 75 | Erection Charges for Handling & Installation of 11 KV VCB, Outdoor Porcelain clad type with complete structure and accessories excluding CT & pannel |
| 76 | 11 KV.C.Ts.(Outdoor dry type) 300-150/5-5 Amps |
| 77 | Erection Charges for Handling & Installation of 11 KV.C.Ts.(Outdoor dry type) 300-150/5-5 Amps |
| 78 | 11 KV control & relay panel with static relay for Transformer protection |
| 79 | Erection Charges for Handling & Installation of 11 KV control & relay panel with static relay for Transformer protection |
| 80 | 11 KV control & relay panel with numerical static relay for double feeder protection |
| 81 | Erection Charges for Handling & Installation of 11 KV control & relay panel with numerical static relay for double feeder protection |
| 82 | 30 V 200 Amp Hour Battery Set in Transparent SAN Container |
| 83 | Erection Charges for Handling & Installation of 30 V 200 Amp Hour Battery Set in Transparent SAN Container |
| 84 | Marshelling box with 10 no. connectors |
| 85 | Erection Charges for Marshelling box with 10 no. connectors |
| 86 | 9 KV Gapless type(5 KA) polymer lightening arrestor |
| 87 | Erection Charges for 9 KV Gapless type(5 KA) polymer lightening arrestor |
| 88 | 33 KV Single Phase PTs. |
| 89 | Erection Charges for Handling & Installation of 33 KV Single Phase PTs. |
| 90 | SHEET METAL METER BOX SUITABLE FOR H.T. STATIC TRAVECTOR METERS WITH TTB |
| 91 | Direct Curent Distribution Board (DCDB) 24 Volts Indoor floor/ wall |
| 92 | Erection Charges for Handling & Installation of Direct Curent Distribution Board (DCDB) 24 Volts Indoor floor/ wall |
| 93 | ACDB 415 V, along with three phase-neutral voltmeter, three phase ammeter |
| 94 | Erection Charges for Handling & Installation of ACDB 415 V, along with three phase-neutral voltmeter, three phase ammeter |
| 95 | LED Lamp with 90 Watt (Complete) for Streetlight luminaire with pressure die cast aluminium housing body output Rated life Burning Hrs 50000 Hr CCT>5500K, IP66 OIR of IS10322/IEC60598, LM79&LM80 LED Efficiency>130 Lm/w,nominal CRI >75, 2 Yr warranty |
| 96 | Erection Charges for Handling & Installation of LED Lamp with 90 Watt (Complete) for Streetlight luminaire with pressure die cast aluminium housing body output Rated life Burning Hrs 50000 Hr CCT>5500K, IP66 OIR of IS10322/IEC60598, LM79&LM80 LED Efficiency>130 Lm/w,nominal CRI >75, 2 Yr warranty |
| 97 | T CLAMP FOR 33KV & 11KV BUS, SUBSTATION upto DOG |
| 98 | Erection Charges for T CLAMP FOR 33KV & 11KV BUS, SUBSTATION upto DOG |
| 99 | Bi Metallic Clamp for Power Transformer of Brass Flat 50x50x10MM |
| 100 | Erection Charges for Bi Metallic Clamp for Power Transformer of Brass Flat 50x50x10MM |
| 101 | Stringing of Each 33 KV Bus- upper and lower including drop jumpering, jointing with clamps, incoming DP/ ME to BUS |
| 102 | Stringing of Each 11 KV Bus-upper and lower bus including, drop jumpering and jointing with clamps,through outgoing VCB/ ME/ DP, upto station transformer |
| 103 | Stringing of All 33 KV & 11 KV Jumpers - from 33 KV gartry through 33 KV VCB to PTR to 11 KV gantry through 11KV VCB |
| 104 | 33 KV composite polymer Strain set with hard ware suitable for Panther Conductor |
| 105 | H-Beams 152 X 152 mm., 37.1 Kg./Mtr.-11 mtr. Long = 408.1 kg (Including with Transportation from Area store Guna/Gwalior/ Bhopal to working Site) |
| 106 | Erection Charges for H-Beams 152 X 152 mm., 37.1 Kg./Mtr.-11 mtr. Long = 408.1 kg {(including Pit Digging - Base Padding of Pole by Stone Block/Pre Cost Block, Pole Erection, Back Filling/Boulder, Earthing Coil)}(Including with Transportation from Area store Guna/Gwalior/ Bhopal to working Site) |
