Sales : +91-777 804 8217
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 14-05-2025 | 2nd Date Corrigendum | Date | 16-05-2025 |
| 2 | 08-05-2025 | Date Corrigendum | Date | 13-05-2025 |
| 3 | 08-05-2025 | Corrigendum NIQ 03 | Other | 08-05-2025 |
| Sl. No. | Item Description |
| 1 | Supply, installation, testing & commissioning of cubicle type both side openable Indoor type dust and vermin proof powder paintedPanel board having fixed with front side double door with railway type locking arrangement suitable 415V 3 phase, 4 wire 50 Hz AC supply made out of 2 mm thick CRCA sheet so asto accommodate the following mountings complete with copper bus bar, cable allay & channel base at the bottom connection & interconnection by copper wire & strip along with Danger Board andnecessary nuts & bolts complete as reqd. (L&T/Siemens/Schneider/Legrand)415V, 36 Ka 400A 4P MCCB - 1 nos.415V, 400A 4P Changeover - 1 nos.415V 400A Bus Bar415V, 36 Ka 250A 4P MCCB- 1 nos.415V, 36 Ka 160A 4P MCCB- 1 nos.415V, 36 Ka 63A 4P MCCB- 4nos.Indicating Lamp-3 nos.Digital Voltmeter- 1 no.Digital Ammeter- 1 no.Danger Board- 1 no.and all other accessories. |
| 2 | Supplying and fixing double door 4 Way Vertical TPN MCBDistribution board for MCCB incomer with IP-42/43protection, on angle iron frame on wall & mending goodthe damages to original finish incl. Inter connection withsuitable size of copper wire and neutral link & provisionfor earthing attachment |
| 3 | Supplying and fixing double door sheet steel(16SWG), powder coated cable end box for TPNDB horizontal / vertical enclosure with IP-42/43protection, on angle iron frame on wall & mendinggood the damages to original finish with nuts boltsetc incl. provision for earthing attachment |
| 4 | Supplying and fixing double door Horizontal 6 way TPN MCBDistribution board with IP-42/43 protection, concealedin wall after cutting the wall & mending good thedamages to original finish incl. Inter connection withsuitable size of copper wire and neutral link & provisionfor earthing attachment |
| 5 | Supplying and fixing double door 8 Way SPN MCBDistribution board with IP-42/43 protection concealed in wall after cutting the wall & mending goodthe damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment |
| 6 | Supplying and fixing 4 way MCB SS enclosure with IP-20/30 protection, powder coated provision for two/four pole MCB, concealed in wall after cutting the wall & mending good the damages to original finish incl. painting, connection & provision for earthing attachment as per instruction of EIC. |
| 7 | Supplying and fixing 415 V Four Pole MCCB ofBreaking capacity 25kA/35kA with fixed thermaland fixed magnetic / adjustable thermal and fixedmagnetic setting in existing DBs / enclosure andnecessary connection160 AFP MCCB |
| 8 | Supplying and fixing 240/415 V MCB of Breakingcapacity 10kA & C characteristics on din rail ofexisting DBs and necessary connection63TP MCB |
| 9 | 63 FP MCB |
| 10 | (6-32) A DP MCB |
| 11 | (6-32) A SP MCB |
| 12 | Supply & Fixing 240 V, 6 A, 3 pin Modular type plugsocket (Brand approved by EIC) with 6A Modular typeswitch, without plug top on 4 Module GI Modular typeswitch board with 3 Module top cover plate flushed inwall incl. S&F switch board and cover plate and makingnecy. connections with PVC Cu wire and earth continuitywire etc. |
| 13 | Supply & Fixing 240 V, 16 A, 3 pin Modular type plugsocket (Brand approved by EIC) with 16A Modular typeswitch, without plug top on 4 Module GI Modular typeswitch board with top cover plate flushed in wall incl.S&F switch board and cover plate and making necy.connections with PVC Cu wire and earth continuity wireetc. |
| 14 | Distn. wiring in 22/0.3 (1.5 sqmm) single core stranded \"FR\"PVC insulated & unsheathed single core stranded copper wire(Brand approved by EIC) in 19 mm bore, 3 mm thick polythenpipe complete with all accessories embedded in wall tolight/fan/call bell points with Modular type switch (Brandapproved by EIC) fixed on Modular GI switch board with topcover plate flushed in wall incl. mending good damages tooriginal finish.2x22/0.3 (Ph. & N) and 1x22/0.3 as ECCAverage run 9 mtr |
| 15 | Distn. wiring in 22/0.3 (1.5 sqmm) single core stranded \"FR\"PVC insulated & unsheathed single core stranded copper wire(Brand approved by EIC) in 19 mm bore, 3 mm thick polythenpipe complete with all accessories embedded in wall to 240 V6A 5 pin plug point incl. S&F 240 V 6A 3 pin Modular typeplug socket & Modular type switch (Brand approved by EIC)incl. S&F earth continuity wire, fixed on 4 Module GI switchboard with 3/4 Module top cover plate flushed in wall incl.mending good damages to original finish.2x22/0.3 (Ph. & N) and 1x22/0.3 as ECCOn Board |
| 16 | Supplying & Fixing iron beam fan clamp of two piece type, as per approved specification, fabricated from 40 mm x 9 mm MS sheet flat suitable for beam having flange upto 150 mm wide – (As per Drawing no. 476 of PWD Specification Book – May 1991) |
| 17 | Supply & Fixing 240V, Modular Socket (2 Module) type fan regulator (Step type) (Brand approved by EIC) on existing Modular GI switch board JVith top cover plate incl. making necy. Connections etc .. |
| 18 | Fixing only ceiling fan complete with blades, canopy, fork, rubberbush etc. incl. S&F connecting wire for down rod upto 30 cm incl.painting the rod with approved paint and making necessaryconnection as required by 2x1.5 sqmm flexible copper wire. |
| 19 | Extra for supplying additional wire for down rod & painting the rodexceeding 30 cm by 2x1.5 sqmm flexible copper wire. |
| 20 | Supply & Fixing louver shutter on wall with necy. Bolts & nuts (6 mm dia x 62 mm long) For GI 23 cm Exhaust fan (9\") |
| 21 | Fixing only exhaust fan after making hole in wall and making gooddamages and smooth cement finish etc. as practicable aspossible and providing necy. length of PVC insulated wire andmaking connection for exhaust of following diameter: 23MM (9\") |
| 22 | Fixing only single/twin fluorescent light fitting complete with allaccessories directly on wall/ceiling with HW block and ceilingplates, nipples etc. as required |
| 23 | Supplying and Drawing 1.1 KV single core stranded \"FR\"PVC insulated & unsheathed single core stranded copper wire(Brand approved by EIC) of the following sizes in the prelaidpolythene pipe and by the prelaid GI fish wire and makingnecy. connection as required 3x1.5sqmm |
| 24 | 2x36/0.3 (2.5 sqmm) + 1x22/0.3 (1.5 sqmm) as ECC |
| 25 | 2x80/0.4 (10 sqmm) + 1x84/0.3 (6 sqmm) as ECC |
| 26 | 4x80/0.4 (10 sqmm) + 2x84/0.3 (6 sqmm) as ECC |
| 27 | Supply of recess/ Surface mounted 18 W LED down light which range is brake through technology and reliable heat management to deliver a long lasting efficient solution. |
