| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 09-05-2025 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 16-05-2025 |
| 2 | 29-04-2025 | AMENDMENT | BOQ | 09-05-2025 |
| Sl. No. | Item Description |
| 1 | Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth for foundation, shafts, man holes,for under ground cable / erection of poles, stays, locatingfault of LT cable and stay assembly etc not exceeding 10 square metre on plan and getting out in any type of soil including dressing/trimming of sides and leveling, grading and ramming of bottom of excavation complete all as specified and directed. |
| 2 | All as per Ser item No 1.00 here in before but depth exceeding 1.5 metre and not exceeding 3.0 metre complete all as specified and directed. |
| 3 | Returning, filling in, in soil, including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick each layer complete all as specified and directed. |
| 4 | Removing excavated material/soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed. |
| 5 | Material and labour for sand cushioning to cable with a layer of sand 8 cm deep before laying the cable and 15 cmsdeep after laying the cable (punned down to 18 cms depth after laying and stretching of cable) complete all as specified and directed. |
| 6 | Supply and lay bricks, common burnt clay, sub class \"B\", old size, laid in perpendicular direction to cable as cable protection complete all as specified and directed. |
| 7 | All as per Srl Item No 6.00 here in before but except bricks, complete all as specified and directed.Note:- Old bricks retrieved from Ser Item No 11.00 to 21.00 here in after shall be re-used. |
| 8 | Material and labour for PCC 1:4:8 type D-2 using 40mm graded stone aggregate, mechanically crushed stone for mass filling in polepit and foundation etc complete all as specified and directed. |
| 9 | Material and labour for cement concrete (1:3:6) type C-1using 20mm graded crushed stone aggregate as in coping of pole and strut, stayaround the poleetc complete all as specified and directed. |
| 10 | Material and labour for PCC 1:2:4 Type B-1 using 20 mm graded stone aggregate for coping of poles including necessary form work and finishing the exposed surface even and smooth with out using extra cement complete all as specified and directed. |
| 11 | Disconnecting & taking out defective underground cable from trenches, pole, pipe, floor, wall etc including bricks and locate the fault, rectify the defect and relaying the XLPE cable underground PVC insulated and overall sheathed aluminum conductor heavy duty 1100 volts including connecting and testing for any size complete all as specified and directed.Note:- Excavation/earth work & sand cushioning, bricksandjoint shall be measured & paid for separately. |
| 12 | Supply, laying, connecting & testing in replacement of XLPE underground cable insulated, and overall sheathed with aluminium conductor heavy duty 1100 volts grade 10 sqmm 4.0 core laid in trenches/ on pole/road crossing or passing through existing/new pipe under road crossing clamping on wall incl aluminium thimbles/lugs etc including taking out bricks complete all as specified and directed.Note: (i) Earth work, sand, bricks, returning fillingwill be paid seperately. (ii) Cost of laying electrical cable through new/existing pipe under road, buildings, railway tracks, highways are incl in the quoted rates. (iii)All equipments, machinery or tool if required for laying electrical cable through new/existing pipes are provided by the contractor without any extra cost. |
| 13 | All as per Srl item No 12.00 here in before but for 16 Sqmm 4 core . |
| 14 | All as per Srl item No 12.00 here in before but for 25 Sqmm 3.5 core . |
| 15 | All as per Srl item No 12.00 here in before but for 35 Sqmm 3.5 core . |
| 16 | All as per Srl item No 12.00 here in before but for 50 Sqmm 3.5 core . |
| 17 | All as per Srl item No 12.00 here in before but for 70 Sqmm 3.5 core . |
| 18 | All as per Srl item No 12.00 here in before but for 95 Sqmm 3.5 core . |
| 19 | All as per Srl item No 12.00 here in before but for 120 Sqmm 3.5 core . |
| 20 | All as per Srl item No 12.00 here in before but for 150 Sqmm 3.5 core . |
| 21 | All as per Srl item No 12.00 here in before but for 185 Sqmm 3.5 core . |
| 22 | Supply and fixing in replacement of size PVC insulated aluminium conductor 10 sqmm 2 core, 1100 volts grade heavy duty cableserved with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire, one twin core cable flat or circular complete all as specified and directed. |
| 23 | Supply and fixing in replacement of 2.5 sqmm 3 core copper cable PVC unsheathed multi stranded (FRLS) 1100 volts grade PVC insulated round passing through PVC conduit pipe heavy duty, including electrical connection suitable size of lugs, nuts and bolts complete all as specified and directed. |
| 24 | Supply and fixing in replacement of 1.5 Sqmm single core copper cable PVC unsheathed multi stranded (FRLS) nominal cross sectional area 1100 volts conforming to IS 694 passing through PVC conduit pipe including electrical connection suitable size of lugs, nuts and bolts complete all as specified and directed. |
| 25 | Supply and fixing in replacement of 2.5 Sqmm single core copper cable PVC unsheathed multi stranded (FRLS) nominal cross sectional area 1100 volts conforming to IS 694 passing through PVC conduit pipe including electrical connection suitable size of lugs, nuts and bolts complete all as specified and directed. |
| 26 | Supply and fixing in replacement of rigid non-metallic PVC conduit of dia 20 mm exclusive of boxes (Junction/terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc complete all as specified and directed. Note: PVC pipe will be clamped at three position on pole and cost of clamp, nut, bolts etc are incl in quoted rates |
