| 1 | Section-IComprehensive maintenance of IR system installed at DIPAC in reliable safe and efficient operating condition through MoU with OEM by regularly examining and carried out planned maintenance in systematic and controlled manner suitable for following accessories in IR system complete all as specified and directed:-(a)Premier Elite 168 panel -- 01 No.(b)Premier 8XP-- 04 Nos.(c)Premier LCD Keypads -- 09 Nos.(d)Premier CO Gsm -- 01 No.(e)Wired PIR Prestige DT -- 07 Nos.(f) Inpaq E White Shock Sensor -- 07 Nos.(g)Sounder Odyssey3 -- 04 Nos.(h)Synchronized Twin Beam -- 21 Nos.NOTES:- (i)Contractor will conclude AMC with OEM and copy of the agreement along with invoice will be submitted to Engineer-in-Charge and GE before commencement of AMC.No payment will be made to contractor without submission of valid AMC agreement.(ii)After complaint lodging within 02 hours OEM required to reach on site including Sundays and Holidays.(iii) The contract including 100% spare parts (Except batteries) including labour, battery will be supplied by the Department under Schedule \"B\" for free for fixing only. Fixing charges of battery will be included in the quoted rate. |
| 2 | Notes for item No. 1:-(iv) Monthly check shall be carried out by OEM only as per mentioned in particular specification.(v) As per user requirement when IR system brief required Contractor provide within two days and rates for the same will be included in the quoted rate. (vi) The contractor will have to submit MOU as per given on page No 124 to 126 from M/s CREATIVE TELECOM P. LTD within Twenty Eight days of acceptance of tender, failing which theco. (vii) Contractor will conclude AMC with OEM and copy of the agreement alongwith invoice will be submitted to Engineer-in-Charge and GE before commencement of AMC. No payment will be made to contractor without submission of valid AMC agreement. (viii)The above maintenance include complete maintenance of existing IR system by regularly and systematically examining adjusting fabricating as and when required for smooth and efficient functioining of the equipment. |
| 3 | Section-IIDismantling/opening up existing ceiling fan size of 1200 mm sweep, taking out all burnt/damaged windings insulating materials & cleaning internally as well as externally, rewinding the fan motor with super enamelled copper wire as per existing size/specification, replacement of complete insulating materials, varnishing drying up, cleaning & greasing of bearing/buses using new grease, reassembling and testing and transporting back to site and refixing to original position.The rates quoted by the contractor shall deemed to include replacement of defective slip pin and roller rubber if worn out and connecting wire of 3 core 1.5 Sqmm pvc flexible copper wire upto 1.0 mtrcomplete all as specified & as directed. |
| 4 | Ditto- all as per item No 2.00 here-in-before but Ceiling fan of size 1400 mm sweep. |
| 5 | Ditto- all as per item No 2.00 here-in-before but exhaust fan size 450 mm sweep. |
| 6 | Ditto- all as per item No 2.00 here-in-before but exhaust fan size 225/250/300 mm sweep. |
| 7 | Ditto- all as per item No 2.00 here-in-before butcabin fan 300 mm sweep. |
| 8 | Taking down of ceiling fan / exhaust fan of any size/sweep for overhauling/ servicing comprising dismantaling , cleaning internally and externally including applying one coat of synthetic enamel paint (1st grade quality) by spray machine and cleaning/lubricating of bearing/buses using fresh lubricant (Oil grease) re-assembling, hanging on same position, connecting and testing for proper functioning complete all as specified and as directed. Notes: (i) Replacement of defectivespares for making the ceiling fan units in satisfactory working conditionwill be measured & paidseparately under relevant items as \"Supply only\".(ii) Labour charges for taking out old spares & refixing of new sparesshall deemed to be included in unit quoted rate. (iii) Required defective split pin, roller rubber and suitable connecting wire of same size and core shall deemed to be included in unit quoted rate. |
