| 1 | Taking down carefully copper/ aluminium point wiring (light, fan and power socket etc) complete (except concealed conduit) including fittings such as switches ceiling roses, pendent, regulators, sockets, earth plug and socket etc and making good matching to the existing colour to the disturbed surface complete all as specified and directed by Engr-in-charge. |
| 2 | M&L for colour code point wiring FRLS PVC insulated and sheathed cable with 1.5 sqmm copper conductor single core multistandred 1100 volt grade conforming to IS 694 drawn through PVC casing caping with suitable size GI flush box fitted with modular cover plate with frame (inner/ outer plate) for mounting 6 Amps switch with socket on independent board including FRLS 1.5 sqmm earth wire copper insulated wire connected to common earth dolly including making good the existing disturbed surface using wall putty and matching colour emulsion paint all as directed at the site for the following:-Notes:-i. Necessary PVC rigid junction boxes for identifying junction as required on site/ directed by Engineer in charge for point wiring work with PVC dummy plates shall deemed to be included in the quoted rate.ii.Same size wire shall be used for phase, neutral and earth conductor.iii. The wiring shall be done strictly by following proper colour coding using red , blue, yellow for phase, black for neutral and green for earth leads.iv. Size of copper earth wire must be equal to size of current carrying conductor upto size 16 sqmm. |
| 3 | (a) One Light/ fan point controlled by one switch |
| 4 | (b) One 3 pin socket outlet 5 Amps on the same board with other switches |
| 5 | (c) 5 Amps socket point on independent board |
| 6 | All as per item No.02 here in above but 2.5 sqmm for 15 Amps socket on independent board complete all as specified and directed by Engr-in-charge. |
| 7 | All as per item No.02 here in above but 4 sqmm for 16/20 Amps socket on independent board complete all as specified and directed by Engr-in-charge. |
| 8 | All as per item No.02 here in above but one bell/buzzer point controlled by one push button complete all as specified and directed by Engr-in-charge. |
| 9 | M&L for sub main wiring colour coded using 2 runs of 2.5 sqmmFRLS PVC insulated copper conductor 1100 Volts grade conforming to IS specification drawn through PVC casing caping along with 1 run of 2.5 sq mm PVC insulated copper conductor FRLS cable as earth lead connected to common earth dolly, including taking down the unserviceable wiring complete all as specified and directed by Engineer-in-Charge. |
| 10 | M&L for sub main wiring using 2 runs of 4 sqmm FRLS PVC insulated copper conductor 1100 Volts grade conforming to IS specification drawn through and including PVC casing caping along with 1 run of 4 sq mm PVC insulated copper conductor FRLS cable as earth lead connected to common earth dolly, including taking down the unserviceable wiring complete all as specified and directed by Engineer-in-Charge. |
| 11 | M&L for sub main wiring using 2 runs of 6 sq mm FRLS PVC insulated copper conductor 1100 Volts grade conforming to IS specification drawn through and including PVC casing caping along with 1 run of 6 sq mm PVC insulated copper conductor FRLS cable as earth lead connected to common earth dolly, including taking down the unserviceable wiring complete all as specified and directed by Engineer-in-Charge. |
| 12 | M&L for sub main wiring using 4 runs of 10sqmm FRLS PVC insulated copper conductor 1100 Volts grade conforming to IS specification drawn through and including PVC casing caping along with 2 runs of 10 sqmm PVC insulated copper conductor FRLS cable as earth lead connected to common earth dolly, including taking down the unserviceable wiring complete all as specified and directed by Engineer-in-Charge.Notes for item No.06 to 09:-The unit rate quoted shall be deemed to be inclusive of following:-(a) Cutting chases for laying/fixing conduits.(b) Making good of the disturbed surfaces to match with existing one.(c) One run of PVC conduit/casing and caping alongwith number of runs of cables as described in corresponding items will be measured as one unit for payment purpose.(e) The wiring shall be done strictly by following proper colour coding using red, yellow and blue for phase, black for neutral and green for earth leads.(f) Necessary PVC rigid junction boxes for identifying junction as required on site/ directed by Engr-in-charge for point wiring work with PVC dummy plates shall deemed to be included in the quoted rate. |