| 27 | Supplying and fixing in replacement oflight gradegalvanised mild steel pipe 80 mm bore with all fittings, laid under roads, drain, paths, fixed to poles/walls with suitablemild steel clamps, bolts, nuts and washers complete all as specified and directed. Note:- Excavation & earth work shall be measured and paidfor separately under appropriate item of this schedule. |
| 28 | All as per Srl item No 27.00 here-in-before but of size 50 mm bore. |
| 29 | Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique or manual boring and necessary machine including HDPE pipe of 50mm to 150 mm dia suitable for 0.4 mpa working pressure complete all as specified and directed. |
| 30 | Rectification of complaints under E/M installations area of security light, street light, hanger light, flood light and high mast lights, UG cables, LT panels, OH conductor, service wires and allied works by attendng daily complaints including Sunday and other holidays for round the clockand making the same serviceable in all respects alongwith replacement of any major part but including small length of cable (not more than 20 mtr), adhesive tape and other connected minor accessories shall also include to visual inspection of OH lines, Earth Resistance of street poles etc.Quoted rate also include excavation offaulty cable/all type lights are making seviceable with accessories of all nature likeNo light, faulty insulator, broken conductor & cable fault , burnt out MCCB`s, MCBs, isolators, switch fuses,service cables etc complete all as directed to the entire satisfacation of Engineer-in-charge.Note :-(i)Any complaint left unattended by the electrician will be communicated to the JE in-charge /AGE E/M with reason. No charge will be paid for the per complainttill the complaint is resolved. (ii)New material /stores provided for completing the job shall be measured and paid for separately under relevant items of BOQ. (iii)Contractor shall provide all type of T&P of LT street lights network, bamboo ladder with safety gloves to each electrician for attending the external electric complaints. (iv)Contractor shall provide the complaint register 200 pages – 3 No, complaint book with 100 slips- 5 No. Booklets serially numbered in triplicate.(v)Contractor will provide 01 No. Experienced Electrician having minimum 5 years experience ( 01x one shifts per day) and 01 No. Helper having minimum 2 years experience( 01 x one shifts per day) including Sundays and Holidays to attend HT Complaints. (vi) Contractor will provide well experienced and well conversant of one person for lodging the complaint in complaint cell of each power houseduring workinghours from 0900hrs to 1700hrs on all working days including Sunday & all Holidays. (vii)The Contractor will provide insurance cover of minimum Rs 5 lakh per head under IE Rules 2003 and Minimum wages Act.(viii) The Electrician and helper will be interviewed by JE E/M /Engr-in-charge for verification of experience, character and sound mind and body. |
| 31 | Dismantling and taking down security light, street light, hanger light, flood light and high mast lights of any type at any height fittings such asHPSV/HPMV/MH/LED light of 50 Watt/ 60 watt / 70/72 watt/ 90 watt/ 120 watt/ 150 watt/ 200 watt and 300 watt of any make etc. AC 230 volts any wattage from pole/wall roof top/hanger roof including washing/cleaning of perplex cover inspection for location of faultand replacing of defective spare/parts required for smooth functioning, tightening of electric connection and assembling and reconnecting all as per site requirment complete all as specified and directed. Note: Defective spare/ part of relevant light fitting shall be measured and paid separately under relevant item as supply only. |
| 32 | Supply only LED electronic driver/adaptor/SPDfor40-60 watt LEDsecurity light fitting existingmake complete all as specified and directed. |
| 33 | Supply only LED electronic driver/adaptor/SPDfor70/72 watt LEDsecurity light fitting existing make complete all as specified and directed. |
| 34 | Supply only LED electronic driver/adaptor/SPDfor90 watt LEDsecurity light fitting existing make complete all as specified and directed. |
| 35 | Supply only LED electronic driver/adaptor/SPDfor60-150 watt LEDflood light fitting existing makecomplete all as specified and directed. |
| 36 | Supply only LED electronic driver/adaptor/SPDfor200-300 watt LEDflood light fitting existing make complete all as specified and directed. |
| 37 | Supply only PCBA (printed circuit board assembly) with thermal padand lens for LED street light fitting existing capacity/makecomplete all as specified and directed. |
| 38 | Supply only PCBA (printed circuit board assembly) with thermal pad and lens for LED flood light fitting existing capacity/make complete all as specified and directed. |
| 39 | Taking down old unsv Prestressed Concrete LT pole and supply and erection of Prestressed Concrete LT pole 9.0 mtr long in true vertical position 102x172 mmm at top and 102 x 279 mm at bottom class-10 incl providing black and white strips with synthetic enamel paint 30 cm each alternate upto 1.5 mtr above the coping of pole starting with black stripcomplete all as specified & directed. Note:- (i) Earth work and PCC shall be measured and paid seperately.(ii) Description as per direction of Engineer-in-Charge will be printed on each pole without any extra cost. |
