| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 08-04-2025 | Online Pre Bid Meeting Link | Other | 24-04-2025 |
| Sl. No. | Item Description |
| 1 | Interior/Civil Work |
| 2 | Providing and laying vitrified glassy/ mirror finish tiles having size 590mm to 605mmx to 590mmto605mm of 8 to10 mm thickness and confirming IS.15622-2006 matching with exsiting(Group Bla) of approved make, shade and pattern for flooring, dado & Skirting in required position laid on a bed of 1:4 cement mortar including neat cement float, filling joints, curing and cleaning etc. complete |
| 3 | M20 Concrete for Bed : Providing and laying Cast in situ/Ready Mixcement concrete in M20 of trap/ granite/quartzite/gneissmetalforstepsincludingsteelcentering,formwork, laying/pumping,compacting, rougheningthem if special finish is tobe provided, finishingunevenand honeycombed surface and curing etc. complete. The Cement Mortar 1:3 plaster is considered for rendering uneven and honeycombed surface, only. Newly laid concrete shall be covered bygunnybag,plastic,tarpaulinetc.(Woodencenteringwill notbeallowed.), withfully automaticmicro processorbased PLC with SCADA enabled reversible DrumType mixer/concreteBatchmixplant(Panmixer)etc. complete. With fine aggregate (Crushed sand VSI Grade) |
| 4 | Dismantlingbrickmasonryinlimeorcementmortarandstackingthematerilsas directed with all leads, lifts etc |
| 5 | Providing Autoclaved Aerated Concrete Block masonary ofconformingtoIS:2185 (Part 3)-1984inextrafine jointing mortaroffixoblockofUltraTechorequivalentin superstructure including striking joints,raking outjointsandscaffolding etc.Complete. (The test shall be carried out conforming to IS:6441 (Part I) - 1972) |
| 6 | Providinginternalcementplaster12mm thickinsinglecoatincementmortar1:3 without neeru finish to concrete or brick surfaces, in all position including scaffolding and curing etc. complete. |
| 7 | PROVIDING & FIXING CLEAN ROOM ESD FLOORING (TARKETT)-2 MM THICK,The surface should be cleaned and surface preparation should be done using self Levelling Compound.This will be achieve a leveling of about 2mm thickness. This should allowed to be cured for 18 hours depends on weather condition or maximum 24 hrs before installation of ESD flooring. Conductive Adhesive should be spread by toothed adhesive spreader 250 - 300gms/sq. m .Copper grouting strip shall be placed /put as per the safety standard.(1.Surface to Ground & Surface to Surface Resistance tests should be carried out once the installation is completed. This will be Complaint to ESO / ESD S.7.1 standards for ESD Floor. 2. Total system resistance test as per EOS / ESD STM 97.1 standards also should be carried out. 3.Walking body voltage tests also should be carried out as per EOS / ESD STM 97.2 standards.) |
| 8 | Luster Painting: Providing and applying impression luster paint of approved make & approved brand Emulsion paint to interior walls and ceilings of approved quality, colour and shade to new surface in two coats, including subsurface prparation by Acrylic putty and Acrylic primer coats including scaffolding, preparing the surface. etc. complete (Low VOC). |
| 9 | New partition, ceiling and aligned work |
| 10 | Providing & Fixing in position, Acoustical partition (Flooring to 3m height) made from 12mm w p Plywood & 1mm laminate on both side,50x50 mm commercial-wood frame of 600x600 c to c having wooden supports from wall of required length, infront of 1000 Gsm synthetic wool 50 mm , including cost of required Cut-Outs, decorative mouldings / finishing-items/paint & Scaffolding, as per Architectural & Acoustical Design & Instructions & Complete in all aspects. including all materials labour,finishing etc complete. (Laminates colour & pattern should match with existing clour and pattern of floor) |
| 11 | Providing & Fixing in position Acoustical partition , partly laminated partly glaze (Flooring to 3m height) ( finished in laminate on both the sides for part area and toughened glass 12mm thk. as per design) Acoustical partition made from 12mm w p Plywood & 1mm laminate on both side, 50x50mm commercial wood frame of 600x600c to c having teak wood supports from wall of required length, in front of 1000 Gsm synthetic wool 50mm thick including cost of required Cut-Outs, decorative mouldings/ finishing-items / pain & Scaffolding, as per Architectural & Acoustical Design & Instructions & Complete in all aspects. including all materials labour, finishing etc complete. Laminate to be of Merino(Micro line) range. (Note : Fosted glass film matching with existing pattern has to be provided by vendor only, make 3M or equivalent) (Toughen glass dimesion 0.9m (ht) with suitable length) |