| 13 | M&L for sub main wiring color coded using 2 runs of 2.5sq mm FRLS PVC insulated copper conductor 1100 Volts grade conforming to IS specification drawn through existing conduit along with 1 run of 2.5 sq mm PVC insulated copper conductor FRLS cable as earth lead connected to common earth dolly, including taking down the unserviceable wiring complete all as specified and directed by Engineer-in-Charge. |
| 14 | M&L for sub main wiring using 2 runs of 4 sq mm FRLS PVC insulated copper conductor 1100 Volts grade conforming to IS specification drawn through in existing conduit along with 1 run of 4 sq mm PVC insulated copper conductor FRLS cable as earth lead connected to common earth dolly, including taking down the unserviceable wiring complete all as specified and directed by Engineer-in-Charge. |
| 15 | M&L for sub main wiring using 2 runs of 6 sq mm FRLS PVC insulated copper conductor 1100 Volts grade conforming to IS specification drawn through in existing conduit along with 1 run of 6 sq mm PVC insulated copper conductor FRLS cable as earth lead connected to common earth dolly, including taking down the unserviceable wiring complete all as specified and directed by Engineer-in-Charge.Notes for item No.10 to 12:-The unit rate quoted shall be deemed to be inclusive of following:-(a) Cutting chases for laying/fixing conduits.(b) Making good of the disturbed surfaces to match with existing one.(c) Number of runs of cables as described in corresponding items will be measured as one unit for payment purpose.(e) The wiring shall be done strictly by following proper colour coding using red, yellow and blue for phase, black for neutral and green for earth leads.(f) Necessary PVC rigid junction boxes for identifying junction as required on site/ directed by Engr-in-charge for point wiring work with PVC dummy plates shall deemed to be included in the quoted rate. |
| 16 | Supply and fix in repair switch, piano, flush mounting type, single pole, one AC 230V grade 5 Amps ISI marked complete all as specified and directed by Engineer-in-Charge. |
| 17 | All as per item No.13 here in above but 15 Amp ISI marked complete all as specified and directed by Engineer-in-Charge. |
| 18 | Supply and fix in repair modular bell push 6 Amps 1 module all as specified and directed by Engineer-in-Charge. |
| 19 | Supply and fix in repair socket outlet 5 amp multi pin type ISI marked complete all as specified and directed by Engineer-in-Charge. |
| 20 | Supply and fix in repair socket outlet 3 pin 15 amp multi pin type ISI marked complete all as specified and directed by Engineer-in-Charge. |
| 21 | Supply and fix in repair fan regulator electronic step up type type 100/120 Watt AC 230 watts complete all as specified and directed by Engineer-in-Charge. |
| 22 | Supply and fix in repair ceiling rose 3 terminal 240V PVC/Poly carbonate insulated body ISI marked complete all as specified and directed by Engineer-in-Charge. |
| 23 | S&F in replacement decorative wall light (Globe Type ) fixture made up of poly carbonate suitable up to 1 x 10 W LED Bulb (B-22 base ) making connection to ceiling rose to fitting with 3 core 1 sqmm copper conductor complete all as specified and directed by Engineer-in charge.Make:- Havells/Philips/crompton/Bajaj/Wipro. |
