| Sl. No. | Item Description |
| 1 | Civil work others |
| 2 | Sec.2.0 ELECTRICAL WORKS SITC of mains with 2nos. of1.5sqmm Cu.PVC insulated FRLS flexible wire with ISIapproval for 650 V/1100 Vand 1 no 1.5 sqmmCu. PVCinsulated flexible wires with ISI approval for 650 V/1100 Vas earthwires tobe drawnin 25 mm diameter rigidPVC conduit ofmedium guagehaving ISI amd FIA approval with all necessary accessories. |
| 3 | SITC ofmains with 2nos. of2.5 sqmm Cu.PVC insulated FRLS flexible wire with ISIapproval for 650 V/1100 Vand 1 no 2.5 sqmmCu. PVCinsulated flexible wires with ISI approval for 650 V/1100 Vas earthwires tobe drawnin 25 mm diameter rigidPVC conduit ofmedium guagehaving ISI amd FIA approval with all necessary accessories. |
| 4 | SITC ofmains with2nos.of4sqmm Cu.PVC insulated FRLS flexible wire with ISIapproval for 650 V/1100 Vand 1 no 4.0 sqmmCu. PVCinsulated flexible wires with ISI approval for 650 V/1100 Vas earthwires tobe drawnin 25 mm diameter rigidPVC conduit ofmedium guagehaving ISI amd FIA approval with all necessary accessories. |
| 5 | Supplying and erecting LED indoor fittings with LEDs of wattage 0.2 Watt to 0.5 Watt assembled on single MCPCB,with housing used as a heat sink shall be made of thick sheet Steel conforming to IS: 513/CRCA/ aluminium die castpowder coated and high U.V. & corrosion resistancewith diffuserwith company mark/name 160V to 270V, Power Factor more than 0.95, THD < 15%,CCT3000 K to 6500K, Luminaire efficacy> 85 lumens/watt ,LED LED driver efficiency > 85 %( fitting required LM-79 & LM-80 Certificates)(NOTE: Below description have shown ranges of Wattage capacity of LED fittings.The Engineer incharge may select any wattage capacity between the ranges shown.)22-24 Watts, Surge - 2KV,IP-20, conventional 4 feet ( Cat-III ) |
| 6 | SITC Recessed with trim luminaire Zing with LED (Light Emitting Diode) system power: 24W, Luminous flux of luminaire 2400 lm, Colour temperature of 4000 K, neutral white, CRI > 80, 230 V constant current driver, 70% of luminous flux after 50,000 operating hours; Energy efficient LEDs, Direct light emission, Luminaire housing in die-cast aluminium, Polyester powder black coloured coat applied over a 5- stage pre-treatment, Potruted prismatic diffuser for homogenous light distribution, ZHLS (ZERO HALOGEN LOW SMOKE) internal wiring, electronic control gear, Protection class I, IP 20Ø = 210 mm, Ø (ET) = 196 mm, H = 70 mmZing 24 W LED 3462 |
| 7 | SITC COB based surface mounted downlight luminaire Rea 152 with system power: 25 W, Luminous flux of luminaire 2500 lm, Colour temperature of 4000 K, Neutral white, CRI > 80, 230 V constant current driver, 70% of luminous flux after 50,000 operating hours; Energy efficient LEDs, Direct light emission, Luminaire housing in aluminium, Polyester powder grey coloured coat applied over a 5- stage pre-treatment, Clear acrylic with aluminium reflector and a beam angle of55°, ZHLS (ZERO HALOGEN LOW SMOKE) internal wiring, Electronic control gear, Protection class I, IP 20, Ø = 152 mm, H = 165 mm Rea25 W 152 LED 3054 |
| 8 | SITC COB based surface mounted downlight luminaire Rea 150 with system power: 45W, Luminous flux of luminaire 4500lm, Colour temperature of 4000K, Neutral white, CRI>80, 230 V constant current driver, 70% of luminous flux after 50,000 operating hours; Energy efficient LEDs, Direct light emission, Luminaire housing in aluminium, Polyester powder Black coloured coat applied over a 5- stage pre-treatment, Clear acrylic with reflector with beam angle of 55°, ZHLS(ZERO HALOGEN LOW SMOKE) internal wiring, Electronic control gear,Protection class I, IP 20, Ø = 150 mm, H = 220 mm Rea -45 W LED 3054 |
| 9 | SITC Recessed luminaire Solo with HPE (High Performance Efficiency) LED (Light Emitting Diode), system power: 35 W, Luminous flux of luminaire 3500 lm, colour temperature of 4000 K, Neutral white, CRI > 80, 230V constant current driver, 70% of luminous flux after 50,000 operating hours, Energy efficient LEDs, Direct light emission, CRCA metal housing with ceiling trim, Polyester powder white coloured coat applied over a 5- stage pre - treatment, Opal diffuser for a homogenous light distribution ZHLS (ZERO HALOGEN LOW SMOKE) internal wiring, integral electronic control gear, Protection class I, IP 20, Ø = 330mm, DA(Ø) = 320 mm, H = 106 mm Solo 35 W LED 0113 |
| 10 | SITC Recessed ceiling luminaire Solo with LED(Light Emitting Diode) system power: 25 W, luminous flux of luminaire 2500 lm, colour temperature of 4000 K, neutral White, 230V constant current voltage, CRI > 80, constant current driver, 70% of luminous flux after 50,000 operating hours, energy-efficient LEDs, direct light emission, metal housing with ceiling trim polyester white powder coat appliedover a 5-stage pre-treatment, opal diffuser for glare-free uniform light, integral electronic control gear, Protection class I, IP40, Ø = 330mm, DA(Ø) = 320 mm, H = 106 mmSolo 24 W 330 LED 0113 |
| 11 | Surface-mounted Splash essential with HE-High Efficiency LED (Light Emitting Diode) system power: 20W, the luminous flux of luminaire lm 2400lm, the colour temperature of 4000K, CRI >80, 230V constant current driver, 70% of luminous flux after 50,000 operating hours, energy-efficient LEDs with high CRI, direct light emission, luminaire profile in light grey polycarbonate, Opal diffuser for homogenous light distribution, ZHLS(ZERO HALOGEN LOW SMOKE) internal wiring, electronic control gear Protection class I, IP65 L = 1220mm, B = 80mm, H = 69mmSplash Essential 25 WLED 1022 |
| 12 | Pendant luminaire Volt S Ring 1500 with HE-High Efficiency LED (Light Emitting Diode) system power: 80W, luminous flux of luminaire 7200lm, colour temperature of 4000K, Neutral white, CRI>80, 230V constant current driver, 70% of luminous flux after 50,000 operating hours, direct light emission, curved luminaire profile in aluminium, powder coated White, Prismatic diffuser for uniform illumination, Electronic control gear. Protection class I, IP20 Ø = 1500 mm, B = 55 mm, H = 75 mm, PL max = 1500 mmVolt S Ring80 WATT1500 LED 0910 |
| 13 | COB based LED recessed downlight, Aston, with HPE (High-Performance Efficiency), with system power: 35 W, Luminous flux of luminaire 3500 lm, Colour temperature of 4000 K, Neutral white, CRI > 80, 230V constant current driver, 70% of luminous flux after 50,000 operating hours; energy-efficient LEDs, direct light emission, housing in die-cast aluminium, Polyester powderwhite coloured coat applied over a 5-stage pre-treatment ceiling trim, Clear glass cover with aluminium reflector and a beam angle of 55°, ZHLS (ZERO HALOGEN LOW SMOKE) wiring, Electronic control gear,Protection class II, IP 40,Ø = 162 mm, DA(Ø) = 150 mm, H = 180 mm. Aston 35 WattLED 3138 |
| 14 | XLPE armoured cable of 1100 V grade of copper conductor of following size 3C X 6 SQMM CU ARMEREDCABLE |
| 15 | XLPE armoured cable of 1100 V grade of copper conductor of following size 4C X 16 SQMM CU ARMERED CABLE |
| 16 | Copper cable of 1100V grade of copper conductor of following size 4C x 70 SQM CU flexibal Cable. |
| 17 | Supply of 4000 mm long,keselesdiva combo Decoretiv . GI 76mm & 60mm street light polewith ovelbracker approved shed complete with 316*316mmbase plate as per requirement complete in all respect as per drawing. Junction box 80mm*125mmshall be in concealed manner (inside the pole)withone no 6A SP mcb and 4 way 32A Connector strip suitable to terminate armoured cables w Adequate size cutout with opeanable hinged door should beprovided on pole with necessary gasket to ensure water tight arrangement for pulling cables and installation of mcb, connectors etc,3 core round flexible wire from junction box complete in all respect as perfollowingtypeposttopLightFixturewithall necessaryHadware,InternalWiringwithLamp,Ballastetc.allrequiredaccessoriesCompleteinallrespect. Posttop Light fixture-Make - Keselec VALE 50WWW LED ASYM POST TOP 50 W LED 3000K DECORETIVE IP 66 OPTIC LUMINAIREWITH ALUMINIUM BODY CLEAR ACCYLIC. |
| 18 | Supply of 7000 mm long,keseles Decoretiv .Casting& Gibotam 166mm & top 76 mm Topstreet light polewith Singal Arm1000 mmHenging bracker approved shed complete with 300*300 mmbase plate as per requirement complete in all respect as per drawing. Junction box shall be in concealed manner (inside the pole)withone no 6A SP mcb and 4 way 32A Connector strip suitable to terminate armoured cables w Adequate size cutout with opeanable hinged door should beprovided on pole with necessary gasket to ensure water tight arrangement for pulling cables and installation of mcb, connectors etc,3 core round flexible wire from junction box complete in all respect as peDecorative Light Fixture- following type of LED Pendant type of Luminaires. The housing of the luminaries shall be aluminium spun body suitable for mounting to internally threaded type of designation M30, clear acrylic V diffuser and its cover shall be tempered protective toughened glass.It shall have inbuilt driver with THD <15%;Overvoltage protection,surge voltage protection etc as per .The fixture shall have IP protection of IP65 and impact resistance of IK07.The fixture shall comply50Wattwith Powerfactor>0.9;CRI>70;Colour Temperature3000k,System |
| 19 | Supply, of750mm*16mm j bolt cable entry pipe 8 swg ciol erathing rcc foundation 1000*600*600mmConcrete foundationwith base plate.Excavation for erection of poles as per drawing complete in all respect Pole |
| 20 | ELW 19.00 UPSSupply, Installation, Testing & Commissioning of ON LINE UPS system with 15 mins battery backup and with battery rack complete in all respect. 20KVA UPS 3 ph in 3 ph out for balance load |
| 21 | Supply, Installation, Testing & Commissioning of ON LINE UPS system with 15 mins battery backup and with battery rack complete in all respect. 60KVA UPS 3 ph in 3 ph out for balance load |
| 22 | Supply, Installation, Testing & Commissioning of ON LINE UPS system with 15 mins battery backup and with battery rack complete in all respect. 80KVA UPS 3 ph in 3 ph out for balance load |
| 23 | ELW 20.00 Exit signSITC of Self contained single sided exit sign for wall / ceiling / pendant cantilever mounting with 3 W LED tube for Non maintained battery backup emergency lighting for 2 hours duration.Prolite makeor approved equal in quality and design. |
| 24 | Sec.3.0 Facade LightingSupplying and erecting, testing and commissioning of Non-Pixel Linear flexWattage : 14W/MOperating Voltage : DC24VColour : RGB IP Rating : IP67 |
| 25 | Supplying and erecting, testing and commissioning of Linear washer Wattage :18WOperating Voltage : DC24VColour : RGBW(W=3000K)Diamension: Lenght 1000mmBeam Angle : 15°x55°IP Rating : IP66IK Rating : IK06 |
| 26 | Supplying and erecting, testing and commissioning of Linear washer Wattage :18WOperating Voltage : DC24VColour : RGBW(W=3000K)Diamension: Lenght 1000mmBeam Angle : 15°x55°IP Rating : IP66IK Rating : IK06 |
| 27 | Supplying and erecting, testing and commissioning of Flood light Wattage 12WOperating Voltage : DC24VColour :RGBW(W=3000K)Beam Angle : 45°IP Rating : IP66IK Rating : IK08 |
| 28 | Supplying and erecting, testing and commissioning of Flood lightWattage 24WOperating Voltage : DC24VColour :RGBW(W=3000K)Beam Angle : 15°IP Rating : IP66IK Rating : IK08 |
| 29 | Supplying and erecting, testing and commissioning ofLinear washer Wattage :18WOperating Voltage : DC24VColour : RGBW(W=3000K)Diamension: Lenght 1000mmBeam Angle : 15°x55°IP Rating : IP66IK Rating : IK06 |
| 30 | Supplying and erecting, testing and commissioning of Linear washer Wattage :18WOperating Voltage : DC24VColour : RGBW(W=3000K)Diamension: Lenght 1000mmBeam Angle : 15°x55°IP Rating : IP66IK Rating : IK06 |
| 31 | Supplying and erecting, testing and commissioning of Aluminium ProfileAluminium profile for Linear Flex |
| 32 | Supplying and erecting, testing and commissioning of Accessories Interconnection cable 2 Mtr/ starter cable |
| 33 | Supplying and erecting, testing and commissioning ofPower SupplyAC100~200V input, DC24V output, 200W, constant voltage power supply IP Rating : IP67 |
| 34 | Supplying and erecting, testing and commissioning ofMain controller |
| 35 | Supplying and erecting, testing and commissioning of Sub controller 8 port sub controller |
| 36 | Supplying and erecting, testing and commissioning of Decoder 3ch decoder |
| 37 | Supplying and erecting, testing and commissioning of Splitter 4ch DMX splitter |
| 38 | Supplying and erecting, testing and commissioning of cat -6 utp cableDMX |
| 39 | Supplying and erecting, testing and commissioning ofcontrolig wiriring for fassard |
| 40 | Sec.4.0 Electrical Panel Supplying,unloadingatsite,shiftingtosite,assembling,leveling,grouting,erecting,Testing,& Commissioningcompartmentalizedtype Panelswithpowdercoated fabricatedfromCRCAsheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detailtednerspecifications.The successfultendererwillhave toprepare generalarrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. LAUNDRY PANEL-01 ( SLD ). As per Single line diagram. |
| 41 | Supplying,unloadingatsite,shiftingtosite,assembling,leveling,grouting,erecting,Testing,& Commissioningcompartmentalizedtype Panelswithpowdercoated fabricatedfromCRCAsheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detailtednerspecifications.The successfultendererwillhave toprepare generalarrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. LAUNDRY PANEL-02 ( SLD ). As per Single line diagram. |
| 42 | Supplying,unloadingatsite,shiftingtosite,assembling,leveling,grouting,erecting,Testing,& Commissioningcompartmentalizedtype Panelswithpowdercoated fabricatedfromCRCAsheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detailtednerspecifications.The successfultendererwillhave toprepare generalarrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. MGPS PANEL-13 ( SLD ). As per Single line diagram. |
| 43 | SITC of 100 A FP MCCB with sheet steel metal enclouser with ELR |
| 44 | SITC of 80 A FP MCCB with sheet steel metal enclouser with ELR |
| 45 | Providing of 32 A x 250 V Plug & socket with interlocked switched socket, DP MCB and surface mounting box FOR laundry. |
| 46 | Providing of 32 A x 440 V Plug & socket with interlocked switched socket, FP MCB and surface mounting box FOR laundry. |
| 47 | Providing of 63 A x 440 V Plug & socket with interlocked switched socket, FP MCB and surface mounting box FOR laundry. |
| 48 | Supply, installation, testing and commissioningof hand held portable operator terminals (POT) minimum 7 inch. TFT display with capacitive touch screen type, shall be able to view graphs , alarms , parameters etc. POT shall have integrated web server and a BACnet/ IP web interface to connect a HTML5 browser to a device on the network. POT With all required connectors etcas per technical specification etc. |
| 49 | Field instrumentsSupplying, installing, testing and commissioning of the following sensors/ transmitters. The DDC shall support sensor with4...20 mA, DC 0 ... 10 V, LG-Ni 1000, 2x LG-Ni1000, Pt 1000 , NTC 10k, NTC 100k, 1000 Ohm. Supply, Installation, Testing, Commissioning of Outdoor type Ambient Temperature with Humidity Sensor with radiation shield, IP65 rated(Temp Range -30 to +50 °C, RH: 0-100 %).as per technical specification etc. as required. |
| 50 | Supply, Installation, Testing, Commissioning of Air Differential Pressure switches the for indicating the Blower status ( Min 100- 1000 PA).as per specifcation |
| 51 | Supply, Installation, Testing, Commissioning of Air Differential Pressure switches the for indicating the Filter status (Min 30- 300 PA) as per specifcation |
| 52 | Supply, Installation, Testing, Commissioning of Duct Type Temperature with Humidity Sensor, IP65 rated with RH accuracy 5%, temp accuracy +_ 0.7 deg (-40to 70 Degree) |
| 53 | Supply, Installation, Testing, Commissioning of Air Type Differential Pressure Transmitter( 0-3000 PA) Across AHU/ CSU Blower. |
| 54 | Supply,Installation,Testing,CommissioningofWaterType absolute Pressure Transmitter, range should be Min 0-10Bar, 0-10V Output To know actual pressure in supply line, Output actual pressure of pump. |
| 55 | Supply,Installation,Testing,CommissioningofWaterType Differential Pressure Switch |
| 56 | Supply, Installation, Testing, Commissioning of Immersion Temperature Sensor,IP 65 rated thermister type, LG-Ni 0.15m with SS Thermowell. |
| 57 | Supply, Installation, Testing, Commissioning of Ultrasonic type Flow Meter |
| 58 | Supply, Installation, Testing, Commissioning of Ultrasonic type Level Transmitter (5mtr. Depth ) |
| 59 | Supply,Installation,Testing,CommissioningofWaterType Differential Pressure Sensor |
| 60 | Supply,Installation,Testing,CommissioningofWaterType Water Flow switch |
| 61 | Supply, Installation, Testing, Commissioning of High & Low Level Switch for Cooling Tower (Max 1mtr. Depth ) |
| 62 | Supply, Installation, Testing, Commissioning of Room Type Co2 Monitoring for Fresh Air( Measuring Range :- 0-2000 ppm Co2) |
| 63 | IBMS Cabling-Supplying, laying ,testing and commissioning of2 Core X 1.0 Sqmm Shielded Copper Cable (per I/Opoints hard wired to DDC). as per technical specification etc. as required. |
| 64 | Supplying, laying, testing and commissioning of 4 Core X 1.0 Sqmm UnShielded Flexible Copper Cable (per I/Opoints hard wired to DDC). as per technical specification etc. as required. |
| 65 | Supplying, laying, testing and commissioning of 4 Core X 1.0 Sqmm Shielded Copper Cable (per I/O points hard wired to DDC). as per technical specification etc. as required. |
| 66 | Supplying, laying, testing and commissioning of 2 Core X 1.5 Sqmm ShieldedCopper Cable (per Soft I/O points toDDC). as per technical specification etc. as required. |
| 67 | Supplying, laying ,testing and commissioning of 3 Core X 1.5 Sqmm Flexible Cable (per DDC to UPS Power Supply). as per technical specification etc. as required. |
| 68 | HVAC- VRV SYSTEM Lifting & Shifting, Supply, Installation, Testing, Commissioning of floor mounted top / side discharge type AC Outdoor unit with Variable refrigerant flow system with required indoor units, refrigerant piping, refnet connection, individual controller, Necessary integrator for BMS with open protocol. The quote for the work should include necessary, lifting charges for mounting the Condensing units with rubber pads, first charge of 410A refrigerant and mounting of indoor units and other accessories. The outdoor unit shall be factory assembled, weather proof casing, constructed from heavy gauge mild steel panels and coated with baked enamel finish. The unit should be completely factory wired, tested with all necessary controls. The outdoor unit shall be modular in design and should be allowed for side by side installation. Each modular inverter outdoor shall be having minimum 1 digltal scroll / inverter & 1 fixed scroll compressors , Heat exchanger, condenser fan etc., capable to operate at 3 Phase, 415 +/- 10 % Volts, 50hz power supply.The unit shall be provided with its own microprocessor control panel & electrical compartment with all necessary electrical and control components.Supply of Variable Refrigerant System with all accessories( Make : DAIKIN ) VRF Out-door Units( 60 H.P. ) |
| 69 | 36H.P. |
| 70 | 28H.P. |
| 71 | 16H.P. |
| 72 | 12H.P. |
| 73 | 08H.P. |
| 74 | Indoor Units Wall Mounted type VRF IDU 1.5 TR |
| 75 | Indoor Units Wall Mounted type VRF IDU 2.0 TR |
| 76 | Ceiling mounted 4way-Cassette Type VRF IDU 0.6 TR |
| 77 | Ceiling mounted 4way-Cassette Type VRF IDU 1.5 TR |
| 78 | Ceiling mounted 4way-Cassette Type VRF IDU 2.0 TR |
| 79 | Ceiling mounted 4way-Cassette Type VRF IDU 2.5 TR |
| 80 | Ceiling mounted 4way-Cassette Type VRF IDU 3.3 TR |
| 81 | Ceiling Suspended Ductable type high staic unit 4.0 TR |
| 82 | Ceiling Suspended Ductable type high staic unit 6.0 TR |
| 83 | Ceiling Suspended Ductable type high staic unit 8.0 TR |
| 84 | Remote Controllers Corded Remote Controllers for VRV System to modulationg Temprature and adjust fan speed of indoor unit. ( Cooling Mode ) |
| 85 | Cordless Remote Controllers for VRV System to modulationg Temprature and adjust fan speed of indoor unit. ( Cooling Mode ) |
| 86 | Central Remote Controller for above system comprising of all required Software. PC will be supplied by client. System should control & monitor all installed IDU / ODU. Following should be minimum controlling & monitoring features that system should cover; Start / Stop, Temperature settings, Mode control, Group formation, view alarms, Fault Diagnosis. |
| 87 | All refrigerant joints with insulation |
| 88 | Supply & laying of copper sheilded communication cable as per OEM size. |
| 89 | Supply, installation, Testing& Commissioning of the following components for VRF system All refrigerant copper piping for Variable Refrigerant system having along with insulation and supports, between indoor & outdoor units duly insulated as per specifications. All piping inside the room, inside the vertical shaft & over the terrace shall be properly supported with hanger & exposed piping shall be properly covered with UV treated cloth & should be in closed tray if required with properly supported. The rates shall be included with all control & communication cables for communicating indoor unit to outdoor unit & Central Control Monitors laid in Clamped PVC pipe. The rate shall includes topping up refrigerant for complete system having total refrigerant piping length is for 60 H.P. SYSTEM |
| 90 | Supply, installation, Testing& Commissioning of the following components for VRF system All refrigerant copper piping for Variable Refrigerant system having along with insulation and supports, between indoor & outdoor units duly insulated as per specifications. All piping inside the room, inside the vertical shaft & over the terrace shall be properly supported with hanger & exposed piping shall be properly covered with UV treated cloth & should be in closed tray if required with properly supported. The rates shall be included with all control & communication cables for communicating indoor unit to outdoor unit & Central Control Monitors laid in Clamped PVC pipe. The rate shall includes topping up refrigerant for complete system having total refrigerant piping length is for 36 H.P. SYSTEM |
| 91 | Supply, installation, Testing& Commissioning of the following components for VRF system All refrigerant copper piping for Variable Refrigerant system having along with insulation and supports, between indoor & outdoor units duly insulated as per specifications. All piping inside the room, inside the vertical shaft & over the terrace shall be properly supported with hanger & exposed piping shall be properly covered with UV treated cloth & should be in closed tray if required with properly supported. The rates shall be included with all control & communication cables for communicating indoor unit to outdoor unit & Central Control Monitors laid in Clamped PVC pipe. The rate shall includes topping up refrigerant for complete system having total refrigerant piping length is for 28 H.P. SYSTEM |
| 92 | Supply, installation, Testing& Commissioning of the following components for VRF system All refrigerant copper piping for Variable Refrigerant system having along with insulation and supports, between indoor & outdoor units duly insulated as per specifications. All piping inside the room, inside the vertical shaft & over the terrace shall be properly supported with hanger & exposed piping shall be properly covered with UV treated cloth & should be in closed tray if required with properly supported. The rates shall be included with all control & communication cables for communicating indoor unit to outdoor unit & Central Control Monitors laid in Clamped PVC pipe. The rate shall includes topping up refrigerant for complete system having total refrigerant piping length is for 16 H.P. SYSTEM |