| 28 | Supply ,Transportation, Loading & unloading of Industrial box type luminaire suitable for single T8 LED tube of 20w (4ft) for SINGLE batten and LED tube of 20w with extruded aluminium body. |
| 29 | supply of 250 V 48\"(1200mm) sweep BLDC ceiling fan with 50% energy consumption complete with blades, condencer, canopy, down rod etc. complete and suitable for 23,Ov ac operation. |
| 30 | AC Exhaust fan Of 10\"(300mm) sweep, turbo, Grey withfan motor,condencer, Ftame, Blade etc, complete and suitable for 230v ac operation. |
| 31 | Supply of high speed wall mounting bracket fan 240 V 400 mm sweepfixed with close mesh guard , pull chain arrangement for speed control and sturd and heavy duty blades for higher displacement of air . |
| 32 | supply and fixing of angular batten with 9 Watt LED Bulb |
| 33 | Supply of LED Bulkhead that fits in vartiety of applications and serves as simple energy efficient alternative to CFL/incandescent bulkhead luminaires |
| 34 | Fixing only bulk head /ceiling fitting on wall /ceiling by screws etc. |
| 35 | Supplying & fixing medium gauge GI Pipe ( ISI-Medium)Protection with necessary fittings and jointing metarials asrequired 50 mm dia |
| 36 | 80 mm dia |
| 37 | Compound Lighting: Supplyand delivery of 3 Meter Decorative Pole, Single Arm With Single Light ornamentalpoles with LED post top lantern (including lamp) made out of cast aluminium embellishments. The pole s are primer coated and painted with polyurethane paint. Poles are suitable for Single side Luminaires. The poles have a service window at the bottom comprising four way 25Amp connector terminal and a MCB. Poles can be mounted with four numbers Anchor bolts as per foundation details provided by Manufacturer\"s company. (Make-HPL/K-LITE/Orient) as approved by EIC. |
| 38 | Supply and providing of suitable size & height of 461mm X 461mm CC foundation including erection the pole and depth below the G.L 1000mm approx. including fixing of existing 4 nos foundation nuts & bolts with washer and cement plaster & neat cement polish,painting or as per direction of E-I-C andG.S. |
| 39 | Extra on items 1& 2 above, for providing CC (6:3:1) base block (around the pole) dimension 0.45x0.45x0.60 mt. above ground level, neatly cemented finish (3 mm thick), at the base pole (in lieu of CC muffing) incl. drilled hole in pole suitable for alkathene/polythene pipe entry, for street light wiring, without Loop Box |
| 40 | Supplying and fixing PVC Rigid Conduit \"FR\" [Precision Make]on wall, ceiling with saddles and other accessories as required and mending good damages to building works 25 mm dia |
| 41 | Supply ,Transportation, Loading & unloading offollowing types of 1.1KV grade XLPE 1.1kv grade AI armoured XLPE cable2 CORE 10 sq. mm |
| 42 | i) 3.5 core X 70 sq.mm. |
| 43 | i) 3.5 core X 300 sq.mm. |
| 44 | 2X2.5 SQMM UN ARMOURED CU CABLE for under water lights |
| 45 | 4X4 SQMM UN ARMOURED CU CABLEfor connecting pump to control panel. For location in Plant Room for Re-circulating Pump. |
| 46 | Supply ,Transportation, Loading & unloading of unarmoured 42x 1.5 Sq. mm. Providing electrical cable 2 x 1.5sq. mm. copper cable for connecting pump to control panel. For location in Plant Room for DOSING PUMP |
| 47 | Supply & Fixing of perforated GI cable tray with perforation not more than 17.5% suspended from ceiling incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support.With out angle iron support200x50x1.25mm (18SWG) |
| 48 | Laying of cable as below, on existing Cable Tray and binding with suitable size GI wire upto 50 sqmm |
| 49 | Laying of one No. cable upto 35 sqmmin underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed |
| 50 | Supplying and fixing compression type gland complete with brassgland, brass ring & rubber ring for dust & moisture-proof entry ofXLPE/PVC armoured cables as below :2 CORE 10 sq. mm |
| 51 | i) 3.5 core X 70 sq.mm. |
| 52 | i) 3.5 core X 300 sq.mm. |
| 53 | Finishing the end of following XLPE/PVC armoured cables bycrimping method incl. supplying and fixing solderless socket(Dowels make), tapes, anticorrosive paste & jointing materials :2 CORE 10 sq. mm |
| 54 | i) 3.5 core X 70 sq.mm. |
| 55 | i) 3.5 core X 300 sq.mm. |
| 56 | Supply & Fixing EI danger board on wall 15 cm x 10 cm (6\"x4\") |
| 57 | Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level andpartly above ground level driven to an average depth of 3.65 Mts. below the ground level as below. By TATA-Medium GI pipe |
| 58 | Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 8636 cm x 46 crn deep (below Ground level) complete with cemented brick work(I:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size ,36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe |
| 59 | Extra for treatment of soil by using salt & charcoal or coke for plate electrode |
| 60 | Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 25 rnm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required |
| 61 | Connecting the equipments to earth busbar including S & F GI (Hot Dip) wire of size as below on wall/floor with staples buried inside wall/floor as required and making connection to bolts, nuts, washerscable lugs etc. as required and mending good damages Solid GI wireNo. 8 SWG |
| 62 | Site Preparation, Temporary Latrine, Placement & levelling of RigMachine, Mast hoisting and Casing drilling (Upto 6 mtr.) Placementof Casing with all allied works necessary to commence drillingwoks and wind up of all machineries after completion of Drilling. |
| 63 | Registivity Test |
| 64 | Labour for boring through any type of soil for sinking tube well of required dia. with top enlargement by rig boring system (either by reserve circulation or by direct rotary method) including hire charges and labour for rig machine, tools and plants, staging, force pumping set and making arrangement for water required for boring etc. complete and lowering ofpipes, strainers, blind pipes etc. complete. b) For depth upto 250 metre for 150 mm dia. Tube well with top enlargement of 250 mm dia.(upto 50 metre). |
| 65 | (ii) Next 50 metre |
| 66 | (iii) Next 50 metre |
| 67 | Supplying, fibre glass reinforced Epoxy resin slotted of 1 mm slot width in 6.1m length of approved make and as per direction of the Engineer - in - Charge(b) 150 mm nominal dia- 7.00 mm wall thickness |
| 68 | Lowering the tube well assembly (UPVC Casing pipe ,well pipe, strainer along with UPVC accessories) vertically in a position with proper lowering arrangement by applying necessary jointing compound including labour cost for subsequent gravel packing and machine operation cost etc. |
| 69 | Cost of Consumables for drilling rigs and machineries. |