| 24 | Supply and in replacement of old unserviceable single phase electronic meters temper proof LCD display with polycarbonate cover 230 V, 10- 60Amp, accuracy class-I 50Hz, conforming to IS 13779, IP-54, with parameters to show data, time, current reading, load, PF, voltage and KWH including taking down of old meter and deposit at MES complete all as specified and directed by Engineer-in-Charge. Make:- L&T/ HPL/Elmeasure/SecureNote-:1. Contractor has to deposit Old energy meters to MES for safe custody and it will be MES property and contractor has to submit the old meter Sl no, final reading of old meter, New meter Sl No, initial reading of the new meter for proper accounting of revenue.2. Contractor will provide a additional single phase meter to his concern electrical rep for checking of old U/S or faulty meter at the time of faulty meter complaint received and checking arrangement will be provided in the same quoted rate checking procedure will be carried out as parrallel connection complete as directed by EIC. |
| 25 | Supply and fix in repair call bell ding dong AC 230 volts.complete all as specified and directed by Engineer-in-Charge. |
| 26 | S&F in repair modular switch one way 6 Amps 1 module ISI marked complete all as specified and directed by Engineer-in-Charge. |
| 27 | S&F in repair modular socket 6 Amps 2 module multi pin ISI marked complete all as specified and directed by Engineer-in-Charge. |
| 28 | S&F in repair modular switch one way 16 Amps 1 module ISI marked complete all as specified and directed by Engineer-in-Charge. |
| 29 | S&F in repair modular socket 16 Amps 2 module ISI marked complete all as specified and directed by Engineer-in-Charge. |
| 30 | S&F in repair white cover plate 2/3/4module including taking down the defective one complete all as specified and directed by Engineer-in-Charge. |
| 31 | Supply and fix in repair switch socket combination 5/16 Amps 5 in one flush type ISI marked complete all as specified and directed by Engineer-in-Charge. |
| 32 | Supply and fix in repair MCB single pole AC 240 Volts, 6 to 32 Amps C-Series complete all as specified and directed by Engineer-in-Charge. |
| 33 | Supply and fix in repair MCB single pole & neutral, AC 240 Volts, up to 32 Amps C-Series complete all as specified and directed by Engineer-in-Charge. |
| 34 | Supply and fix in repair MCB Triple pole & neutral, 40 Amps, 415 Volts AC C-Series complete all as specified and directed by Engineer-in-Charge. |
| 35 | Supply and fix in repair RCBO\"s for earth leakage protection double pole 300mA, 40 Amps complete all as specified and directed by Engineer-in-Charge. |
| 36 | Supply and fix in repair modular AC Socket with MCB single pole 25/32Amps C-Series, AC 240 Volts complete all as specified and directed by Engineer-in-Charge. |
| 37 | Supply and fix in repair lamp holder, PVC type suitable for pendent /batten fittingscomplete all as specified and directed by Engineer-in-Charge. |
| 38 | Supply and fix in repair condenser 4 mfd, AC 440 Volts suitable for exhaust fancomplete all as specified and directed by Engineer-in-Charge. |
| 39 | Supply and fix in repair condenser 2.5 mfd, AC 440 Volts suitable for ceiling fan/exhaust fan complete all as specified and directed by Engineer-in-Charge. |
| 40 | Supply and fix in repair fan regulator (modular) electronic step up type 100/120 Watt AC 230 Volts complete all as specified and directed by Engineer-in-Charge. |
| 41 | Supply and fix hyllam sheet 3 mm thick suitable for switch boards etc complete all as specified and directed by Engineer-in-Charge. |
| 42 | Supply and fixing LED lamp 10 Watt B 22 suitable for batten/pendant holdercomplete all as specified and directed by Engineer-in-Charge. |
| 43 | Supply and fix in repair MCB DB SPN 240V double door outdoor type, 12 way with bush bar of appropriate current carrying capacity, neutral link, earth bar and din railcomplete all as specified and directed by Engineer-in-Charge. |
| 44 | Supply and fix in repair MCB DB TPN 415V double door type, 6 way with bush bar of appropriate current carrying capacity, neutral link,earth bar and din railcomplete all as specified and directed by Engineer-in-Charge. |
| 45 | Supply and fix in replacement surface and wall mounted 10 W 2 feet LED batten, out put lumen greater than 100 lumen/watts extruded channel in thermally conductive material for efficient heat dissipation with polycarbonate diffuser and integrated electronic driver, making connection to ceiling rose to fitting with 3 core 1 sqmm copper conductor complete all as specified and directed by Engineer-in -charge.Make:- Crompton/Philips/Wipro/Havells. |