| 93 | Supply, installation, Testing& Commissioning of the following components for VRF system All refrigerant copper piping for Variable Refrigerant system having along with insulation and supports, between indoor & outdoor units duly insulated as per specifications. All piping inside the room, inside the vertical shaft & over the terrace shall be properly supported with hanger & exposed piping shall be properly covered with UV treated cloth & should be in closed tray if required with properly supported. The rates shall be included with all control & communication cables for communicating indoor unit to outdoor unit & Central Control Monitors laid in Clamped PVC pipe. The rate shall includes topping up refrigerant for complete system having total refrigerant piping length is for 12 H.P. SYSTEM |
| 94 | Supply, installation, Testing& Commissioning of the following components for VRF system All refrigerant copper piping for Variable Refrigerant system having along with insulation and supports, between indoor & outdoor units duly insulated as per specifications. All piping inside the room, inside the vertical shaft & over the terrace shall be properly supported with hanger & exposed piping shall be properly covered with UV treated cloth & should be in closed tray if required with properly supported. The rates shall be included with all control & communication cables for communicating indoor unit to outdoor unit & Central Control Monitors laid in Clamped PVC pipe. The rate shall includes topping up refrigerant for complete system having total refrigerant piping length is for 08 H.P. SYSTEM |
| 95 | Mechanical Ventilation for ToiletSupply, Installation, Testing & Commissioning of ceiling suspended type Inline Exhaust Air Fan, as per specificationswith site fabricated GI required Gauge thick ducting and alluminium outlet grills & louveres.400 CFM Inline Axial Exhuast Fan for Toilet ( Floor Mounted ) |
| 96 | Mechanical Ventilation for ToiletSupply, Installation, Testing & Commissioning of ceiling suspended type Inline Exhaust Air Fan, as per specificationswith site fabricated GI required Gauge thick ducting and alluminium outlet grills & louveres.1000 CFM Inline Axial Exhuast Fan for Toilet ( Floor Mounted ) |
| 97 | Mechanical Ventilation for ToiletSupply, Installation, Testing & Commissioning of ceiling suspended type Inline Exhaust Air Fan, as per specificationswith site fabricated GI required Gauge thick ducting and alluminium outlet grills & louveres.1100 CFM Inline Axial Exhuast Fan for Dirty Room & Store Area (Floor Mounted ) |
| 98 | Mechanical Ventilation for ToiletSupply, Installation, Testing & Commissioning of ceiling suspended type Inline Exhaust Air Fan, as per specificationswith site fabricated GI required Gauge thick ducting and alluminium outlet grills & louveres.1100 CFM Inline Axial Fresh Air Fan for Dirty Room & Store Area ( Floor Mounted ) |
| 99 | Mechanical Ventilation for ToiletSupply, Installation, Testing & Commissioning of ceiling suspended type Inline Exhaust Air Fan, as per specificationswith site fabricated GI required Gauge thick ducting and alluminium outlet grills & louveres.1200 CFM Inline Axial Fresh Air Fan for Room & Passage Area (Floor Mounted ) |
| 100 | Mechanical Ventilation for ToiletSupply, Installation, Testing & Commissioning of ceiling suspended type Inline Exhaust Air Fan, as per specificationswith site fabricated GI required Gauge thick ducting and alluminium outlet grills & louveres.1800 CFM Inline Axial Fresh Air Fan for Room & Passage Area (Floor Mounted ) |
| 101 | M. S. structure for installing VRF / DX outdoor units duly epoxy coated / galvanized. |
| 102 | Fire Retardant Canvass connections |
| 103 | Rigid UPVC drain pipe of 10 Kg/cm2. rating with 9 mm thick.nitrile rubber insulation.32mm dia. |
| 104 | Rigid UPVC drain pipe of 10 Kg/cm2. rating with 9 mm thick.nitrile rubber insulation.25 mm dia. |
| 105 | Rigid UPVC drain pipe of 10 Kg/cm2. rating with 9 mm thick.nitrile rubber insulation.19 mm dia. |
| 106 | insulation work Supplying, fixing Duct Acoustic Insulation of open cell nitrile rubber sheet having density of 180-220 kg/m3 and recommanded thickness of 15 mm. It shall be fixed inside of the duct with the help of adhesive complete as per specifications and as required.15mm |
| 107 | insulation work Supply & Installation of Under Deck Insulation with Class ‘O’ Nitrile Rubber with tough Aluminum foil facing & as per detail specifications - 25mm |
| 108 | Refrigerent charge of VRV system with Nitrogen pressure testing, vaccume test & all neccesary activity with eco-friendly refrigerent gas as per site conditions. |
| 109 | Design, Supply, Lifting & Shifting at actual proposed location of site, Installation, Testing & Commissioning of Floor Mounted Air Handling Units as specified below; Double Skinned powder coatedinner & outer skin of 0.6 mm & 43 mm thick, 40 kg / m3 PUF Sandwitched insulated aluminium sectionalized construction Comprising of Fan section with 65 mm static best efficiency Plug type Fan with variable frequency driven (VFD)by IP55 / 4P TEFC Fan Motor / fire resistant flexible fan outlet connection, The AHU shall comprise filter section with MERV 6 pre filter for return & fresh air, Fine filter section with MERV 12 filter, Cooling coil section with Chilled water Coil complete with Copper tube 12 FPI AL finned 4R deep chilled water cooling Coils, SS 304 condensate drain pan duly insulated with 15 mm thick cross linked polymer Nitrile rubber insulation, with Mixing box with Aluminium Aerofoil damper for supply, return & Fresh air, necessary vibration isolation arrangement by providing spring isolators ; Motor selection tosuit the below capacity for each AHU rating by AC Vendor including transmission losses. ;Electrical Starter suitable for Respective AHUs, Panel supplied with matching rating for SA Fan motor, required DC Supply for control Valve, including short circuit / overload MCB protection,Motor Status On / Off / Trip, command, Automanual, Status contacts for remote operation through Operating Panels, Temperature Indicator availability on Panel with BAS compatiibility; Starter panel shall be minimum 14G MS powder coated with ventilation fan, inside light and duly internally wired and tested, Unit shall be supplied with Digital Thermostat with water proof casing BMS compatible with interface modbus / bacnet protocol to connect the BMS panel ; Prices to include dispatch of AHU in Semi-knocked down condition, assembly at site and lifting / shifting to actual locations as per layouts; Performance to be complied - common for below AHUs: dB<=60 at 3 M distance; Price shall be complete with electrical Starters for each AHU matching the motor ratings and as specified above ; AHU dimensions, configuration (top discharge / side discharge), pipe connection side & door side shall be tailor made as per final layout and space constraints. No extra claim shall be payable for such customisation; Schedule below shows.(With 5 Micron Filteration)4220 CFM 10.64 TR for PICU Ward |
| 110 | Design, Supply, Lifting & Shifting at actual proposed location of site, Installation, Testing & Commissioning of Floor Mounted Air Handling Units as specified below; Double Skinned powder coatedinner & outer skin of 0.6 mm & 43 mm thick, 40 kg / m3 PUF Sandwitched insulated aluminium sectionalized construction Comprising of Fan section with 65 mm static best efficiency Plug type Fan with variable frequency driven (VFD)by IP55 / 4P TEFC Fan Motor / fire resistant flexible fan outlet connection, The AHU shall comprise filter section with MERV 6 pre filter for return & fresh air, Fine filter section with MERV 12 filter, Cooling coil section with Chilled water Coil complete with Copper tube 12 FPI AL finned 4R deep chilled water cooling Coils, SS 304 condensate drain pan duly insulated with 15 mm thick cross linked polymer Nitrile rubber insulation, with Mixing box with Aluminium Aerofoil damper for supply, return & Fresh air, necessary vibration isolation arrangement by providing spring isolators ; Motor selection tosuit the below capacity for each AHU rating by AC Vendor including transmission losses. ;Electrical Starter suitable for Respective AHUs, Panel supplied with matching rating for SA Fan motor, required DC Supply for control Valve, including short circuit / overload MCB protection,Motor Status On / Off / Trip, command, Automanual, Status contacts for remote operation through Operating Panels, Temperature Indicator availability on Panel with BAS compatiibility; Starter panel shall be minimum 14G MS powder coated with ventilation fan, inside light and duly internally wired and tested, Unit shall be supplied with Digital Thermostat with water proof casing BMS compatible with interface modbus / bacnet protocol to connect the BMS panel ; Prices to include dispatch of AHU in Semi-knocked down condition, assembly at site and lifting / shifting to actual locations as per layouts; Performance to be complied - common for below AHUs: dB<=60 at 3 M distance; Price shall be complete with electrical Starters for each AHU matching the motor ratings and as specified above ; AHU dimensions, configuration (top discharge / side discharge), pipe connection side & door side shall be tailor made as per final layout and space constraints. No extra claim shall be payable for such customisation; Schedule below shows.(With 5 Micron Filteration)6245 CFM & 14.77 TR for NICU ward/Nurse station |
| 111 | Design, Supply, Lifting & Shifting at actual proposed location of site, Installation, Testing & Commissioning of Floor Mounted Air Handling Units as specified below; Double Skinned powder coated inner & outer skin of 0.6 mm & 43 mm thick, 40 kg / m3 PUF Sandwitched insulated aluminium sectionalized construction Comprising of Fan section with 50 mm static best efficiency Plug type Fan driven by suitable pole Eff - 1 TEFC Motor with Drive Package driven by IP55 / 4P TEFC Fan Motor / fire resistant flexible fan outlet connection, The AHU shall comprise filter section with Air filtering media with 10 micron pre filter, Cooling coil section with Chilled water Coil complete with Copper tube 13 FPI AL finned 4R deep chilled water cooling Coils, SS 304 condensate drain pan duly insulated with 15 mm thick cross linked polymer Nitrile rubber insulation, with Mixing box with Aluminium Aerofoil damper for supply, return & Fresh air, necessary vibration isolation arrangement by providing spring isolators ; Motor selection to suit the below capacity for each AHU rating by AC Vendor including transmission losses. ;Electrical Starter suitable for Respective AHUs, Panel supplied with matching rating for SA Fan motor, required DC Supply for control Valve, including short circuit / overload MCB protection,Motor Status On / Off / Trip, command, Automanual, Status contacts for remote operation through Operating Panels, Temperature Indicator availability on Panel with BAS compatiibility; Starter panel shall be minimum 14G MS powder coated with ventilation fan (only for VFD AHU Panels), inside light and duly internally wired and tested, Unit shall be supplied with Digital Thermostat withwater proof casing BMS compatible with interface modbus / bacnet protocol to connect the BMS panel ; Pricesto include dispatch of AHU in Semi-knocked down condition, assembly at site and lifting / shifting to actual locations as per layouts; Performance to be complied - common for below AHUs: dB<=60 at 3 M distance; Price shall be complete with electrical Starters for each AHU matching the motor ratings and as specified above ; AHU dimensions, configuration (top discharge / side discharge), pipe connection side & door side shall be tailor made as per final layout and space constraints. No extra claim shall be payable for such customisation; Schedule below shows.4865 CFM & 17.8 TR |
| 112 | Design, Supply, Lifting & Shifting at actual proposed location of site, Installation, Testing & Commissioning of Floor Mounted Air Handling Units as specified below; Double Skinned powder coated inner & outer skin of 0.6 mm & 43 mm thick, 40 kg / m3 PUF Sandwitched insulated aluminium sectionalized construction Comprising of Fan section with 50 mm static best efficiency Plug type Fan driven by suitable pole Eff - 1 TEFC Motor with Drive Package driven by IP55 / 4P TEFC Fan Motor / fire resistant flexible fan outlet connection, The AHU shall comprise filter section with Air filtering media with 10 micron pre filter, Cooling coil section with Chilled water Coil complete with Copper tube 13 FPI AL finned 4R deep chilled water cooling Coils, SS 304 condensate drain pan duly insulated with 15 mm thick cross linked polymer Nitrile rubber insulation, with Mixing box with Aluminium Aerofoil damper for supply, return & Fresh air, necessary vibration isolation arrangement by providing spring isolators ; Motor selection to suit the below capacity for each AHU rating by AC Vendor including transmission losses. ;Electrical Starter suitable for Respective AHUs, Panel supplied with matching rating for SA Fan motor, required DC Supply for control Valve, including short circuit / overload MCB protection,Motor Status On / Off / Trip, command, Automanual, Status contacts for remote operation through Operating Panels, Temperature Indicator availability on Panel with BAS compatiibility; Starter panel shall be minimum 14G MS powder coated with ventilation fan (only for VFD AHU Panels), inside light and duly internally wired and tested, Unit shall be supplied with Digital Thermostat withwater proof casing BMS compatible with interface modbus / bacnet protocol to connect the BMS panel ; Pricesto include dispatch of AHU in Semi-knocked down condition, assembly at site and lifting / shifting to actual locations as per layouts; Performance to be complied - common for below AHUs: dB<=60 at 3 M distance; Price shall be complete with electrical Starters for each AHU matching the motor ratings and as specified above ; AHU dimensions, configuration (top discharge / side discharge), pipe connection side & door side shall be tailor made as per final layout and space constraints. No extra claim shall be payable for such customisation; Schedule below shows.11935 CFM & 26.43 TR |
| 113 | Design, Supply, Lifting & Shifting at actual proposed location of site, Installation, Testing & Commissioning of Floor Mounted Air Handling Units as specified below; Double Skinned powder coated inner & outer skin of 0.6 mm & 43 mm thick, 40 kg / m3 PUF Sandwitched insulated aluminium sectionalized construction Comprising of Fan section with 50 mm static best efficiency Plug type Fan driven by suitable pole Eff - 1 TEFC Motor with Drive Package driven by IP55 / 4P TEFC Fan Motor / fire resistant flexible fan outlet connection, The AHU shall comprise filter section with Air filtering media with 10 micron pre filter, Cooling coil section with Chilled water Coil complete with Copper tube 13 FPI AL finned 4R deep chilled water cooling Coils, SS 304 condensate drain pan duly insulated with 15 mm thick cross linked polymer Nitrile rubber insulation, with Mixing box with Aluminium Aerofoil damper for supply, return & Fresh air, necessary vibration isolation arrangement by providing spring isolators ; Motor selection to suit the below capacity for each AHU rating by AC Vendor including transmission losses. ;Electrical Starter suitable for Respective AHUs, Panel supplied with matching rating for SA Fan motor, required DC Supply for control Valve, including short circuit / overload MCB protection,Motor Status On / Off / Trip, command, Automanual, Status contacts for remote operation through Operating Panels, Temperature Indicator availability on Panel with BAS compatiibility; Starter panel shall be minimum 14G MS powder coated with ventilation fan (only for VFD AHU Panels), inside light and duly internally wired and tested, Unit shall be supplied with Digital Thermostat withwater proof casing BMS compatible with interface modbus / bacnet protocol to connect the BMS panel ; Pricesto include dispatch of AHU in Semi-knocked down condition, assembly at site and lifting / shifting to actual locations as per layouts; Performance to be complied - common for below AHUs: dB<=60 at 3 M distance; Price shall be complete with electrical Starters for each AHU matching the motor ratings and as specified above ; AHU dimensions, configuration (top discharge / side discharge), pipe connection side & door side shall be tailor made as per final layout and space constraints. No extra claim shall be payable for such customisation; Schedule below shows.2000 CFM & 4.0 TRfor Septic Dialysis at Second Floor |
| 114 | Treaed Fresh Air UnitDesign, Supply, Lifting & Shifting at actual proposed location of site, Installation, Testing, Commissioning and Field Performance Validation of Floor Mounted / Loft Mounted Treated Fresh Air Unit as specified below; Double Skinned with inner & powder coated outer skin of 0.8 mm, Density 40 Kg / m³ & 40 mm thick PUF Sandwitched insulated sectionalized construction Comprising of Fan section with best efficiency Plug Fan driven by suitable pole Eff - 1 Motor with VFD, IP55 / 4P TEFC Fan Motor / fire resistant flexible fan outlet connection, The AHU shall comprise filter section with 20+10 micron pre filter, Cooling coil section complete with Copper tube 13 FPI AL finned 6 / 8 R deep DX cooling Coils, SS 304 condensate drain pan duly insulated with 15 mm thick cross linked polymer Nitrile rubber insulation, necessary vibration isolation arrangement by providing spring isolators;Motor selection to suit the below capacity for each AHU rating by AC Vendor including transmission losses. ; Electrical Panel supplied with matching rating for Fan motor, including short circuit / overload MCB protection,Motor Status On / Off / Trip, command, Automanual, Status contacts for remote operation through Operating Panels, Temperature Indicator availability on Panel with BAS compatiibility; Panel shall be minimum 14G MS powder coated with ventilation fan, inside light and duly internally wired and tested, 5 RMT. Cables from AHU Panel to AHU, UNit shall be supplied with Digital Fan Coil Thermostat with Fibre water proof casing BMS compatible Temp control thermostat with interface modbus protocol to connect the DDC panel (230V operating / Power On / Off provision, 3 speed fan switch & Temp Edit facility / Digital Temp Display) ;Prices to include dispatch of AHU in Semi-knocked down condition, assembly at site and lifting / shifting to actual locations as per layouts; Performance to be complied - common for below AHUs: Fan Exit velocity<=1800 FPM; Coil Face Velocity=500 FPM max; Filter Face=400 FPM max; dB<=60 at 1 M distance.Price shall be complete with alluminium anodized duct dampers along with fire retardant canvass connections for supply & Fresh air; AHU dimensions, configuration (single-tier / double-tier, top discharge / side discharge), pipe connection side & door side shall be tailor made as per final layout and space constraints. No extra claim shall be payable for such customisation; Price shall includes AHU kit With electronic expansion valve, microprosser & necessary things to connect outdoor units of Variable Refrigerant System as specified below -6.0 TR / 1600 CFM @ 50 mm Static Capacity for 8 HP VRV ODU |
| 115 | 9.0 TR / 2500 CFM @ 50 mm Static Capacity for 12 HP VRV ODU |
| 116 | 12.0 TR / 3200 CFM @ 50 mm Static Capacity for 16 HP VRV ODU |
| 117 | Design, Supply, Lifting & Shifting at actual proposed location of site, Installation, Testing, Commissioning and Field Performance Validation of Decorative Wall Mounted type Chilled Water based High Wall type Fan Coil Units with energy saving Single Phase BLDC motor / EC Motor (Electronically Commuted Motor),Filter section with prefilters, Hydrophilic Al fins and Copper Chilled / HotWater multi step Cooling Coil section with minimum 2 Row and minimum 13 FPI Chilled Water Cooling Coil, fixed outside FCU, Cu piping with required couplings to fit CHW field In / Out piping; All piping are to be insulated with closed cell elastomeric nitirile rubber insulation. Unit shall be supplied with Digital Display type cordless remote and capable of connecting with BMS with interface modbus protocol to connect the DDC panel (230V operating / Power On / Off provision, 3 speed fan switch & Temp Edit facility / Digital Temp Display) and supplied with 10 RMT cable from Controller to FCU as required. The Performance of units should be certified by a reputed third party agency and available for witness testing facility at manufacturer\"s factory.400 CFM (HI WALL) |
| 118 | Supply, installation, testing and commissioning of cabinet type Floor Mounted / Loft Mounted Type single skinned Centrifugal Exhuast Air Unit; unit shall have leakproof canvass connection along with damper at suction side & descharge side cowl; ready to start unit hooked upwith 4P TEFC with IP 55 protection motor with pully / belt drive arrangement on adjustable frame; fan motor assembly mounted on corrossion proof-painted MS baseframe; baseframe to rest on vibration isolation pads. The unit shall be supplied with Starter Panel of required motor capacity.3900 CFM / 40mm Static Pressure for Toilet |
| 119 | Supply, installation, testing and commissioning of cabinet type Floor Mounted / Loft Mounted Type single skinned Centrifugal Exhuast Air Unit; unit shall have leakproof canvass connection along with damper at suction side & descharge side cowl; ready to start unit hooked upwith 4P TEFC with IP 55 protection motor with pully / belt drive arrangement on adjustable frame; fan motor assembly mounted on corrossion proof-painted MS baseframe; baseframe to rest on vibration isolation pads. The unit shall be supplied with Starter Panel of required motor capacity.500 CFM / 25 mm SP for Dirty Utility Exhaust |
| 120 | Sec Air Moving Equipment Design, Supply, Lifting & Shifting at actual proposed location of site, Installation, Testing & Commissioning of Floor Mounted Air Handling Units as specified below; Double Skinned powder coatedinner & outer skin of 0.6 mm & 43 mm thick, 40 kg / m3 PUF Sandwitched insulated aluminium sectionalized construction Comprising of Fan section with 65 mm static best efficiency Plug type Fan with variable frequency driven (VFD)by IP55 / 4P TEFC Fan Motor / fire resistant flexible fan outlet connection, The AHU shall comprise filter section with MERV 6 pre filter for return & fresh air, Fine filter section with MERV 12 filter, Cooling coil section with Chilled water Coil complete with Copper tube 12 FPI AL finned 4R deep chilled water cooling Coils, SS 304 condensate drain pan duly insulated with 15 mm thick cross linked polymer Nitrile rubber insulation, with Mixing box with Aluminium Aerofoil damper for supply, return & Fresh air, necessary vibration isolation arrangement by providing spring isolators ; Motor selection to suit the below capacity for each AHU rating by AC Vendor including transmission losses. ; Electrical Starter suitable for Respective AHUs, Panel supplied with matching rating for SA Fan motor, required DC Supply for control Valve, including short circuit / overload MCB protection,Motor Status On / Off / Trip, command, Automanual, Status contacts for remote operation through Operating Panels, Temperature Indicator availability on Panel with BAS compatiibility; Starter panel shall be minimum 14G MS powder coated with ventilation fan, inside light and duly internally wired and tested, Unit shall be supplied with Digital Thermostat withwater proof casing BMS compatible with interface modbus / bacnet protocol to connect the BMS panel ; Prices to include dispatch of AHU in Semi-knocked down condition, assembly at site and lifting / shifting to actual locations as per layouts; Performance to be complied - common for below AHUs: dB<=60 at 3 M distance; Price shall be complete with electrical Starters for each AHU matching the motor ratings and as specified above ; AHU dimensions, configuration (top discharge / side discharge), pipe connection side & door side shall be tailor made as per final layout and space constraints. No extra claim shall be payable for such customisation; Schedule below shows.(With 5 Micron Filteration)11350 CFM / 27.70 TR For PICU, NICU, Nurse Station & Passage at Ground Floor |