| 107 | 11 KV Pin Insulator Polymer Composit (5 KN) |
| 108 | Erection Charges for fixing of 11 KV Pin Insulator Polymer Composit (5 KN) |
| 109 | Stay set complete without Stay wire 16 mm. (Painted) |
| 110 | Erection charges for Stay set 16 mm. Complete erection including Pit digging, binding of stay wire at eye bolt , stay insulator and anchor rod &tigtning on pole) |
| 111 | STAY WIRE 7/3.15 MM.(7/10 SWG) |
| 112 | Concreting of stay (20 mm / 25 mm) @ 0.3 cmt. per stay |
| 113 | Labour charges for Concreting of stay (20 mm / 25 mm) @ 0.3 cmt. per stay |
| 114 | BIS certified Energy Efficiency Level-III (Old)/Level-II (New) Convential 11/0.433KV, 100 KVA Distribution Transformer |
| 115 | Handling & Installation ofDistribution Transformer (100 KVA DTR) on DP, tightening with turn buckles on both sides, poles clamping and boting of base jumpering on HT side (Including hydra charges in urban area and chain pully charges in rural area) |
| 116 | Clamp A type 65x8mm of MS Flat for R.S. Joist(175x85mm) |
| 117 | 11 KV(45KN) Composite Polymer Disc Insulators |
| 118 | Erection Charges for fixing of 11 KV(45KN) Composite Polymer Disc Insulators with Strain H/W |
| 119 | 11 KV Strain Hardware (T&C type) fittings |
| 120 | 11 KV D.O. Fuse Unit Polymer type |
| 121 | Erection Charges for fixing of 11 KV D.O. Fuse Unit Polymer type |
| 122 | Complete jumpering of DTR |
| 123 | Danger Boards Enamelled 11 KV |
| 124 | Erection charges for Danger Boards Enamelled 11 KV |
| 125 | L.T. Distribution box with Isolator on Incoming with HRC fuse for 100 KVA DTR (300 Amp. Isolator & 6 no. J type Al Hook) |
| 126 | Handling & Installation of 100 KVA Dist. Box on DP, complete wiring, connecting LT cable on bushing and LT feeders (2 Nos.)) |
| 127 | Concreting of foundation of VCB (1:3:6) @ 3.5 cmt per VCB plinth |
| 128 | Labour Charges for Concreting of foundation of VCB (1:3:6) @ 3.5 cmt per VCB plinth |
| 129 | Erection of Plinth per VCB- 33KV or 11KV[Pit digging-size(3x2x0.6) = 3.6 cu. Mtr,Base filling byKopra -1.92 cmt., concreting, curing and back filling of pits ] |
| 130 | PTR Fndn.Cncrt.:1:1.5:3 Rio 5.634,1:5:8 Rio 7.545 cmt&M.S.Flat/rod 324.87 kg (as per Drawing) |
| 131 | Labour Charges for PTR Fndn.Cncrt.:1:1.5:3 Rio 5.634,1:5:8 Rio 7.545 cmt&M.S.Flat/rod 324.87 kg (as per Drawing) |
| 132 | Furniture for control room Table 600mmx 900mm- 1no., Chair- 3no., |
| 133 | Copper Control Cable 2 Core. 2.5 Sq.mm. (Unarmoured) |
| 134 | Erection Charges for Copper Control Cable 2 Core. 2.5 Sq.mm. (Unarmoured) |
| 135 | Copper Control Cable 4 Core. 2.5 Sq.mm. (Unarmoured) |
| 136 | Erection Charges for Copper Control Cable 4 Core. 2.5 Sq.mm. (Unarmoured) |
| 137 | Copper Control Cable 8 Core. 2.5 Sq.mm. (Unarmoured) |
| 138 | Erection Charges for Copper Control Cable 8 Core. 2.5 Sq.mm. (Unarmoured) |
| 139 | Copper Control Cable 12 Core. 2.5 Sq.mm. (Unarmoured) |
| 140 | Erection Charges for Copper Control Cable 12 Core. 2.5 Sq.mm. (Unarmoured) |
| 141 | EARTHING SET (40MM , 3 METER GI PIPE , GI WIRE, EARTHING CLMAP AND NUT BOLT) |
| 142 | PVC insulated 2 core armoured 4 sqmm Aluminium conductor 1100 Volts |
| 143 | Erection Charges for PVC insulated 2 core armoured 4 sqmm Aluminium conductor 1100 Volts |
| 144 | 33 KV Strain hardware (T&C type) fittings suitable for Panther |
| 145 | PVC insulated 4 core armoured 16 sqmm Aluminium conductor 1100 Volts |
