| 1 | Installation of smoke extraction system, fire check door & pressurization System in Internal stair cases and talk back system in Main Hospital Building, Oncology Building, & Administrative Building atDr. Ram Manohar Lohia Institute of Medical Sciences, Vibhuti Khand, Gomti Nagar, Lucknow(U.P.) |
| 2 | SITC of 48 mm thick steel door shutter of 120 min fire rated confirming to BS-476, Part-22 and IS:3614 part-II ; fabricated with 2 nos of 0.8 mm thick glavanized steel sheet sandwiching Honeycomb materials in between.Door frame are manufactured with 1.2mm thick galvanized steel sheet pressed to form Double rebate profile of . The frame and shutter are finished with powder coating of approved colourwith SS ball bearing hinges , Door Closer, Vision Panel , Panic Bar Double/ Single Leaf , Panic Trim . |
| 3 | FIRE DOOR FOR ALL EIGHT FLOOR STAIR CASE IN HOSPITAL BUILDING |
| 4 | Door width mm |
| 5 | 4855 X14 |
| 6 | Door Height mm |
| 7 | 3500, |
| 8 | Aluminnium Door Dismental and new Fire door fixing & Civil Worlk wall laying from cement ,sand ,murag etc. |
| 9 | SITCofAMCACertifiedAxialFlowfan complete withall accessories as per specifications Both side Bird Screenand any other item required to make the system complete. Fans shall be suitable for 415V, 3 Phase, 50 Hz AC power supply. |
| 10 | 21000 CFM 18 MMWGHigh Tem. (H Class 250 Degree ) |
| 11 | 15000 CFM 18 MMWGHigh Tem. (H Class 250 Degree ) |
| 12 | 6000 CFM 18 MMWGFresh Air (F Class Normal) |
| 13 | 11500 CFM 18 MMWG (Stair Case) Normal Motar F Class |
| 14 | 5200 CFM 18 MMWG(Lift well) Normal Motar F Class |
| 15 | 20000 CFM18 MMWG High Tem. (H Class 250 Degree ) |
| 16 | 17000 CFM18 MMWG(Stair case) (Normal Moter) F Class |
| 17 | 13500 CFM18 MMWG(LIFT WELL) (Normal Moter) F Class |
| 18 | SITCof Backward CurvedCentifugalFan with Cabinet |
| 19 | DIDW Backward curved Exhuast fan complete with TEFC moter, pulleys, V - Belt guards etc. Double Skin Backward curved non overloding type Centrifugal fan with Fire retardent& waterproof cabinet . |
| 20 | 25000 CFM50MM WG, Centrifugal Fan ( Fire Rated moter) ( H Class IE2 Motar) |
| 21 | 20000 CFM50MM WG, Centrifugal Fan ( Fire Rated moter) ( H Class IE2 Motar) |
| 22 | Civil Work of window cutouts of Different Sizes window dismantling and Repairing for wall after fan Installation work |
| 23 | Finishing with Deluxe Multi surface paint system for interiors and exteriors using Primer as per manufacturers specifications : 13.48.1 Two or more coats applied on walls @ 1.25 ltr/10 sqm over and including one coat of Special primer applied @ 0.75 ltr /10 sqm |
| 24 | Removing dry or oil bound distemper, water proofing cement paint and the like by scrapping, sand papering and preparing the surface smooth including necessary repairs to scratches etc. complete. |
| 25 | SITC ofSmoke Spill Singal Speed Jet Fan |
| 26 | Flow 6400 CFM |
| 27 | Diameter : 400mm |
| 28 | Motor Rating : 2.4 kW |
| 29 | RPM :2880 |
| 30 | Motor Insulation : H Class 250deg for 2hr |
| 31 | Both Side 1.5D Long Silencer |
| 32 | SITC of FIRE ALARM TALK BACK SYSTEM FOR EVERY ROOM AND HALL IN HOSPITAL BUILDING |
| 33 | Simplex type talk-back master control panel is a reliable & user friendly way of communication between local unit & control station. This communication with master station is done through talkback unit. Talkback unit is located in remote location and is connected with the main control panel the cable. When we push the switch of the unit, it get connected with the main panel. One way communication is only possible in this system. |
| 34 | Customized master control station for Talkback system. Used for 1-way simplex type communication, 128 Zone system,Simple to connect talkback slave unit,Push and talk facility,Front LED display for unit location display , 16 swg CRCA sheet Housing AC and DC meter to measure supply (Optional), Inbuilt battery charger and battery space . |
| 35 | Talkback Master Control Panel (Simlex Type) 120 Zone |
| 36 | Talkback Master Control Panel (Simlex Type) 100 Zone |
| 37 | TB–SU–SPX , Individual(1 units) |
| 38 | 2Cx1.5 mm2Copper Armoud |
| 39 | Supplying, installation, testing and commissioning Cable Heavy duty 750 volt grade for Fans |
| 40 | 3Cx2.5 mm2Copper Armoud |
| 41 | 3Cx6.0 mm2Copper Armoud |
| 42 | 2Cx0.75 mm2Copper LEAD WITH MS CONDUIT 16 GAUGE 20MM |
| 43 | 3.5Cx400.00 mm2 Armoud Alumiunnim |
| 44 | SITC of G I Ductingcomplete with rubber gaskets, elbwo, hanger ,support 22 gauge |
| 45 | Panel Logic Control with starter Panel Supplying, installation, testing and commissioning of cubical type main MV panel board suitable for 3 phase, 415 volts, 50 Hz, and of 25 KA rupturing capacity at 415 volts, fabricated from minimum 2 mm thick and doors of 1.6 mm thick CRCA sheet powder coated through seven tank process facility for prickling and degreasing complete with suitable rating digital Amp meter with CTs, 0-500 Volt meter with selector switch, phase indication lamp with control MCB, suitable rating Al. Bus Bar, mountings, interconnections, earthing etc. as required. The electrical panel with feeders for suitable nos. of starters for 3 phase dual speed fans with suitable motor rating at high/low speed. PLC with necessary logic for CO detection and control of suitable Nos of Axial fans bysensor and shall be connected with each panel to provide input to panel for running the required number of fans in particular zone. Potential free contact shall be provided for BMS integration. CO Sensors shall be designed to detect CO gas in the air with sensing range between 0-250 PPM. |
| 46 | SITC of Aluminnum Gravaity Lovers For Fan |
| 47 | SITCCOSensor |
| 48 | Supply Installation testing and commissioning of CO Set andCO2 sensing system for automatic running and modulating of motors forventilation and exhaust fan for pollution and fire mode as required. |
| 49 | SITCOF 300 MM X 50 G I CABLE complete all Respect |
| 50 | CFD Analysis: |
| 51 | Carrying out CFD Analysis to demonstrate the following |
| 52 | in the areas ventilated by main & jet fans: |
| 53 | CFD Analysis shall also provide Drawing showing the Locations and Orientation of Jet Fans. The Installation of Jet Fans shall be carried out at the |
| 54 | locations recommended by CFD Analysis. |
| 55 | Carrying out Successful CFD Analysis of the Complete Ventilation System, as mentioned above and in the specifications, for: |
| 56 | SITC of UL/FM Certified Extinguishing agent filled in PESO Approved Filling Station: 2 Kg FK-5-1-12 Clean agentfilled in PESO approved stored pressure type seamless steel cylinder as per IS 7285 (life 15years) with automatic type DLP valve assembly PI marked, TPED (Transportable Pressure Equipment Directive) approved, Used Standards for type approvals ISO 17871:2015 in conjunction with EN ISO 10297:2014 EN ISO 14246: 2017-12, Push in connector, End of line adapter, UL lisetd Pr. Switch, end of line plug, T connector, Safety Burst Disc at 28 Bar and Mounting Bracket.Stored Pressure type fitted with Pressure gauge, UV Resistance, Operating Pressure 15 bar, Hydraulic Pressure Tested to 250 bar, Burst Pressure at 350 bar, Red Powder coated. Certified by National Test House, Dept of Consumer Affairs, Govt. of India. system design as per NFPA 2001 & Installed as per LPS 1666. |
| 57 | SITC of UL Certified Linear pneumatic Heat Detection Tube (ID-6mm & OD-8mm) for automatic fire detection & supperession system made by special modified polyamaide (PA), colour red RAL300, burst temperature 1310C, inner diameter 6mm, outer diameter 8mm. Pressurised with dry nitrogen at 15 bar pressure with all necessary fittings & supports. Certified by National Test House, Dept of Consumer Affairs, Govt. of India. |
| 58 | SITC of End of line adaptor with Pressure Gauge |
| 59 | SITC of Pressure Switch_UL Listed |
| 60 | SITC of End of Line Plug_UL Listed |
| 61 | SITC of T- Connector_UL Listed |
| 62 | SITC of Master Control Unit with inbuilt Sounder with , 2 NO/NC potential free relay contact for Main Fire Alarm. Modbus for BMS Integration. Gas discharge led indicator, battery led indicator, system status Led indicator, AC power ON Led indicator. |
| 63 | GST Extra as applicable |