| 1 | 5.1.1 Centrifugal Monoblock Pump set (Single Stage) Providing, installation, testing and commissioning of Centrifugal Monoblock pump set conforming to IS 9079 , 2 pole motor operating at synchronised speed of 3000 RPM with requisite MOC impeller, priming funnel, cock, suitable flanges at suction and delivery side. Pump shall have common shaft for pump and motor. Motor shall be suitable for working on 415 V ± 10%, 3 Ph, 50 Hz A.C. Supply. Motor shall be TEFC type and Pump set shall be suitable for working at various discharge and head requirements as per scope of work. Pump shall be erected onC.C. foundation / cross channels / RSJ frame block with suitable foundation bolts grouted in C.C. foundation block etc. complete in all respect as perspecification, scope of work and direction of Engineer in Charge of following power rating, suitable for prescribed duty conditions mentioned in TD. |
| 2 | 15.0 KW (20 HP) |
| 3 | STAR DELTA STARTER 15.0 KW (20.0 HP)- :For 2 motors (1 W+ 1S) I/C -MCB 63A ,FP, 10 KA, C Curve (1) , Analog Voltmeter 96*96mm ( 0-500V ) (1), Volt Selector Switch (1) , Analog Ammeter 96*96mm ( 0-60A ) (1), Amp. Selector Switch (1), C. T. 60/5A CL 1.0 5VA (3) , Indicating Lights ( Red-1, Yellow -1) (2), Indicating Lights ( Blue - 1 ) (1), Control MCB 6A SP 10 KA C Curve (3) and O/G-MCB 40A ,TP, 10 KA, C Curve (2), Power Cont 25A TP AC3 Duty(2), 2 NO+2 NC Aux. Block(2), Thermal Overload Relay (9-13A )(2), Control MCB 6A SP 10 KA C Curve (2), Single Phase Preventer (2), Indicating Lights (Red- 1, Green - 1, Amber-1)(6), Push Button 22.5 ( Red - 1, Green - 1 )(4), Selector Switch 1 Pole, 2 Way (2), Capacitor 440VAC Heavy Duty MPP Type 7.5Kvar (2), S/D Timer(2) |
| 4 | Supply & Fixing of ISI marked three core PVC flat submersible cableas per IS 694:1990 or amended up to date and conductor as per class 5 of IS 8130:1980including making connection etc. |
| 5 | 3 core 10.0 Sq.mm |
| 6 | Supplying & Installing 100 mm diameter sealed diaphragm bourdon type pressure gauge of range 0 to 10 kg.including all jointing material as per specification with safety cover. |
| 7 | Manually Operated Resilient Seated Sluice Valves of Class PN 1.6 Providing,lowering,aligning,fixinginpositioninpipelineatworksite,DID/F Resilientseated(softseated)SluiceValves(GateValves),Vacuumtight(bubble tight), straight and pocket less body passage of approved make of following class & diacompleteconfirmingtoBS-EN-1171/AWWAC-509andoffollowing specifications:Body & bonnet ofDuctile castiron ofgrade GGG40/GGG50as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2 1985 and subsequent revisions, Wedge of same material as body & shall vulcanisedrubber lined with EPDM (food grade quality) and seals of NBR Face to facedimensionsasperBS5163-89/IS14846/2000(amendeduptodate)/Din 3202F4,Stem/spindleofSSAISI316/410Electrostaticepoxypowder(EP-P)/ Fusion bond epoxy ( Non-Toxic- suitable for drinking water) coated with minimum thicknessof250micronsinsideandoutside,DrilledasperIS1538.Nut-Bolt confirmingtoIS:1363andIS:1367 (Galvanisedsteel)Insertionrubberofblack EPDM 6mm thick. Suitablesupport structure as per directions of EIC, Sluice valves includingall jointing& jointingmaterial, labour,testingandcommissioningalong withpipelineasperTechnicalSpecificationsandasperdirectionofEngineer-in- charge. |
| 8 | 100 mm dia |
| 9 | 150 mm dia |
| 10 | Providing and fixing of flanged/ plain ended MS Specials made from MS sheet strips of relevant IS specification of approved thickness by welding,lowering,laying,aligning,fixinginpositionatalllevel/ depths in trenches complete includingall taxes, material,labour, inside lining, outside coating, testingandcommissioning alongwithpipelineaspertechnicalspecifications anddirection of Engineer-in-charge. |
| 11 | MS pipespecialsup to600mmdia (withminimum5mmthickness sheet) |
| 12 | Dismantling of cement concrete pavement for pipe line line and chambers by mechanical means using pneumatic tools, cutting the peripheral edge by CC cutter, breaking to pieces not exceeding 0.02 cum in volume and stock piling at designated locations and disposal of dismantled materials up to a lead of 1000 meters. Measurement for dismantled trench to be madeas per standard trench width specified in tender document and no extra payment shall be made be made for trench width more than specified, re-handling of material/earth to complete the tasks as per technical specification and scope of work. |
| 13 | Providing and laying in position cement concrete in specified grade over prepared base course complete including finishing, curing, all material, labour, machinery, lighting, guarding for road restoration work in trenches of pipe line and chamber work. Measurement for CC work to be madeas per standard trench width specified in tender document and no extra payment shall be made be made for trench width more than specified,complete work as per technical specification and scope of work. |
| 14 | Plain cement concrete pavementof M-30 Grade |
| 15 | SITC of D/F Full bore type Electromagnetic Flow Meter of approved make of following dia and specifications complete: Media : Water (Raw/ Chlorinated) ,Pressure : up to 1.5MPa, Process temp: - 50 deg C, Flow/Meter Tube : SS 304,Electrode : SS AISI 316L /Hastelloy C276/ Tantalum, Lining Material : Hard Rubber/ Neoprene / Poly-urethane (PU) , Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Cast Aluminium, with anticorrosive paint & provide completely sealed (leak proof) construction as per requirement of IEC 60529, Accuracy : ± 0.5 % M.V.- velocity 0.3 to 10 m/s, Transmitter/ signal convertor Enclosure : Die Cast Aluminium, Power Supply : 80-240 V AC - 50Hz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart,Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parametersand totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) and IP 67 for transmitter/ convertor, including Surge Arrester, if required, and all materials required for making connection etc. complete in all respect as per technical specification and direction of Engineer In-Charge.Note: Rates are exclusive of tail piece / dismantling joints and earth work. |
| 16 | EFM 150 mm |