| 146 | Erection Charges for PVC insulated 4 core armoured 16 sqmm Aluminium conductor 1100 Volts |
| 147 | XLPE Cable 1 core unarmoured 70 sqmm Aluminium conductor 1100 Volts |
| 148 | Erection Charges for XLPE Cable 1 core unarmoured 70 sqmm Aluminium conductor 1100 Volts |
| 149 | XLPE Cable 1 core unarmoured 150 sqmm Aluminium conductor 1100 Volts |
| 150 | Erection Charges for XLPE Cable 1 core unarmoured 150 sqmm Aluminium conductor 1100 Volts |
| 151 | AAAC Rabbit conductor 0.05 sq. inch. (55 sq.mm. Al.Eq.) |
| 152 | Erection Charges for AAAC Rabbit conductor 0.05 sq. inch. (55 sq.mm. Al.Eq.) |
| 153 | D.O.Mounting Channel 75x40x6mm |
| 154 | D.C. Channel 100x50x6mm 4.8 mtrs center to center |
| 155 | Erection Charges for D.C. Channel 100x50x6mm 4.8 mtrs center to center |
| 156 | Transformer mounting Channel (100X50x6 mm.) |
| 157 | Erection Charges for Transformer mounting Channel (100X50x6 mm.) |
| 158 | D.C. Cross-arms 8 ft centre to center (100x50x6mm) Channel |
| 159 | Erection Charges for D.C. Cross-arms 8 ft centre to center (100x50x6mm) Channel |
| 160 | Transformer clamping set 50X50 X6 mm Angle 460mm long |
| 161 | 33 KV Top clamps 75x75x6 mm Angle (S/s) |
| 162 | Erection Charges for 33 KV Top clamps 75x75x6 mm Angle (S/s) |
| 163 | 11 KV Top clamp 65X65X6 mm. angle type (S/s) |
| 164 | Erection Charges for 11 KV Top clamp 65X65X6 mm. angle type (S/s) |
| 165 | ACSR Panther conductor 0.20 sq. inch (200 sq.mm Al.Eq.) |
| 166 | Erection Charges for ACSR Panther conductor 0.20 sq. inch (200 sq.mm Al.Eq.) |
| 167 | DLMS Compliant LT THREE Phase Whole Current Static Energy Meters (10-60A) with Optical Communication Port Duly fitted in meter box |
| 168 | 3 phase 4 wire 3x63.5 volts lb=5 amps Imax = 10 amp, HT trivector meter class of accuracy 0.5s, DLMS Compliant category A Meters along with GSM (GPRS compatible ) modems (For substation metering)(Erection rate of installationof HTmeter(11 KV / 33 KV both) excluding ME with modem complete ,meter box with TTB, cabling & wiring ) |
| 169 | H-Beams 152 X 152 mm., 37.1 Kg./Mtr.-9 mtr. Long= 333.9 kg (Iron Steel Scrap) |
| 170 | Erection Charges for H-Beams 152 X 152 mm., 37.1 Kg./Mtr.-9 mtr. Long= 333.9 kg (Iron Steel Scrap){(including Pit Digging - Base Padding of Pole by Stone Block/Pre Cost Block, Pole Erection, Back Filling/Boulder, Earthing Coil)}(Including with Transportation from Area store Guna/Gwalior/ Bhopal to working Site) |
| 171 | H-Beams 152 X 152 mm., 37.1 Kg./Mtr.-7 mtr. Long= 259.7 kg (Iron Steel Scrap) |
| 172 | Erection Charges for H-Beams 152 X 152 mm., 37.1 Kg./Mtr.-7 mtr. Long= 259.7 kg (Iron Steel Scrap){(including Pit Digging - Base Padding of Pole by Stone Block/Pre Cost Block, Pole Erection, Back Filling/Boulder, Earthing Coil)}(Including with Transportation from Area store Guna/Gwalior/ Bhopal to working Site) |
| 173 | H-Beams 152 X 152 mm., 37.1 Kg./Mtr.-11 mtr. Long= 408.1 kg (Iron Steel Scrap) |
| 174 | Erection Charges for H-Beams 152 X 152 mm., 37.1 Kg./Mtr.-11 mtr. Long= 408.1 kg (Iron Steel Scrap){(including Pit Digging - Base Padding of Pole by Stone Block/Pre Cost Block, Pole Erection, Back Filling/Boulder, Earthing Coil)}(Including with Transportation from Area store Guna/Gwalior/ Bhopal to working Site) |
| 175 | 30 V -10Amp Battery Charger Rectifier type |
| 176 | Erection Charges for Handling & Installation of 30 V -10Amp Battery Charger Rectifier type |
| 177 | 33 KV Polymer Lightening arrestor Gapless type |
| 178 | Erection Charges for 33 KV Polymer Lightening arrestor Gapless type |
| 179 | 11 KV Composite Polymer AB Switch Horizontal Movement type |
