| 1 | 5.1Providing, installation, testing and commissioning of Centrifugal Monoblock pump set conforming to IS 9079 , 2 pole motor operating at syncronised speed of 3000 RPM with requisite MOC impeller, priming funnel, cock, suitable flanges at suction and delivery side. Pump shall have common shaft for pump and motor. Motor shall be suitable for working on 415 V 10%, 3 Ph, 50 Hz A.C. Supply. Motor shall be TEFC type and Pump set shall be suitable for working at various discharge and head requirements as per scope of work. Pump shall be erected onC.C. foundation / cross channels / RSJ frame block with suitable foundation bolts grouted in C.C. foundation block etc. complete in all respect as perspecification, scope of work and direction of Engineer in Charge of following power rating, suitable for prescribed duty conditions mentioned in TD. |
| 2 | 5.1.1Centrifugal Monoblock Pump set (Single Stage) 5.1.1.59.3 KW (12.5 HP |
| 3 | 4.7Providing and laying in position cement concrete M10 grade nominal mix 1:3:6 (1 Cement : 3coarse sand : 6 graded stone aggregate 40 mm nominal size) in base course complete including all material, labour, machinery, lighting, guarding for road restoration work in trenches of pipe line and chamber work. Measurement for CC work to be madeas per standard trench width specified in tender document and no extra payment shall be made be made for trench width more than specified,complete work as per technical specification and scope of work. |
| 4 | 4.5Dismantling of cement concrete pavement for pipe line line and chambers by mechanical means using pneumatic tools, cutting the peripheral edge by CC cutter, breaking to pieces not exceeding 0.02 cum in volume and stock piling at designated locations and disposal of dismantled materials up to a lead of 1000 meters. Measurement for dismantled trench to be madeas per standard trench width specified in tender document and no extra payment shall be made be made for trench width more than specified, re-handling of material/earth to complete the tasks as per technical specification and scope of work |
| 5 | 4.1 Earth work in excavation by mechanical means (Hydraulic Excavator )/ manual means in trenches of required width and gradient for laying and jointing of pipe line including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5 Mtr. including taking out the excavated soil, and then returning the soil as required in layers not exceeding 20cm in depth including consolidating each deposited layer by ramming, watering etc. and disposal of surplus excavated soil as directed within a lead of 50 Mtr. including required all safety provisions etc.: All kind of soil |
| 6 | 6.8 Providing, lowering, aligning, fixing in position in pipe line at work site, DI D/F Resilient seated (soft seated) Sluice Valves (Gate Valves) , Vacuum tight(bubble tight), straight and pocket less body passage of approved make of following classanddia complete confirfing to BS-EN-1171/ AWWA C-509 and of following specifications: Bodyandbonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2-1985 and subsequent revisions, Wedge of same material as bodyandshall vulcanisedrubber lined with EPDM (food grade quality) and seals of NBR Face to face dimensions as per BS 5163-89/ IS 14846/2000 (amended up to date) /Din 3202 F4, Stem/ spindle of SS AISI 316/ 410 Electrostatic epoxy powder(EP-P)/ Fusion bond epoxy ( Non-Toxic- suitable for drinking water) coated with minimum thickness of 250 microns inside and outside, Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367(Galvanised steel) Insersion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC, Sluice valves including all jointingandjointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer-in-charge. |
| 7 | Note: Rates are exclusive of tail piece/ dismantling joints and earth work.6.8.1Manually Operated Resilient Seated Sluice Valves of Class PN 1.6 6.8.1.10450 mm dia |
| 8 | 1.15Providing and fixing of flanged/ plain ended MS Specials made from MS sheet strips of relevant IS specification of approved thickness by welding,lowering,laying,aligning,fixinginpositionatalllevel/ depths in trenches complete includingall taxes, material,labour, inside lining, outside coating, testingandcommissioning alongwithpipelineaspertechnicalspecifications anddirection of Engineer-in-charge. |
| 9 | 7.2 SITC STAR DELTA Starter type LT Panel of followingrating:all switchgears are of PHED approved makes, CRCA sheet of Panel enclosure is of TATA/ Essar 1.6mm/ 2.0mm thick duly Electrostatic Powder Coated with angle frame including other ancillaries ( Insulators, Acrylic Sheet , Baklight Sheet, Hardware, Wire, Name Plates, Lugs, Pvc Channel , Mcb Chanel , Lock, Hing , Bidding , Connectors, Netural Links , Sprial , SaddleandPacking Material ) etc. and 100A/ 125A ,TPN, Aluminum Bus Bar with Colour coated heat shrinkage sleeves complete as per Technical Specifications and as per direction of Engineer-In-Charge.7.2.3 STAR DELTA STARTER 11.0 KW (15.0 HP)- :For 2 motors (1 W+ 1S) |
| 10 | I/C -MCB 63A ,FP, 10 KA, C Curve (1) , Analog Voltmeter 96*96mm ( 0-500V ) (1), Volt Selector Switch (1) , Analog Ammeter 96*96mm ( 0-60A ) (1), Amp. Selector Switch (1), C. T. 60/5A CL 1.0 5VA (3) , Indicating Lights ( Red-1, Yellow -1) (2), Indicating Lights ( Blue - 1 ) (1), Control MCB 6A SP 10 KA C Curve (3) and O/G-MCB 40A ,TP, 10 KA, C Curve (2), Power Cont 25A TP AC3 Duty(2), 2 NO+2 NC Aux. Block(2), Thermal Overload Relay (9-13A )(2), Control MCB 6A SP 10 KA C Curve (2), Single Phase Priventer (2), Indicating Lights (Red- 1, Green - 1, Amber-1)(6), Push Button 22.5 ( Red - 1, Green - 1 )(4), Selector Switch 1 Pole, 2 Way (2), Capacitor 440VAC Heavy Duty MPP Type 7.5Kvar (2), S/D Timer(2) |
| 11 | 2.19SupplyandFixing of ISI marked three core PVC flat submersible cableas per IS 694:1990 or amended up to date and conductor as per class 5 of IS 8130:1980including making connection etc. 2.19.43 core 16.0 Sq.mm |
| 12 | 5.7 Providing and fixingat site with necessary packing,Horizontal Centrifugal Split Casting pumps with 4 poleinduction motor operating at syncronised speed of speed 1500 RPM as per IS 12615: 2011 or amended up to date , CI casing and casing ring, SS 316 impeller, SS 410 Shaft and shaft sleeve, coupling guard, common base plate, foundation bolts, Cement concrete foundation etc. complete with all respect as per the specification and scope of work and direction of Engineer in Charge of following range of duty conditions.5.7.3Discharge 20 to 30 LPS and head 41 to 50 M |
| 13 | 2.16Supply and Fixing of Electric feeder panel (having projected canopy)for submersible pump set Single phase upto 5 HP, comprising of DOL Starter, MCB, Indicating Light, Ammeter, Volt meter, connection plate, condensers of approved make and the panel enclosure should be made out from 18 gauge M.S. Sheet with powder coating. Panel size Height 600 mm Width 500 mm depth 250 mm with Stand ( made of angle iron of size 35x35x5mm) duly bolted/screwed with enclosure box having 4 legs, each leg s length 18and double door including in built locking system.The legs should be embedded in M-15 cement concrete platform. The size of CC platform should be equal or bigger than the base size of panel having height of at least 200 mm from ground level. The operation of panel should be suitable for on 240 Volt AC Supply. |
| 14 | 2.14SupplyandInstallation of single phase ISI marked submersible motor pump set of three star or better rating of BEE and as per IS: 8034-2018 (pump) and IS 9283-2013 (motor) or as amended up to date of approved make of following duty condition with required accessories including making connection suitable for tube well/DCB. The job includes lowering of motor pump, installation of complete fittingandaccessories, jointing of electrical cables up to switch board, testing of submersible pump set and interconnection up to water mains, complete in all respect |
| 15 | 2.23SupplyandFixing tube well coverof MS sheet 8mm thick at topand5mm thick 100mm wide shroud around the edge so as to form a cap on the top end of casing pipe with GI Nipple 45cm longandtwo GI flanges at both ends in 80mm sizes passing through a hole in the centre of MS sheet. A 25 mm socket with end plug shall also be welded over top plate. A GI nipple having outside thread of size 1/2(for installation pressure gauge) shall be providedandwelded with 80mm GI nipple near top plate nipple shall be provided with end plug. |
| 16 | 2.22SupplyandFixing M S clamp set of 50x6 mm flat from iron with nuts and bolts etc for holding the riser pipe assembly of submersible pump set. |
| 17 | 2.21 Plate Earthing as per IS:3043 with G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying3 to 4 mtr. below the ground level with 20 mm dia. G.I.Bclass watering Pipe including all accessories like nut, bolts, reducer ,nipple, wire meshed funnel, and C.C.finished chamber covered with hinged type with locking arrangement C.I. Cover,C.I. Frame of size 300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required. |
| 18 | 2.20SupplyandFixing XLPE insulated / P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor Armoured of IS:7098-I/1554-1 approved makein ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick underlayer ofsand, second Class bricks covering, refilling earth, compaction of earth, making necessary connection, testing etc. as required of size. |
| 19 | 2.19SupplyandFixing of ISI marked three core PVC flat submersible cableas per IS 694:1990 or amended up to date and conductor as per class 5 of IS 8130:1980including making connection etc. 2.19.13 core 4.0 Sq.mm |
| 20 | 2.18Supply and Fixing of electric control feeder panel comprising of suitable rating MCCB , fully automatic star-delta starter, over load relay,ampere meter with CTs, volt meter, phase preventer, suitable starting capacitors, phase indicators, lighting arrangement etc complete suitable for three phase pump set. The panel should have space for energy meter ( supplied by DISCOM).All these equipments shall be housed by panel box made out from 18 gauge M.S. Sheet with powder coating. Panel should be ofminimum size 900 x 600 x 450 mm with Stand ( made of angle iron of size 35x35x5mm) duly bolted/screwed with enclosure box having 4 legs, each leg s length 18and double door including in built locking system.The legs should be embedded in M-15 cement concrete plat form. The size of CC platform should be equal or bigger than the base size of panel having height of at least 200 mm from ground level. The panel should have opening of suitable size in front of space for energy meter with glass for meter reading. The operation of panel should be suitable for on 440 Volt AC Supply. 2.18.2Above 10 HP and up to 15 HP |
| 21 | 2.15SupplyandInstallation of 3 phase ISI marked submersible motor pump set ofthree star or better rating of BEEand as per IS: 8034-2018 (pump) and IS 9283-2013 (motor) or as amended up to date of approved make of following duty condition with required accessories including making connection suitable for tube well/DCB. The job includes lowering of motor pump, installation of complete fittingandaccessories, jointing of electrical cables up to switch board, testing of submersible pump set and interconnection up to water mains, complete in all respect.2.15.6 9.3KW (12.5 HP)andhead above 120 mtr |
| 22 | 2.24ProvidingandLowering in tube well ISI marked GI Pipe medium duty ( Bclass), Steel tube as per IS:1239 or amended up to date and zinc coating as per IS 4736, threaded and double flanged (welded) on both ends and two number25x3mm MS flat welded on both ends between pipeandflange, rubber washerandnut bolts etc. complete in all respect.2.24.250 mm dia |
| 23 | 2.12Labour charges for making slots on blank pipes made of ERW MS black pipe ISI marked of following sizes, the slotting should be as per IS:8110-1985. 2.12.3200 mm dia nominal bore of 5.4mm thickness |
| 24 | 2.8Testing verticality of tube well by plumbing system and yield test and draw down test by pumping system as per IS : 2800 (Part II) 1979 or as per amended up to date. |
| 25 | 2.7 Deepening of existing tube well by DTH system beyond existing depth up to 100 mtr. and above in all type of rocks including flushing of tube well and obtaining sand free water. 2.7.2 Nominal bore 200 mm dia. |
| 26 | 2.19SupplyandFixing of ISI marked three core PVC flat submersible cableas per IS 694:1990 or amended up to date and conductor as per class 5 of IS 8130:1980including making connection etc. 2.19.23 core 6.0 Sq.mm |
| 27 | 2.18Supply and Fixing of electric control feeder panel comprising of suitable rating MCCB , fully automatic star-delta starter, over load relay,ampere meter with CTs, volt meter, phase preventer, suitable starting capacitors, phase indicators, lighting arrangement etc complete suitable for three phase pump set. The panel should have space for energy meter ( supplied by DISCOM).All these equipments shall be housed by panel box made out from 18 gauge M.S. Sheet with powder coating. Panel should be ofminimum size 900 x 600 x 450 mm with Stand ( made of angle iron of size 35x35x5mm) duly bolted/screwed with enclosure box having 4 legs, each leg s length 18and double door including in built locking system.The legs should be embedded in M-15 cement concrete plat form. The size of CC platform should be equal or bigger than the base size of panel having height of at least 200 mm from ground level. The panel should have opening of suitable size in front of space for energy meter with glass for meter reading. The operation of panel should be suitable for on 440 Volt AC Supply. 2.18.1Above 5 HP and up to 10 HP |
| 28 | 2.15SupplyandInstallation of 3 phase ISI marked submersible motor pump set ofthree star or better rating of BEEand as per IS: 8034-2018 (pump) and IS 9283-2013 (motor) or as amended up to date of approved make of following duty condition with required accessories including making connection suitable for tube well/DCB. The job includes lowering of motor pump, installation of complete fittingandaccessories, jointing of electrical cables up to switch board, testing of submersible pump set and interconnection up to water mains, complete in all respect.2.15.4 7.5 KW (10 HP)andhead above 120 mtr. |
| 29 | 2.11Supply of ERW M.S. black casing pipe ISI marked (IS: 4270/2001) or amended up to dateoffollowing sizes 2.11.2200 mm dia NB (Thickness of pipe 5.4mmandmass of tube 28.46 Kg/m) |
| 30 | 2.6Construction of tube well from ground level and up to 100 mtr depth and above to accommodate housing assembly pipe in all type of unconsolidated formation such as pebbles, boulders, collapsible formation etc. by Odex drilling method as per IS: IS:2800 Part 1: 1991 andIS:2800 Part II: 1979 (both amended upto date) and technical specifications. The work will include lowering of housingand strainer pipe assembly and casing shoe including cost of casing shoe, but excluding cost of the casing pipe. The work would be completed afterobtaining sand free water. 2.6.3Nominal bore 200 mm dia.2.1.4 Add 15% extra on above item (Item no 2.1.1 to 2.1.3) for drilling depth beyond 100 mtr and up to 200 mtr, rate shall be applicable for only extra depth beyond 100 mtr and up to 200 mtr. |
| 31 | 2.6Construction of tube well from ground level and up to 100 mtr depth and above to accommodate housing assembly pipe in all type of unconsolidated formation such as pebbles, boulders, collapsible formation etc. by Odex drilling method as per IS: IS:2800 Part 1: 1991 andIS:2800 Part II: 1979 (both amended upto date) and technical specifications. The work will include lowering of housingand strainer pipe assembly and casing shoe including cost of casing shoe, but excluding cost of the casing pipe. The work would be completed afterobtaining sand free water. 2.6.3Nominal bore 200 mm dia.2.1.4 Add 15% extra on above item (Item no 2.1.1 to 2.1.3) for drilling depth beyond 100 mtr and up to 200 mtr, rate shall be applicable for only extra depth beyond 100 mtr and up to 200 mtr. |
| 32 | 7.2 SITC STAR DELTA Starter type LT Panel of followingrating:all switchgears are of PHED approved makes, CRCA sheet of Panel enclosure is of TATA/ Essar 1.6mm/ 2.0mm thick duly Electrostatic Powder Coated with angle frame including other ancillaries ( Insulators, Acrylic Sheet , Baklight Sheet, Hardware, Wire, Name Plates, Lugs, Pvc Channel , Mcb Chanel , Lock, Hing , Bidding , Connectors, Netural Links , Sprial , SaddleandPacking Material ) etc. and 100A/ 125A ,TPN, Aluminum Bus Bar with Colour coated heat shrinkage sleeves complete as per Technical Specifications and as per direction of Engineer-In-Charge.7.2.1 STAR DELTA STARTER 7.5 KW (10.0 HP)- : For 2 motors(1 W+ 1S)I/C -MCB 63A ,FP, 10 KA, C Curve (1) , Analog Voltmeter 96*96mm ( 0-500V ) (1), Volt Selector Switch (1) , Analog Ammeter 96*96mm ( 0-60A ) (1), Amp. Selector Switch (1), C. T. 60/5A CL 1.0 5VA (3) , Indicating Lights ( Red-1, Yellow -1) (2), Indicating Lights ( Blue - 1 ) (1), Control MCB 6A SP 10 KA C Curve (3) andO/G-MCB 32A ,TP, 10 KA, C Curve (2), Power Cont 18A TP AC3 Duty(2), 2 NO+2 NC Aux. Block(2), Thermal Overload Relay (7-10A )(2), Control MCB 6A SP 10 KA C Curve (2), Single Phase Priventer (2), Indicating Lights (Red- 1, Green - 1, Amber-1)(6), Push Button 22.5 ( Red - 1, Green - 1 )(4), Selector Switch 1 Pole, 2 Way (2), Capacitor 440VAC Heavy Duty MPP Type 5Kvar (2), S/D Timer(2) |
| 33 | 6.8 Providing, lowering, aligning, fixing in position in pipe line at work site, DI D/F Resilient seated (soft seated) Sluice Valves (Gate Valves) , Vacuum tight(bubble tight), straight and pocket less body passage of approved make of following classanddia complete confirfing to BS-EN-1171/ AWWA C-509 and of following specifications: Bodyandbonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2-1985 and subsequent revisions, Wedge of same material as bodyandshall vulcanisedrubber lined with EPDM (food grade quality) and seals of NBR Face to face dimensions as per BS 5163-89/ IS 14846/2000 (amended up to date) /Din 3202 F4, Stem/ spindle of SS AISI 316/ 410 Electrostatic epoxy powder(EP-P)/ Fusion bond epoxy ( Non-Toxic- suitable for drinking water) coated with minimum thickness of 250 microns inside and outside, Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367(Galvanised steel) Insersion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC, Sluice valves including all jointingandjointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer-in-charge.100 mm |
| 34 | 6.3 Providing, lowering, aligning, fixing in position in pipe line, CI double flanged swing type Non Return Valves (NRV)of approved make of following Pressure ratinganddia complete, confirming to IS: 5312 (part -1)/ 2004 (amendedup to date) and of following specifications: Body, Coveranddisc of Grey cast iron of IS:210/ FG200. Face to face dimensions as per IS 5312 (part -1):2004 , Flanges Drilled as per IS:1538. Epoxy(Non-Toxicandsuitable for drinking water) applied on body, cover and disc inside and outside . Body seat ring of SS/CS Door face ring - EPDM/ Neoprene (food grade quality) ,Shaft of HTB1/ SS- AISI- 410 ,Hinge Maleable cast iron / SS AISI 316/410 ,Bonnet Gasket EPDM, Bush- Leaded tin Bronze/ PTET, GasketEPDM/NBR,Nut-Bolt as per IS:1363 and IS: 1367 (galvenised steel) ,Insersion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EICincluding jointingandjointing material, labour, testing and commissioning along with pipeline as per Technical Specificationandas per direction of Engineer-in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work.of approved make (IS: 5312 amended upto date) of following Class and dia complete including all material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer-in-charge. Note: Rates are exclusive of tail piece/ dismantling joints and earth work. 6.3.1Class PN 1.0,6.3.1.2100 mm dia |
| 35 | 4.3 Earth work in excavation by mechanical means (Hydraulic Excavator )/ manual means in trenches of required width and gradient for laying and jointing of pipe line including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5 Mtr. including taking out the excavated soil, and then returning the soil as required in layers not exceeding 20cm in depth including consolidating each deposited layer by ramming, watering etc. and stacking serviceable material for measurements and disposal of unserviceable material as directed, with in a lead of 50 Mtr. including all safety provisions required .:4.3.3Hard rock(blasting prohibited) |
| 36 | 4.3 Earth work in excavation by mechanical means (Hydraulic Excavator )/ manual means in trenches of required width and gradient for laying and jointing of pipe line including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5 Mtr. including taking out the excavated soil, and then returning the soil as required in layers not exceeding 20cm in depth including consolidating each deposited layer by ramming, watering etc. and stacking serviceable material for measurements and disposal of unserviceable material as directed, with in a lead of 50 Mtr. including all safety provisions required .:4.3.1Ordinary rock |
| 37 | 1.1Providing, lowering, laying in trenches, aligning, fixing in position and jointingDuctileIron(DI)ISI markedK-7gradeS and Spipesas per IS:8329-2000 (amendedup todate),withinternalcementmortar lining suitable for potablewater with rubber ring (EPDM)joints as per IS: 5382-1985 including all taxes (Central and local), transportation and freight charges, inspection charges, loading/ unloading charges,including cost of labour and material, specials (Tee, bend etc.) satisfactory hydraulic testing, disinfection, commissioning etc. complete as per technical specifications and direction of Engineer-in-charge. (excluding earth work)Note : Providing and fixing of all requisite specials as per drawing, design and layout are inclusive in RM measurement of the item and shall not be paid separately. 1.1.2100 mm |
| 38 | 6.3 Providing, lowering, aligning, fixing in position in pipe line, CI double flanged swing type Non Return Valves (NRV)of approved make of following Pressure ratinganddia complete, confirming to IS: 5312 (part -1)/ 2004 (amendedup to date) and of following specifications: Body, Coveranddisc of Grey cast iron of IS:210/ FG200. Face to face dimensions as per IS 5312 (part -1):2004 , Flanges Drilled as per IS:1538. Epoxy(Non-Toxicandsuitable for drinking water) applied on body, cover and disc inside and outside . Body seat ring of SS/CS Door face ring - EPDM/ Neoprene (food grade quality) ,Shaft of HTB1/ SS- AISI- 410 ,Hinge Maleable cast iron / SS AISI 316/410 ,Bonnet Gasket EPDM, Bush- Leaded tin Bronze/ PTET, GasketEPDM/NBR,Nut-Bolt as per IS:1363 and IS: 1367 (galvenised steel) ,Insersion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EICincluding jointingandjointing material, labour, testing and commissioning along with pipeline as per Technical Specificationandas per direction of Engineer-in-charge.Note: Rates are exclusive of tail piece/ dismantling joints and earth work.of approved make (IS: 5312 amended upto date) of following Class and dia complete including all material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer-in-charge 6.3.1Class PN 1.0100mm dia |
| 39 | 7.2 SITC STAR DELTA Starter type LT Panel of followingrating:all switchgears are of PHED approved makes, CRCA sheet of Panel enclosure is of TATA/ Essar 1.6mm/ 2.0mm thick duly Electrostatic Powder Coated with angle frame including other ancillaries ( Insulators, Acrylic Sheet , Baklight Sheet, Hardware, Wire, Name Plates, Lugs, Pvc Channel , Mcb Chanel , Lock, Hing , Bidding , Connectors, Netural Links , Sprial , SaddleandPacking Material ) etc. and 100A/ 125A ,TPN, Aluminum Bus Bar with Colour coated heat shrinkage sleeves complete as per Technical Specifications and as per direction of Engineer-In-Charge.7.2.1 STAR DELTA STARTER 7.5 KW (10.0 HP)- : For 2 motors(1 W+ 1S)I/C -MCB 63A ,FP, 10 KA, C Curve (1) , Analog Voltmeter 96*96mm ( 0-500V ) (1), Volt Selector Switch (1) , Analog Ammeter 96*96mm ( 0-60A ) (1), Amp. Selector Switch (1), C. T. 60/5A CL 1.0 5VA (3) , Indicating Lights ( Red-1, Yellow -1) (2), Indicating Lights ( Blue - 1 ) (1), Control MCB 6A SP 10 KA C Curve (3) andO/G-MCB 32A ,TP, 10 KA, C Curve (2), Power Cont 18A TP AC3 Duty(2), 2 NO+2 NC Aux. Block(2), Thermal Overload Relay (7-10A )(2), Control MCB 6A SP 10 KA C Curve (2), Single Phase Priventer (2), Indicating Lights (Red- 1, Green - 1, Amber-1)(6), Push Button 22.5 ( Red - 1, Green - 1 )(4), Selector Switch 1 Pole, 2 Way (2), Capacitor 440VAC Heavy Duty MPP Type 5Kvar (2), S/D Timer(2) |
| 40 | 2.20SupplyandFixing XLPE insulated / P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor Armoured of IS:7098-I/1554-1 approved makein ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick underlayer ofsand, second Class bricks covering, refilling earth, compaction of earth, making necessary connection, testing etc. as required of size.2.20.110.0 Sq.mm, 4 core |