| 12 | Providing & Fixing in position, Wooden Frame for Acoustical Partition (3m to ceiling Height) (Only Frame work, ply and laminate not to be considered)Providing & fixing in position a wooden framework for acoustical partition from 3m to ceiling height using 50x50 mm commercial wood frame at 600x600 mm center-to-center spacing, with necessary wooden supports from the wall of the required length. The work includes necessary cut-outs, scaffolding, and finishing as per architectural & acoustical design and instructions, complete in all respects, including all materials, labor, and finishing |
| 13 | Column cladding with commercial wood frame, finished in laminate Fluorescent. The t.w. frame 2\" x 1 1/2\" @ 1\"6\"x1\"6\" grid covered with 6mm comm. Plywood on the outer side (no plywood required on inside partion). The approved colour fluroscent laminate matching with existing laminate colour of minimum 1 mm thickness shall be used |
| 14 | Providing & fixing custom-designed showcase with storage boxes panel in ply panel wall, storing boxes of size 450mmx300mmx600mm along both sides of the corridor for displaying C-DAC products. The showcase will be made using high-quality plywood with a decorative laminate finish, incorporating necessary shelving, glass panels (in front)( vertical gap between boxes 600mm, horizontal gap between boxes 350mm), and other essential materials. The work includes precise fabrication, finishing, and installation as per approved design, ensuring durability, aesthetics, and functionality. Complete in all respects, including materials, labor, and necessary fittings. ( please ref ere the drawing attached with tender) |
| 15 | Providing and fixing in position Gypsum board false ceiling with 12.5 mm thick Gypsum boards, screwed/fixed to the under structure of suspended G.I. Grid constructed and suspended from the main ceiling consisting of ceiling sections of size 25 x 50 mm maximum center to center distance of 600 milimetre perimeter channel and intermediate channels at maximum center to center distance 1200 milimetre galvanized grid should be fixed to reinforced cement concrete slab. The gypsum board should be fixed to galvanized iron grid with necessary screws. The boards should be taped and filled from underside to give smooth, seamless ceiling. The rate should include necessary additional ceiling sections and intermediate channels. Additional intermediate channels should be fixed to strap hangers for additional support to prevent strapping at every 1200 milimetre item to be completed in all respect including necessary sleeves for ducts finishing of joints cut outs, painting including labour, material, lifts etc. all complete. |
| 16 | Providing and Fixing Mineral Fibre Acoustical Suspended Ceiling System with Fine Fissured (Bevelled Tegular) Edge Tiles of size 15mm Exposed Grid. The tiles should have Humidity Resistance (RH) of 99%,NRC 0.6, Light Reflectance 85%, Thermal Conductivity k = 0.052 - 0.057 w/m K, Colour White, Fire Performance UK Class 0 / Class 1 (BS 476 pt - 6 &7) in module size of 600 x 600 x 16mm , with Recycled content of 31 %. The tile shall be laid on precoated G.I channel height of 32 with 15 mm wide T - section flanges colour white having rotary stitching and XL2 CLIP on all T sections i.e. the Main Runner, 1200 mm and 600 mm Cross Tees with a web height of 32mm and a load carrying capacity of 7.57 Kilograms/M2 and pull out stength of minimum 100 Kilograms.. The T Sections have a Galvanizing of 90 grams per M2 and need to be installed with Suspension system, etc. complete (Pattern to be matched with exisiting false ceiling pattern) |
| 17 | FIRED RATED DOUBLE DOOR -1800X2400 MM double leaf2 hour fire rated Entrance door frame and leaves shall be made from galvanized steel 46mm thick fully flush, door shell in specially designed honeycomb structure for reinforcements & 1 hour fire rated vision glass of size 300 mm X 300 mm. Door will be primed with zinc-phosphate stoving primer and finished with epoxy paint as required, complete with all accessories like door closer, handle, lock etc. All door shall be provisioned with GI frame required . |
| 18 | Providing and fixing solid core flush doorwith vision glass shutter in double leaf 32 mm thick decorative type of exterior grade as per detailed drawings approved face laminate 1 mm thick on both faces or as directed, all necessary beads, mouldings and lipping, wrought iron hold fasts, chromium platedfixturesandfastenings,withbrassmortiselock,chromiumplated handlesonboth sides, etc. complete. |
| 19 | Providing and fixing frame with /without ventilator of size as specified with Country non teak wood for doors and windows including chamfering, rounding, rebating, iron hold fast of size 300mmx40mmx5mmwith oil painting, etc. complete |
| 20 | Providing and Fixing Vertical Blinds of approved Make and shade of 100mm regular fabric with powder coated aluminium channel with telting PVC chain & bottom weight plate with all necessary fixtures and fitting etc. complete. (Sample to be final by Engineer In charge prior execution of work) |