| 70 | Development (Min. 8 Hr. continuous) of tube well by using suitable air compressor (Min. Capacity: 600CFM & operating Pressure 14 Bar) followed by yield testing with BHT pump (Head :45 to 50mtr.,Discharge :1100 to 1000 LPM and 25 BHP engine) all complete including To & Fro Transportation cost and Cost of fuels, lubricants & Labour etc. |
| 71 | Water sample collection and chemical test including Arsenic Test. |
| 72 | Transportation cost of drilling equipment and accessories rigmachine etc. including cost of fuel,Lubricant & loading unloadingthe materials from store/stack yard /suppliers godown andunloading /stacking the same at site.(Upto 60.0 km distance) |
| 73 | Supply and delivery of UPVC pipe (CD) conforming to IS 12818:2010. (CIPET Certified) b) 250 mm Dia |
| 74 | d) 150 mm Dia |
| 75 | Supply and delivery of UPVC Reducerb) 250mmx 150 mm dia. (250mmx200mm-1 no & 200mmx150mm-1no) |
| 76 | Supply and delivery of UPVC EndCapb) 150 mm dia. |
| 77 | Supply and delivery of UPVC Capb) 250 mm dia. |
| 78 | Supply and delivery of M.S. Housing clamp 250 mm dia. |
| 79 | Supply and delivery of M.S .Centre guide (Special Type). |
| 80 | Supply and delivery of Washed gravels size ranging from 1.80 mm to 4.74 mm. conforming to IS 4097 : 1967. |
| 81 | Supply and delivery of Bentonite Powder conforming to IS 6186 :1986 |
| 82 | Electro-logging charge. |
| 83 | Supply and delivery or clear water vertical wet type submersible pump suitable for bore well conforming to IS : 8034 ( and as amended thereafter ) with standard MOC for potable clear coldwater and BEE 3 Star Rated capable of dischargirg noted M3/hr against head of water column. The pump shall be directly coupled with a contineous rated 2- pole Suitable wet type verticalsquirel cage induction motor conforming to IS : 9283 ( and as amended hereafter ), suitable for (and as amended t, operation in AC Three phases 415 V, Sd[Z(category B motor) |
| 84 | Labour charges for lowering the submersible pump set, column pipes with necessary accessories including fitting & fixing the same in the tubewell including proper electrical connection with generator all complete as per direction of Engineer-in-charge and also withdrawal of the same after completion of the test. |
| 85 | Supply, installation, testing & commissioning of Outdoor type dust and vermin proof powder painted Sub Panel board having fixed with front side double door with railway type locking arrangement suitable 415V 3 phase, 4 wire 50 Hz AC supply made out of 2 mm thick MS sheet so asto accommodate the following mountings complete with bus bar of 315 Amp capacity & channel base at the bottom connection & interconnection by copper wire & strip along with necessary nuts & bolts complete as reqd. (Make-Havells/Siemens/ABB make).a) 63A 415 Volt TPN SFU withHRC FUSE-1 nob)63A Capacity 415 Volt 4 bar AL busbar of bars size 50mmX10mmX1mtr c) 32A 415 Volt TPN SFU with 3 nos HRC FUSE-1 nod )32A 250 Volt DP MCB - 3 nose) 0-150 Amp Digital Ammeter-1 nof)250/5 A CT-3 nos g) 0-500 digital Voltmer-1noh) LED Indicating Lamp-3 nos i)Caution board-1 no |
| 86 | Supply, fabrication & installation of header assembly made of 150 mm dia 1.2 meter long black MS pipe having both sides sealed by welding provision for with MS sheet for 1 No. 50 mm dia inlet & 4 nos 50 mm dia outlet to be fixed on 50 & 40 mm short pieces welded with 150 mm header including 4 nos gun metal wheel wash out line with provision for pressure gauge and 1/2\"\" Fullway valve,nipple and presure gaugeto be fixed on Headerwith all supporting arrangement & painting etc as per direction of EIC. |
| 87 | Making of brick pillar of suitable size with neat cement plastering for supporting lead/plumbing line as per instruction of EIC. |
| 88 | S & F 20 mm dia G.I. Pipe (Jindal-M) for protection of cable. |
| 89 | Supply of 1.1 KV grade 4 core 16 sqmm PVC/A cable |
| 90 | laying 1.1 KV grade 4 core 16 sqmm PVC/A cable mainly in U.G. With proper brick protection including earthing attachment as per G.S. |
| 91 | S & F compression type cable gland suitable for 4 core 16 sqmm PVC/A cable. |
| 92 | Finishing the cable ends by crimping method for 4x16 sqmm PVC/A cable. |
| 93 | Supplying, fitting and fixing CPVC (Chlorinated Polyvinyl Chloride) pipes of approved make conforming to IS-15778: 2007 . with all necessary accessories, specials viz. socket, bend, tee, union, cross, elbo, nipple,longscrew, reducing socket, reducing tee, short piece etc. fitted with holder bats clamps, including cutting pipes, fitting, fixing etc. complete in all respect including cost of all necessary fittings as required,jointing materials in any position above ground. (Payment will be made on the centre line measurements of total pipe line including all specials. No separate payment will be made for accesories, specials. (i) CPVC Pipes Class-1,SDR-11 50 mm(Dia) |
| 94 | Sign BoardSupply & lnstallation of 6\" depth box type M,S. structure duly fabricated &.welded by 40 mm x 40 mm M.S. square pipe 3 mm thick lSI mark frame with back side & four sides covered by 24SWG MS sheet including Aluminium channel and fixing arrangement without ACP sheet includiug painting,. slze :20\" x 6.5\" to be made such a manner that it can be opened towards up direction for taking maintenance. |
| 95 | S&F 4mm thick white ACP sheet on MS structure. Size 20 ftX 6.5 ft |
| 96 | Supply & fixing of special type imported acrylic letter suitable height as per site requirment fixed on ACP sheet.The letter front( English/Bengali bold) letter colour- Blue |
| 97 | Supply & fixing ofLED inside the acrylic letters.the specification of lED is given below; a) LED white samsung (Korea) module. ( 3 nos. LED in a module)b) type:double line fixed.c) Life:70,000 burning hours.d) Intensity- same & smooth through out no brighter or light or dark patches.e) Visibility: 50 mtr. at least for normal eye.f) Power supply: required amp (mean well LRS·< >-12)g) Ambient air 0-50 c 100% relative humidity.h) Power consumpdon: 1.08 watt per module. |
| 98 | S & F water proof 350 watt power supply system [P65. 50/60 Hz frequency 108 to 305 VAC power supply, >.095 power factor for LED lamp, (Make: Meanwell /Groen) |
| 99 | S&F 50mm X 50mm X 6mm MS angle on wall including painting for fixing of sign board. |
| 100 | Distribution wiring in 1.1 KV single core stranded \"FR\"PVC insulated & unsheathed copper wire (Brandapproved by EIC) in 20mm size PVC rigid conduit \"FR\"(Precision make) incl. necy. fittings as required. 2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC |
| 101 | CONTRAL PANNEL. Main pannel Providing motor control centres fabricated from 16 gauges M.S. sheet with powder coated finish. The control panels should be comparable with H.P. of the motor as specified, in the Technical Specification. One incoming main 250 Amp. TPN MCCB with rotary handle. Aluminum bus bar in separate chamber, fully taped of 300 Amps capacity. One 96 mm square panel type Digital voltmeter with reading 0-500 V with rotary selector switch for reading voltage between phases. One 96 mm square panel type Digital Ampere meter (0-100 Amp) complete with CT\"S and selector switches. Isolation MCBof required rating, for each unit.-Fully automatic DOL starter with pushbutton and ON/OFF indicating lights for each unit,for following requirements :- 16 Nos \"ON\" & 16 Nos \"OFF\". i)Recirculation pumps 5nos. of required Approx. 10.0 HP each (4 working + 1 stand by), switch fuse unit of 32 Amps System Unit for Main Pool. ii)Chlorine Dosing pumps 1 nos. of required Approx. 1.0 HP eachswitch fuse unit of 16 Amps System Unit for Main Pool. iii)Soda Ash Dosing pumps 2 nos. of required Approx. 1.0 HP each , switch fuse unit of 16 Amps System Unit for Main Pool. iv)Alum Solution Dosing pumps 2 nos. of required Approx. 1.0 HP each , switch fuse unit of 16 Amps System Unit for Main Pool. Two Rotary switches for Auto/Manual ON/OFF operations for each unit for 32 Amps System Unit. Neon phases indicating lights on the incoming mains 3 Nos. R-4-B. MPRD2 Single phasepreventorfor each motor (16 Nos.). All internal wiring colour coded from incoming mains to various switchgear, starter, motor, indicating lamp and bus bar. All the cable entry to the panel shall be from the top. Make : As per approved make. |
| 102 | (a) Under water Lights.Delivery, supply, erection, testing and commissioning of Under water lights of Type - Under water light with cablewith niche. The flood lamps shall complay with P68 degree of protection and should be resistant to dust, soildbodies and humidity, M, Lamp watts - 20 Watt Led, Bulb voltage -12V, Candescant, Size - 280 mm X 150 mmincluding all accessories, fitting, fixing, all Taxes & T&eP required for the work complete as per direction of EIC |
| 103 | (b) Junction Box/ Deck Box.Delivery, supply, erection, lesting and commissioning of Junction Box / Deck Box having Material of ConstructionABS No of Inlet - 3, Size of Inlet-3/4 Threaded Capacity including all accessories, fitting, fixing, all Taxes &T&P required for the work complete sper direction of EIC |
| 104 | (c) Flexible Conduit.Delivery, supply, erection, testing and commissioning of Flexible Conduit, Length of conduit -1 M, EndConnection -3/4* Threaded End, Purpose - For connecting light to junction box including all accessories, fiting,Fixing, all Taxes & T&P required for the work complete as per direction of EIC |
| 105 | OUT DOON PANEEL FOR UNDER WATER LIGHTS(a) Contriler: Delivery, supply, erection, testing and commissioning of motor control centres fabricated from 16 gauges MS sheet with necessary double door, gasket , MCB switch ,channel for fixing controller/Transformer, Input Power supply -220/240 V, Output power supply -12 -16 V, Current -400 VA, Protection -ENG0742 inchuding all accessories, fiting, fixing, all Taxes andT&P required for the work complete as per direction of EIC |
| 106 | RE-CIRCULATION PUMPSDelivery, supply, erection, testing and commissioning of Type -Centrifugal pumps with pre filter basket attached, Capacity - 104 m3/hour, Dicharge head - 13 meter, Total Shutoff Pressure of Pump - 20meter maximum, with body of CI, Impeller - Bronze ,Shaft - Carbon Steel, Shaft Sleave-Bronzeand suction connection - 4\" as per B.S , Discharge connection - 4\" as per B.S 2501 and with motor of Power rating 440 V3 Phase50 Hz, 10 H.P, R.P.M 1450 including all accessories, fitting, fixing, all Taxes & T & P required for the work complete as per direction of Consultant. (Make : Kirloskar Brothers ) |
| 107 | MAINTENANCE EQUIPMENT -(a) Vaccum Head. Delivery, supply,erection, testing and commissioning of Vacuum Head of Type doublelength 840 mm, Material of construction - Brightly Polished SS andchromium plated, to be towed with cable with 2 connections, Connection -2 inch Clip including all accessories, fitting, fixing, all Taxes & T&Prequired for the work complete as per direction of Consultant. (Make : WTI) |
| 108 | (b) Handle. Delivery, supply, erection, testing and commissioning of handleof Reinforced Aluminium, Type - Telescopic, End connection - adaptable to all accessories, Total length of Handle - 13 meter including all accessories,fitting, fixing, all Taxes & T & P required for the work complete as perdirection of Consultant. (Make : WTi) |
| 109 | (d) Deep Bag Net. Delivery, supply, erection, testing and commissioning ofDeep Bag Net ,Material of construction - Polypropylene and whitepolyester netting, end connection - 2\" wing nut including all accessories,fitting, fixing, all Taxes & T&P required for the work complete as perdirection of Consultant. (Make : WTI) |
| 110 | (e) Shallow net Delivery, supply, erection, testing and commissioningof Shallow Net ,Material of construction - Polypropylene and whitepolyester netting, end connection - 2\" wing nut including all accessories,fitting, fixing, all Taxes & T&P required for the work complete as perdirection of Consultant. (Make :WTI) |
| 111 | (f) Curved Brush for pool basin and scum liners. Delivery, supply, erection,testing and commissioning of Curved Brush for pool basin and scum lines,Material of construction - Polypropylene and aluminium, End connection -wing nut, Total length of brush - 18 inches including all accessories, fitting,fixing, all Taxes & T&P required for the work complete as per direction ofConsultant. (Make : WTI) |
| 112 | (g) Straight Brush for Pool Bottom. Delivery, supply, erection, testing andcommissioning of Straight Brush for Pool Bottom. Material of construction -Polypropylene and aluminium, End connection - wing nut , Total length ofbrush - 330 mm including all accessories, fitting, fixing, all Taxes & T&Prequired for the work complete as per direction of Consultant. (Make : WTI) |
| 113 | (h) Algae Brush for Pool basin and scum liner. Delivery, supply, erection,testing and commissioning of Algae Brush for Pool basin and scum linerMaterial of construction - Aluminium back with Stainless steel bristles, Endconnection - wing nut, Total length of brush 9 inches including allaccessories, fitting, fixing, all Taxes & T&P required for the workcomplete as per direction of Consultant. (Make :WTI) |
| 114 | (i) Test Kit Delivery, supply, erection, testing and commissioning of TestKit of residual Chlorine and pH Type including all accessories, fitting,fixing, all Taxes & T&P required for the work complete as per direction ofConsultant. (Make : WTl) |