| 40 | Taking down old unsv Steel tubular LT pole and supply and erection of steel tubular swaged poles 9.0 mtr long complete with cast iron base plate, finial taper plug, bolts,nuts and screws as specified type 410 SP-31, providing synthetic enamel aluminium paint over one coat of red oxide primer and black and white strips with synthetic enamel paint 30 cm each alternatively upto 1.5 mtr above the coping of pole starting with black strip complete all as specified & directed.Note:- (i) Earth work and PCC shall be measured and paid seperately.(ii) Description as per direction of Engineer-in-Charge will be printed on each pole without any extra cost. |
| 41 | Supply and fixing in replacement ofstay assembly complete with all accessories, such as stay plate 230x230x6 mm, stay rod 215 cm long and 16 mm dia with nuts incl GI bow turn buckle, GI stay wire, Loop type insulator etc all as per electrical plate No 1 or SSR part 1 and as directed incl taking down old unsv stay assycomplete all as specified & directed.Note- The quoted rate shall include the cost of loop type insulator, stay clamps, excavation, PCC, stay wire, stay bow, turn buckle, nuts etc. complete. |
| 42 | Material and labour in replacement of Loop insulator Porcelain, vitreous white/brown/green insulator including one galvanized mild steel spindle, two galvanized iron washers and one galvanized iron nut, large size with overall dimensions 90mmx 140mm, clearance of hole 25.5 mm complete all as specified and directed. |
| 43 | Material and labour in replacement for shackle type porcelain vitreous white or brown insulator including GI straps washers, insulator bolts and nuts for working pressure 1100 volts, 75 mm hight, 90 mm dia, section of strip 30mmx3mm & dia of bolt 12 mmcomplete all as specified & directed. |
| 44 | Taking down old unserviceable ACSR conductor and material and labourforaluminium conductor steel reinforced (ACSR) conductor of size 6/1 x 2.59(Weasel) and6/1 x 2.11 (Squirrel) or other existing type conductor ISI marked for LT over head lines on poles including stretching, tightining of poles insulator with winding wire of suitable size with insulator/strechingof ACSR conductor complete all as specified and directed. |
| 45 | Taking down old unserviceable cross-arms and material and labour for cross arms,bracings, supports, clamps and back plates fabricated from structural steel section incl nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as specified and directed. |
| 46 | Supply and fixin replacement indoor/outdoor end terminationjoint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 35-120 Sqmmcomplete all as specified & directed |
| 47 | Supply and fixin replacement indoor/outdoor end terminationjoint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 150-240 Sqmmcomplete all as specified & directed |
| 48 | Supply and fix in replacement indoor/outdoor end terminationjoint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 300-400 Sqmmcomplete all as specified & directed |
| 49 | Supply and fixin replacement straight through joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 35-120 Sqmm complete all as specified & directed. Note: The quoted rate shall include the earth work, RF and removal of soil etc. |
| 50 | Supply and fixin replacement straight through joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 150-300 Sqmmcomplete all as specified & directed. Note: The quoted rate shall include the earth work, RF and removal of soil etc. |
| 51 | Dismantling andtaking down old u/searthing and provision of earthing complete with galvanisedearth plate electrode 600mm x 600mmx 6.00mm thick surrounded by charcoal and salt, burried directly in ground vertically in a pit of depth not less than 2.25m belowground level with top edge of the earthplate not less than 1.5m belownormal groundlevel, connected to 25x4 mm GI strip earth lead by means of bolts, nuts, checks nuts and washers made out of galvanized iron or steel, earth wire protected by galvanized steel pipe 40mm bore medium grade and connected to main switch or main control board all as shown in electrical plate No.3 of SSR Part-I & including necessary excavation and earth work. The rate also include charcoal & salt in alternate layers, 20mm bore GI pipe medium grade for watering and 40mm bore GIprotection pipe (light grade), funnel, wire mesh,cast iron cover andframe etc including testing on completion complete all as specified and directed. Note : (i) The quoted rate shall include the cost of earth work, GI pipe for watering, GI protection pipe, funnel, wire mesh, RCC cover, etc. complete. RCC cover shall be 50mm thick in 1:2:4 type B-1 using 8mm bars @10cm c/c both way. (ii) The quoted rate shall include the cost of the earth pit covers to be conspicuously marked of plate with standgrouted in PCC. (iii) On testing after completion if the desired earth resistanceis more than 2Ώthe earthing will be redone at no extra cost. |
| 52 | All as per item Srl Item No. 51.00 here in before but for connected to galvanised earth lead wire of 4.0 mm dia by means of GI nuts bolts, check nuts and washers and connected to earthing test point drawn through 15 mm bore GI pipe medium grade for protection of GI earth lead wire including 20mm bore GI pipe medium grade for watering GI funnel. |
| 53 | Supply and fixing in replacement MCCB TPN 400 Amps, 415 Volts, 50 KA,4 pole , Ics=100% Icu, overload adjustable short circuit adjustable type incl connection complete all as specified and directed. |
| 54 | All as per Srl item No 53.00 here in before but MCCB TPN 250 Amps, 415 Volts, 25 KA, 4 pole complete all as specified & directed. |
| 55 | All as per Srl item No 53.00 here in before but MCCB TPN 200 Amps, 415 Volts, 25 KA, 4 pole complete all as specified & directed. |
| 56 | All as per Srl item No 53.00 here in before but MCCB TPN 125 Amps, 415 Volts, 16 KA, 4 pole complete all as specified & directed. |
| 57 | All as per Srl item No 53.00 here in before but MCCB TPN 100 Amps, 415 Volts, 16 KA, 4 pole complete all as specified & directed. |