| 21 | Providing and Fixing Roller Blinds of approved Make and shade of regular fabricwith powder coated aluminium channel if required) with telting PVC chain & bottom weight plate with all necessary fixtures and fitting etc. complete. (Sample to be final by Engineer In-charge prior execution of work) |
| 22 | Supplying, fitting & fixing Surface mounted overhead Door Closer for 2 hour fire rated doors of different size (e.g size -EN-3 for leaf width upto 900mm) CE certified, marked & conforming to EN - 1154 of approved quality (Internationally reputed brand like Dorma, Geze, Hafele, Assabloy & Magnum etc.) fitted and fixed Complete as per direction & satisfaction of Engineer -in Charge including all taxes & incidental charges. |
| 23 | Furniture |
| 24 | Staff Chair : Providing and fixing Motion Mid back office chair with suitable caster wheels, Contact-Tilt Mechanism , Seat Height Adjustable, Adjustable arm rest, Mesh back fabric, lumbar back support. Finish colour –Black. PU foam cushion seat. Note -The chair should be from the same OEM of modular workstation |
| 25 | Staff Table: Supply & installation of1200x600 size tableTable of Three layer prelaminated particle board(Wood Product) of IS 12823/Latest1)Table top Material-Three layer prelaminated particle board(Wood Product) of grade II type II of IS 12823/Latest2)Leg Material-NO LEGS3)Thickness of table top ±2 mm25 millimeter4)Length of table top ±10 mm1200 millimeter5)Depth of table ±10 mm600 millimeter6)Height of table ±10 mm750 millimeter7)Warrantee period in number of years18) Product shall be ISO 9001:2015, ISO 14001:2015,ISO 18001:2007 certified9)Frame type- Free standing10)Understructure of table- Gable end and modesty panelApproved / Recommended makes- Godrej /Neelkamal/ Featherlite or equivalent as approved by client. |
| 26 | Supply and fixing of Godrej Pedestal Unit of 646x390x440 mm . Construction & Material- 1)Welded Assembled 2)0.8 thk CRCA for Body Shell, Drawer Front & tray, Front Side Stiffener, Rear Side Stiffener & Bottom 3)1.2 thk CRCA Top Stiffener & Bottom stiffener Drawer Fronts- 1)Metal Front Straight Edge 2)18 thk Wooden (PLB) Front Straight Edge / PVC Lipping on all Edges Drawer Specification- 1)All Drawers with Double extension precision ball slide 2)390 wide Pedestals File drawer - suitable for storing Fullscape files in Depth wise manner. A4 files in width wise manner 3)450 wide Pedestals File drawer - suitable for storing Fullscape files in Width & Depth wise manner. A4 files in depth wise manner 4)In 585 deep units, 1 no of File hanger provided in File Drawer 5)For Drawer pulling, side wise tapered recess provided in shell behind Drawer Fronts. Locking- 10 lever Cam Lock & Central RH locking with actuator & lock channel mechanism for ‘Box-Box-File’ & ‘4 Box’ Pedestals • Swiveling non-lockable Castors mounted below the body shell |
| 27 | Supply & fixing of Table size 1500x750mm with extended return unitTable of Three layer prelaminated particle board(Wood Product) of IS 12823/Latest 1)Table top Material-Three layer prelaminated particle board(Wood Product) of grade II type II of IS 12823/Latest 2)Leg Material-NO LEGS 3)Thickness of table top ±2 mm25 millimeter 4)Length of table top ±10 mm1500 millimeter 5)Depth of table ±10 mm750 millimeter 6)Height of table ±10 mm750 millimeter 7)Warrantee period in number of years1 8) Product shall be ISO 9001:2015, ISO 14001:2015,ISO 18001:2007 certified 9)Frame type- Free standing 10)Understructure of table- Gable end and modesty panel |
| 28 | Dismantling, Shifting, and Re-Installation of Lab Table: Dismantling, shifting, and re-installation of the existing lab table from the 4th lab to the new lab area on the 1st floor (North side). The work includes careful disassembly, safe transportation, and proper reinstallation, ensuring stability and alignment as per the original setup. Complete in all respects, including necessary labor, tools, and finishing. |
| 29 | Storage Area at Lower Ground |
| 30 | Providing & Fixing in Position, Partition with One-Sided Plywood for Storage Area at Lower Ground Floor : Providing & fixing in position a partition made with 12mm WP plywood on one side and an exposed 50x50 mm commercial wood frame at 600x600 mm center-to-center spacing on the other side to create a storage area at the lower ground floor. The partition will have necessary wooden supports from the wall and ceiling of the required length etc complete in all aspects, including all materials, labor, and finishing. |
| 31 | Providing & Fixing 1mm Laminate on Plywood Partition or Plywood Surface: Providing & fixing 1mm thick laminate of approved make and shade on the provided plywood partition or plywood surface. The work includes proper surface preparation, adhesive application, edge finishing, and ensuring a smooth and seamless finish as per the approved design and instructions. Complete in all respects, including all materials, labor, and finishing. |
| 32 | ELECTRICAL AND ALLIED WORKS |
| 33 | Supply and installation of suitable ways Main Distribution Panel, Metal type,Double Door (As approved by client / consultant / architect), RAW(Raw+AC+ Lighting) Panel surface / flush mounted on wall, with digital metering Phase wise (Voltage & current )on Panel ,Copper Bus bar,LED Indicators, all accessories completed ,interconnected wiring complete with earthing lugs, including DB wiring dressing with ferruling, termination of circuits with ping type copper lugs, blank plates, etc. housing following switchgears : (Schneider / Hager / Siemens / Legrand make as approved by client /consultant) (Note :- DB size & type selection shall be done with reference to the total number of modules / poles available in the DB which shall be suitable for housing of below mentioned switchgears & components forming a complete set.) a) 1 no., 250 A, FP MCCB, \"C\" curve type 25kA, MCCB with Thermal Magnetic release(I/C), of approved make with over load (O/L), short circuit (S/C) & Earth Fault (E/F) protection. The Breaker shall be suitable for 415 Volts 50 Hz., AC supply. The breaker shall have breaking capacity of 25kA for 1 Sec. as required. (Schneider / Hager / Legrand / Siemens / L&T make)as incomer b) 18nos,63A,4P,MCB,\"C\"curvetype+ 06Nos.16/32AmpDP-MCB(Schneider / Hager / Legrand / Siemens / L&T make) as outgoings -Full set as above. |
| 34 | Suply and installation of 6-way, TPN, Metal type, Double Door (As approved by client / consultant / architect), Raw/Light/AC/UPS OUTGOING SUB -DB in respective rooms, surface / flush mounted on wall, interconnected wiring complete with earthing lugs, including DB wiring dressing with ferruling, termination of circuits with ping type copper lugs, blank plates, etc. housing following switchgears : (Schneider / Hager / Siemens / Legrand make as approved by client / consultant) (Note :- DB size & type selection shall be done with reference to the total number of modules / poles available in the DB which shall be suitable for housing of below mentioned switchgears & components forming a complete set.) a) 1 no., 63A, FP MCB, \"C\" curve type as incomer b) 9 nos, 16/25/32A, SP, MCB, \"C\" curve typeAND 3 nos, 63A, TP, MCB, \"C\" curve typeas outgoings -Full set as above. |
| 35 | Supply and installation of 12-way, VTPN, Metal type, with Plain / Transperant DoubleDoor (As approved by client / consultant / architect), UPS Main Power Distribution Board , surface / flush mounted on wall, interconnected wiring complete with earthing lugs, including DB wiring dressing with ferruling, termination of circuits with ping type copper lugs, blank plates, etc. housing following switchgears : (Schneider / Hager / Siemens / Legrand make as approved by client / consultant)a) 1 no.,125A, MCCB, \"C/D\" curve type 25kA, MCCB with Thermal Magnetic release, of approved make with over load (O/L), short circuit (S/C) & Earth Fault (E/F) protection. The Breaker shall be suitable for 415 Volts 50 Hz., AC supply. The breaker shall have breaking capacity of 25kA for 1 Sec. as required. (Schneider / Hager / Legrand / Siemens / L&T make)as incomeras b) 12 nos, 63A,TP , MCB, \"C/D\" curve type(Schneider / Hager / Legrand / Siemens / L&T make) as outgoings Full set as above. |
| 36 | Supply and installation of 8-way,SPN, Metal type, Double Door (As approved by client / consultant / architect) UPS /Raw Power Distribution Board, surface / flush mounted on wall, interconnected wiring complete with earthing lugs, including DB wiring dressing with ferruling, termination of circuits with ping type copper lugs, blank plates, etc. housing following switchgears : (Schneider / Hager / Siemens / Legrand make as approved by client / consultant),I/C-32 A DP MCB,6 Numbers 10/16 AMP SP MCB as Outgoings |
| 37 | Supply & Installation of 25/32A, DP, MCB, box with 20A, metal clad / modular plug-socket including power circuit of (4/6 sq.mmX3core) copper flexible wires directly taken from the relevant Raw/AC DB of the room through PVC conduits for room CASETTE /SPLIT A/C including allnecessary hardware & accessories, etc. (Schneider / Hager / Legrand / Siemens / L&T make) |
| 38 | ELECTRICAL & ALLIED WORKS - CABELS / MAINSSupply & Installation of 1100V grade armoured cable having sector / circular shaped aluminium / copper conductor PVC insulated cores, laid up, PVC tape wrappe d inner sheathed, GI strip / wire armoured and overall extruded PVC sheathed confirming to IS: 1554, laid on wall / ceiling using GI clamps & spacers as per route shown at site and further as directed by Consultant at site in the following sizes :- (Make - Polycab / Finolex / RR / Havells)NOTE :- All cables shall be provided with temporary labelling at every 5mtrs & then finally with metal indentification tags showing the size & the location from/to the respective Panel / DB, at both the ends.Therate should include terminations at both ends with suitabls lugs and glands as applicable |