| 115 | POOL BAISIN MAIN DRAIN Delivery, supply, erection, testing andcommissioning of Main Drain Grates having Velocity - 0.5 m / sec throughthe grill, Material of construction, frame & Grill - AISI 316 Stainless SteelPolished, Suction Grill size - 500 mm X 512 mm and Grills fixed with SSScrew including all accessories, fitting, fixing, all Taxes & T & P requiredfor the work complete as per direction of Consultant. (Make : WTI) |
| 116 | (b) Floor Inlets. Delivery, supply, erection, testing and commissioning ofFloor Inlets having Flow capacity / inlet - 10000 LPH, Material ofconstruction - ABS Plastic, Outside connection - 2\" BSP (M) including allaccessories, fitting, fixing, all Taxes & T&P required for the work completeas per direction of Consultant. (Make : WTI) |
| 117 | COMPETITION EOUIPMENT.(a) Floats Lanes. Delivery, supply, erection,testing and commissioning of Float lanesof Type- Float assembled onpolyester rope Width interior turbine machine, Material of Construction -Injected Plastic and SS anchors, Float Dimensions - 148 mm dia, Float linelength - 50 meter including all accessories, fitting, fixing, all Taxes & T&Prequired for the work complete as per direction of Consultant. (Make : WTI) |
| 118 | (b) Starting Blocks. Delivery, supply, erection, testing and commissioningof Starting Block of Type - Adjustable non - slip platform, 0 -10 degree C,Material of Construction of platform - Base - stainless steel AISI - 304,Steps - Polyester and fiberglass, Dimension of Platform - 500 mm x 500mm, Height of platform - 700 mm, Accessories - Anchoring fixture to beincluded including all accessories, fitting, fixing, all Taxes & T&Prequired for the work complete as per direction of Consultant. (Make : WTIl) |
| 119 | c) False Start Indicator Post.Delivery, supply, erection, testing andcommissioning of False start indicator Post having Material of ConstructionStainless steel AISI - 316 , No of Post - Two, One of them with a pully andquick cord fixing and loosing device, Height of Post - 1.8 meter, 48 mm diapipe, Acessories -False start float line with polyster cord and float of 25meter including all accessories, fitting , fixing , all Taxes & T&P required forthe work complete as per direction of Consultant. (Make : WTI) |
| 120 | (d) Back Stroke Indicator Post -Delivery, supply, erection, testing andcommissioning of Back Stroke Indicator Post having Material ofConstruction - Stainless steel AISI - 316 , No of Post- Four / set, Height ofPost - 1.8 meter, 48 mm dia pipe, Acessories - Back Stroke indicator flagsand Polyester Rope - 2 nos including all accessories, fitting , fixing , allTaxes & T&P required for the work complete as per direction ofConsultant. (Make :WTI) |
| 121 | Providing and fixing Butterfly valves including necessary nuts, bolts,gaskets etc. complete.160 mm dia |
| 122 | Providing and fixing Butterfly valves including necessary nuts, bolts,gaskets etc. complete.110 mm dia |
| 123 | Providing and fixing C.I double flanged horizontal / vertical type non-returnvalve including nuts, bolts, 3mm thick rubber insertions complete to I.S :5312, Part-I, swing type, class PN 1.0.160 mm dia |
| 124 | Providing and fixing C.I double flanged horizontal / vertical type non-returnvalve including nuts, bolts, 3mm thick rubber insertions complete to I.S :5312, Part-I, swing type, class PN 1.0.110 mm dia |
| 125 | PUDDLE FLANGES Supply and installation of PVC Puddle Flanges &Sleeves of appropriate size and FRP Wielded Plate . 160 mm dia |
| 126 | PUDDLE FLANGES Supply and installation of PVC Puddle Flanges &Sleeves of appropriate size and FRP Wielded Plate . 110 mm dia |
| 127 | COMMISSION OF POOL -Commission of the Pool including cost ofChemicals for the Period of One Month |
| 128 | ii) DOSING SYSTEM-PH ADJUSTMENT DOSING SYSTEM. (ALUM) (a)Pump and MS Stand Supply, erection, testing and commissioning DosingPump, Pump having capacity 0-46 Liters/hour, Flow adjustment - Byadjusting stroke length from 0 -100% manually, Power rating - 230 V 50Hz, MS Stand, Material of construction - MS Fabricated -including allaccessories, fitting , fixing (Make : Pump - Toshcon, MS Stand - Candy |
| 129 | ii (b) Tank for Alum- Supply, erection, testing and commissioning of Tankwith Capacity - 500 Liters, Open top with LID White Colour, Material ofConstruction - HDPE including all accessories, fitting, fixing. (Make :Sintex) |
| 130 | Air Blower Suppply, tesing and commissioning of Air Blower having capacity of 102 cfm at 0.4 kg/sqcm pressure complete with 5 HP three phase motor, 65 mm dia CI butterfly valve and 65mm CI Non return valve (Make : Motor- Kirlosker/Crompton Greeves, Butterfly Valve, NRV - Sir/Zoloto) |
| 131 | PLUMBING Providing and fixing PVC pipes complete with UPVC Fittingsi.e, tees, elbows, sockets, necessory clamps / support etc the same asper instructions of Engineer-in-charge. Make : Price/Finolex/Supreme . 250mm dia (10 kg) |
| 132 | (b) Tank for Soda Ash/HCL - Supply, erection, testing and commissioningof Tank with Capacity - 200 Liters, Open top with LID White Colour,Material of Construction - HDPE including all accessories, fitting, fixing,all Taxes & T & P required for the work complete as per direction ofConsultant. (Make : Sintex) |
| 133 | (b) Tank- Delivery, supply, erection, testing and commissioning of Tankwith Capacity - 1000 Liters, Open top with LID White Colour, Material ofConstruction - HDPE including all accessories, fitting, fixing, all Taxes & T& P required for the work complete as per direction of Consultant. (Make :Sintex) |
| 134 | (c) Hose Pipe Delivery, supply, erection, testing and commissioning ofHose pipe 60 meter Material of construction PVC , Size-2\" including allaccessories, fitting, fixing, all Taxes & T&P required for the work completeas per direction of Consultant.) |
| 135 | Suction Pump -Delivery, supply, erection, testing and commissioning of Suction Pump having capacity 15 M3 / hour, Discharge Connection 1 1/2\", Material of construction - PVC, Power rating - 440 V 3 phase, Protection - IP 65 protection, Mounted on MS Trolley including all accessories, fitting, fixing, all Taxes & T & P required for the work complete as per direction of ; Consultant. (MAke: Pump- Kirloskar Brothers,Moter- Kirloskar or crompton greeves, Trolley- Candy, Cable- Polycab or equ. ). |
| 136 | Providing & Fixing MS Headers and MS Pipe and flanges with MS wieldedaccording to the Size with necessary flanges nut Bold washer Etc. |