| 58 | All as per Srl item No 53.00 here in before but MCCB TPN 63 Amps, 415 Volts, 16 KA, 4 pole complete all as specified & directed. |
| 59 | Material and labour for Detecting of fault in cable HT/LT with fault locator equipment which is capable to supply as per cable of HT/LT (11 KV/430 Volts) serviceable to cable including Straight throughjoint of size 70-300 Sqmmcomplete all as specified & directed.Note:- (a) HT fault which is detected through cable fault locator will only be paid under this item including transportation charges deemed to be included in the quoted rate. (b)Charge of cable fault locator and DG set, transportation charge deemed to be included in the quoted rate. (c) Earth fault locator will be provided by the contractor for even single HT fault and no delay on this account will be acceptable otherwise penalty will levied Rs. 500/- per hour. |
| 60 | Supply and fixing in replacement of LT line separators 1100 V grade PVC spacer to separate LT conductor from each other 5 line as per IScomplete all as specified & directed |
| 61 | All as per Srl Item No 60.00 here in before but 4 line complete all as specified & directed. |
| 62 | Re-streching of loose over head ACSR conductor of any type/GI wire and repair of the broken conductors andaddingnew length (if required) in placeof old and burnt conductor of any size on existing poles with proper sagging including winding with winding wirecomplete all as specified & directed. (Old conductor shall be reused where required for repairing broken length of conductor as directed by Engr-in-charge). |
| 63 | Trimming of Tree branches falls into OH lines of HT/LT & minimum clearance of 3 Mtrfrom branches ,proper shutdown will be taken and maintained in the register complete all as specified & directed |
| 64 | Material and labour in replacement of aluminium terminals (thimbles) after cutting the worn out/faulty cable end from LT pillar/panel box including necessary earth work for taking out the cable from loop line, returning, filling in and making cable lead by providing aluminium lugsincluding crimping with crimping tools in the existing LT cable 16 Sqmm 4 core upto 50 Sqmm & necessary connection complete all as specified and directed. |
| 65 | All as per Srl item No 64.00 here in before but size of LT cable 70 Sqmm 3.5 core upto 120 Sqmm 3.5 core complete all as specified and directed. |
| 66 | All as per Srl item No 64.00 here in before but size of LT cable 150 Sqmm 3.5 core upto 400 Sqmm 3.5 core complete all as specified and directed. |
| 67 | Material & Labour for excavator for cable digging in emergency during nights/ off working hours/days as required at site complete all as specified and directed. |
| 68 | Material & Labour for spray painting on complete LT panels/FeederPillar Boxes of any size and any type two coats of synthetic enamel aluminium paint on outer shell and inner shell over a coat of red oxide including standcomplete all as specified and directed. |
| 69 | Repair of LT panel of any type and anysize including replace of old unsv items such as busbar, insulaor, CT/PT coils, insulating sleaves, front and rear doors, door hinges, gland, lugs volt meter, ammeter, indicator, locking arrangement and internal copper wiring after cleaning of surface including removing rusted particles removing dust tightening nut, bolts welding complete all as specified and directed. Note: (i)Cost of marking description on the front door as per direction of Engr-in-Charge is incl in quoted rate. (ii)Cost of misc items like copper cable, lugs thimbles etc if required are included in quoted rates. (iii) Cost of welding works such ashinges, locking arrangement, door and angles are included in qouted rates. |
| 70 | Material & Labour for surface cleaning of LTsteel tubular poles9 mtrs long including removing rusted particles painting withtwo coats of synthetic enamelaluminium paint over a coat of red oxide including stand cross arms, bracing, supports,clamps eye hooks, security light bracket clamps etc providing black & white strips alternatively 30cm each from coping upto 1.5 mtr height starting with black strip using synthetic enamel paints incl repairing and painting on coping with cement base white paint complete all as specified and directed.Note: (i)The quoted rate shall includes marking of numbers on each LT pole as per direction of Engr-in-Charge.(ii)The quoted rates shall including the repairing of coping with cement / PCC |
| 71 | Material & Labour for cement base paint for Prestressed Concrete pole 9 mtr includingblack & white strips alternatively 30cm each from coping upto 1.5 mtr height starting with black strip using synthetic enamel paint and painting with two coats of synthetic enamel aluminium paint over a coat of red oxide including cross arms bracing supports, clamps, eye hooks, security light bracket, clamp etc incl repairing and painting on coping with cement base white paintcomplete all as specified and directed.Note: (i)The quoted rate shall includes making of numbers on each LT pole as per direction of Engr-in-Charge.(ii)The quoted rates shall including the repairing of coping with cement / PCC |
| 72 | Material and labourfor spraying chemical (Round up) on area to remove unwanted vegitation/grass at various locationscomplete all as specified and directed. |
| 73 | Supply and fixing in replacement of on load change over switch with sheet steel Enclosure 415 V, 4 pole, 100 Amps capacity fixed on walls/MS frame/pole/LT panel for electric supply distribution between main and DG set incl necessary connection of cable from LT panels to change over switches complete all as specified and directed. |
| 74 | Supply and fixing in replacement of on load change over switch with sheet steel Enclosure 415 V, 4 pole, 200 Amps capacity fixed on walls/MS frame/pole/LT panel for electric supply distribution between main and DG set incl necessary connection of cable from LT panels to change over switches complete all as specified and directed |
| 75 | Supply and fixing in replacement of off load change over switch with sheet steel Enclosure 415 V, 4 pole, 100 Amps capacity fixed on walls/MS frame/pole/LT panel for electric supply distribution between main and DG set incl necessary connection of cable from LT panels to change over switches complete all as specified and directed. |
| 76 | Material and labour for Chemical spray (DC 2.26 contact cleaner) in container of 415 ml/300g for precision blended multipurpose product for prevents corrosion penetrates, lubricants, displaces and seals out moisture release rusted mechanisum cleanese etc complete all as specified and directed. |
| 77 | Supply and fixing in replacement of fabrication of Kiosk box made out of fibre material complete with TPN ,aluminium busbar and suitable for one number MCB (SP) including one No MCB (SP) 6 Amps 240 volts with glands for incoming & out going cable including fixing of flat iron clamps of size 20x4mm on PCC/Steel tubular pole complete all as specified and directed. Make: Havells/Sintex. |
| 78 | Supply and fix in replacement of MCB SP 6-32 Amps, 240 volt,10 KA \"C\" curveincluding all accessories complete all as specified and directed. |
| 79 | Supply and fix in replacement of MCB DP 16-40 Amps, 240 volt,10 KA \"C\" curveincluding all accessories complete all as specified and directed. |
| 80 | Supply & fixing in replacementof Automatic Street Light Control Switch with Infrared Sensor based NATURE SWITCH & Voltage Monitoring System (VMS). Three phase, 25 Amps per phase, MCB rating 32 Amp, max load 8-12 kw incl circuit copper wire 10 sq.mm.Nature Switch operation should be based on Natural Light Lux level. Required Illuminance Level for Switching ON is ≤ 60 Lux and for switching OFF ≥ 10 Lux. The Sensor should also have part night operation facility of min. 4 to max. 12 hrs. VMS should have Adjustable Over & Under Voltage Trip level and Protection against Phase Loss, Neutral Loss & Phase Reverse. The Sensor & VMS along with suitable Power Contactor(s) and Incoming-Outgoing MCBs should be enclosed in a pole/wall mountable Enclosure made of Rust Proof, Electric Shock Proof, Termite proof and FR grade SMC Junction box conforming to IP54. The circuit should also have provision for Manual Operation (i.e. By-Pass Option for both Sensor (NS-02) and VMS) complete all as specified and directed.Note :- (i) S S Nut bolts, clamp for fixing on poles/wall are included in quoted rates. (ii) The sensor must have the warranty of min of 2 years. (iii) The test certificate and warranty certificate must be provided by supplier. (iv) Cost of marking description on the box is incl in quoted rate. |
| 81 | All as per Srl item No 80.00 here in before but for single phase, 25 Amps per phase, MCB rating 40 Amp, max load 5-8 kw . |
| 82 | Supply and fix inreplacementof Lithium based Energy Efficient Integrated Solar Street Light of 24Watt” in Single FRP body with duly Polyurethane coating (Camouflage color) , encases with Monocrystalline Solar PV Panel of 53/55Wp , Lithium Battery 11.1/12.8V, 28.6AH with inbuilt BMS, IP 66, IK 08, High brightness W-LED(160-180lm/watt) lamp with Aluminum reflector for better light distribution , CRI >70, Color Temperature 5700K - 6500K, Microcontroller based charge controller cum driver, automatic dimming function ( first four hours at full brightness & rest of the time at lower light level with Microwave Sensor), Dusk to Dawn Operation, suitable to working temperature: (-) 10C to (+)55C, weight not more than 12-14kg with adjustable MS clamp suitable for pole/wall mounting etc complete as required. Protections: Short Circuit, overload, Reverse polarity and battery protections. Firm should provide Vital Parameters Test report from NABL accredited lab and should be of made in India with CE & ROHS compliant including tubular pole 6 mtr height with bottom base plate 200x200x12 mm , outdoor dia not less than 65 mm with heavy duty GI pipe or steel thickness 3mm and suitable arrangement to mount solar light as directed on pole including foundation PCC 1:3:6 type C-1using 20mm graded crushed stone aggregate and erection as per manufacturer drawing, providing synthetic enamel aluminium paint over one coat of red oxide complete all as specified and directed. Make : AXXON (AXN-24W)/ PHILIPS/ BAJAJ/ WIPRO |
| 83 | Supply & fixingin replacement of Integral LED Flood light Luminaries 100 Watts consisting of suitable number of LEDs andmounted on MCPCB high pressure die cast aluminium housing with sealed toughened glass cover with secondary optics lens,IP 66 protection suitable for mast light mounting, 5700K,LED efficiency >130 lm/Watt and system efficiency 110 lm/W , 240 Volts AC, 50 Hz, CRI>70% operating voltage range 160 V-270 V, Power factor> 0.95, working temperature range -10ºC to 50ºC,built in surge protection of more than 10 kV ,Confirm the tests from auth labs :LM79 & LM 80, incl proper fixing and testing of flood lights on 9/11 mtr long steel tubular pole and provide facility of power supply as suitable for maint work of light fittings incl make proper connection of new and existing light fittings complete with cutting , welding , drilling holes, nut bolts, washer complete all as specified and directed. |
| 84 | All as per Srl item No 83.00 here in before but for 150 Watts complete all as specified and directed. |
| 85 | All as per Srl item No 83.00 here in before but for 200 Watts complete all as specified and directed. |