| 46 | S&F in replacement wall mounted 20 W 4 ft LED batten, out put lumen greater than 100 lumens/watt extruded channel in thermally conductive material for efficient heat dissipation with polycarbonate diffuser and integrated electronic driver making connection to ceiling rose to fitting with 3 core 1 sqmm copper conductor complete all as specified and directed by Engineer-in charge.Make:- Crompton/Philips/Wipro/Havells. |
| 47 | Supply and fix in repair LED down light fitting 18W, out put lumen greater than 100 lumen/watts with round shaped surface mounted, PDC aluminium housing and high translucent frosted plastic diffuser makes it a robust luminaire, efficacy 100lm/w with driver making connection to ceiling rose to fitting with 3 core 1 sqmm copper conductor complete all as specified and directed by Engineer-in charge.Make:- Crompton/Philips/Wipro/Havells. |
| 48 | Supply and fix in repair LED Bulk head fitting 9/10W output lumen greater than 100 watts with oval shaped surface mounted LED, PMMA diffuser, powder coated white finish housing with driver making connection to ceiling rose to fitting with 3 core 1 sqmm copper conductor complete all as specified and directed by Engineer-in charge.Make:- Crompton/Philips/Wipro/Havells. |
| 49 | Supply and fix in repair surface mounted 18W luminaire 1x1 Tile, output lumen greater than 100 lumen/watts glare free uniform illumination housing with opel diffuser with colour temp 6000K with driver making connection to ceiling rose to fitting with 3 core 1 sqmm copper conductor complete all as specified and directed by Engineer-in charge.Make:- Crompton/Philips/Wipro/Havells. |
| 50 | Supply and fix in repair recess mounted36W luminer 2x2Tile, out put lumen greater than 100 lumen/wattsGlare free uniform illimination housing with opel diffuser with colour temp 6000K with drivermaking connection to ceiling rose to fitting with 3 core 1 sqmm copper conductor complete all as specified and directed by Engineer-in charge.Make:- Crompton/Philips/Wipro/Havells. |
| 51 | Supply and fix in replacement suspended LED luminaire output lumens greater than 100 lumens/watt provides soft light and glare free 20W LED, making connection to existing ceiling rose to fitting with 3 core, 1 sqmm copper conductor complete all as specified and directed by Engineer-in charge.Make:- Crompton/Philips/Wipro/Havells. |
| 52 | Supply and fix PVC blanker for filling DBs unfilled gap available after fixing MCBs complete all as specified and directed by Engineer-in charge. |
| 53 | Welding / brezzing of broken Panel DB door / meter box door with suitable size of CI/MS hinges suitable for locking arrangement to all type of doors and painting the same door as per existing colour complete all as specified and directed by Engineer-in charge. |
| 54 | Notes:-1. The contractor should visit at site before quoting the tender to know the working condition of the station.2. All requisite safety measures are to be adopted by contractor on site.3. The contractor shall provide and deploy sufficient electricain ( as aproved by GE / Engineer-in-Charge) shall report at 9:00Hrs to JE E/M or Engineer-in-Charge to collect the complaints card in working days and complete the same complaints within 24Hrs.4. The complaints shall be rectified within 24hrs if the complaints is/are not attended or not completed within 24hrs (except repairs / replacement of major items) recovery will be done at Rs. 500/- per complaint per day.5. For Major parts like replacement of MCB DB\"s / MCCB DB\"s should be rectified within three working days, if the contractor not rectify recovery will be done at Rs. 1000/- per complaint per day.6. After completion of Job card , the contractor has to produce Job Card duly signed by user & JE.7. If contractor fail to provide their electricain to attend the complaints then recovery will be done at Rs.1000 per day. |