| 121 | Design, Supply, Lifting & Shifting at actual proposed location of site, Installation, Testing & Commissioning of Floor Mounted Air Handling Units as specified below; Double Skinned powder coatedinner & outer skin of 0.6 mm & 43 mm thick, 40 kg / m3 PUF Sandwitched insulated aluminium sectionalized construction Comprising of Fan section with 65 mm static best efficiency Plug type Fan with variable frequency driven (VFD)by IP55 / 4P TEFC Fan Motor / fire resistant flexible fan outlet connection, The AHU shall comprise filter section with MERV 6 pre filter for return & fresh air, Fine filter section with MERV 12 filter, Cooling coil section with Chilled water Coil complete with Copper tube 12 FPI AL finned 4R deep chilled water cooling Coils, SS 304 condensate drain pan duly insulated with 15 mm thick cross linked polymer Nitrile rubber insulation, with Mixing box with Aluminium Aerofoil damper for supply, return & Fresh air, necessary vibration isolation arrangement by providing spring isolators ; Motor selection to suit the below capacity for each AHU rating by AC Vendor including transmission losses. ; Electrical Starter suitable for Respective AHUs, Panel supplied with matching rating for SA Fan motor, required DC Supply for control Valve, including short circuit / overload MCB protection,Motor Status On / Off / Trip, command, Automanual, Status contacts for remote operation through Operating Panels, Temperature Indicator availability on Panel with BAS compatiibility; Starter panel shall be minimum 14G MS powder coated with ventilation fan, inside light and duly internally wired and tested, Unit shall be supplied with Digital Thermostat withwater proof casing BMS compatible with interface modbus / bacnet protocol to connect the BMS panel ; Prices to include dispatch of AHU in Semi-knocked down condition, assembly at site and lifting / shifting to actual locations as per layouts; Performance to be complied - common for below AHUs: dB<=60 at 3 M distance; Price shall be complete with electrical Starters for each AHU matching the motor ratings and as specified above ; AHU dimensions, configuration (top discharge / side discharge), pipe connection side & door side shall be tailor made as per final layout and space constraints. No extra claim shall be payable for such customisation; Schedule below shows.(With 5 Micron Filteration)4300 CFM / 6.12 TR With 1.50 kW Strip Heaters & Humidistate For CT Scan Room at Ground Floor |
| 122 | Design, Supply, Lifting & Shifting at actual proposed location of site, Installation, Testing & Commissioning of Floor Mounted Air Handling Units as specified below; Double Skinned powder coatedinner & outer skin of 0.6 mm & 43 mm thick, 40 kg / m3 PUF Sandwitched insulated aluminium sectionalized construction Comprising of Fan section with 65 mm static best efficiency Plug type Fan with variable frequency driven (VFD)by IP55 / 4P TEFC Fan Motor / fire resistant flexible fan outlet connection, The AHU shall comprise filter section with MERV 6 pre filter for return & fresh air, Fine filter section with MERV 12 filter, Cooling coil section with Chilled water Coil complete with Copper tube 12 FPI AL finned 4R deep chilled water cooling Coils, SS 304 condensate drain pan duly insulated with 15 mm thick cross linked polymer Nitrile rubber insulation, with Mixing box with Aluminium Aerofoil damper for supply, return & Fresh air, necessary vibration isolation arrangement by providing spring isolators ; Motor selection to suit the below capacity for each AHU rating by AC Vendor including transmission losses. ; Electrical Starter suitable for Respective AHUs, Panel supplied with matching rating for SA Fan motor, required DC Supply for control Valve, including short circuit / overload MCB protection,Motor Status On / Off / Trip, command, Automanual, Status contacts for remote operation through Operating Panels, Temperature Indicator availability on Panel with BAS compatiibility; Starter panel shall be minimum 14G MS powder coated with ventilation fan, inside light and duly internally wired and tested, Unit shall be supplied with Digital Thermostat withwater proof casing BMS compatible with interface modbus / bacnet protocol to connect the BMS panel ; Prices to include dispatch of AHU in Semi-knocked down condition, assembly at site and lifting / shifting to actual locations as per layouts; Performance to be complied - common for below AHUs: dB<=60 at 3 M distance; Price shall be complete with electrical Starters for each AHU matching the motor ratings and as specified above ; AHU dimensions, configuration (top discharge / side discharge), pipe connection side & door side shall be tailor made as per final layout and space constraints. No extra claim shall be payable for such customisation; Schedule below shows.(With 5 Micron Filteration)6850 CFM / 14.10 TR For Pre Op Room and Corridor at Second Floor |
| 123 | Design, Supply, Lifting & Shifting at actual proposed location of site, Installation, Testing, Commissioning and Field Performance Validation of Ceiling Suspended ChilledWater Fan Coil Units as specified below with; Single Skin Fan Coil Units in standard construction with Fan section with DIDW multi blowers & energy saving Single Phase BLDC motor/ EC Motor (Electronically Commuted Motor), Filter section with prefilters, Hydrophilic Al type Copper Coil section with minimum 3 Rows and minimum 13 FPI Chilled / Hot Water Cooling Coil, pre-assembled valve station with set of brass ball valve with \"Y\" strainer set, Insulated extended L shaped Drain Pan, supplied with pre-calibrated matching size 2 way / Pressure independent modulating cum balancing valve of minimum PN25 rating with P/T plugs and minimum IP54 t electrothermic / motoric modular actuator (0 to 10 Volt DC Signal), fixed on FCU Cu piping with required couplings and ends flanged to fit CHW field In / Out piping and its compatible 24VAC control transformer; All valve assemblies are to be insulated with closed cell elastomeric nitrile rubber insulation. UNit shall be supplied with Digital Fan Coil Thermostat with Fibre water proof casing BMS compatible with interface modbus protocol to connect the DDC panel (230V operating / Power On / Off provision, 3 speed fan switch & Temp Edit facility / Digital Temp Display) and supplied with 10 RMT cable from Controller to FCU as required. The Performance of units should be certified by a reputed third party agency and available for witness testing facility at manufacturer\"s factory.500 CFM |
| 124 | Design, Supply, Lifting & Shifting at actual proposed location of site, Installation, Testing, Commissioning and Field Performance Validation of Ceiling Suspended ChilledWater Fan Coil Units as specified below with; Single Skin Fan Coil Units in standard construction with Fan section with DIDW multi blowers & energy saving Single Phase BLDC motor/ EC Motor (Electronically Commuted Motor), Filter section with prefilters, Hydrophilic Al type Copper Coil section with minimum 3 Rows and minimum 13 FPI Chilled / Hot Water Cooling Coil, pre-assembled valve station with set of brass ball valve with \"Y\" strainer set, Insulated extended L shaped Drain Pan, supplied with pre-calibrated matching size 2 way / Pressure independent modulating cum balancing valve of minimum PN25 rating with P/T plugs and minimum IP54 t electrothermic / motoric modular actuator (0 to 10 Volt DC Signal), fixed on FCU Cu piping with required couplings and ends flanged to fit CHW field In / Out piping and its compatible 24VAC control transformer; All valve assemblies are to be insulated with closed cell elastomeric nitrile rubber insulation. UNit shall be supplied with Digital Fan Coil Thermostat with Fibre water proof casing BMS compatible with interface modbus protocol to connect the DDC panel (230V operating / Power On / Off provision, 3 speed fan switch & Temp Edit facility / Digital Temp Display) and supplied with 10 RMT cable from Controller to FCU as required. The Performance of units should be certified by a reputed third party agency and available for witness testing facility at manufacturer\"s factory.600 CFM |
| 125 | Design, Supply, Lifting & Shifting at actual proposed location of site, Installation, Testing, Commissioning and Field Performance Validation of Decorative Wall Mounted type Chilled Water based High Wall type Fan Coil Units with energy saving Single Phase BLDC motor / EC Motor (Electronically Commuted Motor),Filter section with prefilters, Hydrophilic Al fins and Copper Chilled / HotWater multi step Cooling Coil section with minimum 2 Row and minimum 13 FPI Chilled Water Cooling Coil, combination of Automatic/ Dynamic Balancing valve and an in-built2 way ON / OFF control valve of minimum PN 16 rating with pair of brass ball valve with \"Y\" strainer set, fixed outside FCU, Cu piping with required couplings to fit CHW field In / Out piping; All piping are to be insulated with closed cell elastomeric nitirile rubber insulation. Unit shall be supplied with Digital Display type cordless remote and capable of connecting with BMS with interface modbus protocol to connect the DDC panel (230V operating / Power On / Off provision, 3 speed fan switch & Temp Edit facility / Digital Temp Display) and supplied with 10 RMT cable from Controller to FCU as required. The Performance of units should be certified by a reputed third party agency and available for witness testing facility at manufacturer\"s factory.500 CFM |
| 126 | Design, Supply, Lifting & Shifting at actual proposed location of site, Installation, Testing, Commissioning and Field Performance Validation of Decorative Wall Mounted type Chilled Water based High Wall type Fan Coil Units with energy saving Single Phase BLDC motor / EC Motor (Electronically Commuted Motor),Filter section with prefilters, Hydrophilic Al fins and Copper Chilled / HotWater multi step Cooling Coil section with minimum 2 Row and minimum 13 FPI Chilled Water Cooling Coil, combination of Automatic/ Dynamic Balancing valve and an in-built2 way ON / OFF control valve of minimum PN 16 rating with pair of brass ball valve with \"Y\" strainer set, fixed outside FCU, Cu piping with required couplings to fit CHW field In / Out piping; All piping are to be insulated with closed cell elastomeric nitirile rubber insulation. Unit shall be supplied with Digital Display type cordless remote and capable of connecting with BMS with interface modbus protocol to connect the DDC panel (230V operating / Power On / Off provision, 3 speed fan switch & Temp Edit facility / Digital Temp Display) and supplied with 10 RMT cable from Controller to FCU as required. The Performance of units should be certified by a reputed third party agency and available for witness testing facility at manufacturer\"s factory.600 CFM |
| 127 | Supply, installation, testing and commissioning of cabinet type Floor Mounted / Loft Mounted Type single skinned Centrifugal Exhuast Air Unit; unit shall have leakproof canvass connection along with damper at suction side & descharge side cowl; ready to start unit hooked upwith 4P TEFC with IP 55 protection motor with pully / belt drive arrangement on adjustable frame; fan motor assembly mounted on corrossion proof-painted MS baseframe; baseframe to rest on vibration isolation pads. The unit shall be supplied with Starter Panel of required motor capacity.3900 CFM / 40mm Static Pressure for Toilet |
| 128 | Supply, installation, testing and commissioning of cabinet type Floor Mounted / Loft Mounted Type single skinned Centrifugal Exhuast Air Unit; unit shall have leakproof canvass connection along with damper at suction side & descharge side cowl; ready to start unit hooked upwith 4P TEFC with IP 55 protection motor with pully / belt drive arrangement on adjustable frame; fan motor assembly mounted on corrossion proof-painted MS baseframe; baseframe to rest on vibration isolation pads. The unit shall be supplied with Starter Panel of required motor capacity.3450 CFM / 40mm Static Pressure for Toilet |
| 129 | Supply, installation, testing and commissioning of cabinet type Floor Mounted / Loft Mounted Type single skinned Centrifugal Exhuast Air Unit; unit shall have leakproof canvass connection along with damper at suction side & descharge side cowl; ready to start unit hooked upwith 4P TEFC with IP 55 protection motor with pully / belt drive arrangement on adjustable frame; fan motor assembly mounted on corrossion proof-painted MS baseframe; baseframe to rest on vibration isolation pads. The unit shall be supplied with Starter Panel of required motor capacity.2600 CFM / 40mm Static Pressure for Toilet |
| 130 | INSULATED CHILLED WATER PIPING Insulation (Closed Cell Nitrile Rubber GC bonded 2 layers of paint).Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / m3 density, thermal conductivity 0.037 W/MK or better at 20 °C mean temperature class ‘O’ insulation Closed Cell Nitrile Rubber GC bonded applied by suitable adhesive and, over and above glass cloth to be applied, complete including repairing of damage to building etc. as per specifications and as required complete in all respect.Note:-The Pipes of sizes 150 mm & below shall be M.S. ‘C’ class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.200 mm dia.(32 mm thick insulation) |
| 131 | INSULATED CHILLED WATER PIPING Insulation (Closed Cell Nitrile Rubber GC bonded 2 layers of paint).Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / m3 density, thermal conductivity 0.037 W/MK or better at 20 °C mean temperature class ‘O’ insulation Closed Cell Nitrile Rubber GC bonded applied by suitable adhesive and, over and above glass cloth to be applied, complete including repairing of damage to building etc. as per specifications and as required complete in all respect.Note:-The Pipes of sizes 150 mm & below shall be M.S. ‘C’ class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.150 mm dia.(32 mm thick insulation) |
| 132 | INSULATED CHILLED WATER PIPING Insulation (Closed Cell Nitrile Rubber GC bonded 2 layers of paint).Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / m3 density, thermal conductivity 0.037 W/MK or better at 20 °C mean temperature class ‘O’ insulation Closed Cell Nitrile Rubber GC bonded applied by suitable adhesive and, over and above glass cloth to be applied, complete including repairing of damage to building etc. as per specifications and as required complete in all respect.Note:-The Pipes of sizes 150 mm & below shall be M.S. ‘C’ class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.125 mm dia.(32 mm thick insulation) |
| 133 | INSULATED CHILLED WATER PIPING Insulation (Closed Cell Nitrile Rubber GC bonded 2 layers of paint).Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / m3 density, thermal conductivity 0.037 W/MK or better at 20 °C mean temperature class ‘O’ insulation Closed Cell Nitrile Rubber GC bonded applied by suitable adhesive and, over and above glass cloth to be applied, complete including repairing of damage to building etc. as per specifications and as required complete in all respect.Note:-The Pipes of sizes 150 mm & below shall be M.S. ‘C’ class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.80 mm dia.(32 mm thick insulation) |
| 134 | INSULATED CHILLED WATER PIPING Insulation (Closed Cell Nitrile Rubber GC bonded 2 layers of paint).Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / m3 density, thermal conductivity 0.037 W/MK or better at 20 °C mean temperature class ‘O’ insulation Closed Cell Nitrile Rubber GC bonded applied by suitable adhesive and, over and above glass cloth to be applied, complete including repairing of damage to building etc. as per specifications and as required complete in all respect.Note:-The Pipes of sizes 150 mm & below shall be M.S. ‘C’ class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.65 mm dia.(32 mm thick insulation) |
| 135 | INSULATED CHILLED WATER PIPING Insulation (Closed Cell Nitrile Rubber GC bonded 2 layers of paint).Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / m3 density, thermal conductivity 0.037 W/MK or better at 20 °C mean temperature class ‘O’ insulation Closed Cell Nitrile Rubber GC bonded applied by suitable adhesive and, over and above glass cloth to be applied, complete including repairing of damage to building etc. as per specifications and as required complete in all respect.Note:-The Pipes of sizes 150 mm & below shall be M.S. ‘C’ class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.50 mm dia.(32 mm thick insulation) |
| 136 | INSULATED CHILLED WATER PIPING Insulation (Closed Cell Nitrile Rubber GC bonded 2 layers of paint).Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / m3 density, thermal conductivity 0.037 W/MK or better at 20 °C mean temperature class ‘O’ insulation Closed Cell Nitrile Rubber GC bonded applied by suitable adhesive and, over and above glass cloth to be applied, complete including repairing of damage to building etc. as per specifications and as required complete in all respect.Note:-The Pipes of sizes 150 mm & below shall be M.S. ‘C’ class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.40 mm dia.(32 mm thick insulation) |
| 137 | INSULATED CHILLED WATER PIPING Insulation (Closed Cell Nitrile Rubber GC bonded 2 layers of paint).Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / m3 density, thermal conductivity 0.037 W/MK or better at 20 °C mean temperature class ‘O’ insulation Closed Cell Nitrile Rubber GC bonded applied by suitable adhesive and, over and above glass cloth to be applied, complete including repairing of damage to building etc. as per specifications and as required complete in all respect.Note:-The Pipes of sizes 150 mm & below shall be M.S. ‘C’ class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.32 mm dia.(19 mm thick insulation) |
| 138 | INSULATED CHILLED WATER PIPING Insulation (Closed Cell Nitrile Rubber GC bonded 2 layers of paint).Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / m3 density, thermal conductivity 0.037 W/MK or better at 20 °C mean temperature class ‘O’ insulation Closed Cell Nitrile Rubber GC bonded applied by suitable adhesive and, over and above glass cloth to be applied, complete including repairing of damage to building etc. as per specifications and as required complete in all respect.Note:-The Pipes of sizes 150 mm & below shall be M.S. ‘C’ class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.25 mm dia.(19 mm thick insulation) |
| 139 | INSULATED CHILLED WATER PIPING Insulation (Closed Cell Nitrile Rubber GC bonded 2 layers of paint).Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / m3 density, thermal conductivity 0.037 W/MK or better at 20 °C mean temperature class ‘O’ insulation Closed Cell Nitrile Rubber GC bonded applied by suitable adhesive and, over and above glass cloth to be applied, complete including repairing of damage to building etc. as per specifications and as required complete in all respect.Note:-The Pipes of sizes 150 mm & below shall be M.S. ‘C’ class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.19 mm dia.(19 mm thick insulation) |
| 140 | INSULATED VALVESSupplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications.BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/ hot eater circulation as specified125mm dia. |
| 141 | INSULATED VALVESSupplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications.BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/ hot eater circulation as specified80mm dia. |
| 142 | INSULATED VALVESSupplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications.BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/ hot eater circulation as specified65mm dia. |
| 143 | INSULATED VALVESSupplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications.BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/ hot eater circulation as specified50mm dia. |
| 144 | INSULATED VALVESSupplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications.AUTO BALANCING VALVE complete with Flanges Nutbolts and Working parts80mm dia. |
| 145 | INSULATED VALVESSupplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications.Y - STRAINER of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation as specified.65mm dia. |
| 146 | INSULATED VALVESSupplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications.Y - STRAINER of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation as specified.50mm dia. |
| 147 | Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required |
| 148 | Providing & fixing in position the mercury in glass industrial type thermometres. |
| 149 | Supplying, fixing, testing and commissioning of wafer type Butterfly Valve as per IS 13095 with pair of matching flanges (as per ASME 16.5), neoprene gasket, nut bolts and duly insulated with same specification of same size piping as per specification for:80mm dia. |
| 150 | Supplying, fixing, testing and commissioning of Manual balancing valve with pair of matchingflanges(asperASME16.5),neoprenegasket,nutboltsandduly insulatedwithsamespecificationofsamesizepipingasperspecificationfor40 mm dia. |
| 151 | Supplying, fixing, testing and commissioning of Manual balancing valve with pair of matchingflanges(asperASME16.5),neoprenegasket,nutboltsandduly insulatedwithsamespecificationofsamesizepipingasperspecificationfor32 mm dia. |
| 152 | Supplying, fixing, testing and commissioning of Manual balancing valve with pair of matchingflanges(asperASME16.5),neoprenegasket,nutboltsandduly insulatedwithsamespecificationofsamesizepipingasperspecificationfor25 mm dia. |
| 153 | INSULATED VALVESSupplying, fixing, testing and commissioning of CI Y Strainer with pair of matching flanges (as per ASME 16.5), neoprene gasket, nut bolts and duly insulated with same specification of samesize piping as per specification for:32mm dia. |
| 154 | INSULATED VALVESSupplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications.SS BALL VALVE complete with Flanges Nutbolts with SS Body and Working parts.25mm dia. |
| 155 | INSULATED VALVESSupplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications.Supplying, fixing, testing and commissioning of Automatic Air Purge Valve at AHU chilled water outlet pipe duly insulated to the same specifications as the connected piping and adequately supported as per specifications.20mm dia. |
| 156 | SITC 100MM DIAL PG 0-10 KG/CM2Supply & Installation of dial type Pressure Gauge 100 mm size with SS needle valve and fittings 0-10 kg / cm2 range installed as per P & I Diagram. |
| 157 | SITC 100MM DIAL TG 0-50 DEG CSupply&InstallationofdialtypeTemperatureGauge100mmsizewithSSthermowell / coupling / glycerine or eq. conductive fulid and fittings 0 - 50 °C range installed as per P&I diagram. |
| 158 | Supplying,fixing, testing and commissioning of Brass ball valve with SS body and working parts, flanges, duly insulated with same specification of same size piping asper specification40mm dia. |
| 159 | Supplying,fixing, testing and commissioning of Brass ball valve with SS body and working parts, flanges, duly insulated with same specification of same size piping asper specification32mm dia. |
| 160 | Supplying,fixing, testing and commissioning of Brass ball valve with SS body and working parts, flanges, duly insulated with same specification of same size piping asper specification25 mm dia. |
| 161 | INSULATED VALVESSupplying, fixing, testing and commissioning of Automatic Air Purge Valve at AHU chilled water outlet pipe duly insulated to the same specifications as the connected piping and adequately supported as per specifications.20mm dia. |
| 162 | INSULATED VALVESSupply, Installation, Testing and Commissioning of following sizes 2 way modulating control valve in a single body. The actuator shall be capable of accepting upto 10V DC and upto 20 mA electric signal and shallprovide similar transduced feedback output to control system. Maximum close off pressure shall not be less than 6 Bar for upto 50 mm valves and 7 Bar for 65 mm & above. Valves should have pressure rating of 25 Bar minimum.65mm dia. |
| 163 | INSULATED VALVESSupplying, fixing, testing and commissioning of following valves, gauges and strainers for condenser water circulation as per specifications.Supply, Installation, Testing and Commissioning of following sizes 2 way modulating control valve in a single body. The actuator shall be capable of accepting upto 10V DC and upto 20 mA electric signal and shallprovide similar transduced feedback output to control system. Maximum close off pressure shall not be less than 6 Bar for upto 50 mm valves and 7 Bar for 65 mm & above. Valves should have pressure rating of 25 Bar minimum.50mm dia. |
| 164 | INSULATED VALVESSupplying, fixing, testing and commissioning of following valves, gauges and strainers for condenser water circulation as per specifications.Supply, Installation, Testing and Commissioning of following sizes 2 way modulating control valve in a single body. The actuator shall be capable of accepting upto 10V DC and upto 20 mA electric signal and shallprovide similar transduced feedback output to control system. Maximum close off pressure shall not be less than 6 Bar for upto 50 mm valves and 7 Bar for 65 mm & above. Valves should have pressure rating of 25 Bar minimum.40mm dia. |
| 165 | INSULATED VALVESSupplying, fixing, testing and commissioning of following valves, gauges and strainers for condenser water circulation as per specifications.Supply, Installation, Testing and Commissioning of following sizes 2 way modulating control valve in a single body. The actuator shall be capable of accepting upto 10V DC and upto 20 mA electric signal and shallprovide similar transduced feedback output to control system. Maximum close off pressure shall not be less than 6 Bar for upto 50 mm valves and 7 Bar for 65 mm & above. Valves should have pressure rating of 25 Bar minimum.25 mm dia. |
| 166 | BALL VALVE WITH STRAINER 25 mm Dia |
| 167 | Sec.5.0 Ducting, Grills, Diffuser and Insulation DUCTING, GRILLS, DIFFUSER AND INSULATIONSupply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular / round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.Thickness 0.63 mm sheet |
| 168 | Sec.5.0 Ducting, Grills, Diffuser and Insulation DUCTING, GRILLS, DIFFUSER AND INSULATIONSupply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular / round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.Thickness 0.80 mm sheet |
| 169 | Ducting, Grills, Diffuser and Insulation DUCTING, GRILLS, DIFFUSER AND INSULATIONSupply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular / round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.Thickness 1.00 mm sheet |
| 170 | Sec.5.0 Ducting, Grills, Diffuser and Insulation DUCTING, GRILLS, DIFFUSER AND INSULATIONSupply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular / round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.Thickness 0.63 mm sheet |
| 171 | Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular / round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.Thickness 0.80 mm sheet |
| 172 | Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc., as per specifications. |
| 173 | Supply, installation, testing and commissioning of Motorized (ON-OFF Type) duct mounted GI volume control damper with enthalpy sensor and necessary control wire (minimum 1.5 sq. mm) for integration within AHU roomDamper |
| 174 | Supply, installation, testing and commissioning of Motorized (ON-OFF Type) duct mounted GI volume control damper with enthalpy sensor and necessary control wire (minimum 1.5 sq. mm) for integration within AHU roomActuator |
| 175 | Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications. |
| 176 | Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete as required. |
| 177 | Supplying, fixing testing commissioning of supply air diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable core. |
| 178 | Supplying, fixing testing commissioning of Return air diffusers of powder coated aluminium without volume control dampers with anti smudge ring & removable core. |
| 179 | Supply, installation, testing & commissioning of thermal insulated flexible duct of following sizes duly supported at regular interval as per site requirement etc. complete as required as per specifications.200mm dia. |
| 180 | Supplying, Fixing,testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications.Fire Damper |
| 181 | Supplying, Fixing,testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications.Actuator |
| 182 | Supply and fixing of acoustic lining of supply air duct and plenum with 25 mm thick resin bonded glass wool having density of 32 kg/m³, with 25 mm X 25 mm GI section of 1.25 mm thick, at 600 mm centre to centre covered with Reinforced Plastic tissue paper and 0.5 mm thick perforated aluminum sheet fixed to inside surface of ducts with cadmium plated nuts, bolts, stick pins, CPRX compound etc. complete as required and as per specifications. |
| 183 | Supplying and fixing of following thickness duly laminated aluminum foil of mat finish closed cell Nitrile rubber (Class “O”) insulation on existing duct after applying suitable adhesive for Nitrile rubber. and above Bonded Treated Woven Glass Fibre for Outer covering of Insulation Material GC bonded applied by suitable adhesive. Density: 200 +/- 20 gsm Thickness: 0.18 mm / 7 mill, The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required.19mm |
| 184 | 25 mm Dia. |
| 185 | 40 mm Dia. |
| 186 | Supplying and fixing of following thickness duly laminated aluminum foil of mat finish closed cell Nitrile rubber (Class “O”) insulation on existing duct after applying suitable adhesive for Nitrile rubber. and above Bonded Treated Woven Glass Fibre for Outer covering of Insulation Material GC bonded applied by suitable adhesive. Density: 200 +/- 20 gsm Thickness: 0.18 mm / 7 mill, The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required.25mm |
| 187 | CABLE TRAYSSupplying and fixing following sizes of GI Ladder type cable traysincluding couplers,fittings and other accessories as required, and duly suspended from the ceiling with suspenders/fixed on ceiling / walls on fastners etc as per specifications complete as required. 300 x 50 mm |
| 188 | 150 x 50 mm |
| 189 | Operation & Maintenance WorksSYSTEM OPERATION & MAINTENACE : Bidder shall indicate their charges for the following :Comprehensivepreventivemaintenancecontract for theentirechilled watersystem& VRF System supplied / Installed by the HVAC contractor inclusive of all parts, consumables and labour for all equipment supplied as well as replacement of any equipment / component / part which can not be repaired to the satisfaction of the Client. The Operation contract shall also include operatrion of entire chilled water System & VRV System based on 2 persons for 2 shifts & 1 person for night shift and 365 days per year. Only operation cost shall be considered during defect liability period.1st year Cost of maintenance shall be inclusive in the DLP and no extra payment will be paid for the maintenance in the first year after handing over.For Chiller Plant of 650 Tr & VRV Plant of 264 HpOnly Opearation Cost During DLP |
| 190 | Operation & Maintenance WorksSYSTEM OPERATION & MAINTENACE : Bidder shall indicate their charges for the following :Comprehensivepreventivemaintenancecontract for theentirechilled watersystem& VRF System supplied / Installed by the HVAC contractor inclusive of all parts, consumables and labour for all equipment supplied as well as replacement of any equipment / component / part which can not be repaired to the satisfaction of the Client. The Operation contract shall also include operatrion of entire chilled water System & VRV System based on 2 persons for 2 shifts & 1 person for night shift and 365 days per year. Only operation cost shall be considered during defect liability period.1st year Cost of maintenance shall be inclusive in the DLP and no extra payment will be paid for the maintenance in the first year after handing over.For Chiller Plant of 650 Tr & VRV Plant of 264 Hp1st Year after DLP |
| 191 | Operation & Maintenance WorksSYSTEM OPERATION & MAINTENACE : Bidder shall indicate their charges for the following :Comprehensivepreventivemaintenancecontract for theentirechilled watersystem& VRF System supplied / Installed by the HVAC contractor inclusive of all parts, consumables and labour for all equipment supplied as well as replacement of any equipment / component / part which can not be repaired to the satisfaction of the Client. The Operation contract shall also include operatrion of entire chilled water System & VRV System based on 2 persons for 2 shifts & 1 person for night shift and 365 days per year. Only operation cost shall be considered during defect liability period.1st year Cost of maintenance shall be inclusive in the DLP and no extra payment will be paid for the maintenance in the first year after handing over.For Chiller Plant of 650 Tr & VRV Plant of 264 HP2nd Year after DLP |
| 192 | Operation & Maintenance WorksSYSTEM OPERATION & MAINTENACE : Bidder shall indicate their charges for the following :Comprehensivepreventivemaintenancecontract for theentirechilled watersystem& VRF System supplied / Installed by the HVAC contractor inclusive of all parts, consumables and labour for all equipment supplied as well as replacement of any equipment / component / part which can not be repaired to the satisfaction of the Client. The Operation contract shall also include operatrion of entire chilled water System & VRV System based on 2 persons for 2 shifts & 1 person for night shift and 365 days per year. Only operation cost shall be considered during defect liability period.1st year Cost of maintenance shall be inclusive in the DLP and no extra payment will be paid for the maintenance in the first year after handing over.For Chiller Plant of 650 Tr & VRV Plant of 264 HP3rd Year after DLP |
| 193 | Operation & Maintenance WorksSYSTEM OPERATION & MAINTENACE : Bidder shall indicate their charges for the following :Comprehensivepreventivemaintenancecontract for theentirechilled watersystem& VRF System supplied / Installed by the HVAC contractor inclusive of all parts, consumables and labour for all equipment supplied as well as replacement of any equipment / component / part which can not be repaired to the satisfaction of the Client. The Operation contract shall also include operatrion of entire chilled water System & VRV System based on 2 persons for 2 shifts & 1 person for night shift and 365 days per year. Only operation cost shall be considered during defect liability period.1st year Cost of maintenance shall be inclusive in the DLP and no extra payment will be paid for the maintenance in the first year after handing over.For Chiller Plant of 650 Tr & VRV Plant of 264 HP4th Year after DLP |
| 194 | Operation & Maintenance WorksSYSTEM OPERATION & MAINTENACE : Bidder shall indicate their charges for the following :Comprehensivepreventivemaintenancecontract for theentirechilled watersystem& VRF System supplied / Installed by the HVAC contractor inclusive of all parts, consumables and labour for all equipment supplied as well as replacement of any equipment / component / part which can not be repaired to the satisfaction of the Client. The Operation contract shall also include operatrion of entire chilled water System & VRV System based on 2 persons for 2 shifts & 1 person for night shift and 365 days per year. Only operation cost shall be considered during defect liability period.1st year Cost of maintenance shall be inclusive in the DLP and no extra payment will be paid for the maintenance in the first year after handing over.For Chiller Plant of 650 Tr & VRV Plant of 264 HP5th Year after DLP |