| 86 | All as per Srl item No 83.00 here in before but for 300 Watts complete all as specified and directed. |
| 87 | Supply & fixingin replacement ofLED street light fitting60 watts made up of pressure die cast aluminium housing with high efficiency LEDs as lighting source and lens embedded ,toughened glass having TOP Opening seperate driver compartment with IP 66 protection and impact resistance of IK07 consisting of suitable number of LEDs with sealed toughened glass cover, 5700K,LED efficiency >110 lm/Watt and system efficiency 110 lm/W , 240 Volts AC, 50 Hz, CRI>70% operating voltage range 140 V-270 V, Power factor> 0.95,mains current 0.270A, working temperature range-10ºC to 50ºC,built in surge protection of more than 10 kV, better optics for uniform distrubution with multiple LEDs not less than 2 watt each and having optical grade polycarbonate lens with all accessories , suitable for side entry, pole mounting with bracket arm OD 40 mm, recommended mounting height with suitable inground reinforcement is 8 mtrs, Confirm the safety test as per IS 15885 part-2 from auth labs :LM79 & LM 80, incl proper fixing and testing of street lights on 9/11 mtr long steel tubular poleincl make proper connection of new and existing light fittings complete with cutting , welding , drilling holes, nut bolts, washer complete all as specified and directed. Note :- PVC heavy duty conduit pipe along with 3/1 run of 1.5/2.5 sqmm PVC insulated unsheathed/sheathed copper multistranded conductor from MCB box to streetshall be measured and paidfor separately. |
| 88 | All as per item ser No 87.00 here in before but for 70/72 Watts . |
| 89 | All as per item ser No 87.00 here in before but for 90 Watts . |
| 90 | Supply, installing, testing & commissioning in replacement ofoutdoor type cubical panel board of size 1.2mX1.2mX.5m,outer shell made out of3.15 mm thick CRCA sheet and inner shell made out of 2 mm thick CRCA sheet and MS angle section 50x50x6 mm mounted on PCC 1:2:4 type B-1 platform 60 cm aboveand 45 cm below the ground level,frame factory fabricated with front and back openable double door system and cable alloy(Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable/open ablewith arrangement of pad locking on both doors incl 2 no. of pad locks of three keys shall be used to make the outer shell completely vermin proof suitable for 3 phase 4 wire 415 Volt, 50 Hz, incl Copper bus bar of 600 A , tested at factory approved from CPRI factory fabricatedhaving modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction confirming to IS:61439/2011Part-1 andpart -2 type test certificate with not less thanIP-65and breaking capacity 65 KA comprising of the following :-(a) MCCB400 Amps, Amps 4 pole 415 Volts AC with thermal magnetic 50 KA, Ics=100%, Icu class-2 front face isolation with positive break indication with double break contacts with spreader and phase barrier complete all as directed. - 01 No(b) MCCB200 Amp, 415 volt, 4 pole, breaking capacity 25 KA ,(Outgoing)-02 Nos. (c) MCCB125 Amp, 415 volt, 4 pole, breaking capacity 25 KA , (Outgoing)-02 Nos(d) MCB32 Amp, 415 volt, TPN, breaking capacity 10 KA (Outgoing)-01 Nos(e) RYB indication LED type, 22.5 mm dia, protected with MCB SP 2 Amp showing 3 phase supply -03 Nos (f) Multimeter of accuracy class 1 having showing parameters of3 phase voltage ,current,fequency, PF, kW, kVA, kVAR, kWH - 01 No(g) Misc items like screws, cable tie, copper cable 1.5/2.5 Sqmm, cabe lugs, sleeves, cable glands etc complete are included in quoted rates. |
| 91 | Supply and installing, testing & commissioningin replacement of factory fabricated outdoor type feeder pillar board of size 700X600X500 mm , outer shell made out of3.15 mm thick CRCA sheet and inner shell made out of 2 mm thick CRCA sheet and MS angle section 50x50x6 mm mounted on PCC 1:2:4 type B-1 platform 60 cm aboveand 45 cm below the ground level,frame factory fabricated with front openable double door system and cable alley(Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable/open ablewith arrangement of pad locking on door01 no of pad lock of three keys shall be used to make the outer shell completely vermin proof suitable for 3 phase 4 wire 415 Volt, 50 Hz, tested at factory approved from CPRI factory fabricatedhaving modern fabrication and testing process followed by powder coated painting after 7-tank pre treatement control & power wiring with suitable size of copper conductor along with suitable gasket to make it dust/vermin proof and general construction confirming to IS:61439/2011Part-1 andpart -2 type test certificate with not less thanIP-56and breaking capacity 65 KA comprising of the following :-(a) MCCB 125 Amps TPN, 25 KA -01 No(b) Al busbar of capacity 200 Amps with colour coated heat shrinkable sleeve and suitable hole for out going connection - Set of four.(c) Misc items like screws, cable tie, copper cable 1.5/2.5 Sqmm, cable lugs, sleeves, glands etc complete are included in quoted rates. |
| 92 | All as per item ser No 91.00 here in before butsize 750X750X500 mm comprising of the following :-(a) MCCB 160 Amps TPN, 16 KA -01 No(b) Aluminium busbar of capacity 200 Amps with colour coated heat shrinkable sleeve and suitable hole for out going connection - Set of four.(c) RYB indication LED type, 22.5 mm dia, protected with MCB SP 2 Amp showing 3 phase supply with suitable CTs -03 Nos(d) Multimeter of accuracy class 1 having showing parameters of3 phase voltage ,current,fequency, PF, kW, kVA, kVAR, kWH - 01 No(e) Misc items like screws, cable tie, copper cable 1.5/2.5 Sqmm, cabe lugs, sleeves, cable glands etc complete are included in quoted rates.Notes for item Srl Item No.90.00 to 92.00 : (i) The quoted rate shall include minor items such as lugs, nuts & bolts, washers, top insulators, sleeves, provision of extra holes in bus bar etc.(ii)All internal wiring shall be done with suitable size of PVC insulated solid copper conductor FRLS cable conforming toIS-694. (iii) Panel drawing shall be got approved before placing of orderfrom Engr-in-Charge/GE.(iv) The bus connection for cable from main bus bar to outgoing MCCB will be connected through suitable rating bus bar strip type duly insulated. (v) Cable will be entered in panles through gland. (vi) Cost of marking description and matter on the front door as specified and directed by Engr-in-Charge is incl in quoted rate. |