| 9 | Supply only fan capacitor 2.50 to 3.15 MFD complete all as specified and as directed. |
| 10 | Supply only ball bearing/bush for exhaust fan of any size complete all as specified and as directed. (Note for Item Nos. 8.00 & 9.00:Labour charges for taking out old spares & refixing of new sparesshall deemed to be included in unit quoted rate of Item No 7.00 here- in- before.) |
| 11 | Dismantling and taking out defective geyser of any capacity of any makeand rectification of defects including repairing and refixing at same position, connecting and testing for proper functioning complete, replacing spares as required , wire terminals, soldering / crimping required at site for proper functioning of the equipment complete all as specified and as directed.Notes: (i) Replacement of defectivespares for making the geyser units in satisfactory working conditionwill be measured & paidseparately under relevant items as \"Supply only\".(ii) Labour charges for taking out old spares & refixing of new sparesshall deemed to be included in unit quoted rate. (iii) Required small pieces of wire terminals, soldering / crimping and suitable connecting wire of same size and core shall deemed to be included in unit quoted rate. |
| 12 | Supply only the following new spares for geyser of any capacity:- |
| 13 | Thermostat for geyser/solar water heater suitable to work up to 80\" C . |
| 14 | Indicator lamp. |
| 15 | Inner assembly for geyser upt 50 Litres capacity. |
| 16 | Inspection plate for 25/50 Litres capacity. (Make:- As per sample) |
| 17 | PVC connection pipe nylon threaded 15mm dia., 450mm long with chromium plated brass couplings on both ends suitable for 15mm bore tubing. |
| 18 | Heating element 2000 Watt suitable for 50 ltr geyser. |
| 19 | Heating element 1500 Watt suitable for 25 ltr geyser. |
| 20 | Polycarbonate plug top, 3-pin, 5/6 Amps. |
| 21 | Polycarbonate plug top, 3-pin, 15/16 Amps. (Note for item No 11.01 to 11.09:-Labour charges for taking out old spares & refixing of new sparesshall deemed to be included in unit quoted rate of Item No 10.00 here- in- before.) |
| 22 | Material and labour for servicing of solar water heater 500 LPD capacity NPX indirect solar water heating system and making good any leakage alongwith replacement of gasket etc. including testing complete and making the heater functional including taking down old serviceable one complete all as specified and as directed. ((Note:- Spare parts shall be measured and paid seperately under relevent items.) |
| 23 | Ditto- all as per item No 12.00 here-in-before but for 300 LPD capacity |
| 24 | Ditto- all as per item No 12.00 here-in-before but for 200 LPD capacity |
| 25 | Supply only electrical heating element thread type 4 KW single phase suitable for solar water heater complete all as specified.(Note for item No 15.00:-Labour charges for taking out old spares & refixing of new sparesshall deemed to be included in unit quoted rate of Item No 12.00 to 14.00 here- in- before.) |
| 26 | Material and labour for descalling of the collectors and hot water tank 500 ltrs capacity with the chemical solvent for removing all silt/rust complete and making the whole system leak proof complete all as specified and directed. |
| 27 | Ditto- all as per item No 16.00 here-in-before but for 300 LPD capacity |
| 28 | Ditto- all as per item No 16.00 here-in-before but for 200 LPD capacity |
| 29 | Supply and fixing in repair Galvanised iron pipe medium grade 20 mm bore with necessary fittings such as tees, elbows, bends, reducers, unions etc fixed along wall/ floor/roof including covering with insulation all around with 25mm thick bonded mineral wool preformed \"SNAPON\" pipe sections of density 144 KG/Cum conforming to IS 9842 as directedof rock wool/ mineral wool, chicken mesh and cladding with 26 SWG alum sheet including chasing/cutting of wall as required including taking down old unserviceable one complete all as specified and as directed. |
| 30 | Supply and fixing in repairs Hot water tap of brass/gun metal 15 mm bore complete all as specified and as directed. |