| 137 | Supply & Installation of 60 KVA DG Set:(make-JAKSON/ KIRLOSKAR/ ASHOK LEALAND)Supply, Testing & Comissioning of 60KVA Silent Diesel Generator Set, water cooled, developing of CPCB-IV+ ENGINE with 12/24 volt self starter arrangement including rated DC 12/24V battery, mechanical governor with Gen Set controller, natural aspiration having dry tye air filter couled with Alternator capable of developing 62.5 KVA at 415V 50Hz at 1500 rpm, 3-phase 4-wire conforming to BS EN 60034-1/IS:4722 and will be suitable for tropical condition brushless type, screen protected, revolving field self excited self regulator through AVR, IP protection: 23, permissible overload of 10% for one hour in 12 hrs of operation. Class-H insulation, voltage regulation+1% DG mounted on base with AVM pad complete all as direted adn housed in accoustic enclosure required for Emergency Power Supply. |
| 138 | InstallationEarth excavation of foundation trenches or drains, in all sorts of soil ( including mixed soil but excluding laterite or sandstone ) including removing, spreading or stacking the spoils with in a lead of 75 m as directed . The item includes necessary trimming the sides of trenches , levelling dressing and ramming the bottom, bailling out water as required complete. (a) Depth of excavation not exceeding 1500 mm. |
| 139 | Single brick flat soling of picked jhama bricks including ramming and dressing bed to proper level and filling joints with local sand. |
| 140 | Ordinary cement concreat (mix 1:2:4) with graded stone chips (20 mm nominal size) excluding shuttering and reinforcement , if any ,in ground floor as per relevent IS codes.(a) River bazree. |
| 141 | Brick work with 1st class bricks in cement mortar (1:6)ln foundationand plinth |
| 142 | Filling in foundation or plinth by fine sand in layers not exceeding 150 mm as directed and consolidating the same by thoroughsaturation with water, ramming complete including the cost of supply of sand. (payment to be made on measurement of finished quantity) |
| 143 | Controlled Cement concrete with well graded stone chips (20 mm graded nominal size) excluding shuttering and reinforcement with complete design of concrete as per IS : 456 and relevant special publications, submission of job mix formula after preliminary mix design after testing of concrete cubes as per direction of Engineerincharge. Consumption of cement will not be less than 300 Kg ofcement with Super plasticiser per cubic meter of controlled concrete but actual consumption will be determined on the basis of preliminary test and job mix foumula. In ground floor and foundation. [using concrete mixture] (a) M 20 Grade (Pakur Variety) |
| 144 | Plaster ( to wall, floor ,ceiling etc ) with sand and cement morter including rounding off or chamfering corners as directed and raking out joints including throating , noising drip course, scaffolding / staging where neccy. (ground floor ). [ Excluding cost of chipping over concreat surface) .(a)with 1:4 cement morter 15mm thick plaster. |
| 145 | Neat cement punning about 1.5 mm thick in wall ,dado,window,sills,floor,drain etc. |
| 146 | M.S. Structural works in columns, beams etc. With simple rolled structural members (e.g. Joists, angle, channel sections conforming to IS: 226, IS: 808 & SP (6)-1964 connected to one another with bracket, gussets, cleats as epr design, direction of Engineer-in-charge complete including cutting to requisite shape and length, fabrication with necessary bolting, metal arc welding conforming to IS: 816-1956 & IS: 1995 using electrodes of approved make and brand fonforming to IS: 814-1957, haulage, hoisting and erection all complete. The rate includes the cost of rolled steel section, consumables such as electrodes, gas and hire charge of all tools and plants and labour required for the work including all incidental charges such as electricity charges, labour insurance charges etc.For Structural Works in Roof Trusses etcusing joists, channels and angles of specified section weighing less than 22.5 kg/m. |
| 147 | Galvanised corrugated iron sheet work (excluding the supporting frame work) fitted and fixed with 10 mm dia J or L hook-bolts, limpet and bitumen washers and putty complete with 150 mm end lap and one corrugation minimum side lap (Payment to be made on area of finished work) (GCI sheet to be supplied by contractor).(i) In Roof:(a) With 0.63 mm thick sheet. |
| 148 | Supply and fixing 100mm dia M.S pipe to extend the exhaust pipe line including welding,bend,reducers and all accessories as required at site or as per E-I-C. |
| 149 | Supply of 1.1 KV following grade PVC/Armoured AL cable with 2XlO SWG GI wire as earthing attachment and mending good all damages to building works.(Polycab/Crystal/ KEI)a) 3.5 core X50 sq.mm |
| 150 | Laying of one no cable above 35 sqmm and upto 185 sqmm inunder ground trench 460mm wide x760mm average depth , with brick protection on the top of the cable with 8(eight) nos. Bricks per meter including filling the space between the bricks and cable and also the trench with shifted soil , leveling up and restoring surface duly rammed. |
| 151 | Supply and fixing compression type cable gland complete with brass gland, brass ring and rubber ring for dust and moisture- proof entry of XLPE/PVC armoured cable.(a) For 3.5 core x 50 sqmm size. |
| 152 | Finishing of the above cable ends by soldering with cable sockets and insulated tapes etc, including supplying sockets, soldering materials , tapes etc . and making connection to switch.(a) For 3.5 core x 50 sqmm size. |
| 153 | Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the Ground (for Morrum soil) |
| 154 | Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required. |
| 155 | Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos.12 mm dia holes on the GI pipe. |
| 156 | Supplying & fixing sheet metal (16 SWG) Iron Clad Busbar chambers on angle iron frame on wall, incl.earthing attachment and painting as required – (As per Drawing no. 470 of PWD SpecificationBook – May 1991)200A Capacity 415 Volt 4 bar AL busbar of bars size50mmX5mmX1mtr-1 No. |
| 157 | Supplying and fixing 415V, 200A TPN SFU with sheetsteel enclosure on flat iron/angle iron frame on wallwith nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating.(L&T) |
| 158 | Supplying and fixing 415V, 100ATPN SFU with sheet steel enclosure on flat iron/angle iron frame on wallwith nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating.(L&T) |
| 159 | Supplying and fixing 415V,100A FP Changeover switch with Sheet Steel enclosure on angle iron frame on wall with nuts bolts etc.(HAVELLS) |
| 160 | Supplying & Fixing of 40 mm GI pipe (ISI-M) |
| 161 | Supply and filling of diesel oilfor trial run of the set. |
| 162 | Installationof CCTV surveillance: Supply, installation, testing & commissioning of IP IR Indoor/Outdoor Bullet Camera, pole / wall / ceiling mount 1/3\" 3 megapixel progressive scan CMOS, 2304 (H) × 1296 (V), H.264, Auto/Manual, 1/3(4)–1/100000 s, 0.1 lux, F1.4 (Colour); 0 lux (IR LEDs on), Up to 30 m (100 ft) IR range, 2.7–12 mm F1.4 motorized focus/zoom lens, Built-in PoE, IP66 Rated, ONVIF Profile S, Profile G, Supports up to 128 GB microSDHC, includingpower supply units and all ancillary equipment & all accessories complete.[Make: as directed by E-I-C]. |