| 93 | Material and labour in replacement for cable jointing kit for 11 KV (Earthed) grade cable for straight through coldshrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm complete all as specified and directed. |
| 94 | Material and labour in replacement for cable jointing kit for 11 KV (Earthed) grade cable for straight through coldshrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm complete all as specified and directed. |
| 95 | Material andLabour in replacement for cable end termination jointing kit HT 11 KV grade earthed system cold shrinkable outdoor type complete with jointing material suitable for HT XLPEcable 50-95 sqmm 3 core 11 KV grade earthed system complete all as specified and directed. |
| 96 | Material andLabour in replacement for cable end termination jointing kit HT 11 KV grade earthed system cold shrinkable outdoor type complete with jointing material suitable for HT XLPEcable 120-185 sqmm 3 core 11 KV grade earthed system complete all as specified and directed. |
| 97 | Material and labour in replacement of broken earth pit with RCC cover of size 300x300x300 mm madeof PCC 1:2:4 type B1 using 20 mm graded crushed stone aggregate, and earth pit cover made out of RCC 1:2:4 type B1, cover reinforced with 8 mm dia TMT bars @ 100 mm centre to centre both ways with handle made out of 8 mm dia bar, watering arrangement with funnel and wire mesh and including reconnecting of earth lead of any type with new nuts, bolts and washers as required at site with testing result complete all as specified and directed. |
| 98 | Repairing of existing unserviceable PCC coping of LT/HT pole by breaking completely and material and labour for PCC 1:2:4 type B1, (using 20mm graded crushed stone aggregate) of size 600X600X300mm including form work and applying two coats of cement base paint complete all as specified and directed. |
| 99 | Taking down old unserviceable ammeter with selector switch and supply and fixing new rotary type ammeter with selector switch, three phase, 5 Amps, Ammeter 0-300 Amps including making electrical connection complete all as specified and directed. |
| 100 | Taking down old unserviceable volt meter 0-500 volts with selector switch and supply and fixing new rotary type volt meter with voltage selector switch, three way, 2 Amps, 500 Volts including making electrical connection complete all as specified and directed. |
| 101 | Taking down old unserviceable Indicator any type any colour and supply and fixing new Indicator red/yellow/green including making electrical connection with suitable size of copper lugs duly crimped complete all as specified and directed. |
| 102 | Dismantling of brick work or stone masonary, precast cement concrete walling built in cement mortar including all quoins, arches, pillars etc. complete all as specified and directed. |
| 103 | Material and labour for brick work with sub class ‘B’ bricks burnt, straight or curved on plan exceeding 6 metre mean radius built in cement mortar (1:6), complete all as specified and directed. |
| 104 | Material and Labour for Brick work with sub class ‘B’ bricks (Except Bricks), straight or curved on plan exceeding 6 metre mean radius, built in cement mortar (1:6) complete all as specified and directed. Note:- The serviceable bricks obtained from Serial item No 102.00 Shall be used after removing mortar, cleaning the bricks with water, etc. |
| 105 | Taking down cement plaster on brick or stone walls, etc. including raking out joints, hacking for key, scrubbing downwith water, etccomplete all as specified and directed. |
| 106 | Material andlabour for 15 mm thick rendering in cement mortar (1:4)on surface of any description of brick or concrete and finished the surface even and fair using extra cement including preparation of new plastered surfaces of walls complete all as specified and directed. |
| 107 | Material and Labour for preparation and applying two coats of oil bound distemperon new plastered/old surface of wall complete all as specified as directed. |
| 108 | Material & labour for rough cast plastering over and incl 10 mm thick rendering in cement mortar 1:3 and while it is still in plastic state the roughcast mixture consisting of crushed stone or fine gravel aggregate (which is generally of size between 6 to 12 mm depending on the texture required) mixed with coarse sand and cement in the ratio of 1: 1: 1 shall be applied and finished even. The mix of cement and sand shall be made slightly wetter than normal for rendering to ensure that larger aggregates are thoroughly coveredcomplete all as specified and directed.Rough cast plaster shall be applied asspecified clause 14.22 of SSR Part-I . |
| 109 | Material and Labour for two coats of synthetic enemel paints on steel Surfaces exc 10cm girth over a coat of red oxidecomplete all as specified and directed. |
| 110 | Material & Labour for in replacement of steel nuts, bolts, washers of any size required at site complete all as specified and directed. |
| 111 | Supply and fixing in replacement of rolled mild steel plates (plain or chequered) channels, square cut or notched (ordinary and counter sunk)forming holes, with riveted, bolted or welded attachmentFe-290 (Gde E- 165)for existing LT panel doors/gates complete all as specified and directed. |
