| Sl. No. | Item Description |
| 1 | SUPPLY - 220 KV GIS SUBSTATION AT GOKUL NAGAR |
| 2 | SUBSTATION EQUIPMENTS |
| 3 | Auto Transformer: |
| 4 | Auto Transformer: 220/132 kV, 160 MVA Transformer with all accessories and 5% extra oil in non-returnable drums |
| 5 | RTCCPanel fitted with Transformer Monitoring cumTap changer controlSystem (TCS)alongwithassociatedacessoriescompletein all respect. (For 160 MVA Trfs.) |
| 6 | Power Transformer: |
| 7 | PowerTransformer: 132/33kV, 50 MVATransformer (oil filled)with all accessories and 5% extra oil in non-returnable steel drums |
| 8 | RTCCPanel fitted with Transformer Monitoring cumTap changer controlSystem (TCS)alongwithassociatedacessoriescompletein all respect.(For 50 MVA Trf.) |
| 9 | 220 kV Indoor GIS Switchgear Equipments |
| 10 | 245kV, 1600A, SF6 gas insulated Transformer bay module each comprising of SF6 gas insulated circuit breaker, current transformer, bus-bar disconnectors with common earthing switch, line disconnector with safety earthing switch, SF6 gas monitoring system for complete bay, local control cubicle, SF6 Gas Insulated terminal connection for connecting Auto Transformer (Air/ SF6) with GIS through gas insulated interconnection bus (rating 1600A) complete with all accessories. Interconnection of GIS to Outdoor Auto Transformers through 245 kV SF6 Gas Insulated bus inteconnection Duct (Suitable length as per Layout for each of 3-phases and rated current of module) consists of SF6 gas insulated bus interconnection duct, outdoor SF6-Air Terminations (3 Single Phase) with terminal connector suitable for double AAC Tarantulla, support structures with suitable clamp/ connectors etc. Other accessories/items if any to complete transformer bay module alongwith SF6 gas insulated bus interconnection duct and terminations as indicated in the SLD/ Layout of substation and as per technical specifications. |
| 11 | 245kV, 1600A, SF6 gas insulated Feeder bay module (Type A)each comprising of SF6 gas insulated circuit breaker, current transformer , bus-bar disconnectors with common grounding switch, line disconnector with safety grounding switch, high speed fault making grounding switch, SF6 gas monitoring system for complete bay, local control cubicle, SF6 Gas Insulated terminal connection for connecting Incoming overhead line terminal equipments (Air/ SF6) with GIS through gas insulated interconnection bus (rating 1600A) complete with all accessories. Interconnection of GIS to overhead line terminal equipments through 245 kV SF6 Gas Insulated bus inteconnection Duct (Suitable length as per Layout for each of 3-phases and rated current of module) consists of SF6 gas insulated bus interconnection duct, outdoor SF6-Air Terminations (3 Single Phase) with terminal connector suitable for Single AAC Tarantulla, support structures with suitable clamp/ connectors etc., if any to complete feeder bay module as indicated in the SLD/ Layout of substation and as per technical specifications. |
| 12 | 245kV, 1600A, SF6 gas insulated Feeder bay module(Type B) each comprising of SF6gas insulatedcircuit breaker, current transformer , bus-bar disconnectors with common grounding switch, line disconnectorwithsafetygroundingswitch,highspeed faultmaking groundingswitch,surge arrestors, PT, SF6gas monitoringsystem for complete bay, local control cubicle, gas insulated terminal connection for connecting XLPE cable with cable termination enclosureand other accessorieswithGISetc. tocompletefeeder bay module as indicated in the SLD/ Layout of substation and as per technical specifications. |
| 13 | Double Bus Arrangement, 245kV, 3 Single Phase, SF6 gas insulated metal enclosed 2500A bus bars running along the length of the switchgear to interconnect each of circuit breaker bay module. Each bus bar set shall be complete with voltage transformer complete disconnector with safety earthing switches, local control cubicle (if required), SF6 gas monitoring system etc. for the complete bus as indicated in the SLD/ Layout of substation and as per technical specifications. |
| 14 | 245kV, 2500A, SF6 gas insulated Bus Coupler Bay Module comprising of SF6 gas insulated circuit breaker, current transformer, disconnectors with safety earthing switches, Local control cubicle, SF6 gas monitoring system for complete bay etc. as indicated in the SLD/ Layout of substation and as per technical specifications. |
| 15 | 132 kV Indoor GIS Switchgear Equipments |
| 16 | 145kV, 1250A, SF6 gas insulatedTransformer bay module each comprising of SF6gas insulated circuit breaker, current transformer, bus-bardisconnectorswithcommonearthingswitch,line disconnector with safety earthing switch, SF6gas monitoring system for completebay, localcontrolcubicle,SF6Gas Insulatedterminal connection for connecting Power Transformer (Air/ SF6)with GIS through gas insulatedinterconnectionbus (rating1250A)complete with all accessories. Interconnection of GIS to Outdoor Power Transformersthrough145 kVSF6 GasInsulatedbus inteconnection Duct (Suitable length as per Layout for 3-phases and rated current of module) consistsofSF6gas insulatedbus interconnectionduct, outdoor SF6-AirTerminations(for3-Phases) with terminal connectorsuitable for 50 mm Al Pipe, support structureswith suitable clamp/ connectorsetc.Other accessories/items ifany tocomplete transformer bay module alongwithSF6 gas insulatedbus interconnectionductand terminationsas indicatedinthe SLD/Layout ofsubstationand as per technical specifications. |
| 17 | 145kV, 1250A, SF6gas insulatedTransformer bay module each comprising of SF6gas insulated circuit breaker, current transformer, bus-bardisconnectorswithcommonearthingswitch,line disconnector with safety earthing switch, surge arrestors, SF6gas monitoringsystem for completebay, localcontrolcubicle,SF6Gas Insulated terminalconnection forconnecting PowerTransformer (Air/ XLPE) with GIS through XLPE cable with cable termination enclosure and other accessories etc. to complete transformer bay moduleas indicatedinthe SLD/Layout ofsubstationand as per technical specifications. |