| 31 | M&L for MS Angle iron/MS plate including nuts,bolts,washers, welding,drilling holes for bolts in any shape or size as indicated or directed for making staging of the tank and applying two coats of aluminium paint over a coat of red oxide zinc chrome primer including preparation of steel surface including taking down old serviceable one complete all as specified and as directed. |
| 32 | Supply and fixing of LED recessed mounting square slimLED down lighter 36 Watt for AS/GB/POP ceiling2\"x2\" size complete with internally prewired and connecting up with twin core flexible copper conductor cable of suitable size including takng down of old unserviceable one complete all as specified and directed. |
| 33 | Supply and fixing of Basic all purpose surface and wall mounted LED batten with polycarbonate housing & integrated electronic driver LED tube light fitting 9 watt including LED tube, 230 volt including takng down of old unserviceable onecomplete all as specified and directed. |
| 34 | Supply and fixing in repairs Moulded Case Circuit Breaker (MCCB) 4 pole,100 Amp , with breaking capacity 16KA complete all as specified and as directed. |
| 35 | Supply and fixing in repairs Moulded Case Circuit Breaker (MCCB) 4 pole,125 Amp , with breaking capacity 16KA complete all as specified and as directed. |
| 36 | Supply and fixing in repairs Miniature Circuit Breaker (MCCB) 4 pole, 63 Amp , with breaking capacity 16KA complete all as specified and directed. |
| 37 | Supply and fixing in repairs Moulded Case Circuit Breaker (MCCB) 4 pole,250A , with breaking capacity 36KA complete all as specified and directed by Engr-in-charge. |
| 38 | Supply and fixing in repairs miniature circuit breaker (MCB) single pole and neutral with thermal overload as well as magnetic short circuit tripping device with quick break trip free mechanism robust design and terminals having heat resistant moulding suitable for single phase and neutral circuit of 240 volts, 40 Ampere current rating, \"C\" curve, 10 KA breaking capacity complete all as specified and directed. |
| 39 | Ditto all as per item No 28.00 above but for SPN 6 to 32 Amps current rating. |
| 40 | Ditto all as per item No 28.00 above but forSP 6 to 32 amps current rating. |
| 41 | Ditto all as per item No 28.00 above but for \"B\" curveSP 40 Amps current rating. |
| 42 | Supply and fixing in repairs sheet metal enclosure, single pole and neutral with two pin earth plug and socket complete with one single pole MCB 20/32 Amp, 240 volts fixed with half grouting on wall complete all as specified and directed. |
| 43 | Taking down carefully existing surface/ concealed unserviceable aluminum/ copper point wiring(light, fan, socket, power or sunken box) complete including fittings such as switches, ceiling roses, pendants, regulators, sockets, light fittings,etc.and making good to disturbed surfaces of walls, floors, ceilings, etc. where required and finished the existing surfaces after complete of new point wiring as specified here-in-after complete all as specified and as directed. |
| 44 | Material and labour for point wiring with 1.5sqmm (nominal area) PVC insulated and unsheathed single core FRLS (conforming to IS-694) copper cable 1100 volts grade with multi stranded copper conductor includingPVC casing caping (medium grade) of adequet size dia with all fittings and accessories including 2mm thick sunk MS pressedsteel terminal boxes of appropriate size with 3.0mm thick plastic laminated sheet top cover with cadmium plated iron screws completeincluding PVC insulated and unsheathed FRLS (conforming to IS-694) single core multi strandedcopper conductor cable of size 1.5sqmm green colour as earth continuty conductor connected to common earth dolly for one light/ fan point controlled by one, one way switch complete all as specified and as directed. {Notes:- (i) Switches and sockets to be measured and paid for separately under relevent items.} |
| 45 | ditto- all as per item No. 34.00 above but one 5/6amps socket outlet point on the same board with other switches complete all as specified and as directed. |
| 46 | All as per item No 34.00 above but for one 5 pin 5/6 Ampere socket outlet point controlled by one one way switch on independent board complete all as specified and as directed. |
| 47 | Material and labour for point wiring for one 15/16 Ampere socket outlet independent point using 2.50 sqmm FRLS size (Nominal cross sectional area), PVC insulated, unsheathed 1100 volts grade single core multi-stranded copper conductor cable in proper colour coding drawn into and including non metallic rigid PVC conduit medium grade concealed (not less than 25 mm dia) for wall and 25mm PVC medium grading grade casing and caping in the ceiling wherever required with and including its all necessary fittings and accessories fixed concealed, sunk cast iron or 1.2 mm thick pressed steel terminal box for mounting fittings and covered with 3 mm thick white bakelite / laminated hard glossy surface sheet top cover fixed with brass screws and cup washers including one continuous run of PVC insulated (green colour) 2.50 sqmm FRLS size stranded copper conductor cable as in earth wire and connecting all metal parts to common earth dolly complete all as specified and directed. |
| 48 | Supply and fixingswitch piano, flush type, ivory finish 5/6 Ampere single pole, one way complete, all as specified and directed. |
| 49 | Supply and fixingsocket out let 2 in 1, 3 Pin, 5/6 Ampere, 230V AC, flush type complete all as specified and as directed. |
| 50 | Supply and fixingswitch piano, flush type, ivory finish 15/16 Ampere single pole, one way complete, all as specified and directed |
| 51 | Supply and fixingsocket out let 2 in 1, 3 Pin suitable for 5/6 Ampere and 3 Pin suitable for 15/16 Ampere flush type complete all as specified and as directed |
| 52 | Supply and fixingceiling rose, 3 phase, PVC / polycarbonate, surface type, 65mm x 50mm, insulated body, three terminals complete all as specified and as directed. |
| 53 | Supply and fixingmodular switch one module, 5/6 Amp, one way, 230 volts AC complete all as specified and as directed |
| 54 | Supply and fixingmodular switch one module, 15/16 Amp, one way, 230 volts AC complete all as specified and as directed |
| 55 | Supply and fixing of modular socket outlet (two module) 6Amps, 2/3 pin compained , 230 volts AC complete all as specified and as directed |
| 56 | Supply and fixing of modular socket out let (two module), 2 in 1, 3 Pin suitable for 5/6 Amp and 3 Pin suitable 15/16 Amp combined, 230 volts AC complete all as specified and as directed |
| 57 | Supply and fixing of electric ding dong buzzer, 230 volt AC, single pole, complete all as specified and as directed |
| 58 | Supply and fixing of flush type bell push, 5 Amps complete all as specified and as directed |
| 59 | Supply and fixing of lamp holder, PVC/polycarbonate type, insulated body with back plate of batten fitting complete all as specified and as directed. |
| 60 | Supply and fixing of stepped type 5 steps 100 watts electronic fan regulator flush type on the existing phenolic laminated sheets etc as required all as specified and as directed. |
| 61 | Supply and fixing of Modular Fan regulator step type, 1 Module size complete all as secified and as directed. |
| 62 | Taking down unserviceable sub main wiring of any type and any size including wooden batten, PVC conduit or casing caping complete all as specified and as directed. |
| 63 | Material and labour for sub main wiring with two runs of single core 4.0 Sqmm (nominal area) PVC insulated copper conductor FRLS (conforming to IS-694), stranded,unsheathed1100 volts grade in PVC Conduit (heavy grade) of 25mm dia or more dia with all fittings and accessories surface type including one run 4.0 Sqmm single core unsheathed stranded copper conductor cable FRLS (conforming to IS-694)as earth wire complete all as specified and as directed Note :(a) Two runs of 4.00 sqmm copper cable and one run of 4.00 sqmm copper cable (earth wire) alongwith PVC conduit measured as one unit length.(b) Extra length of cable required for connetion to DBs shall deemed to be included in the unit quoted rate and shall not be measured separately.(c)Earth wire shall run inside the conduit.(d) Suitable colour code of wire shall be maintained for phase / neutral / earth). |
| 64 | Material and labour for sub main wiring with two runs of single core 6.0 Sqmm (nominal area) PVC insulated copper conductor FRLS (conforming to IS-694), stranded,unsheathed1100 volts grade in PVC Conduit (heavy grade) of 20mm dia or more dia with all fittings and accessories surface type including one run 6.0 Sqmm single core unsheathed stranded copper conductor cable FRLS (conforming to IS-694)as earth wire complete all as specified and as directed Note :(a) Two run of 6.00 sqmm copper cable and one run of 6.00 sqmm copper cable (earth wire) alongwith PVC conduit measured as one unit length.(b) Extra length of cable required for connetion to DBs shall deemed to be included in the unit quoted rate and shall not be measured separately.(c)Earth wire shall run inside the conduit.(d) Suitable colour code of wire shall be maintained for phase / neutral / earth). |
| 65 | Material and labour for sub main wiring with two runs of single core 10.0 Sqmm (nominal area) PVC insulated copper conductor FRLS (conforming to IS-694), stranded,unsheathed1100 volts grade in PVC Conduit (heavy grade) of 25 mm dia or more dia with all fittings and accessories surface type including one run 10.0 Sqmm single core unsheathed stranded copper conductor cable FRLS (conforming to IS-694)as earth wire complete all as specified and as directed.Note : (a) Two run of 10.00 sqmm copper cable and one run of 10.00 sqmm copper cable (earth wire) alongwith PVC conduit measured as one unit length.(b) Extra length of cable required for connetion to DBs shall deemed to be included in the unit quoted rate and shall not be measured separately.(c)Earth wire shall run inside the conduit.(d) Suitable colour code of wire shall be maintained for phase / neutral / earth). |
| 66 | Supply, Installation, Testing and Commissioning of BIPOD Maintenance Free Chemical Earthing Based on 3000mm long Copper Bonded Earthing Electrode 200 Microns (Met-Chem) 50mm Outer Dia duly filled with ITPC-EECP15 fixed with Copper Strip 20 x 3mm riveted or fixed with SS nut bolts incl excavation/Earth work in any strata, returning filling, disposal of surplus soil, earth pit size 2.4m x 2.4m x 3.6m deep in PCC 1:3:6 type C-1 using 20mm graded stone aggregate, funnel, with CI Frame and cover (Earth Pit not less than 3.00M deep below ground level). The Electrode is surrounded by Chemical (ITPC-EECP15) a mixture of Sulphate, Silica, Iron Oxide, Nickel Oxide, Magnesium Oxide, Sodium Oxide, Zinc Oxide, Copper Sulphate etc (Earth Enhanced Compound Powder) & Crystallized Copper Material (CCM). Earth can have resistance <1 Ohm by using earth electrode is used as per the site requirements. Chemical Compound Powder to be provided minimum 100Kg perper earthing including taking down old unserviceable one complete all as specified and directed.Notes:-(a)Material used shall be alloy coated (250 - 300 microns) GI pipes of length 3000 mm.The outer dia of pipe shall be 76.30 mm and inner dia of pipe shall be 42.40 mm.The dimensions may vary +/- 0.10 mm).(b)BFC - Two bags (25 Kg capacity of each bag).The quantity of BFC shall be generally for normal / good soils.In case the soil resistivity is high then the quantity of BFC shall be increased till get the desired result and the cost of the same is deemed to be included in the quoted rates. |
| 67 | Supply and fixing in repairs of MCB Metalica Distributition board, Double door, concealed flush to wall for mounting MCBs, factory made , conforming to IS : 13032 fabricated out of CRCA sheet not less than 1.20 mm thick fitted with DIN channel, neutral link and 200 Amps rated bus bar. DBs shall be semi glossy finished with epoxy polyster based powder paint sprayed and backed at high temperature , between powder paint process to ensure smooth finish and protection against corrosion atmosphere. The DBs shall be double door type with hinged door with locking arrangement. The DBs shall be of same make as MCBs, DB shall also be provided with lable marking indicating the incoming and outgoing circuits on all ways as specified , the DBs shall be of IP 42 protection class for the following complete all as specified and as directed. |
| 68 | TPN 4 way, 415 Volts TPN Metalica Distribution Board. |
| 69 | SPN 12 way, 230 Volts SPN Metalica Distribution Board. |
| 70 | SPN 8 way, 230 Volts SPN Metalica Distribution Board. |
| 71 | SPN 4 way, 230 Volts SPN Metalica Distribution Board. |
| 72 | Supply and fixing in replacement of MCCB incommer distribution board VTPN 04 way with metal double door CRCA steel sheet surface, powder coated, IP-54 protection suitable for MCCB as incommer and MCB as outgoing, 415 Volt 3 phase complete with appropriate size copper busbar and neutral link complete including MCCB 160A, cutting chases to wall for fixing of DB and making good disturbed surface complete all as specified and as directed. |
| 73 | Supply and fixing in repairs MCB TPN, 63 Amp, 10 KA, \"C\" curve type with overload and short circuit protection incl making necessary DB connection, testing and commissioning complete all as specified and as directed. |
| 74 | Supply and fixing of Basic all purpose decorative Slim Linear surface and wall mounted LED batten with Aluminium Channel housing, Square Profile & Lumens efficiency 105 Lumens/Watt integrated electronic driver LED tube light fitting of size 1182mm (length) 24 watt , 230 voltincluding takng down of old unserviceable one complete all as specified and directed |
| 75 | Supply and fixing in repair LED light fitting 1x9W/ 1X10W bulkhead luminaires including LED light driver holder, connecting up with three core flexible copper conductor cable of suitable sizeincluding taking down old unserviceable one complete all as specified and as directed. |
| 76 | Supply, laying and testing cable XLPE insulated screened PVC bedded, galvanized steel strip , electric power cables (heavy duty) with Aluminium Conductor of size 10 Sqmm 2 Core, 1100 Volts grade including cable glands, lugs, Saddling on wall (if required), nuts, bolts and washers of suitable size including taking out old unserviceable cable complete all specified and as directed. |
| 77 | ditto- all as per item sl No 66.00 but 16 sqmm, 4 core. |
| 78 | ditto- all as per item sl No 66.00 but 25 sqmm, 4 core. |
| 79 | Supply and fixing in repairs of aluminium lugs suitable for 16 Sqmm suitable for Aluminium/Copper cables complete all specified and as directed. |
| 80 | Supply and fixing in repairs of aluminium lugs of suitable for 25/35 Sqmm suitable for Aluminium/Copper cables complete all specified and as directed. |
| 81 | Supply and fixing in repairs modular White cover plate with frame, 3 module size as per site requirement complete all as specified and as directed. |
| 82 | Supply and fixing in repairs modular White cover plate with frame, 4 module size as per site requirement complete all as specified and as directed. |
| 83 | Supply and fixing in repairs modular White cover plate with frame, 6 module size as per site requirement complete all as specified and as directed. |
| 84 | Supply and fixing in repairs modular White cover plate with frame, 8 module size as per site requirement complete all as specified and as directed. |
| 85 | Supply and fixing in repairs of modular metal flush box, 1.6 mm thick,4 module,mounting in the wall for fitting cover plate with frame on switch/socket complete all as specified and as directed. |
| 86 | Supply and fixing in repairs of modular metal flush box 1.6 mm thick,6 module,mounting in the wall for fitting cover plate with frame on switch/socket complete all as specified and as directed. |
| 87 | Supply and fixing in repairs PVC Gang Box suitable for one No 15 Amps Switch and Socket complete all as specified and as directed. |