| 112 | Supply and fixing self-fusing Ethylene Propylene Rubber (EPR)based high-insulating voltage tape (sleeves) of width not less than 19 mm and thickness not less than 0.75 mm of any length to protectHT XLPE cable from moisture and current leakage complete all as specified and directed. |
| 113 | Supply and fixing in replacement of nature switch operation should be based on natural light lux level, required illuanance level for switching on is <30 Lux and for switching off >10 lux , the sensor should also have part night operation facility of min 4 hrs to max 12 hrscomplete all as specified and directed.Make:- Swadeep , Model nature switch -02(sensor) or equivalent as approved by GE. |
| 114 | Supply and fixing in replacement of contactor 3 pole 18 Amp in street light timer box coil operating voltage 230 volt complete all as specified and directed. Make- BCH/L&T or equivalent as approved by GE |
| 115 | Supply and fixing in replacement of contactor two pole 25/40 Amp in street light timer box coil operating voltage 230 volt complete all as specified and directed. Make- L&T/BCH or equivalent as approved by GE |
| 116 | Supply and fixing in replacement ofcontactor coil (230V)for MU series 25/40 Amps 2 pole contactorscomplete all as specified and directed. Make- L&T (Cat No CS90793) or equivalent as approved by GE |
| 117 | Supply and fixing in replacement ofcontactor coil (240V)for freedom series 18 Amps 3 pole contactorscomplete all as specified and directed. Make- BCH, Cat No CE15D1N-K or equivalent as approved by GE |
| 118 | Supply and fixing in replacement ofVMS (voltage monitoring series) in street light timer box, including all salient features such as selectabe under/over voltage trip levels, protection against phase loss & natural loss, protecotion against phase reversal and phase to phase unbalance (10%), voltage sensing principle and LED indications for power and fault conditions complate all as specified and directed. Make- L&T, Cat No SM500 or equivalent of C&S/ Siemens |
| 119 | Taking down old unserviciable board and supply and fixing of Retro reflective sign board type route indicator of size 600 x 750 sqmm made of ACP sheet of 3mm thick ACP sheet shall be fixed on MS frame with legs of MS angle section 35mm X 35mm X 4mm grouted in PCC 1:3:6 type C-1, 750mm above the ground level and 600mm below the ground level. The background of board to be provided with red colour, letters and border with white retro reflective tape. Same description shall be mentioned on both sides of ACP sheet complete all as specified and directed.NOTE:- (i) Excavation, earth work, PCC, nuts, bolts, fastners, paint on MS frame and legs shall be included in quoted rates by contractor.(ii) The size of letters and description shall be all as per sample approved by Engr-in-Charge. |
| 120 | Material & Labour for maintenance, servicing and cleaning of LED solar lights andsolar panels every month, checking of all components including replacement of old unsv items such as on/off button, dry cell, solar panelscomplete all as specified & directed. Note : (i)Cost ofall tools, hydra and ladder required for maintenanne of solar lightis incl in quoted rate (ii)Cost of misc items like nuts, bolts, thimbles, insulating sleaves etc if required are included in quoted rates. |
| 121 | Supply, installing, testing & commissioning of Ceasefire Quick Resonse system Clean Agent Gas (HFC 236 fa based Fire Suppression System 2Kg Cylinder - with 20 Mtr Heat Sensing Tube,For Open Cabinet with Forced airflow, System operating pressure 15 bar at 20⁰C ,System operating temperature range : -20⁰C to +60⁰C,The sensing tube must be made of a special modified Polyamide (PA) in Black color with an outer diameter of 6mm,Tube’s technical specifications should be certified by the OEM to its own specifications,The complete system should be tested & Certified to Standard LPS 1666:Issue 1.0 by LPCB approved with complete test reports, Complete system should be tested & Certified to Standard LPS 1666:Issue 1.0 by LPCB for following type of enclosures - Enclosed,Open with Natural airflow, Open with Forced Airflow compete all as specified and directed. |
| 122 | Supply and fix multi-function meter 4 Wire / 3 Phase, auxiliary Supply: 175 – 265V AC, Voltage Measurement: 20 – 300V AC (L – N) / 35- 485V AC (L-L), current measurement: 50mA – 6.5A (Rated current 5A) , Frequency 50 Hz, electrical instrument installed in panels; this device measures various electrical parameters such as voltage, current, power factor and active power including making electrical connection including taking down existing complete all as specified and directed. |
| 123 | Supply and fix in replacement of bracket made out of GI tubing 40 mm dia single piece not welded, bended at proper angle, light grade 1.5 mtr long including painting with aluminium paint over one coat of red oxide primer to the bracket including 1.0sqmm 3.0 core flexible copper cablein PVC conduit with clamp from juction box to connecter of street light fitting complete all as specified and directed. |
| 124 | Supply and fix in replacement of MS clamp suitable for holding street light bracket on steel/PCC polemade out of 40 mm x6 mm thick flat iron with M.S nuts bolts 50 mm long 10 mm dia-3 Nos with flat washer 3mm thick -02 No for each includingpainting with aluminium paint over one coat of red oxide primer to the M.S clamps complete all as specified and directed. |
| 125 | Note:-Amount of credit ofRs. 111387.00 for retrieved materials is mentioned in Schedule of Credit of tender documents in pdf form which will be deducted offline while acceptance of tender. |