| 180 | Erection Charges for 11 KV Composite Polymer AB Switch Horizontal Movement type |
| 181 | 33 KV Composit Polymer AB Switch complete withhandle & pipe |
| 182 | Erection Charges for 33 KV Composit Polymer AB Switch complete withhandle & pipe |
| 183 | 11 KV PT Single Phase |
| 184 | Erection Charges for Handling & Installation of 11 KV PT Single Phase |
| 185 | 33 KV CTs.Outdoor Oil immersed type 300-150/5-5 Amps |
| 186 | Erection Charges for Handling & Installation of 33 KV CTs.Outdoor Oil immersed type 300-150/5-5 Amps |
| 187 | 140 Kg.,8.0 Mtrs. long PCC pole |
| 188 | Erection Charges for 140 Kg.,8.0 Mtrs. long PCC pole { Pole Erection - (including Pit Digging - Base Padding of Pole by Stone Block/Pre Cost Block, Pole Erection, Back Filling/Boulder, Earthing Coil)} (Including with Transportation from Area store Guna/Gwalior/ Bhopal to working Site) |
| 189 | Back Clamp for 140 Kg PCC Pole MS Flat 50x6 mm |
| 190 | Clamp for 140 Kg PCC Pole MS Flat 50x6 mm |
| 191 | G.I. WIRES 4.0 MM. (8 SWG) |
| 192 | Erection Charges for G.I. WIRES 4.0 MM. (8 SWG) |
| 193 | Concreting of stay (16 mm / 12 mm) @ 0.2 Cmt. per stay |
| 194 | Labour Charges for Concreting of stay (16 mm / 12 mm) @ 0.2 Cmt. per stay |
| 195 | 11 KV V cross arm 65X65X6 mm. angle type |
| 196 | Erection Charges for Fixing of 11 KV V cross arm 65X65X6 mm. angle type |
| 197 | 11 KV Top Clamp 65X65X6 mm |
| 198 | Erection charges for fixing of 11 KV Top Clamp 65X65X6 mm |
| 199 | AAAC Raccoon conductor 0.075 sq. inch (80 sq.mm. Al.Eq.) |
| 200 | Labour Charges for Stringing of AAAC Raccoon conductor 0.075 sq. inch (80 sq.mm. Al.Eq.) |
| 201 | Earthing for PCC Pole 4.00 mm-8 SWG G.I wire- 0.8 Kg, per pole |
| 202 | Horizontal & Cross Bracing set of MS angle of 50X50X6 mm for 8 ft (2.4 mtr ) centre DP |
| 203 | Erection charges for Horizontal & Cross Bracing set of MS angle of 50X50X6 mm for 8 ft (2.4 mtr ) centre DP |
| 204 | 11 KV Carpet guarding |
| 205 | Labour Charges for 11 KV Carpet guarding |
| 206 | Galvanized Iron (GI) Flat 50X6 MM |
| 207 | Erection charges for Galvanized Iron (GI) Flat 50X6 MM(G.I.Flat 50x6 mm. digging of 0.5 m deep trench for laying earthing including welding and back filling)[Galvanised mild steel flat (50x6 mm.) For mesh as per details (i) Along PTR 35mx2no.=70 M. across (ii)PTR Alingment 15 m x 7 no.+ 20 x 3 (165 m),(iii) Connections of mesh to 1 earth spike / pipe 0 .5mx 10no. 5m (iv) Connections of mesh to 4pipes earth 8mx 2no. 16 m (v)Connections for 11& 33 kvVCB5mx14 no. 70 m(vi) Connections for 11& 33 kv ct8mx14 no. 112 m (vii)Connections for 11& 33 kv ME20mx 5no. 100 m(viii) Connections for 11& 33 kv LA 30mx 7 no. 210 m (ix) Double connections for PTR neutral and body earth38mx 1 no. 38 m (x)Connections for AB, Isolater handel, 4mx11no. 44m] |
| 208 | G.I.Pipe 40 mm Dia C grade type |
| 209 | G.I.Pipe 40 mm Dia C grade type(G.I. Pipe 40 mm dia errection with pit digging & back filling)[GI pipe 40 mm.,( 3 mtr.Each pipe) (total no. of pits 3 & set of 4 no. Pipe in 2 pits (2x1.5x3m=9 cubic mtr) for neutral and LA] |
| 210 | Earthing rod 3 mtrs.(Gelvanised) 25 mm rod |
| 211 | Earthing rod 3 mtrs.(Gelvanised) 25 mm rod (single spike/earth rod 10 pits distributed for mesh formationavoiding PTR movement area ) (errection with pit digging & back filling) |
| 212 | GI Pipe 150 MM B Grade |
| 213 | GI Pipe 150 MM B Grade [Erection charges forbore through T/w drilling machine suitable for G.I. Pipe150 mm ] |
| 214 | Bentonite Compound Powder |
| 215 | GST @ 18% |