| 163 | Supply, installation, testing and commissioning of 16CH NVR, 2 SATA HDD Slot (Max 8TB), 12VDC,Realtime Recording Resolution(32 Channels @ 720P,24 Channels @1080P),Realtime Local Playback( 8 Channels @ 720P,4 Channels @1080P),Multiplex Operation,H.264 High profile,BNC/VGA/HDMI output, main profile, baseline,HDD Redundancy,Free DDNS,Network backup, USB HDD, USB writer, SATA writer,1 RS485, support 18 kinds of PTZ protocols,ONVIF 2.0,1 channel Audio Input and Output. [Make: as directed by E-I-C]. |
| 164 | Supply & installation ofSurveillance HDD 4 TB each[Make: as directed by E-I-C]. |
| 165 | Supply & installation of42U rack complete with all accessories . [Make: as directed by E-I-C]. |
| 166 | Supply, of22\" LED color monitor with HDMI Port[Make: as directed by E-I-C]. |
| 167 | Supply, installation, testing and commissioning of 8 port- gigabit-10/100/1000,poe switch.[Make: as directed by E-I-C]. |
| 168 | Supply & Installation of Desktop having specification: i3, 6 generation, 4GB RAM, 1TB HDD, 18.5\" LED Monitor, Speaker 2.0, Wifi Keyboard & Mouse with genuine Windows 10. [Make: as directed by E-I-C]. |
| 169 | Supply & laying of 6 core fiber optic cable./ CAT6 Cable. [Make: as directed by E-I-C]. |
| 170 | Supply, Installation, Testing & Commissioning of 20kwp Solar Photovoltaic Panels. Poly Crystalline 310Wp to 325Wp (Each) (Make: VIKRAM / WAREE / JINKO / SOVA/ ADANI) The PV modules used must qualify to the latest edition of IEC PV module qualification test or equivalent BIS standards Crystalline Silicon Solar Cell Modules IEC 61215/IS14286 .The rated output power of any supplied module shall have tolerance of +/- 3%.The peak-power point voltage and the peak-power point current of any supplied module and/or any module string (series connected modules)shall not vary by more than 2 (two) per cent from the respective arithmetic means for all modules and/or for all module strings, as the case may be.The module shall be provided with a junction box with either provision of external screw terminal connection or sealed type and with arrangement for provision of by-pass diode. The box shall have hinged, weather proof lid with captive screws and cable gland entry points or may be of sealed type and IP-65 rated. |
| 171 | Supply & Fixing Module Mounting Structure: Hot dip galvanized MS mounting structures may be used for mounting the 10kwp modules/ panels/arrays. Each structure should have angle of inclination asper the site conditions to take maximum insolation.The mounting structure steel shall be as per latest IS 2062: 1992 and galvanization of the mounting structure shall be in compliance of latest IS 4Structural material shall be corrosion resistant and electrolytically compatible with the materials used in the module frame, its fasteners, nuts and bolts.Thiknes of Galvanization shall be more than 75µ. Aluminium structures also can be used which can withstand the wind speed of respective wind zone. Necessary protection towards rusting need to be provided either by coating or anodization.The minimum clearance of the structure from the roof level should be 300 mm [Design to be approved by EIC before fabrication]. |
| 172 | Supply, Installation, Testing & Commissioning of 1 Nos. PV Array Junction Box (AJB) for 10kwp: a) The junction boxes are to be provided in the PV array for termination of connecting cables. The Boxes (JBs) shall be made of Powder Coated Aluminium /cast aluminium/M.S alloy with full dust, water & vermin proof arrangement. All wires/cables must be terminated through cable lugs. The JBs shall be such that input & output termination can be madethrough suitable cable glands.b) Each Junction Box shall have High quality Suitable capacity Metal Oxide Varistors (MOVs) / SPDs, suitable Reverse Blocking Diodes. The Junction Boxes shall have suitable arrangement monitoring and disconnection for each of the groups.Voltage: Max. 1000V DC [Make: Hensel/Spielberg/Citel/ABB/L & T/schneider/Elmax]. |
| 173 | Supply, Installation, Testing & Commissioning of ACDB : Designed for 10kWp solar power plant with all protections as per MNRE guidelines. DC DPBs shall have sheet from enclosure of dust & vermin proof conform to IP 65 protection. The bus bars are made of copper of suitable size. Suitable capacity fuse & MCBs/MCCB shall be provided for controlling the DC power output to the PCU along with necessary surge arrestors . AC Distribution Panel Board (DPB) shall control the AC power from PCU/ inverter, and should have necessary surge arrestors. Interconnection from ACDB to mains at LT Bus bar while in grid tied mode.All switches and the circuit breakers, connectors should conform to IEC 60947, part I, II and III/ IS60947 part I, II and III. All the Panel’s shall be metal clad, totally enclosed, rigid, floor mounted, air - insulated, cubical type suitable for operation on three phase / single phase, 415 or 230 volts, 50 Hz.All indoor panels will have protection of IP54 or better. All outdoor panels will have protection of IP65 or better. [Make: Hensel/Spielberg/Citel/ABB/L & T/schneider/Elmax] |
| 174 | Supply, Installation, Testing & Commissioning of hybrid Solar InverterRating:10kw, 3Ph Inverter, Make: HBL / INVT/ Power-One/Equivalent . Control : Microprocessor /DSP Capacity .Nominal AC output voltage and frequency : 220/415V, 1 Phase / 3Phase,50Hz. Output frequency : 50 Hz . Max. DC input Power 8kW. MPPT Voltage Range 4000 VDC. Max. input current per MPPT 11-26A. Output Voltage Range - 220V/415V AC. Grid Frequency Synchronization range : +/-5 Hz. Ambient temperature considered : -20o C to 60o C. Humidity : 95 % Non-condensing. Protection of Enclosure :: IP-65(Minimum) for outdoor.Grid Frequency Tolerance range : +/- 5 Hz. Grid Voltage tolerance : 280 V to 480 V. No-load losses : Less than 1% of rated power. Inverter efficiency(minimum) : >93%. Inverter efficiency (minimum ) : > 90%.THD : < 3%. Efficiency Measurement IEC 61683/ Equivalent BIS Std.Environmental testing IEC 60068-2 (1,2,14,30) / Equivalent BIS Std.Interfacing with utility grid IEC 61727. Islanding Prevention Measurement IEC 62116. EMI/EMC :IEC 61000-6-3>16 Amps IEC 61000-6-4<16 Amps. Safety:IEC - 62109-1 (2010/4) C - 62109-2 (2011/6).Battery VDC: 120VDC/192/VDC. Charger Capacity: 50A. (Protections) Over Load For 100% Load Buzzer Indication, 101% above Load Trips and Retry for 4times then Inverter shutdown, Output Short Circuit:Circuit Breaker On Mains, Shutdown on Inverter,Battery Reverse Protection: Circuit Breaker, Low Battery:Load Disconnection, Thermal Shutdown:Below 0°C and Above 93:C,lightening/Surge:Protected upto 4KV Surge, Solar Reverse:Blocking Diode is provided to Prevent reverse flow of current, Current Limiting for battery Charging:Available, Battery Charging Current:Battery current limit during low load on solar panel. (Charging)Charging switch OFF:It will charges form solar .Charging switch ON:It will charges from grid when solar charging current is Low.(Environmental)Operating Temperature:-10:Cto 50:C,Relative Humidity:0-95%. Priority:Grid or Solar, LED Display:Mains,Charger,Output,Fault, LCD Display:Batter Voltage; I/P Voltage;I/P Frequency;O/P Voltage; Grid Charging Current; Solar Voltage; Solar Charging Current; Solar Units Saved KWH(up to 999.9Units); Load %; Over Load; Battery Low; UPS/INV Mode IGBT All above IEC’s should be from NABL/ IEC Accredited Testing Laboratories or MNRE Approved Test Centers/ International laboratories. |