| 18 | 145kV,1250A, SF6gas insulated Feeder bay module each comprising of SF6gas insulatedcircuit breaker, current transformer , bus-bar disconnectors with common grounding switch, line disconnectorwithsafetygroundingswitch,highspeed faultmaking groundingswitch,surge arrestors, PT, SF6gas monitoringsystem for complete bay, local control cubicle, gas insulated terminal connection for connecting XLPE cable with cable termination enclosureand other accessorieswithGISetc. tocompletefeeder bay module as indicated in the SLD/ Layout of substation and as per technical specifications. |
| 19 | Double BusArrangement, 145kV, 3Phase,SF6 gas insulated metal enclosed 2500Abus bars running along the length of the switchgear to interconnect each of circuit breaker bay module. Each bus bar set shall be complete with voltage transformer complete disconnector with safety earthing switch, local control cubicle (if required),SF6gas monitoringsystem etc. for the completebus as indicated in the SLD/Layout of substation and as per technical specifications. |
| 20 | 145kV, 2500A, SF6gas insulated Bus Coupler Bay Module comprising of SF6gas insulated circuit breaker, current transformer, disconnectorswithsafetyearthingswitches,Localcontrolcubicle, SF6gas monitoring system for complete bay etc. as indicated in the SLD/ Layout of substation and as per technical specifications. |
| 21 | 33 kV Indoor GIS Switchgear Equipments |
| 22 | MetalcladDoubleBusIndoor GIS SwitchboardIncluding2No. IncomerTransformerFeeders, 8 No.OutgoingFeeders and 1No. bus-Coupler (as per SLD) alongwith all associated accessories CTs. PTs, Control Cubicle and Complete with the Control & Protection schemes [ 36 kV, 2000A, 31.5kA Class] alongwith 0.2 S class AC Static HT-TVM TOD type Energy Meter |
| 23 | CableTermination/PlugforterminatinginMetalcladswitchgear panels for 6 Nos. of Outgoing Feeder panels (for 2 Nos. 3-Phase Outgoingcablecircuitineach)fromeach (Normallycablesizesis 300 Sq. mm ormore andexactsizeshallbe decided withthe distribution company during detailed engineering) |
| 24 | Suitable Capacity EOT Crane for GIS Hall/ Building |
| 25 | Ventilation system for GIS Hall/ Building (as per technical specification) |
| 26 | 33 kV XLPE Cables & Accessories |
| 27 | 3 C, 95 Sq. mm. Al., 33 kV XLPE Cable with Suitable Outdoor & Indoor Terminations [3+3] for connecting the HV side of Substation Transformer to O/G of 36 kV Metal Clad GIS Switchgear |
| 28 | 1C, 630 Sq. mm, Al., 33 kV XLPE Armoured Cable alongwith accosciated accessories and required material as per laying method adopted etc. (This include 12 lengths of cable with suitable Outdoor [12+12] end Terminations) |
| 29 | C&R Panels & SAS system (Complete in all respect, refer Section-V A, B, Part-III, Volume-II) |
| 30 | Control Panel for 220 kV Transformer (220 kV Side) Type: SAS-THCB |
| 31 | Relay Panel for 220 kV Transformer (for both HV & MV) Type: SAS-THRB |
| 32 | Control Panel for 220 kV Feeder Type: SAS-FCB |
| 33 | Relay Panelfor 220 kV Feeder Type: SAS-FRB |
| 34 | Control Panel for 220 kV Bus Coupler Type: SAS-BBCB |
| 35 | Relay Panel for 220 kV Bus Coupler Type: SAS-BCRB |
| 36 | 220 kV Busbar Protection scheme Relay Panel Type: SAS-BBRB |
| 37 | Control Panel for 220 kV Transformer (132 kV Side) Type: SAS-TLCB |
| 38 | Relay Panel for 220 kV Transformer (132 kV Side) Type: SAS-TLRB |
| 39 | 132kV C&R Panel Type SAS-FCA |
| 40 | 132kV C&R Panel Type SAS-FRA |
| 41 | 132kV C&R Panel Type SAS-BCRA |
| 42 | 132kV C&R Panel Type SAS-TCRA |
| 43 | 132kV Busbar Protection scheme Relay Panel Type SAS-BBRA |
| 44 | Substation LAN Commnication/ Monitoring Infrastructure |
| 45 | Substation Network Panel Type SAS-NW |
| 46 | Substation Network Panel Type SAS-FN |
| 47 | Substation Auxiliary Monitoring Panel Type SAS-SAMP |
| 48 | Station HMI [Industrial grade Computer with Approx.21\"TFTmonitor as per specification requirements] |
| 49 | StationHMI (HotStandby)[Industrialgrade Computer with Approx. 21\"TFTmonitor as per specification requirements] |
| 50 | HMIView Node[Industrial gradComputerwith Approx. 21\"TFT monitor as per specification requirements] |
| 51 | DRWorkStation[IndustrialgradeComputer withApprox. 21\"TFT monitor as per specification requirements] |
| 52 | A3 Size Color Laser Printer |
| 53 | Dot Matrix Printer |
| 54 | One Remote WorkstationwithHMI[Industrialgrade Computer with 21\"TFTmonitoras per specificationrequirements]& LaserPrinter (A4 Size) for RCC |
| 55 | Hardware Gateways(for data transmission to RCC& SLDC) |
| 56 | Modems (both sendingand ReceivingEnd) forcommunicationto RCC& SubSLDC[if required as Communication Equipments are proposed] |
| 57 | Software:Applicationas wellas System Softwareas per specificationrequirementsforvarioushardware elementsfor meeting of functional requirement of the specification. |
| 58 | Substation LAN Commnication Infrastructure |
| 59 | Other Items: |
| 60 | Fiber optic cables, connectors, ethernet cables, jack panels connectors, patch cords etc. for completing the substation LAN as per specification requirements. |
| 61 | Trsansducers, Sensors etc. (if not considered in the respective equipment/ items) for accumulating monitoring data as per the specification requirements for new and existing switchyards. |
| 62 | Inverter (3 kVA Capacity) to be operatable on 230VAC and 220 VDC as per availability of supply (Normally on AC) |
| 63 | Inverter (1 kVA Capacity) to be operatable on 230VAC and 220 VDC as per availability of supply (Normally on AC) |
| 64 | 132kV XLPECable & Termination for 132 KV Side of 220/132 KV, 160 MVA Transformer |
| 65 | 1200Sq.mm 132kV XLPE Cable |
| 66 | 132kV Outdoor CableTerminationfor XLPEto Air Terminationon 132 KV Side of 220/132 KV Auto Transformer |
| 67 | 132kV GIS Termination for XLPE Cable |
| 68 | SolidbondingLinkboxwithLink plates,bonding & grounding cable complete with other associated accessories for 1-phase |
| 69 | Instrument Transformers |
| 70 | 245 kV CVT (1 Ph) |
| 71 | Surge Arresters |
| 72 | 220kV classof 198kv rating LAs with grading ring discharge counter with milli ammeter |
| 73 | 132kV classof 120kv rating LAs with grading ring discharge counter with milli ammeter |
| 74 | 33 kV classof 30 kv rating LAs |
| 75 | LT Substation Transformer |
| 76 | 33kV/415V, 630 kVA station transformer complete with all accessories, fittings, terminal connectors etc as specified filled with transformer oil |
| 77 | Batteries & Battery Charger |
| 78 | Batteries (Sizing shall be as per requirement of technical specification) |
| 79 | 220 V [Min. 400 AH] |
| 80 | 48 V [Min. 360 AH] |
| 81 | Battery Charger System |
| 82 | 220 V Float and Boost |
| 83 | 48V Float and Boost |
| 84 | Lighting System |
| 85 | Outdoor Lighting & other Works |
| 86 | Lighting Fixture Type -SF2 as per Specification |
| 87 | Lighting Fixture Type -EEC2 as per Specification |
| 88 | Lighting Fixture Type -SF1 as per Specification |
| 89 | Lighting Fixture Type -EEC1 as per Specification |
| 90 | Emergency Lighting Type-PF |
| 91 | Type-RO, 15A, 240V: Outdoor Receptacle 2 pole, 3-pin type |
| 92 | Type-RP, 63A, 415V : Interlocked switch socket outdoor Receptacle |
| 93 | Hot Dip Galvenized Octogonal Lighting Poles (12 m) |
| 94 | Street Lighting Type-EEA for mounting on above Poles |
| 95 | Sub-Lighting Boxes/Panels Type -SLP at Lighting Mast complete with all controgears and accessories, items etc. |
| 96 | Lighting PanelType ACP-3 as per technical specification |
| 97 | Indoor Lighting & Other Works |
| 98 | Electrification |
| 99 | Electric Fitting (if not covered under Civil Works) with PVC. Conduit, Junction Boxes, pull out boxes, copper wiring, Modular Switchboards, Modular Switches, GI Wire (16SWG) etc. for control room, GIS Hall and administrative office building as per the requirements of the specifications |
| 100 | Illumiation |
| 101 | Lighting fixtures and Receptacles (including accessories/ materials etc. as per requirement alongwith complete accessories andmounting arrangements) |
| 102 | Indoor Lignting Panels |
| 103 | Lighting Panel (Indoor)Type ACP-1 as per technical specification |
| 104 | Lighting Panel (Indoor)Type DCP as per technical specification |
| 105 | Wall mounted fans Approx. 400 mm sweep |
| 106 | Ceiling Fan - Approx. 1400mm sweep with electronic Step regulator |
| 107 | Exhaust Fans |
| 108 | Fire Fighting System |
| 109 | NitrogenInjectionFireProtectionSystemfor160 MVA AutoTransformer complete in all respects. |
| 110 | NitrogenInjectionFireProtectionSystemfor50 MVA PowerTransformer complete in all respects. |
| 111 | Fire Fighting equipment with necessary mounting stands/ fixtures. |
| 112 | DCP Type |
| 113 | i) 5 Kg. |
| 114 | ii) 10 Kg. |
| 115 | Carbon di oxide type – 6 Liters. |
| 116 | Foam Type- 9 Liters |
| 117 | Sand type |
| 118 | i) GI Buckets 9 liters capacity |
| 119 | ii) Steel Stands for four buckets |
| 120 | Fire Detection and Alarm System |
| 121 | Siren along with all accessories as specified in technical specification |
| 122 | Microprocessor based Fire Detection & Alarm System as specified in technical specification |
| 123 | Photo-electric Detectors, Smoke Detectors, Heat Detectors, Linear Heat SensingCables,ManualCallPointsetc. ControlRoom, GIS Hall, Office Building, Store, Testing Laboratory etc. |
| 124 | Power & Control Cables for fire detection & alarm system |
| 125 | Air Conditioning System |
| 126 | High Wall Split AC units of 2 TR Capacity complete with Indoor, Outdoor Units and required accessories, Stablizers etc. |
| 127 | Substation Structures/Supports & Switchyard Erection |
| 128 | 220 kV Side Works: |
| 129 | 220 kV Line Bays: Interconnection of SF6-Air Bushing, LA,CVTwith Single AAC Tarantulla, clamps, connectors etc. as per Substation Layout arrangement and specification requirements |
| 130 | 220 kV Transformer Incomer Bays: Interconnection of SF6-Air Bushing, LA, BPI and Auto Transformer HV Bushing with double AAC Tarantulla conductor clamps, connectors etc. as per Substation Layout arrangement and specification requirements |
| 131 | 132 & 33 kV Side Works: |
| 132 | 145kV Transformer Incomer Bays (for 160 MVA TRf.):145kV GISInterconnections for Transfomer Bay complete with all necessary enclosure support, clamps, connectors, other accessories for successful connection to GIS Switchgear as per Layout of the substation. |
| 133 | 145kV Equipment/SwitchgearInterconnections for TransfomerBay (for 50 MVA Trf.) Interconnection of SF6-Air Bushing, LA, BPI and Power Transformer HV Bushing) [Complete with Three Phase Al. (50mm.Size) tubular conductor Clamps (rigid/flexible /expansion type), Connectors, Straight/V/Y Taps, nut- bolts and other accessories] as per Layout of the substation. |
| 134 | 33kV TransformerBay (fromPower TransformerLV Terminalsto SA,Isolator/PI for CableTermination) [Complete withThree Phase Al. (50 mm.Size) tubular conductor, Clamps (rigid/flexible/expansion type),Connectors,Straight/V/YTaps,nut-boltsandother accessories] as per Layout of the substation. |
| 135 | Tubular Support for Equipments [Complete in all respect with all accessories such as nut & bolts, washers, foundation bolts etc.] |
| 136 | 220 kV Side |
| 137 | CVT |
| 138 | Surge Arresters (Height as required) |
| 139 | Post Insulator Stack (Height as required) |
| 140 | 132 kV Side |
| 141 | 132 kVCable Termination (XLPE to Airtermination forAuto Transformer) |
| 142 | Surge Arresters (Height as required) |
| 143 | Post Insulator Stack (Height as required) |
| 144 | 33 KV Isolator: |
| 145 | Isolators (3 Phase) with Single Earth Switch |
| 146 | LATTICE STRUCTURES (excluding CB Structure) including all nut-bolts, step nut& bolts, spring washers, foundation bolts etc. |
| 147 | LightningCumLightingMasts. ApproximateUnitWeightAppox3.5 MT for each Mast |
| 148 | Galvanized Steel Gantry Structure (220 kV Side) alongwith nut-bolts, washers, foundation bolts etc. for termination of 220 kV Lines( 1 Nos.) and 220/132 KV Transformrs (2 Nos.) as per layout arrangement of the specification |
| 149 | 33 kV Side: |
| 150 | 33 kV XLPE Cable Termination support structure for Connecting to 33 kV Side of 132/33 kV Transformer including 33 kV Class of 30 kV rating LAs (3 Nos.), Supporting PI String (3 Nos.),nut bolts, fixing accessories etc. as per drawing appended in Section-IV of specification |
| 151 | Post Insulators |
| 152 | 245 kV Class Post Insulator Stack |
| 153 | 145 kV Class Post Insulator Stack |
| 154 | 36 KV Class Post Insulator Stack |
| 155 | Other Steel Structures/ members to be designed/ provided by the bidder for the project [Various items such as Galvenized/ Mild Steel Channels, Angles, Plates, round, joist, Hot dip galvenized Nut-Bolts, Electro Galvenized Spring Washersetc. considered for this component of price schedule] [ This shall also include the steel to be used in the civil works excluding reinforcement] |
| 156 | AC Distribution Boxes (Outdoor Type) |
| 157 | Outdoor AC Distbibution Box (Double Front type) |
| 158 | Marshalling KIOSK/box |
| 159 | Conduits, Cable Trays, Cable Tags, Cable Racks & Supports, Cable Glands, Cable Lugs, Gland Plates, Junction Boxes [Excluding the conduits, junction boxes etc. required for electrical & Lighting fittings/fixtures installation in GIS and control room building] |
| 160 | Isolators |
| 161 | Horizontal double break (HDB)motoroperated 33kV isolator complete with all fittings including post insulators, accessories, terminal connectorsandall otheritems (asspecified in technicalspecificationfor2000 AHDBisolatorwithsingle earth switch) |
| 162 | LT Switchgear |
| 163 | LT AC Main Panel |
| 164 | LT AC Distribution Board |
| 165 | Main Lighting Distribution Board |
| 166 | Emergency Lighting Distribution Board |
| 167 | 220VDCDB |
| 168 | 48V DCDB |
| 169 | Earthing System |
| 170 | 40 mm Dia MS Rod |
| 171 | 40 mm dia 3000 mm long MS rod (earth electrodes) with/without test links, RCC pits, C.I .cover hinged at C.I. frame alongwith all associated civil works |
| 172 | 40 mm dia, 3000 mm long GS pipe electrodes with test links and treated earth pits with C.I. cover hinged to C.I. frame alongwith all associated civil works |
| 173 | 3m, 20 mm Dia MS Rod Electrode |
| 174 | 3m, 40 mm Dia MS Rod Electrode |
| 175 | 3m, 42 mm Dia Safe Earthing Electrodes |
| 176 | 3m, 60 mm Dia Safe Earthing Electrodes |
| 177 | 75X12 mm GS Flat |
| 178 | 50X6 mm GS Flat |
| 179 | 50 X 6 mm MS Flat |
| 180 | 25 X 3 mm GS Flat |
| 181 | 50 X 6 mm Copper Flat (for GIS Switchgear Sceening, Sheilding and Earthing) |
| 182 | 3 m, 25 mm Copper Rod |
| 183 | Earth Enhancing Compound for treated pits as above and other requirement as per specification |
| 184 | 1.1kV Grade PVC insulated Al. conductor FRLS power cables and copper conductor armoured FRLS control cables [Excluding the wiring required for electrical & Lighting fittings/fixtures installation in GIS and control room building] |
| 185 | Power Cables(XLPE) |
| 186 | 1Cx630 sq.mm |
| 187 | 3.5Cx300 sq.mm |
| 188 | Power Cable(PVC) |
| 189 | 1Cx150 sq.mm |
| 190 | 3.5Cx70 sq.mm |
| 191 | 3.5Cx35 sq.mm |
| 192 | 4Cx16 sq.mm |
| 193 | Control Cable (PVC) |
| 194 | 2Cx6 sq.mm |
| 195 | 4CX4 sq.mm. |
| 196 | 4CX6 sq.mm. |
| 197 | 2Cx2.5 sq.mm |
| 198 | 5Cx2.5 sq.mm |
| 199 | 7Cx2.5 sq.mm |
| 200 | 10Cx2.5 sq.mm |
| 201 | 14Cx2.5 sq.mm |
| 202 | 19Cx2.5 sq.mm |
| 203 | 27Cx2.5 sq.mm |
| 204 | Optical Line Terminal Units |
| 205 | 220 kV GSS Gokulpura End (220 kV Side) |
| 206 | OLTE equipment consisting of fully wired cabinet with base 19\" equipment rackwith control synchronization, Alarm & Power supply cabinet-1 No, Central Processing card-CPU-2 no power supply unit-48VDC-2 No, OLTE-4 port STM-1(1SSMbps Card)-1 No, SEP duplex LC connector for OLTE Card-4 No, OFC Patch Cords-20M -8 No, 8Port-2w/4w E&M Interface card- 1 No, 4 Port data Interface card-2 No., 4 Port Ethernet Card-1No., 4 Command Integrated Tele-protection Card- 4No., Line Differential relay Interface card(4 port)-4Nos., Interfacecables for Power, data, vol ce, teleprotection, time synchronisation etc as per respective site requirement--1 Lot, Engineeringorder wire phone-1 No., Laptop (Core 7 processing family, 3.1GHz & above 15.0\" LED,1TB HDD, 8GB RAM, DVD R/W) with configuration Software with latest preloaded licensed Microsoft Window OS as offered ) |
| 207 | 220 kV GSS Heerapura End (220 kV Side) |
| 208 | OLTE equipment consisting of fully wired cabinet with base 19\" equipment rackwith control synchronization, Alarm & Power supply cabinet-1 No, Central Processing card-CPU-2 no power supply unit-48VDC-2 No, OLTE-4 port STM-1(1SSMbps Card)-1 No, SEP duplex LC connector for OLTE Card-4 No, OFC Patch Cords-20M -8 No, 8Port-2w/4w E&M Interface card- 1 No, 4 Port data Interface card-1 No., 4 Port Ethernet Card-1No., 4 Command Integrated Tele-protection Card- 2No., Line Differential relay Interface card(4 port)-2Nos., Interfacecables for Power, data, vol ce, teleprotection, time synchronisation etc as per respective site requirement--1 lot Engineeringorder wire phone-1 No. |
| 209 | 220 kV GSS Kotputli End & 220 KV GSS Niwana end(220 kV Side) |
| 210 | OLTE equipment consisting of fully wired cabinet with base 19\" equipment rackwith control synchronization, Alarm & Power supply cabinet-1 No, Central Processing card-CPU-2 no power supply unit-48VDC-2 No, OLTE-4 port STM-1(1SSMbps Card)-1 No, SEP duplex LC connector for OLTE Card-4 No, OFC Patch Cords-20M -8 No, 8Port-2w/4w E&M Interface card- 1 No, 4 Port data Interface card-1 No., 4 Port Ethernet Card-1No., 4 Command Integrated Tele-protection Card- 1No., Line Differential relay Interface card(4 port)-1Nos., Interfacecables for Power, data, vol ce, teleprotection, time synchronisation etc as per respective site requirement--1 lot Engineeringorder wire phone-1 No. |
| 211 | Electronic Private Automatic Exchange (EPAX) |
| 212 | Electronic Push Button Telephone Instruments with required accessories etc. |
| 213 | Digital Protection Coupler |
| 214 | TESTING & MEASURING INSTRUMENTS, TOOLS & TACKLES AND MISCELLANEOUS ITEMS |
| 215 | TESTING EQUIPMENT/ INSTRUMENTS [This shall consist of all the standard accessories, cables, software etc. required for satisfactory operation of equipment meeting functional requirements] |
| 216 | Insulation Tester - 5000 Volts, Digital |
| 217 | Dew Point Meter |
| 218 | SF6 Leakage Detector |
| 219 | SF6 Gas Filling, Evacuation, Filtering, Drying, Storage and Pumping Plant |
| 220 | Digital Multimeter |
| 221 | Digital Clamp Meter |
| 222 | Earth Resistivity tester |
| 223 | Universal relay test kit |
| 224 | Analog Multimeter |
| 225 | Circuit Breaker Operational Analyser |
| 226 | Transformer Testing Van |
| 227 | EHV Cable Fault Locator |
| 228 | PLCC Maintenance/Testing Equipments: |
| 229 | Optical Power Meter (1310/1550 nm) |
| 230 | Laser Power Meter (1310/1550 nm) |
| 231 | OTDR (Optical Time Domain Reflectometer) for 1310/1550 nm with Laser Source |
| 232 | Optical Fiber Fusion Splicer incl. Fiber cleaver |
| 233 | Maintenance Tools& Tackles |
| 234 | Oil Sampling Bottle (1 Liter Capacity) |
| 235 | Vaccum Cleaner |
| 236 | Telescopic ladder aluminium 6 meter height |
| 237 | Ring spanner set |
| 238 | Tube spanner set |
| 239 | Pipe wrench 24 inch |
| 240 | Pipe wrench 18 inch |
| 241 | Hydraulic crimping tools up to 630 sq.mm |
| 242 | Threading die set for pipe threading |
| 243 | Welding machine (arc welding) 10kVA |
| 244 | Heavy duty drilling machine |
| 245 | Bench Vice |
| 246 | Insulated cuttingplier 12 inch |
| 247 | Insulated cuttingplier8 inch |
| 248 | Screw driver 18 inch |
| 249 | Screw driver 12 inch |
| 250 | Hammer 8 lbs |
| 251 | Hammer 2 lbs |
| 252 | Chain pulley block 5 ton |
| 253 | Pipe derrick |
| 254 | Allen Keys |
| 255 | Box Spanners |
| 256 | Office and Miscellaneous Equipments/ Items |
| 257 | Insulation Rubber mat (1mX2mX 12 mm) |
| 258 | Isulation Rubber Gloves (15 kV Tested) |
| 259 | Furniturefor Control Room Building: |
| 260 | Executive Desk bulit in wood and steel with lockable drawings on both side (6 feetX2 ½ feetx 2 ½ feet) |
| 261 | Junior executive table with three drawings on right side One Cup board left side with prelaminated decolam top 20mm thick over painted M.S. Frame ( 4 ½ feet x 2 ½ feetx 2 ½ feet). |
| 262 | Library Shelf with Glass Door (min 4 Shelf) |
| 263 | Steel tubular “S” type with continuous and one feet dia 14guage pipe, cane seat backing, teak wood with quality cane. |
| 264 | Archival Storage 4 Drive Type |
| 265 | Lateral Filing Cabinets |
| 266 | 3 Drawer Unit |
| 267 | 4 Drawer Unit |
| 268 | Steel Almirah of size 6 ½ feetx 3 feet x 19 inch with four shelves making five compartments in 18 guage with three way locking system. |
| 269 | Steel Almirah (with Glass doors) of size 6 ½ feetx 3 feet x 19 inch with four shelves making five compartments in 18 guage with three way locking system. |
| 270 | Minor Almirah of size 4 ½ feet x30 inch x 17 inch with three shelves making four compartments in 18 guage with three waylocking system. |
| 271 | Steel rack of size 5 feet x 3 feet x 16 inches with six shelves making five compartments (22 guage). |
| 272 | Steel file trays of size 16 inches x11 inches x 3 inches of guage 14 SWG. |
| 273 | Steel stools of size 15 inch x15 inch x 18 inch square pipe 16 guage |
| 274 | Steel waste paper baskets of size 12 inch (H) and Approx. 10 inch Dia Round. |
| 275 | Key board (wooden) with Glass door |
| 276 | First Aid Box |
| 277 | Shock Treatment Chart [Laminated with Frame] |
| 278 | Safety Instruction Boards [ Laminated with Frame] |
| 279 | Drinking Water Arrangement |
| 280 | Water Cooler (Storage type, Storage Capacity 40 Ltr, Cooling Capcity 20 Ltr./hr) |
| 281 | RO/ Water Purifier |
| 282 | Refrigirator (380 Lt.) |
| 283 | Substation Name Board [1 No. Glow Type & 1 No. Painted Type] [Size and Color etc. be got approved from owner] |
| 284 | Danger Plate [Size and Color etc. be got approved from owner] |
| 285 | MANDATORY SPARES |
| 286 | AUTO TRANSFORMER |
| 287 | Bushing with metal parts & gaskets of each rating including Neutral bushing |
| 288 | Oil cooler pump with motor |
| 289 | Cooler fan with motor |
| 290 | Buchholz relay complete with floats & contacts |
| 291 | Local and remote winding temperature indicator complete with sensing device & contacts |
| 292 | Magnetic Oil level Guage |
| 293 | Set of starter, contactor, relays and switch for electrical control panels (1 set of each type and range) |
| 294 | OTI For Transformer |
| 295 | POWER TRANSFORMER |
| 296 | HV bushing with metalparts and gaskets |
| 297 | LV bushing with metal parts and gaskets |
| 298 | Neutral bushing with metal parts and gaskets |
| 299 | Magnetic oil level gauge with low oil level alarmcontacts |
| 300 | Winding temperature Hot indicator |
| 301 | Oil temperature indicator |
| 302 | Pressure relief device |
| 303 | Cooler fans |
| 304 | Buchlotz Relay |
| 305 | Complete set of Gasket |
| 306 | 220 kV Indoor GIS Switchgear Equipments |
| 307 | General |
| 308 | Cable Connection Enclosure with the Main Circuit |
| 309 | SF6 Gas pressure relief devices (3 Nos. of each type) |
| 310 | SF6 Pressure gauge cum switch OR Density monitors and pressure switch as applicable (1 no. of each type) |
| 311 | Rubber Gaskets \"0\" Rings and Seal for SF6 Gas of each type |
| 312 | Molecular filter for SF6 gas with Filter bags (20% of total weight) |
| 313 | Coupling device for pressure gauge cum switch for connecting Gas handling plant |
| 314 | All type of Control Valve for SF6 Gas of each type |
| 315 | Bottles of SF6 Gas (40 Kg each) |
| 316 | All type of Couplings for SF6 gas ( 1 No. of each type) |
| 317 | Pipe length (Copper or Steel as applicable) for SF6 Circuit of each type |
| 318 | Covers with all accessories necessary to close a compartment in case of dismantling of any of any part of the Enclosure to ensure the sealing of this compartment as applicable |
| 319 | For 3 Phase Enclosure |
| 320 | For Single Phase Enclosure |
| 321 | Locking device to keep the Disconnectors (Isolators) and Earthing switches in close or open position in case of removal of the driving Mechanismopen position in case of removal of the driving Mechanism |
| 322 | Bus Support insulator of each type for 3 phase/single phase enclosure. (5% of Population) |
| 323 | SF6 to air bushing (each type & rating) |
| 324 | 220 KV SF6 CIRCUIT BREAKER: |
| 325 | Complete Circuit Breaker pole of each type & rating complete with interrupter, main circuit, enclosure and Marshalling Box with operating mechanism |
| 326 | Fixed, moving and arcing contacts including insulating nozzles 3 Nos. of each type |
| 327 | Rubber gaskets, `O\" rings and seals for SF6 gas of each type |
| 328 | Trip coil assembly with resistor as applicable, 3 Nos. of each type |
| 329 | Closing coil assembly with resistor as applicable, 3 Nos. of each type |
| 330 | Molecular filter for SF6 gas with filter bags (10% of total quantity used) |
| 331 | SF6 Pressure gauge cum switch OR Density monitors and pressure switch as applicable (1 no. of each type) |
| 332 | Coupling device for pressure gauge cum switch/ for connecting Gas handling plant, 3 Nos. of each type |
| 333 | Relays, Power contactors, push buttons, timers & MCBs etc of each type & rating |
| 334 | Closing assembly/ valve, 3 Nos. of each type |
| 335 | Trip assembly/ valve, 3 Nos. of each type |
| 336 | Auxiliary switch assembly, 3 Nos. of each type |
| 337 | Operation Counter, 3 Nos. of each type |
| 338 | Rupture disc, 3 Nos. of each type |
| 339 | Windoscope / Observing window, 3 Nos. of each type |
| 340 | Spring operated closing mechanism, 1 Nos. of each type, if applicable |
| 341 | For Hydraulic Operated Mechanism, if applicable |
| 342 | Hydraulic operating mechanism with drive motor, 3 Nos. of each type |
| 343 | Ferrules, joints and couplings, 3 Nos. of each type |
| 344 | Hydraulic filter, 3 Nos. of each type |
| 345 | Hose pipe, 3 Nos. of each type |
| 346 | N2 Accumulator, 3 Nos. of each type |
| 347 | Pressure transducer, 3 Nos. of each type |
| 348 | Valves 3 Nos. of each type |
| 349 | Pipe length (copper & steel) 3 Nos. of each size & type |
| 350 | Pressure switches 3 Nos. of each type 1 Set |
| 351 | Pressure gauge with coupling device, 3 Nos. of each type |
| 352 | Hydraulic Oil (20% of total quantity used) |
| 353 | Pressure Relief Device, 3 Nos. of each type |
| 354 | 220 KV Isolators |
| 355 | Complete set of 3 nos. of single phase / one no. of 3-phase dis-connector including main circuit, enclosure, driving mechanism |
| 356 | 3 no. of single phase / one no of 3-phase Earthing switch including main circuit enclosure, driving mechanism. |
| 357 | Copper contact fingers for dis-connector male & female contact – for one complete (3 phase) dis-connector of each type and rating |
| 358 | Copper contact fingers for earthing switch male & female contacts, for one complete (3 phase) earthing switch of each type and rating |
| 359 | Open / Close contactor assembly, timers, key interlock for one complete (3 phase) disconnector and (3 phase) earthing switch of each type and rating |
| 360 | Push button switch.-each type, as applicable |
| 361 | Limit switch and Aux. Switches for complete 3 phase equipment |
| 362 | For isolator |
| 363 | For earth switch |
| 364 | Rotor housing bearing assembly for complete 3 phase equipment |
| 365 | For Isolator |
| 366 | For earth switch |
| 367 | Motor with gear assembly for complete 3 phase equipment |
| 368 | For Isolator |
| 369 | For earth switch |
| 370 | Hinge pins for complete 3 phase equipment |
| 371 | For Isolator |
| 372 | For earth switch |
| 373 | Bearings for complete 3 phase equipment |
| 374 | For Isolator |
| 375 | For earth switch |
| 376 | Interlocking coil with resistors, timers, key interlock for complete 3 phase equipment (each type and rating) |
| 377 | Relays, Power contactors, resistors, fuses, push buttons & MCBs (complete for one 3 phase equipment) |
| 378 | For Isolator |
| 379 | For Earth Switch |
| 380 | Aux. switch assembly (complete) with 10 NO & 10 NC OR more contacts for both isolator & earth switch |
| 381 | 220 kV CURRENT TRANSFORMER |
| 382 | Complete CT of each type and rating with enclosure. |
| 383 | Secondary bushing of each type |
| 384 | 220 kV PT |
| 385 | Complete PT of each type and rating |
| 386 | 220 kV SURGE ARESTOR |
| 387 | Complete Surge Arrestor including insulating Base with Surge counter & accessories.: GIS type |
| 388 | 132kV Indoor GIS Switchgear Equipments |
| 389 | SF6Gas pressure relief devices |
| 390 | Pressure gauges(of each type) alongwith Coupling device |
| 391 | Rubber Gaskets \"0\" Rings and Seal for SF6Gas |
| 392 | Molecular filter for SF6gas sets |
| 393 | Density Monitor for SF6Gas |
| 394 | All type of Control Valve for SF6Gas |
| 395 | Bottles of SF6Gas (40 Kg each) |
| 396 | Closing coils for circuit breakers |
| 397 | Tripping coils for circuit breakers |
| 398 | Controlswitchand auxiliaryrelaysofeachtype forlocalcontrol cubicle |
| 399 | Miniature Circuit Breaker (as applicable) of each type |
| 400 | Operating Mechanism for Disconnectors |
| 401 | Operating Mechanism for Earth Switch |
| 402 | Motor for Disconnectors |
| 403 | Motor for Earth Switch |
| 404 | Motor for Circuit Breaker Operating Mechanism |
| 405 | One complete set of circuit breaker |
| 406 | Contact fingers and nozzles for circuit breakers |
| 407 | Valve block with drive cylinder for circuit breakers |
| 408 | One complete set of isolator and earthing switch (Single Phase Unit) |
| 409 | 36 kV Metal Clad GIS Switchgears |
| 410 | Drive Mechanism for Circuit Breaker |
| 411 | Drive Mechanism for Combined Disconnector |
| 412 | Spring Charge motor |
| 413 | Trip Coil |
| 414 | Close Coil |
| 415 | Rupture Disk/ Diapharm |
| 416 | LV PanelEquipments:Relay,MCB,Lamps,Push Buttons, terminal Blocks |
| 417 | Pressure Switches |
| 418 | Rubber Gaskets |
| 419 | VT |
| 420 | CT |
| 421 | Bay Control & Protection Unit |
| 422 | C&R Panels & SAS System |
| 423 | Bay Control Unit (220 kV Side of offered type) |
| 424 | Bay Control Unit (132 kV Side of offered type) |
| 425 | Bay Unit (For 220 kV Busbar Protection of offered type) |
| 426 | Bay Protection Unit (Distance for 220 kV Feeders of offered type) |
| 427 | Bay Protection Unit (Line Differential for 220 kV Feeders of offered type) |
| 428 | Bay Protection Unit (Differential for 220 kV Transformersof offered type) |
| 429 | Bay Protection Unit (Back-up Overcurrent & E/F of offered type) |
| 430 | Breaker failure relay (numerical type) |
| 431 | Trip circuit supervision relay |
| 432 | Self reset trip relay |
| 433 | Hand reset trip relay |
| 434 | Timer relay |
| 435 | DC supervision relays |
| 436 | Flag relays |
| 437 | Auxiliary relays |
| 438 | Multifunction Panel Meter |
| 439 | Fiber Optic Cable with Connectors |
| 440 | Transducers (Each Type used in the autoamtion system) |
| 441 | Ethernet Switch (of offered type) |
| 442 | Station Transformer |
| 443 | 10% of total Transformer Oil quantity in non-returnable drums |
| 444 | HV bushing |
| 445 | LV bushing |
| 446 | Pressure relief device |
| 447 | Tap charger contact |
| 448 | Set of valves |
| 449 | Set of gasket |
| 450 | Silica gel required for five replacements |
| 451 | Surge Arrester |
| 452 | 220kV class 198 kV rating LA complete as specified. |
| 453 | 132kV class 120 kV rating LA complete as specified. |
| 454 | 33 kV Class of 30kV rating LA Complete as specified |
| 455 | 2 Nos. Terminal connector of each type as spare |
| 456 | Instrument Transformer |
| 457 | 245 kV CVT (1Ph) |
| 458 | 1 No. Terminal connectors (CVT) each type |
| 459 | Battery & Battery Charger |
| 460 | 220 V& 48 V Type Battery |
| 461 | Cell of Bank |
| 462 | Conectors |
| 463 | Terminal Lugs |
| 464 | 220V/ 48V Battery Chargers |
| 465 | Set of Control Cards |
| 466 | Set of relays |
| 467 | Set of contactor |
| 468 | Micro-switches |
| 469 | Filter Capacitors |
| 470 | Thyristor/ Diode |
| 471 | Set of switches |
| 472 | Set of wound resistors |
| 473 | Potentiometers |
| 474 | Fuses of Thyristor with indicators |
| 475 | L.T. SWITCHGEAR : |
| 476 | Relays |
| 477 | CTs AND PTs |
| 478 | Switches/Push buttons and Meters |
| 479 | TPN Switches/MCB |
| 480 | L.T. Breaker spares |
| 481 | a) Spring charging motor |
| 482 | b) Aux. Contact sets |
| 483 | c) Busbar Seal off insulators |
| 484 | d) Arc-chutes |
| 485 | e) Moving contacts |
| 486 | f) Arcing contacts (Fixed/Moving) |
| 487 | g) Springs (Closing/Opening) |
| 488 | h) Closing coil |
| 489 | i) Tripping coil |
| 490 | j) Aux. finger contact |
| 491 | k) Limit switches |
| 492 | l) Jaw contacts |
| 493 | Busbar |
| 494 | a) Busbar insulators |
| 495 | b) Interphase barrier |
| 496 | c) Busbar strip 1mm (Aluminium) |
| 497 | LIGHTING SYSTEM |
| 498 | Single Pole MCB |
| 499 | Triple pole MCB |
| 500 | Fluorescent tube & Starter |
| 501 | a) Choke |
| 502 | b) Bottom Strips |
| 503 | c) Top covers & reflector (if applicable) |
| 504 | d) Holders |
| 505 | e) Complete fittings |
| 506 | Sodium vapour/Mercury vapour Lamps a) Lamp |
| 507 | b) Ballast |
| 508 | c) Condenser/ Igniter |
| 509 | d) Lamp holder |
| 510 | e) Lamp holder |
| 511 | f) Complete fittings |
| 512 | OLTE Panel |
| 513 | 4 Command Integrated Teleprotection Card |
| 514 | Incandescent lamp |
| 515 | a) Bulbs |
| 516 | b) Holders |
| 517 | c) Complete fittings |
| 518 | Switches and sockets |
| 519 | Junction box |
| 520 | Celing Fan |
| 521 | Clamps & Connectors Set |
| 522 | Fire Protection System |
| 523 | NIFPES System |
| 524 | Fitted Nitrogen Cylinder [48 Lit Water Capacity] |
| 525 | Hose Pipe with Fittings |
| 526 | Heat Sensor Assembly |
| 527 | Fire Survival Cable [sufficient for 1 system] |
| 528 | PNRV (For each type) |
| 529 | Limit Switches for Fire Detector |
| 530 | Fire Detector (for NIFPES System) |
| 531 | Thermostat |
| 532 | Heating Element |
| 533 | Fire Detection and Alarm System |
| 534 | Smoke Detector |
| 535 | Heat Detectors |
| 536 | Manual Call Point |
| 537 | 33 kV Isolators |
| 538 | Solid core insulator Stacks ( Requirement of one Isolator) |
| 539 | Limit switches and auxiliary switches ---Each Set containing one no. of each type andrating as offered |
| 540 | Bearings (requirement of one isolator) |
| 541 | Currentcarrying assembly 2000A total(requirement of one isolator) |
| 542 | Relays, power contactors, MCB’s switch fuses, push buttons and resistors, timers, key inter lock for electrical control circuit as per approved schematic-- Each Set containing one no. of each type andrating as offered |
| 543 | Motor with gear assembly and bevelgear assembly. |
| 544 | Terminal connectors ( one set consisting of 1 no. of each type.) . |
| 545 | SUPPLY LINE WORK : 220kV Lines at 220kV GSS Gokul Nagar(i) 0.205 Km LILO of 220kV S/C Heerapura - Niwana Line using 1200 sq.mm. 220kV XLPE underground Cable(ii) 0.004 Km LILO of 220kV S/C Heerapura - Kotputli Line through overhead upto Gantry of 220kV GSS Gokul Nagar |
| 546 | MAIN MATERIAL /ITEMS |
| 547 | Overhead Line |
| 548 | Super structure of 220 kV D/C Narrow Base TTD type tower with stub and Cleat for termination of XLPE cable/ LILO Tower |
| 549 | (i) Stub 220KV D/C NB TTD (350Mtr SPAN) |
| 550 | (ii) S/S 220KV D/C NB TTD (350Mtr SPAN) |
| 551 | (iii) +3 mtr Extension for 220KV D/C NB TTD (350Mtr SPAN) |
| 552 | Conductor |
| 553 | ACSR Zebra conductor |
| 554 | Zebra conductor hardware |
| 555 | a) Double tension hardware |
| 556 | b) Single Suspension Hardware |
| 557 | c) Single Tension Hardware |
| 558 | c) M.S Joint |
| 559 | d) Al. Repair sleeve |
| 560 | e) Vibration damper |
| 561 | Long rod insulator |
| 562 | a) 220 KV Tension (120 KN) |
| 563 | Disc Insulator 70 KN (B&S type) |
| 564 | Disc Insulator 120 KN (B&S type) |
| 565 | G.I. Nut-Bolt, Step bolt & spring washer assorted size as per requirement & technical specification |
| 566 | Earthing material |
| 567 | a) Pipe type |
| 568 | Others |
| 569 | a) Number plate |
| 570 | b) Phase plate |
| 571 | c) Danger plate (220 KV) |
| 572 | T-clamp (Z-Z) |
| 573 | PG Clamp (Z-Z) |
| 574 | OPGW |
| 575 | 48 Fiber (DWSM) OPGW Fibre Optic Cable |
| 576 | Installation hardware set for above 48 fibre OPGW fibre optic cabling including of all cable fittings and accessories except joint box |
| 577 | Joint Box (48 fibre) |
| 578 | FODP 96F: Indoor type, rack nounted with coupling and pigtails |
| 579 | 220kV XLPE Cpper Cable |
| 580 | 220 kV, Single Core, 1200 Sq. mm XLPE Copper Cable as per foregoing specification requirements |
| 581 | 245 kV rated voltage pre-moulded outdoor end termination kit complete with accessories suitable for the above underground cable |
| 582 | 245 kV rated voltage plug in type pre-moulded end termination kit complete with accessories suitable for the above underground cable for termination in GIS type switchgear |
| 583 | Solid bonding Link box with Link plates, bonding & grounding cable complete with other associated accessories for 1-phase |
| 584 | Galvanized Steel supporting structures/ arrangement, Gantry structures, Ladders etc. for suitable and safe terminations of XLPE cable from Terminal towers maintenaing statutory clearances and safety as per IE rules |
| 585 | Galvanized Steel support structure/ arrangement etc. for suitable and safe termination of XLPE cable to GIS switchgear |
| 586 | Earthing Material including cast iron pipes with suitable clamps, charcol, common salt etc. (for each circuit) |
| 587 | Terminal connector suitable for ACSR Zebra on the item No. 5 to connect cable end termination to Terminal Tower |
| 588 | Warning Tapes as per Specification |
| 589 | 24Fibre OFCand hardware fittings/ accessories alongwith associated , Joint Box & accessories /items as per specification |
| 590 | 245kV class of 198kV rating LA with grading ring, discharge counter with milli meter |
| 591 | Retrofit of Protection Relays (Line differential cum distance protection relay) |
| 592 | SUPPLY LINE WORK: 132kV Lines at 220kV GSS Gokul Nagar(i) 0.215 Km LILO of 132kV Vaishali Nagar-Jhotwara Line using 1200 sq.mm. 132kV XLPE underground Cable(ii) 0.205 Km LILO of 132kV Heerapura- VKIA Line using 500 sq.mm. 132kV XLPE underground Cable |
| 593 | MAIN MATERIAL/ ITEMS |
| 594 | Overhead Line |
| 595 | Super structure of 220 kV D/C Narrow Base TTD type tower with stub and Cleat for termination of XLPE cable |
| 596 | (i) Stub 220KV D/C NB TTD (350Mtr SPAN) |
| 597 | (ii) S/S 220KV D/C NB TTD (350Mtr SPAN) |
| 598 | Conductor |
| 599 | ACSR Panther conductor |
| 600 | Panther conductor hardware |
| 601 | a) Double tension hardware |
| 602 | b) Single Suspension Hardware |
| 603 | c) M.S Joint |
| 604 | d) Al. Repair sleeve |
| 605 | e) Vibration damper |
| 606 | Long rod insulator |
| 607 | a) 120 KN (132 KV Tension) |
| 608 | G.I. Nut-Bolt, Step bolt & spring washer assorted size as per requirement & technical specification |
| 609 | Earthing material |
| 610 | a) Pipe type |
| 611 | Others |
| 612 | a) Number plate |
| 613 | b) Phase plate |
| 614 | c) Danger plate (132 KV) |
| 615 | d) T-Clamp (P-P) |
| 616 | e) PG Clamp(P-P) |
| 617 | Joint Box (48 fibre) |
| 618 | FODP 96F: Indoor type, rack nounted with coupling and pigtails |
| 619 | 132kV XLPE Copper Cable |
| 620 | 132 kV, Single Core, 1200 Sq. mm XLPE Copper Cable as per foregoing specification requirements |
| 621 | 145 kV rated voltage pre-moulded outdoor end termination kit complete with accessories suitable for above 1200 Sq. mm XLPE Copper Cable |
| 622 | 145 kV rated voltage plug in type pre-moulded end termination kit complete with accessories suitable for the above 1200 Sq. mm XLPE Copper Cablecable for termination in GIS type switchgear |
| 623 | 132 kV, Single Core, 500 Sq. mm XLPE Copper Cable as per foregoing specification requirements |
| 624 | 145 kV rated voltage pre-moulded outdoor end termination kit complete with accessories suitable for 132 kV, Single Core, 500 Sq. mm XLPE Copper Cableunderground cable |
| 625 | 145 kV rated voltage plug in type pre-moulded end termination kit complete with accessories suitable for theabove 500 Sq. mm XLPE Copper Cable for termination in GIS type switchgear |
| 626 | Solid bonding Link box with Link plates, bonding & grounding cable complete with other associated accessories for 1-phase |
| 627 | Galvanized Steel supporting structures/ arrangement, Gantry structures, Ladders etc. for suitable and safe terminations of XLPE cable from Terminal towers maintenaing statutory clearances and safety as per IE rules |
| 628 | Galvanized Steel support structure/ arrangement etc. for suitable and safe termination of XLPE cable to GIS switchgear |
| 629 | Earthing Material including cast iron pipes with suitable clamps, charcol, common salt etc. (for each circuit) |
| 630 | Terminal connector suitable for ACSR Panther to connect cable end termination to Outdoor Switchyard Equipment. |
| 631 | Warning Tapes as per Specification |
| 632 | 24Fibre OFCand hardware fittings/ accessories alongwith associated , Joint Box & accessories /items as per specification |
| 633 | 145kV class of 120kV rating LA with grading ring, discharge counter with milli meter |
| 634 | Add: Any other item bidder may require to complete the GIS, works as well as EHV XLPE Cable System as per specification requirements |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy