| 1 | Opening/disconnecting the electrical connection of defetive/burnt our underground LT UG cable of any size & any core from main switch/DB/Junction box/LT Panel/LT O/H line etc.Taking out the length of cable to be required from existing loop, cutting the defective portion of cable, providing to be required thimbles/connectors at cable end and reconnecting the cable in pervious location with existing main switch/DB/Junction box/LT Panel/OH lines etc all as directed by Engineer-in-Charge. Note : (i) The cost of excavation & earth work, returning filling, in relaying of sand/ brick and cost of drawing to be required length from protection pipe, breaking of brick work/concrete/plaster to be required and redoing to be required for work to match the existing surface shall be deemed to be included in quoted rates and nothing extra should be paid on this account.(ii) Additional cable/protection pipe required at site shall be measured and paid seperatly.(iii) During currency period of contract shall depute the suffcient manpower for attending daily complaints. (iv)Minor consumable material required to complete the job as (like tape, nuts bolts, electrical gloves, M seal etc) are including in the quoted rates. (v) Complaint will be done within 48 hrs of receiving complaints while in mobile tele communications or any written/verbal/any comunication medium. (vi) Any delay by the contractor to resolve the complaint above the said period, penality of Rs 100 day will be fined. |
| 2 | Excavation in trenches n.exc. 1.5 m wide and n.exc. 1.5m in depth for foundation, shaft, manholes etc and n exc 10sqm on plan and getting out in any type of soil all complete all as specified. |
| 3 | Excavating in trenches, n exc 1.5 m wide and exc 1.5 m in depth and n. exc 3.00 m in depth for foundation, etc. or laying of cables/poles , etc and n exc 10sqm on plan and n exc 1.5 m in depth andgetting out in any hard dense soil all complete all as specified. |
| 4 | Returning, filling in, including spreading levelling including watering & well ramming in layers n. exc 25 cm as specified in soil complete all as specified and directed by Engineer-in-Charge. |
| 5 | Removing excavated materials n.exc 50 mtr and depositing where directed at level n.exc. 1.50 mtr above the starting point complete all as specified and directed by Engineer-in-Charge. |
| 6 | M&L sand cushioning with dry and clean locally available sand for under ground cable 8 cm before laying cable and 15 cm after laying and punned to 18 cm after laying of cable complete all as specified.(Note : Punned thickness shall be considered for payment purpose) |
| 7 | Supplying and laying,factory made unreinforced precast concrete cable cover LV type-1, flat, of size 250x150x40mm, laid flat and dryin trenches over the cable for protection, length perpendicular to the direction of cable adjacent to each other, complete all as specified and directed. |
| 8 | Cutting/ Trimming of tree branches not exc 10 cm girth, touching/ approching the LT OH line,3 mtr on either sides of LT over head lines mounterd on PCC/Steel poles and clearing the site by throwing the three branches and leaves etc.outside the MD land up to 100 mtr away complete all as specified and directed. |
| 9 | Material and labour for PCC (1:4:8) type D2 using 40mm graded stone aggregate as in foundation filling & mass concrete complete all as specified and as directed by Engineer-in-charge.Note : Demolation of old demanged PCC are included in quoted rates. |
| 10 | M & L for plain cement concrete 1:2:4 type B-1, using 20 mm graded crushed stone aggregate as in coping & bed block etc including weathering, slightly, rounded or chamfered angles and throating as directed necessary form work complete all as specified and directed. Note : Demolation of old demanged PCC are included in quoted rates. |
| 11 | Supply and fixing in replacment for Pin type, porcelain, vitreous, white,brown or green insulator includingone galvanised mild steel spindle,two galvanised iron washersndonegalvanisedironnut, 100 mmheight, 65mm dia for 1100 voltsgradecomplete all as specified and directed |
| 12 | M & L in repair of old unserviceable Earthing complete with galvanisedsteel pipe electrode, 40mm bore,medium grade, 2.5 metres length,buried directly and preferablyvertically in ground with top edgenot less than 1.25 metres belowground level connected withearthing lead of 4mm dia galvanisediron or steel wire all as shown inPlate No. 2 to the earthing test pointall as specified and indicatedincluding testing on completion complete all as specified and directed |
| 13 | Supply and fixing in repair for Shackle type, porcelain, vitreous, white,brown or green insulator of size 100mm height, 115 mm dia for working pressure 1100 volts includingone galvanised mild steel strips 31 mm x 5 mm, washer, insulator bolts and nuts, dia of bolt 14 mmcomplete all as specified and directed. |
| 14 | Material and labour in repair pre stressed concrete poles LT 9 Mtr long 102mmx 172mm at top and 102 mmx279 mm at bottom class-10 complying with reqirement of 15 1678-1978 including painting of pole with two coat of synthetic enamel paint with black and white strips of 30 cm each upto 1.5 Mtr height from the top of PCC coping and numberintg of poles all as specified and directed |
| 15 | M & L in repair Cross arms, bracings, supports,clamps and back plates fabricatedfrom structural steel sectionsincluding nuts, bolts, washers,welding, bending cold or hot,drilling holes for bolts, in any shapeor size as indicated or directed andinclusive of one primer coat, one under coat and one finishing coat ofpaint complete all as specified and directed. |
| 16 | M & L in repairstay assembly comprising of GI stay bow 16 mm dia, 40 cm long complete with accessories as shown in Electrical plate No 1 of SSR Part-I using galvanisedstay rod 20 mm dia, 215 cm long with threaded ends GI nuts, bolts, washers, stay plate 30 cm x 30 cm x 6 mm thick, 2 Nos thimbles, MS clamps made out of 50 mm x 60 mm flat iron, loop stay insulator, stay wire 7/8 SWG complete including painting all exposed surface of MS work including two coats of aluminium paint over a coat of red oxide zinc chromate primer complete all as specified and directed.Note : Loop type insulators, Earth work and concrete work shall be measured and paid for separately under the respective of schedule |
| 17 | S & F and stretching in repair ACSR of any size as per the site requirement on existing HT/LT poles including binding on existing insulator with aluminium binding wire 2 mm dia complete all as specified and directed.Note : For measurement and payment purpose only the weight of ACSR shall be considered.The weight of aluminium bindign wire 2.00 mm shall not be considred. 2.The rate of aluminium binding wire 2.00 mm is included in this item and nothing shall be paid extra on this account |
| 18 | Supply, fixing and stretching in repair 4 mm dia GI earth wire/guard cradles on existing HT/LT poles binding with and including GI binding wire 1.63 mm complete all as specified and directed. Note : For measurement and payment purpose only the weight of 4mm dia GI earth wire/guard cradles shall be considered.The weight of GI binding wire 1.63 mm shall not be considred. 2.The rate of GI binding wire 1.63 mm is included in this item and nothing shall be paid extra on this account |
| 19 | Taking out of Air circuit breaker 4 Pole 630 Amps to 1600 Amps, 415 Volt of breaking capacity not less than 50 KA to 65 KA with electronic/ thermal/micro processor based release,Manual draw out/ Mechinical draw out/ fixed,any type/make, cleaning service & maint of any type ACB including replacement of worn out parts and making fully smooth functioning upto desire level complete all as specified and directed. Note : All the required spare parts will be included rates quoted by the contractor |
| 20 | Cleaning and preparation of old painted surface of LT PCC pole/street light pole/ steel tubular poles complete with cross Arms and base up to 1.50 mtr height from top of PCC foundation block.Making alternative black and white strips VE water proof high density reflective self adhesive strips on pole (each strip 30 cm hight) and wirting pole nos. including applying one coat of cement base paint on exposed surface of PCC coping and foundation blocks complete all as specified and directed. |
| 21 | Supply and fixing in repair PVC separator for 3/4 way conductor complete all as specified and directed. |
| 22 | Supply and fixing in repair PVC separator for 5/6way conductor complete all as specified and directed. |
| 23 | M & L for making the hole under road and hard standing for laying and including inserting Galvanised steel light grade pipe upto 100 mm dia including all fittings as required at site by mechanical drill system or Augar system and making the surface good as per existing surface completed all as specified and directed by Engineer-in-charge Note : The rate of Galvanised steel light grade pipe upto 100 mm dia is paid seprately under appropriate item of schedule of works |
| 24 | M&L for GI pipe light grade with all fittings in replacement fixed to pole and size 40 mm bore laid to floor/ground for mechanical protection of cable including clamp, nuts, bolts and waher etc complete all as specified and directed by Engr-in-charge |
| 25 | M&L for GI pipe light grade with all fittings in replacement fixed to pole and size 80 mm bore laid to floor/ground for mechanical protection of cable including clamp, nuts, bolts and waher etc complete all as specified and directed by Engr-in-charge |
| 26 | M & L for Earth continuity conductor or mainearthing lead fixed to wall on battenor recess or chases or buried inground or drawn in conduit/pipe orfixed to poles or any other indicatedsituation for loop earthing etc. asrequired by using25 mm x 4 mm GI Stripdia galvanised iron orsteel wire complete all as specified and directed by Engr-in-charge |
| 27 | S & Ffor danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for LT of size 20x15cm complete all as specified and directed by Engr-in-charge |
| 28 | Supply and fixing (concealed flush to wall) in repairs factory made DB (made out of CRCA sheet not less than 1.2mm thick, fitted with DIN channel neutral link and 200 Amp rated bus bar) SPN, 4 Way 240V, suitable for mounting MCB/Isolator etc, conforming to IS-13032, DB shall be semi glosy finished with epoxy polyster based powder paint sprayed and backed at high temperature between powder paint process to ensure smooth finish and protection against corrosion atmosphere. The DB shall be double door type with hinged door with locking arrangement, the DBs shall be same make as MCBs, DB shall be provided with level marking indicating the incoming and outgoing circuits on always as specified. The DBs shall be of IP-43 protection class, and including making good disturbed surfaces of walls as necessaty complete all as specified and directed by Engineer-in-charge.Note :- MCB/Isolator etc shall be measured and paid separately under appropriate item of BOQ. |
| 29 | All as per srl item No 28 above but SPN DB 8 way complete all as specified and directed |
| 30 | All as per srl item No 28 above but SPN DB 12 way complete all as specified and directed |
| 31 | All as per srl item No 28 above but TPN 4 way complete all as specified and directed |
| 32 | All as per srl item No 28 above but TPN 8 way complete all as specified and directed |
| 33 | Supply and fixing MCB \"C\" series TPN 415 Volts, 63 Amp, 10 KAwith over load and short circuit protection complete all as specified and directedNote : Old unserviceabl material should be deposited to the MES E/M store by the contractor by his own arrangement without any financial benefits. |
| 34 | All as per srl item No 33 above but MCB SPN 230 Volts 40 Amp, 10 KA complete all as specified and directed |
| 35 | All as per srl item No 33 above but MCB SP 230 Volts 6-32 Amps, 10 KA complete all as specified and directed |
| 36 | Material and labour for Heat Shrinkable straight through joint suitable for LT XLPE cable size 240 Sqmm 3.5 Core 11 KV, 1100 Volt grade heavy duty including digging, Indian/international standards IS : 13573/1992/EC:60502 and deposit old at MES store for furtherdisposal complete all as specified and directred by Engr-in-Charge.Note : Exavation for taking out old U/S cable and for laying of new cable will be measured and paid seperately under respective item of BOQ. |
| 37 | All as per srl item No 36 above but 150 Sqmm 3.5 core 11 KV complete all as specified and directed |
| 38 | All as per srl item No 36 above but 95 Sqmm 3.5 core 11 KV complete all as specified and directed |
| 39 | All as per srl item No 36 above but 50 Sqmm 3.5 core 11 KV complete all as specified and directed |
| 40 | All as per srl item No 36 above but 25 Sqmm 3.5 core 11 KV complete all as specified and directed |
| 41 | Supply and fixing in repair of MCCB 63 Amp, 4 P, 16 KA, Ics=100 % Icu conforming to IEC-60947-2, Adjustable Thermal (0.8 to 1 x In and fixed magnetic release including thimbles, nuts, bolts, washers, spreader links etccomplete all as specified and directed |
| 42 | All as per srl item No 41 above but MCCB 100 Amp, 4 P, 36 KA complete all as specified and directed |
| 43 | All as per srl item No 41 above but MCCB 200 Amp, 4 P, 36 KA complete all as specified and directed |
| 44 | All as per srl item No 41 above but MCCB 250 Amp, 4 P, 36 KA complete all as specified and directed |
| 45 | All as per srl item No 41 above but MCCB 400 Amp, 4 P, 36 KA complete all as specified and directed |
| 46 | All as per srl item No 41 above but MCCB 630 Amp, 4 P, 50 KA complete all as specified and directed |
| 47 | Supply, laying, testing XLPE LT cable size185 sqmm 3.5 core,1100 volts grade heavy duty with XLPE insulated, stranded aluminium conductor served with an inner sheathening of PVC tape armoured with Galvanized steel strip or wire and over all PVC sheathed stranded conductor conforming to IS-7098 (Part-I) with latest amendment,laid in trenches/fixed to wall/pole/laid in floor including necessary connections and suitable size of thimbingcomplete all as specified and directed by Engineer-in-Charge. |
| 48 | All as per srl item No 47 above butXLPE LT cable size 95sqmm 3.5 core,complete all as specified and directed |
| 49 | All as per srl item No 47 above butXLPE LT cable size 50 sqmm 3.5 core,complete all as specified and directed |
| 50 | All as per srl item No 47 above butXLPE LT cable size 25 sqmm 4 core,complete all as specified and directed |
| 51 | All as per srl item No 47 above butXLPE LT cable size 16 sqmm 4 core,complete all as specified and directed |
| 52 | All as per srl item No 47 above butXLPE LT cable size 10 sqmm 4 core,complete all as specified and directed |
| 53 | Note:- Contractor will submit all the old unserviceable item retrived from above mentioned schedule of item to MES store yard.Transportation charges for the same is responsibility of contractor and no extra payment shall be made on this account |