| 175 | 12-200Ah Solar Tubular Batteries-10 Nos with rack for 2hr backup Make: Exide/Quanta/HBL/Equivalent |
| 176 | Supply, Installation, Testing & Commissioning of System Earthings : Each array structure of the PV yard should be grounded/ earthed properly as per IS:3043-1987. The array field, PCU, ACDB and DCDB should also be earthed properly. Earth resistance shall not be more than 5 ohms. It shall be ensured that all the earthing points are bonded together to make them at the same potential. At least 4 nos ground pipe / plate electrod as per PWD schedule for system earthing with soil treatment & earth inspection pit and GI flat of suitable size & quantity should be considered [Make: OBO/Beterman/Gmax]. |
| 177 | Supply of Remote Monitoring System (GPRS Type): The RMS system is integrated or External unit. The following parameters are accessible via the operating interface display in real time separately for solar power plant: AC Voltage., AC Output current,Output Power,DC Input Voltage, DC Input Current, Power produce, Protective function limits (Viz-AC Over voltage, AC Under voltage, Over frequency, Under frequency ground fault. vi. The data shall be recorded in a common work sheet chronologically date wise. The data file shall be MS Excel compatible. The data shall be represented in both tabular and graphical form. viii. Simultaneous monitoring of DC and AC electrical voltage, current, power, energy and other data of the plant for correlation with solar and environment data shall be provided |
| 178 | Supply & Laying of CablesDC & AC: Sizes of cables between array interconnections, array to junction boxes, junction boxes to Inverter etc. shall be so selected to keep the voltage drop of the entire solar system to the minimum. The cables (as per IS) should be insulated with a special grade PVC compound formulated for outdoor use. The size of each type of DC cable selected shall be based on minimum voltage drop however; the maximum drop shall be limited to 1%.The size of each type of AC cable selected shall be based on minimum voltage drop however; the maximum drop shall be limited to 2%. i. Shall meet IEC 60227/IS 694, IEC 60502/IS1554 standards. Cost is inclusive of fixing accessories as required. [Make of AC cable: PolyCab/Sterlite/Finolex/Havells/Anchor, Make of DC PolyCab/Sterlite/Finolex/Havells/Anchor]. |
| 179 | Supply, Installation, Testing & Commissioning of Auto Claening SystemPV Module Clean |
| 180 | Supply, Installation, Testing & Commissioning of all items of this BOQ should comply to the detailed Technical Specification given. |
| 181 | Operation &Maintanance for 5Yrs |
| 182 | 35 Sqmm 4 Core armoured PVC/XLPE Power cable |
| 183 | Providing and fixing carbon – di – oxide fire extinguisher consisting of welded MS cylindrical body, squeeze, lever discharge valve, fitted with internal discharge tube, high pressure discharge hose, discharge nozzle, suspension bracket, finished externa.Capacity4.5 kg. ISI marked |
| 184 | Providing and fixing mechanical foam type ( ISI marked ) fire extinguisher consisting of welded MS cylindrical body, squeeze, lever discharge valve, high pressure discharge hose, discharge nozzle, suspension bracket ISI marked finished externally with red enamel paint and fixed to wall with brackets with internal charger .Capacity9 liters |
| 185 | Providing & fixing water Co2 ( ISI marked ) extinguisher including all accessories with wall bracket with rawl plug.Capacity 9 liters. |
| 186 | Providing & fixing dry powder extinguisher consisting of welded MS cylindrical body, with discharge valve, nozzle and CO2 cartige and hanging arrangement complete Capacity 5 kg. ISI marked |
| 187 | Providing laying, testing & commissioning of \"C\" class heavy duty MS Pipe conforming to IS 1239/3589 i/cfittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation &providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as perIS 10221, refilling the trench etc. of following sizes complete as required.i) 150 mm. dia (wall thickness = 6.3 mm) |
| 188 | Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed temperature thermistor complete with base as required. |
| 189 | Supplying, installation, testing & commissioning of fault isolator complete with base as required. |
| 190 | d) Electronic Hooter cum speaker for fire alarm / evacuation signal, 6 watt capacity including base and module |
| 191 | Supplying, installation, testing & commissioning of addressable manual call point complete as required. |
| 192 | Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required. |
| 193 | Supplying, installation, testing and commissioning of microprocessor based intelligent addresable main fire alarm panel, Central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 kilometre, network communication card, minimum 320 characters graphics/ LCD display with touch screen or other keypad and minimum 4000 event history log in non volatile memory (EPROM), power supply unit(230 + - 5% volt, 50 hertz) 48 hours backup with 24 volt sealed maintenance free betteries with automatic charger. The panels shell have facility to connect printer to print out log and facility to have seamless integration with analogue/ digital voiice evacution system( which is a part of schedule of work under SH: PA system) The Panelshall be compatable for IBMS System withopen protocol BACnet/ modbus over IP complete as per specification Two loop panel |
| 194 | Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required |
| 195 | Supplying and fixing 25 mm dia MS flexible pipe with PVC coating along with all ancillaries and accessories like coupler etc. as required. |
| 196 | j) Addressable control relay module. complete as required as per specifications |
| 197 | k) Addressable Control module for hooter. complete as required as per specifications. |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy