| 1 | Supplying ,Installation, testing and commissioning of 10 KVA (10000 VA, 8000 watts) on line Sine wave microprocessor based,bi-directional static switch for redundant system,frequency converter, user friendly LCD display UPS with external battery bank of 12 Volts 48 AH(16 Nos),M.S battery stand,DC voltage of 192 Volts, input 230 volts, output 230 volts and all other acessories etc as required. |
| 2 | Supplying ,Installation, testing and commissioning of 8 KVA (8000 VA, 6400 watts) on line Sine wave microprocessor based,bi-directional static switch for redundant system,frequency converter, user friendly LCD display UPS with external battery bank of 12 Volts 48 AH(16 Nos),M.S battery stand,DC voltage of 192 Volts, input 230 volts, output 230 volts and all other acessories etc as required. |
| 3 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 4 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 5 | Wiring for light / power plug with 2 x 4 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit alongwith 1 No. 4 sq.mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 6 | Wiring for light/ power plug with 4 x 4 sq.mm FRLS PVC insulated copper conductor single core cable in surface/recessed medium class PVC conduit alongwith 2Nos 4 sq.mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 7 | Supplying and fixing following way, single pole and neutral,sheet steel, MCB distribution board, 240 V, on surface/ recess,complete with tinned copper bus bar, neutral bus bar, earthbar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 8 | a) 12 way , Double door |
| 9 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, 10 KA \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 10 | a) Single pole |
| 11 | Supplying and fixing following rating, double pole, 240 V,isolator in the existing MCB DB complete with connections,testing and commissioning etc. as required. |
| 12 | a) 63 amps |
| 13 | Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V \"C\" curve DP MCB complete with connections, testing and commissioning etc. as required. |
| 14 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 15 | a) 2 X 10 sq. mm + 1 X 6 sq. mm earth wire |