| 1 | Supplying, Fabrication and Installation of 4 mtr. high pole made out of 65 mm dia NB, B class G.I pipe ISI marked duly welded with MS base plate of size 300 mm x 300 mm x 12 mm thick with stiffner of size 130 mm x60 mm x 5 mm thick ,supplying and fixing of suitable size of braket for mounting the light fitting on the pole,suitable earth stud on base plate ,making suitable size hole in pole at a height of 2.5 meter from base plate for cable entry/exit, painting & numbering of pole, making suitable size hole in base plate for cable entry/exit into the pole and fixing the pole on the existing foundation with the existing nuts-bolts, washers etc. complete as required. |
| 2 | Providing and laying in position 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate)reinforced cement concrete foundation of size450 mm x 450 mm x 1200 mm deep (800 mm below ground level and 400 mm above ground level) including excavation of earth, refilling, providing, cutting, bending and placing in position, reinforcement of cold twisted bars of 12mm. dia-1200mm long (approx) -8Nos, and reinforcement ring of cold twisted bar of 8mm dia -1400mm long (approx) -6 nos, (with suitable spacing) including centering & shuttering as required with providing, fixing and positioning of one set of foundation bolts comprising of 4 nos., 16 mm dia, 750 mm long J-Type MS bolts (Threaded portion shall be galvanized) along with 3 nos. GI nuts and 2 nos. GI washers etc. per bolt and 1 no. anchor plate (3mm thick) of suitable size and providing 63 mm.(O.D) DWC pipe ISI marked for cable entry & exit etc. complete as required. |
| 3 | Supplying, installation, testing and commissioning of45 watt LED street light luminaire with lens, made out of Al.pressure die cast housing enclosed with toughened glass, with IP-66 protection, driver, all accessories including providing of suitable size of wire mesh protection cover for fitting, connection testing etc complete as reqd. |
| 4 | Supply & installationof pole connector box made out of Glass Reinforced Polyester Sheet Moulding Compound to IS : 13410-1992 grade S1 of outside dimensions 280 mm(H) x 170 mm(W)x 115 mm (D) (all the corners of the box should be round & not pointed ones) suitable to mount on 40/50/65/80 mm dia GI pole with the followingprovisions/accessories mounting in box complete as reqd.(i)2 nos. clamps made out of 19mm x 3 mm M.S. strip of suitable length for mounting box on the pole.(ii) Water tight front cover with 2 nos. stainless steel hinges & 1 no. screw for tightening.(iii)4 way, 220 V, 30 A, dough moulded connector (SMC with stainless steel inserts)(iv) 16 amp. Moulded SMC rewireable kit-kat---1 no.(v) Suitable size hole at suitable location on rear wall for cable & wire entry.(vi) Earthing bolt M6 x 20 mm |
| 5 | Supplying of following sizes of XLPE insulated PVC sheathed Al. cond. Armoured power cable of 1.1 KV grade including connection, testing etc. as required. a) 2C x 16 sq. mm |
| 6 | b) 4C X 25 sq. mm |
| 7 | Supplying & drawing following size FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/PVC conduit as required.a)3 x 1.5 sq. mm |
| 8 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size direct in ground including excavation and refiling the trench but excludingsand cushioning, protective covering.a) Upto 35 sq. mm |
| 9 | Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of following size in the existing RCC/HUME/METAL pipe as required.a)Upto 35 sq. mm |
| 10 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/recessed conduit/sub main wiring/cable as required. |
| 11 | Supplying, installation, testing and commissioning of feeder pillar with floor mounted Light control LT feeder pillar cubical type double door of size of 1000 mm x 1000 mm x 300 mm deep duly compartmentalized and with general arrangement made out of 2mm thick CRCA sheet having hinged gasket cover and screwed knobs with double locking arrangement and rain protection covers 100 mm and supported with of MS angle iron legs and bottom frame of size 40mm x 40mm x 6mm x 1mtr. long grouted with 1:3:6 CC foundation and should be 0.7 mtr. above ground level. Legs should be covered with brick walls, connections, inter connections with suitable size of FRLS PVC insulated copper conductor using thimbles wherever required, painting, numbering including supply and fixing of following accessories complete etc. as required.(a)63 Amps. Four Pole MCB (\"C\"-Series), 10kA----1 No.(b)16 Amps. SP MCB (\"C\"-Series), 10 kA------ 6Nos(c) Analogue Timer switch for daily operation and toggle switch forauto/manual --1 No. (d) 32 Amps. AC-3, 3 pole power contactor -----1 No. (e) 30 Ampere 4 way neutral link/connector ------2 Nos. (f) Voltmeter(0-500 Volt) 96mm X 96mm square type with selector switch---1 No (g) Phase Indicating Lamp Set with fuses ----1 Set (h) Danger notice plate -----1 No (i) AI. Bus Bar 100 amp. 4 strip, 300 mm long with sleeve and nut bolts-----1 Set.(j)Ammeter (0-30Amp) 96mm X 96mm square type ----1No.(k)Lifting hook on the top of panel board and lighting arrangement inside the feeder pillar---- 1 No. (l) 32 Amps. TP MCB (\"C\" Series), 10KA- 2 Nos. |
| 12 | Supplying, fabrication and installation of wire mesh protection frame for existing feeder pillar made out of 10 SWG MS wire mesh (75mm x 25mm rectangle nominal) of following sizes with angle iron base frame 40 mm x 40 mm x 6 mm angle iron and with MS strip support of size 35 mm x 6 mm and 0.5 mtr. long leg support of same angle as per drawing including providing of suitable size of door with supply & fixing of godown lock including locking arrangment, painting and grouting of angle iron frame with legs in CC (1:2:4) foundation etc. as approved by Engineer-in-charge etc. complete as required.a) 1.5 mtr (W) x 1.00 mtr(D) x 2.00 mtr. (Height). |
| 13 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 14 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 15 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required..a)63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 16 | Supplying, installation, testing and commissioning of45 watt post top latern (for gate light), with wiremesh protection guard made out of angle iron frame and 10 swg wire of suitable size including suitable accessaoris (like bracket, nut , bolt etc.) for fixing of light connection etc.complete as reqd. |