| 195 | SOLAR PLANT Design, Engineering, Supply, Installation, Testing & Commissioning of 10 KWp Grid connected Solar PV Power Plant consisting of Solar PV modules, Power Conditioning Unit (Inverter with all accessories/ features), Junction Boxes, PVC Pipes, Cables/Wires including connectors/plugs/fuses, ACDB, Suitable Lightening Arrestor/Earthlink etc. and accessories along with Tool kit and spares for 1 year. The scope of work includes suitable mounting along with all cables, hardware, nuts, bolts etc. |
| 196 | SOLAR PLANT Design, Engineering, Supply, Installation, Testing & Commissioning of 20 KWp Grid connected Solar PV Power Plant consisting of Solar PV modules, Power Conditioning Unit (Inverter with all accessories/ features), Junction Boxes, PVC Pipes, Cables/Wires including connectors/plugs/fuses, ACDB, Suitable LighteningArrestor/Earthlink etc. and accessories along with Tool kit and spares for 1 year. The scope of work includes suitable mounting along with all cables, hardware, nuts, bolts etc. |
| 197 | SOLAR PLANT Design, Engineering, Supply, Installation, Testing & Commissioning of 35 KWp Grid connected Solar PV Power Plant consisting of Solar PV modules, Power Conditioning Unit (Inverter with all accessories/ features), Junction Boxes, PVC Pipes, Cables/Wires including connectors/plugs/fuses, ACDB, Suitable Lightening Arrestor/Earthlink etc. and accessories along with Tool kit and spares for 1 year. The scope of work includes suitable mounting along with all cables, hardware, nuts, bolts etc. |
| 198 | ELW 02.00 HT PANELSupplying, Testing & Commissioning of HT VCB panel consistingof1no.of400AHT VCB as incoming and3 nos of 400A VCB as outgoing. Thepanel shouldhave tinned copper busbars andextensibletype for future requirements. ThePanel shouldbecompletewith meteringand protection as per specification. (Extensible type) |
| 199 | HT RMU Supplying, Erecting, Testing & Commissioning of 3 Way RMU , 11KV, which should be have 1 Incomer Isolators of 630A and 2 outgoing SF6 Insulated Vaccume circuit Breakers of 630 A for Transformers protection, All functions Of Isolators and Breakers should be supplied with Motorised Mechanism for remote operation ON/OFF of RMU, Each Isolators and Each Breaker function should be supplied with motorized mechasism and also with electrical and Mechanical Interlocking |
| 200 | Compact Sub stationSupply, Testing & Commissioning of 1600 KVA Unitized Sub-station consisting of (1 no 400 A HT VCB as incomer + 1600 KVA Dry type Transformer with OLTC and RTCC Panel +2500 A FP MCCB L.T. Switchgear with all connection accessories, fitting & auxiliary equipment in an Enclosure to supply Low-voltage energy from high-voltage system as detailed in this specification. The complete unit shall be installed on a substation plinth (base) as Outdoor substation located at very congested places as direct engineer in charge |
| 201 | BUSDUCT & RISING MAINS & its accesoriesSupplying,assembling,groutinginslab/wall/beamwith hanging rods/strips /supports, waterproof, dustproof, verminproof busductto befabricated outof 14gauge sheet.Thebusductshouldbeprocessedthrough7tank process.Thebusductshouldbepowdercoated.Alljoints shouldbefittedwithneoprenegasket.Thebusductshould confirmto IP 55 protection.The capacity of the busbar shouldbe2500FPAmps &shouldbe oftinned Aluminium, withnecessaryflexible,bends,reducer, expansionjoints, supports and all assential accessories complete in all respect. Necessary certificate shall be requiredat thetime of supply.Thecapacityof neutralbus shouldbe equalto phasebus.(INDOORDUTYWITH2NOS.AL.EARTHINGSTRIP) ( CSS toStabilizer toMainLT Power Panel & DG SYCN. PANEL TO Main LT Power Panel) |
| 202 | ELW 06.00 MV Switch Gear and power PanelSupplying,unloadingatsite,shiftingto site,assembling, leveling,grouting,erecting,Testing,&Commissioning compartmentalizedtypePanelswithpowdercoated fabricated fromCRCA sheet & folded channel totally enclosed cubical type with pad lock arrangementcomplete in all respect as per detail tedner specifications.The successful tendererwillhave to prepare general arrangement with dimensions&getitapprovethroughEngineer Incharge/ Consultant.Panels should be as per detail single line drawing withrequirednosofincomingandoutgoingfeedersand accessories complete in all respectMAIN LT POWER PANELAs per Single line diagram (panel must be with gas based fire suppresion system) |
| 203 | ELW 06.00 MV Switch Gear and power PanelSupplying,unloadingatsite,shiftingto site,assembling, leveling,grouting,erecting,Testing,&Commissioning compartmentalizedtypePanelswithpowdercoated fabricated fromCRCA sheet & folded channel totally enclosed cubical type with pad lock arrangementcomplete in all respect as per detail tedner specifications.The successful tendererwillhave to prepare general arrangement with dimensions&getitapprovethroughEngineer Incharge/ Consultant.Panels should be as per detail single line drawing withrequirednosofincomingandoutgoingfeedersand accessories complete in all respectDG SYNC. PANELAs per Single line diagram (panel must be with gas based fire suppresion system) |
| 204 | Supplying,unloadingatsite,shiftingto site,assembling, leveling,grouting,erecting,Testing,&Commissioning compartmentalizedtypePanelswithpowdercoated fabricated fromCRCA sheet & folded channel totally enclosed cubical type with pad lock arrangementcomplete in all respect as per detail tedner specifications.The successful tendererwillhave to prepare general arrangement with dimensions&getitapprovethroughEngineer Incharge/ Consultant.Panels should be as per detail single line drawing withrequirednosofincomingandoutgoingfeedersand accessories complete in all respect350KVAR APFCR PANELAs per Single line diagram (panel must be with gas based fire suppresion system) |
| 205 | Supplying,unloadingatsite,shiftingto site,assembling, leveling,grouting,erecting,Testing,&Commissioning compartmentalizedtypePanelswithpowdercoated fabricated fromCRCA sheet & folded channel totally enclosed cubical type with pad lock arrangementcomplete in all respect as per detail tedner specifications.The successful tendererwillhave to prepare general arrangement with dimensions&getitapprovethroughEngineer Incharge/ Consultant.Panels should be as per detail single line drawing withrequirednosofincomingandoutgoingfeedersand accessories complete in all respect.UTILITY BLOCK PANELAs per Single line diagram |
| 206 | Supplying,unloadingatsite,shiftingto site,assembling, leveling,grouting,erecting,Testing,&Commissioning compartmentalizedtypePanelswithpowdercoated fabricated fromCRCA sheet & folded channel totally enclosed cubical type with pad lock arrangementcomplete in all respect as per detail tedner specifications.The successful tendererwillhave to prepare general arrangement with dimensions&getitapprovethroughEngineer Incharge/ Consultant.Panels should be as per detail single line drawing withrequirednosofincomingandoutgoingfeedersand accessories complete in all respect.POST MORTEM BLOCK PANELAs per Single line diagram |
| 207 | Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels withpowder coated fabricated fromCRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect.CANTEEN BLOCK PANELAs per Single line diagram |
| 208 | Supplying,unloadingatsite,shiftingto site,assembling, leveling,grouting,erecting,Testing,&Commissioning compartmentalizedtypePanelswithpowdercoated fabricated fromCRCA sheet & folded channel totally enclosed cubical type with pad lock arrangementcomplete in all respect as per detail tedner specifications.The successful tendererwillhave to prepare general arrangement with dimensions&getitapprovethroughEngineer Incharge/ Consultant.Panels should be as per detail single line drawing withrequirednosofincomingandoutgoingfeedersand accessories complete in all respect.EXTERNAL LIGHTING PANELAs per Single line diagram |
| 209 | DG Set with AMF panelSupplying,installation,testingandcommissioningofDG set of2#1000KVAwithapproximate1180BHPenginewith enclouser&suitablealternatorcompletewithall necessary fuel piping,Aluminium cladding, exhaustpiping, control panel,Autosynchronizing,autoloadsharingAMFPanel, silencer& its piping, Acoustic silencer, Alternatorcable terminationboxsuitableforAluminiumcables,initialbattery charging,baseframe,batteryandchargercompleteinall respect.Scopealsoincludespreparingnecessarydrawing submittingtoauthorities,gettingtheirapproval/sanction andfinalcertificateincluding NOCfrompollutionboard(if required) toenergizethe D G Set. (RateIncludes 2Nos. of 1000kVADgsets,2Nos. Control & AMF Panels and2 No. of RECD kit etc.) |
| 210 | EXHAUST SYSTEMDia 12\" / 300mm, MS ERW B Class Pipe. Shall be duly cleaned with Wire Brush and Coated with 1 coat of Primer & 2 coats of Heat Resistant Paint, Exhaust pipe Thermal Insulation and cladding for 12\"dia pipe, using Rockwool Insulation of density 64Kg/m3 with 50mm thick bound with GI chicken wire mesh & Cladding using 24 SWG Aluminium sheet, 12\" SS Flexible Bellows with Table D Flanges, Gaskets and Hardwares, Thermal Insulation and cladding of Silencers, using Rockwool Insulation of density 64Kg/m3 with 50mm thick bound with GI chicken wire mesh & Cladding using 24 SWG Aluminium sheet, M.S Structural Supports for Exhaust Stack, cable trays, Fuel pipes using ISA / ISMC. Supports shall be Duly Cleaned with Brush follwed by One Coat of Primer and Two Coats of Synthetic Enamel Paint / Aluminium Paint, Lightning Arrestor - Convetional - Spike and Sphere Type, Aviation Lamp - LED Type, 25 x 3 CUStrip for LA earthing with insulators, CU Earth pit for Lightening Arrestor earthing(600x600x3.15mm Cu Plate, 3 Mtrs of Dia 40 mm GI B Class Pipe, 2 Runs of 25x3 Cu strip & Funnel arrangement) |
| 211 | SUPPLY AND INSTALLATION OF OUTDOOR KIOSK LBS WITH VCB PANEL WITH CTPT ARRANGEMENT Dust and Vermin Proof FT Profile Water Resistant Switch Board Complete set of an Outdoor 800 AMP LBS + 1250 AVCB Panel with CT-PTCubicle Arrangement 2mm Sheet steel structure, 5 mm steel supporting load barring structure with anti corrosive chemical treatment & powder coated RAL 7032 including 1)11 KV VCB cubicle board with inbuilt rack in/out trolly & ramp for removal directly on floor 1250 Amp, 230V AC Spring charged motor, 110V DC trip & closing Coil, manual spring charged handle, E stop mechanical push button 1) 11KV LBS -800Amp, built in earth switch, single phasing protection assembly, aux contect 2) 11 KV current transformer : 400/5A, 10VA, 5P10 3) Numerical relay - 3-O/C, 1-E/F,, 4) Master trip LocKout relay, 5)AUx transformer relay. 6) anti pumping feature scheme 7) 8 -windowannaunciator 8) Push button - LBS off, indication on off 9) indicationVCB on off, trip, spring charged, TCH spring charged, Push button VCBon off 10)power pack - 230V/ 110 v DC, 7 AH 30 Min, 3-closing trippingstrock back up. 11) Set of 1-P, 2P MCBs. 12) spaeceheater with termostate with on/off switch and utility socket. 13) provision of cable termination with bimetalick strip on copper busbar ends for alluminnium cable termination. 14) isolated CT-PT cubical separate metering cubicle . Complete in all respect including all required for the same. |
| 212 | Supply, Installation, Testingof 11 KV 3Phase*4 Wire HT Bi directional Meter Accuracy Class 0.2s Make : Secure. Complete in all respect including all required for the same. |
| 213 | Supply, Installation, Testing of 11 KV 3Phase*4 Wire Metering CTPT Unit Accuracy Class 0.2s Ratio : 150/5 Amp. Complete in all respect including all required for the same. |
| 214 | Supply, Installation, Testing of LT Metering set including Secure Make LT meter, Resin Cast CT coil, LT meter box. Complete in all respect including all required for the same. |
| 215 | Supply of GPRS/ GSM MODEM with CODE and Antenna. Complete in all respect including all required for the same. Make Secure |