| 88 | Supply and fixing PVC casing & caping of size20 mm inclusive of all fittings such as tees, bends, elbow, etc and all fixing accessories such as couples,PVC Rawal Plugs, saddles, etc includingmaking surface good as original by plastering and whitewash/ colour/ distemper etc including taking down old unserviceable one complete all as specified and as directed. |
| 89 | Material & Labour for earthing with galvanized steel earth plate electrode of size 60cmx60cmx6mm thick bured directly in ground (earth pit not less than 2.25m deep below the ground level) with top edge of the plate not less than 1.5m below normal ground level, connected to the galvanized earth lead by means of bolts, nuts check nuts and washers of galvanized iron or steel usinggalvanised iron strip 32×6mm as earthing leadas shown in electrical plate No 3 of SSR Part-I connected to earthing test point all as specified or indicated including testing on completion including necessary excavation and earth work in soft/loose soil, returning filling, disposal of surplus soil, earth pit in PCC 1:3:6 type C-1 using 20mm graded stone aggregate pit, funnel, 20mm dia GI medium grade watering pipe, 15mm dia GI medium grade earth lead protection pipe and pre-cast earth pit cover 80mm thick made of RCC (1:1:5:3) type A1 duly reinforced with 8mm dia TMT bar @ 100mm c/c both ways, one lifting handle made out of 10mm dia TMT bar 250mm long embedded in cover slab and cover, wire, copper lugs, etc, mest, charcoal and common salt in alternate layer of 15cm thick including taking down old unserviceable earth plate complete all as specified & as directed. (Note: Each protection pipe and earthing lead upto and including 7.5 meter length is deemed to be included in the quoted rate of this item) |
| 90 | Dismantling the existing old unserviceable exhaust fans of any size in AC plant installations, Supply, fixing and testing of new exhaust fans 450 mm sweep, 230 Volts AC, 50 HZ, 1440 RPM, including louvers and making all necessary arrangements like gouting of bolts on wall as per requirement, nuts, bolts and washes and FI legs and frame complete all as specified and directed |
| 91 | .---Ditto all as per above item no 80.00 but of size 300 mm sweep all as specified and as directed. |
| 92 | Supply and fixing cabin fan 300mm sweep complete70 watts, 2200RPM, 230 Volts, 50Hz including taking down old unserviceable one complete all as specified and as directed. |
| 93 | Dismantling the existing old unserviceable ceiling fans of & supply and fixing new ceiling fans 1200 mm sweep, 230 Volts, 50 Hz AC including making electrical connectios with 0.5 Sqmm PVC copper conductor wire complete all as specified and directed. |
| 94 | Supply & fixing in repairs integral LED street light fitting 45 watts comprising pressure die cast housing with powder coated aluminium housing working as a heat shrink and toughened glass suitable fixing with GI pipe bracket and pre-wired including necessary electric connection from ceiling rose to light fitting complete all as specified and directed(Note:- GI bracket along with clamp, nut & bolts shall be measured and paid seperately under relevent item.) |
| 95 | M & L for GI bracket1.5 Metre long made out of GI pipe \"Light Grade\" of 32 mm dia(including bending of pipe, fixing on pole/Bldg with clamps of size 40mm x6mm of suitable length, nuts and bolts) for fixing of street light fittings including taking down old unserviceable one complete all as specified and directed |
| 96 | Supply & fixing PVC insulated twin core copper conductor cable of size 2.5 sqmm for connection of street light fittings including taking down old unserviceable one complete all as specified and directed |
| 97 | Supplyingand fixing Fire Extinguisher Carbon dioxide (CO2) extinguishers consisting of welded M.S. cylindrical body, light weightsqueeze lever discharge valve fitted with pressure indicating gauge with internal discharge tube, discharge nozzle suspension bracketof capacity 4.5 Kg as per IS: 2878 complete with holding accessories including taking down old unserviceable one complete all as specified & directed |
| 98 | ditto-all as per item No. 87.00 above butCO2 of capacity 6 Kg. |