| 1 | Wiring for light / fan / exhaust fan / call bell point with 2 x1.5 sq. mm pvc insulated Copper conductor cable (FR) in pvc casing and capping complete with 6/10 amps modular type switch, cover plate, surface modular switch board including connection etc as required:- |
| 2 | Medium point:- |
| 3 | Providing and fixing of 3/6 pin 16/20 amps plug point withmodulartype 16/20ampsswitch andsocketincludingconnectionwith 2x2.5 sq. mm PVC insulated Copper conductor cable(FR) on surface modular switch board, earthing the 3rd pin etc. as required:- |
| 4 | Wiring for Circuit/Sub-main wiring with the following sizes PVC insulated copper conductor cable (FR) in PVC casing capping etc. as required. |
| 5 | 2 X 2.5 sq mm |
| 6 | 4 X 6 sq mm |
| 7 | 4 X 10 sq mm |
| 8 | Wiring for Circuit/Sub-main with the following sizes of PVC insulated Copper conductor cable (FR) in existing PVC casing capping/ conduit in recess/ surface including connection etc. as required:- |
| 9 | 1 X 1.5 sq mm |
| 10 | 1 X 2.5 sq mm |
| 11 | 1 X 4.0 sq mm |
| 12 | Supplying and fixing of the following sizes PVC switch boards with cover etc. as required. |
| 13 | 75mm x 75mm (3\" X 3\") :- |
| 14 | 102mm x 178mm (4\" X 7\") :- |
| 15 | Supplying and fixing of the following sizes GI (in recess) and plastic (on surface) modular switch boards etc. as required. |
| 16 | 1-2 module plastic switch board:- |
| 17 | Supplying and fixing of the following sizes modular type cover plates for GI/plastic modular switch boards etc. as required. |
| 18 | 1-2 module |
| 19 | Supplying and fixing of the following modular accessories including necessary connection etc. as required. |
| 20 | 20/25 amps single phase motor starter switch (2M):- |
| 21 | Providingearthing systemwith maintenance free earthing electrode of 50 mm dia & 3 mtr long of dual electrode technology filled with highly conductive compound and back fill compound of 2 nos. 25 kg bag, terminalsize 32mmx 6mm including accessories with masonry enclosure of CIcover plate size 12\"x 12\" having locking arrangement including CC works etc as required:- |
| 22 | Proving and fixing / Drawing 4.06 mm dia (8 SWG) copperwire on surface or inexisting G.I / PVC / Polythene pipe for loop earthing as reqd. |
| 23 | Providng and laying 15mm dia(medium gauge) G.I. pipe for drawing of4.06mm (8SWG) dia G.I./ Copper wire forearth conn. from earth electrodes etc as reqd. |
| 24 | Supplying and installation of change over switch of following ratings with enclosure including necessary connection etc. as required:- |
| 25 | 400 amps FP on load change over switch (Front handle with enclosure):- |
| 26 | Supplying and installation of fuse unit kitkat/ HRC/ HBC of the following ratings in existing main switch/ panel board including necessary connection etc as required:- |
| 27 | 300/320 amps kitkat porcelain fuse unit with base(rewireable) with extended strip:- |
| 28 | Supplying and installation of powder coated steel sheet enclosure (MCB DB) suitable for 240/415 volts MCB/ Isolator/ RCCB (SP/ SPN/ DP/ TP/ TPN/ FP) complete with necessary bus bar, neutral link, din rail, earth bar etc i/c connectionas required. |
| 29 | 4way horizontal TPN MCB DB (Double door):- |
| 30 | 4 way vertical TPN MCB DB suitable for FP MCCB incomer upto 125 amps (Double door):- |
| 31 | Supplying & installation of 10 KA breaking capacity, B/C curve MCB of following ratings in the existing MCB DB including connectionas required:- |
| 32 | 6 to 32 amps SP MCB:- |
| 33 | 40/50/63 amps TP MCB:- |
| 34 | Supplying, installation, testing & commissioning of powder coated prewired panel board suitable for 415 volts TP MCCB as incomer & outgoing including busbar & connection as required of the following ratings & sizes:- |
| 35 | 4 way TP MCCB outgoing & TP MCCB incomer upto 400 amps:- |
| 36 | Supplying, installation, testing & commissioning of powder coated prewired digital meter module complete with ammeter, voltmeter, phase indicator lamp, control fuses, CTs, in the existing panel board including connection etc. as required:- |
| 37 | Supplying, installation, testing & commissioning of powder coated side cable module (1 pair) in the existing panel board including connection etc. as required suitable for the following sizes and ratings:- |
| 38 | 4/6 way outgoing and incomer upto 400 amps :- |
| 39 | Supplying & installation of TP/FP MCCB of following ratings in the existing MCCB enclosure/ panel board including connection etc as required (Ics=100% of Icu with adjustable settings):- |
| 40 | Supplying and fixing of philips Gladius 16 to 100 ampsTP MCCB, Breakingcapacity 16/18KA (Thermal Magnetic):- |
| 41 | 400 amps TP MCCB, Breakingcapacity 36KA (Thermal Magnetic) :- |
| 42 | Supplying and laying of the following sizes XLPE insulated PVC sheathed aluminium conductor armoured cable with necessary connection etc as required. |
| 43 | 3.5 core 185 Sq mm |
| 44 | 3.5 core 35 Sq mm |
| 45 | Excavation of earth for cable trench of 800mm depth & 300mm width in all kinds of soil including back filling of cable trench with the excavated soil with 20cm layer of sand, 3.5 nos bricks per metre for protection including ramming, consolidating to the original shape as per dirrection of Site Engineer :- |
| 46 | Supplying and fixing of Copper terminal ends (LUGS) - long barrel of following sizes: - |
| 47 | 4 sq mm |
| 48 | 6 sq mm |
| 49 | 10 sq mm |
| 50 | Supplying and fixing of aluminium terminal ends (LUGS) - long barrel of following sizes : - |
| 51 | 35 sq mm |
| 52 | 185 sq mm |
| 53 | Supplying and fixing of MS frame made of (25mm x 25mm x 5mm) MS angle with necessary support by (40mm x 6mm) MS flat and 12 mm thick marine plywood on top, grouted on wall with 4 noslegs (25mmx25mmx5mm MS angle20 cm long) finishedwith red oxide and 2 coat synthetic enamel paintincluding necessary cc work, mending the damages & painting etc as required:- |