| 39 | 4C x 10 Sq.mm PVC Coppercable with 2 runs of 12 SWG GI bare wire(Sub Main Panel to ROOMUPS DB) |
| 40 | 4C x 16 Sq.mm PVC Coppercable with 2 runs of 12 SWG GI bare wire (Sub Main Panel toROOM RAW/AC DB) |
| 41 | 3C x 6 Sq.mm PVC Coppercable with 2 runs of 12 SWG GI bare wire(ROOM UPS DB TO UPS SPN DB) |
| 42 | 4C x 4 Sq.mm PVC Copper cable with 2 runs of 12 SWG GI bare wire(ROOM UPS DB TO UPS SPN DB) |
| 43 | 4C x 50 Sq.mm PVC Aluminiumcable with 2 runs of 12 SWG GI bare wire(Main UPSPanel to Site SUB Main UPSPanel /DB) |
| 44 | 4C x 150 Sq.mm PVC Aluminium cable with 2 runs of 12 SWG GI bare wire (Main Raw Panel to Site SubMain RAW Panel /DB) |
| 45 | WORKSTATION UPS POWER WIRINGSupply & Installation of concealed / ressessed UPS point wiring using 600V 3R (P+N+E) x 1.5 Sq.mm copper conductor PVC insulated wires (with proper R,Y,B color code) pulled through already laid PVC raceway on walls and through table partition including 3R (P+N+E) x 2.5 Sq.mm circuit wires from the relevant DB and also including 2.5 sqmm green color copper earth wire and approved make modular type switch plate, switches, MS concealed back box, etc. as required & as approved by the consultant. (The item rate shall include Lighting / Raw /UPS Power Circuit wiring from relevent DB to the switch board with 3Rx2.5 Sq.mm wires & from switch board to next switch board OR to the first lightpoint / primary point / full point) NOTE :- 1. Only PVC insulated wire shall be used; 2. Conduit carrying circuit wiring should not carry point wiring and Conduit carrying point wiring should not carry submain/circuit wiring; 3. Flexible conduits & Elbows are not allowed; 4. The wires from ceiling junction to light points / light fixture shall be drawn in flexible PVC conduit with adptor & cover for junction box & crimp type lugs at both the ends alongwith necessary hardware & accessories, etc. as required;5.Proper ferrules,lugs, must be used in all cabling and wiring on both load / source end; 6. Each switch board must be provided with respective ferrules representing the respective DB, Phase & Circuit numbers; 7. Looping of Neutral / Earth wire between two seperate Primary / Full Points is strictly not allowed; 8. Looping of Neutral / Earth wire between two seperate circuits on similar or other phase is strictly not allowed; 9. Ferulling / numbering / taggning to wires with circuit number & db name for all lighting & raw / ups power shall be strictly followed at both DB & switch board / switch socket boards ends. |
| 46 | Supply & Installation of primary point wiring for UPS or stabilized power plug points on workstations / tablefor computers using 3C X 2.5 Sqmm copper conductor PVC sheathed white color flexible cable pulled through already laid Surface PVC Box raceway and table/workstation partition raceways and taken upto table top using PVC rigid or flexible conduits run within wooden/metal partitions. Each point consisting of 2 nos of 5A , 3 pin sockets above table top/bottom & 2 No., 15A Switch above table top, wired together forming one point. The earth wire of 3 core flexible cable to be of yellow-green color only. (Total 4 no.s desks/points served by one circiut from DB) |
| 47 | Supply & Installation of Secondary point wiring for UPS or stabilized power plug points on workstations / table for computers using 3C X 1.5 Sqmm copper conductor PVC sheathed white color flexible cable pulled through already laid tablepartition raceways and taken upto table top using PVC rigid or flexible conduits run within wooden/metal partitions. Each point consisting of 2 nos of 5A , 3 pin sockets above table top/bottom & 2 No., 10/15A Switch above table top, wired together forming one point. The earth wire of 3 core flexible cable to be of yellow-green color only. ( Maximum 3 no.s desks to be looped from each primary UPS point from first desk as per instruction for staff area and Maximum two point to be looped from each primary UPS point from first desk ) |
| 48 | ELECTRICAL & ALLIED WORKS - WALL PVC -RACEWAYS |
| 49 | Supply and laying PVC Trunking/Raceways with cover, & two cable compartmentfor UPS PowerCircuit Cable and Data cablesa) 75 x 75 x 1.6mm thick PVC Raceways with cover |
| 50 | ELECTRICAL & ALLIED WORKS - LIGHTING POINTS IN ROOM,Supply & Installation of concealed / ressessed / surface light point / fan point / call bell point wiring using 600V FRLS grade 3R (P+N+E) x 1.5 Sq.mm copper conductor PVC insulated wires (with proper R,Y,B color code) pulled through heavy gauge PVC conduits laid concealed over false ceiling or in wall chases or on the ceiling in case of an open ceiling including 3R (P+N+E) x 2.5 Sq.mm circuit wires from the relevant DB and also including 2.5 sqmm green color copper earth wire and approved make modular type switch plate, switches, MS concealed back box, etc. as required & as approved by the consultant. (Each circuit shall not feed more than 8 points OR 800 watts as per following configuration.) (The item rate shall include Lighting / Raw / UPS Power Circuit wiring from relevent DB to the switch board with 3Rx2.5 Sq.mm FRLS wires & from switch board to next switch board OR to the first light point / primary point / full point) |
| 51 | Primary raw light points including the cost of 5A switch |
| 52 | Secondary raw light points looped from the above point(maximum 3 points looped from one primary light point ) |
| 53 | Primary emergency(UPS Supply) light points connected directly to UPS DB |
| 54 | Secondary emergency(UPS Supply) light points looped from the above primary emergency light point(maximum 3 points looped from one primary emergency light) |
| 55 | Supply&Installationof(26-32W)(2\"X2\")fulllitpaneltypeLED Light fixture.,CRI >80,The fitting shall be suitable for grid / plain ceiling type & surface mounted / to be hanged from the ceiling at the height approved by architect. (CGL , PHILIPS WIPRO , GE or equivalent category & model as approved by client / architect / consultant.) |
| 56 | Supply & Installation of (12 W) LED Spotlight/Down light flush mounted Light fixture. (CGL , PHILIPS WIPRO , GE or equivalent category & model as approved by client / architect / consultant.) |
| 57 | Supply & Installation of (3 W) LED Warm White Showcase Spotlight flush mounted Light fixture. (CGL , PHILIPS WIPRO , GE or equivalent category & model as approved by client / architect / consultant.) |
| 58 | ELECTRICAL & ALLIED WORKS - DATA NETWORKING |
| 59 | Supply & Installation of Modular Data point including approved make Cat - 6 UTP cable through already laid trenches, and new flexible conduit in table partion ,RJ45 information outlet face plate, etc. with Termination, Testing and Documentation of UTP Points complete as required.(D-Link or equivalent) |
| 60 | Supply & installation of 24 Port 1 Gbps(Minimum) Unmanage switch including crimping complete in all respect etc. with both ports for Ethernet and Fibre Uplinking(D-Link or equivalent) |
| 61 | Supply & installation of 24 port jack panel in existing network rack(D-Link or equivalent) |
| 62 | Supply of mounting patch cord (3 feet\") |
| 63 | Supply of mounting patch cord (7 feet\") |
| 64 | Supply & Installation of 12 U floor/wall mounted network rack including all necessary hardware, accessories, etc. |
| 65 | Supply & Installation of 42U floor mounted network rack including all necessary hardware, accessories, etc. |
| 66 | Supply & laying of approvedmakeCat -6 UTP cable through PVC conduits,with Termination, Testing and Documentation complete as required for uplinking(D-Link or equivalent) |
| 67 | Supply & laying of approved make LC to LC Duplex6-Core MMF OM3(50/125) Fibre Patrch Cord through PVC conduits,with Termination, Testing and Documentation complete as required for uplinking(Commescope or equivalent) |
| 68 | Supply & installation of 12 port LIU with pigtail , connectors (Loaded) with necessary hardware etc in existing network rack(D-Link or equivalent) make. |
| 69 | Supply & layingof 25 mm PVC conduit pipe (AKGor equivalent) make |
| 70 | Supply & fixing of optic fiber LC to LC patch cord innetwork rack(D-Link or equivalent make ) |
| 71 | Labour charges of fiber optic splicing work with necessary connection and terminations |
| 72 | Supply & fixing of optic fiber 10G SFP+transreceivers ( LC )inswitched in network rack(D-Link or equivalent make ) |
| 73 | ELECTRICAL & ALLIED WORKS - PA SYSTEM |
| 74 | SITC of Speaker wire of 1.5mm, 2 core PVC Speaker Cable, twisted pair manufactured with bright annealed electrolytic oxygen free grade tinned copper conductors, bunched compactly(through new PVC conduit) from amplifier upto speaker and speaker to speaker |
| 75 | SITC OF Speaker 6 watt ( make-BOSCH / AHUJA) or equivalent make |
| 76 | Supply, Installation & Testing of Amplifier ,60 watt,forAddress System suitable to operate on 230V A.C. / 12V D.C. supply with two low impedence microphone input, tone control, protection circuit complete for the speakers output lines. (Ahuja / approved equivalent make) |
| 77 | A compact & reliable single channel VHF Wireless Microphone AWM-520VL. It features a tie-clip microphone with a VHF high band body-pack transmitter and a sensitive noise squelch receiver. Single channel VHF wireless microphone available in six different frequencies. Electrect condenser unidirectional microphone. Transmitter has an on ON/OFF switch and a LED for ON indication. Stylish table-top receiver with a telescopic antenna & noise squelch circuitry.Power ON/OFF switch and output volume control on the front panel.1/4\" (6.3mm) phone jack for audio output on the rear panel of the receiver. Microphone operates with 1×9V battery. Receiver operates on 9V DC through an AC adaptor, supplied along with the microphone. |
| 78 | Active Speaker 400w with stand,400W @ 1% Distortion, Short Circuit, Open Circuit and Thermal ,Built-in soft clip limiter for speaker protection,Integrated stand mounting socket,Ergonomically-shaped handles for easy transportation.Ergonomically-shaped handles for easy transportation,Durable plastic moulded enclosure with a wood grain finish. |
| 79 | Live Mixer 8Channel with USB /BT,8 Mic / Line with high-quality USB MP3 Player and Bluetooth on board,USB MP3 Player on AiR 8U plays & displays track numbers & is supplied with a remote,3 Band EQ per channel,1 Aux send,PFL (Cue) Switch with individual channel control,L/R pan pot and clip LED per channel,Stereo RCA CD input with Control,Delay EFX on board & FX send per channel,Headphone output with level control,Balanced XLR & ¼” Jack Master Output. |
| 80 | Dual Hand Wireless Microphone,Mute Function,Two handheld microphone, Receiver, 12 V AC Adapter, Phono to Phono cord, |
| 81 | Dual UHF Lavalier Wireless Microphone System |
| 82 | XLR to XLR cable 25 mtr. |
| 83 | ELECTRICAL & ALLIED WORKS - FIRE ALARM SYSTEMS |
| 84 | Supply, installation, testing and commissioning of Response indicator for all Above Ceiling Smoke detectors located above false ceiling (The integration of RI with detector and existing repeater/ main fire panel is in vendor scope). |
| 85 | Supply, installation, testing and commissioning of Analogue Addressable Photo-Electrical smoke detector (Above Celing and Below Ceiling) with programmable for timed automatic sensitivity selection with base, junction box and other accessories as required and detectors shall be UL listed.(OSD)below False ceiling(Note- The repeater /main fire panel is already installed. The programming of detectors and its integration with existing fire panel is in vendor scope)Make:-Siemens ( to intergate with existing system),Model-HFP-11 |
| 86 | Supply, installation, testing and commissioning of Analogue Addressable Fault isolator module capable of monitoring shorted loop circuit and automatically restore communication when shorted conditions are corrected.Make:-Siemens ( to intergate with existing system) |
| 87 | Supply, installation, testing and commissioning of Addressable Control Relay ModuleMake:-Siemens ( to intergate with existing system) |
| 88 | Supply, installation, testing and commissioning of AddressableSingle action Manual pull station having an integrally mounted addressable moudle that monitors and reports contact status.Make:-Siemens ( to intergate with existing system) |
| 89 | SITC OF Hooter -addressable digital type with required Hooter operating voltage 12V/24V/220 volt, wiring And allied required accessories.Make:-Siemens ( to intergate with existing system) |
| 90 | SITC OF FRLS Fire CABLE 2 X 1.5 Cu armoured cable |
| 91 | LCD Projector. |
| 92 | SITC of LCD Projector with ceiling mounting stand ,Contrast Ratio:15,000:1,Light Output of 3,300 lumens,HDMI &USB Ports,EPSON-EB series or eqivalent as approved by client |
| 93 | SITC of HDMI Cable as approved by client for projectors (each cable of 15 mtrs length) |
| 94 | TRENCHING / FLOOR -RACEWAYS |
| 95 | Supply and laying Raceways(for under floor trenches / On trays) on existing flooring. Racewaysshall be fixed to the flooring with GI clamps for finished levels as per the site conditions or through partitions with all accessories. The rate shall include preparation of trenches of required sizes by carefully removing the malwa on existing floor for laying Raceways/conduits for power, data, telephone cables etc. The depth of the trenches shall be at least 2 inches from the finished floor level or upto RCC of the slab. The rate shall include the cost of the Raceways/conduits. The rate shall also include the activity of clearing the debris generated from the preparation of trenches |
| 96 | 300 x 40 x 1.6mm thick GI Raceways(for Power cable) |
| 97 | 150 x 40 x 1.6mm thick GIRaceways (for Data Cables & phone cable) |
| 98 | Supply&Installationoffloorjunctionboxeswithouttopcoverforabove raceways, of following sizes, fabricated out of M.S. sheets, fully powder coated with provision for removable M.S. / S.S. screwed cover plates on all four sides for blocking the entry into the junction box. All the junction boxes to be (with stud) \"properly earth - bonded with the raceways pipe using 12 SWG Copper bare wire as directed at site. |
| 99 | for Junction Box of size (350mm x 350mm x 50mm x 2.5mm thick) |
| 100 | for Junction Box of size (200mm x 200mm x 50mm x 2.5mm thick) |
| 101 | Supply&Installationofsuitablesizes2mmthickremovablecoverplate screwed on all four sides of M.S. sheet, fully powder coated, for blocking the entry into the floor junction box for following sizes of junction boxes with rounded corners as per the instruction given & sample approved by the client / architect / consultant at site.Cover plate shall have required no.s of 1\" dia knockouts for flexible conduit outlets as per the requirement. |
| 102 | for Junction Box of size (350mm x 350mm x 50mm x 2.5mm thick) |
| 103 | for Junction Box of size (200mm x 200mm x 50mm x 2.5mm thick) |
| 104 | Supplying & fixing of 2mm thick G.I. Perforated type cable Trays ofapproved make. The cable tray shall be fixed to the ceiling / wall with MS angle support with 35mmx2mm thick GI slotted \"C\" channel patti at an interval of 1 meter or the MS angle iron fabricated support depending upon the location. The rate shall include the cost of Supports, hardware & accessories, etc. complete as required. |
| 105 | Cable Tray :- 300 mm wide x 50 mm height x 2mm thick. |
| 106 | Cable Tray :- 150 mm wide x 25 mm height x 2mm thick. |
| 107 | VOICE/TELEPHONENETWORKING |
| 108 | Supply & Installation of Telephone /Voice point including approved make Cat - 6 UTP cable through already laid trenches / conduits, RJ45 information outlet, in single face plate, in workstation partion wall etc. with Termination, Testing and Documentation of UTP Points complete as required. |
| 109 | Supply, installation, testing and commissioning of indoor type telephone200 pair Main Distribution Frame (MDF) / Box with Krone modules with suitable S.S. frame for mounting tag module, cable, wires and incorporated in 16 SWG MS box with properlockable cover. The box should be fixed on wall with suitable fasteners including painting & earthing. This also includes fixing the cable, distribution chart sufficient space for the cables, wires etc.to be provided in the box. |
| 110 | Supply & Installation of and commissioning of indoor type telephone50 pair MDF with Krone module including all hardware & accessoried , etc. complete as required.with suitable S.S. frame for mounting tag module, cable, wires and incorporated in 16 SWG MS box with proper lockable cover. The box should be fixed on wall with suitable fasteners including painting & earthing. This also includes fixing the cable, distribution chart sufficient space for the cables, wires etc.to be provided in the box |
| 111 | Supply & Laying of 20 pair telephone cable through heavy guage pvc conduit including all necessary hardware & accessories, etc. |
| 112 | Supply & Installation of Modular raw power point including 5 amp switch and socket complete as required with laying of cable of 3CX2.5 SQMM in New PVC Conduitfrom DB to Primary Point(anchor romaor equivalent) (Primary raw Point) |
| 113 | Supply & Installation of Modular raw power point including 5 amp switch and socket complete as required with laying of cable of 3CX1.5 SQMM in New PVC ConduitfromPrimary to Secondary Point (Secondry raw Points) |
| 114 | Supply & Installation of Modular raw power point including 15 amp switch and socket complete as required with laying of cable of 3CX2.5 SQMM in New PVC Conduitfrom from DB to Point |
| 115 | Earthing point |
| 116 | Providing and fixing copper strip 50X6mm for earthing with Insulation ( Yellow),with required accessories on the wall |
| 117 | Providing and fixing insulating supports on wall to hold the above copper strip with required accessories |
| 118 | SITC of 10 Sqmm copper flexible cable from copper strip to Copper strippoint 2 Run ( Green ) with cable through PVC conduit pipe with all required accessoris |
| 119 | 10 Sqmm copper flexible Cable termination ( Copper strip to Copper strip ) including required testing ,accessories lugs,nut bolt etc complete. |
| 120 | HVAC WORK |
| 121 | SITC of Chilled Water piping Insulation on (50mm thick pipe )with 16 mm thick nitrile rubberinsulation covered with 28 Swg aluminium sheet from existing Main Header to existing AHU (Approx.5 mtrs length) |
| 122 | SITC of Temperature/PressureGuage |
| 123 | SITC of TemperatureGuage |
| 124 | SITC of PressureGuage |
| 125 | Supplying, Fixing,testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications. |
| 126 | Actuator |
| 127 | Damper |
| 128 | Testing & commissioning of Existing AHU with exisitng installedvalves Station , controller & VFD (The working of AHU on VFD is in vendor scope) |
| 129 | Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes,hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.Note- 1)All necessary cutting,duct joint gasket ,nutboltetc shall in vendor scope. 2)The neck size of the SA diffuser selection & Floor/AHU CFM balancing is in vendor scope) |
| 130 | Thickness 0.80 mm sheet |
| 131 | Thickness 0.63 mm sheet |
| 132 | Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc, as per specifications.(Note-The VCD is to be installed/fixed inside existing ducting.All necessary cutting,duct joint gasket,nutbolt etc shall be in vendor scope) |
| 133 | Supplying, fixing testing commissioning of supply air diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable core. |
| 134 | Supplying, fixing testing commissioning of Return air diffusers of powder coated aluminium without volume control dampers with anti smudge ring & removable core. |
| 135 | Supplying and fixing of 19 mm thickness duly laminated aluminum foil of mat finish closed cell Nitrile rubber (Class \"O\") insulation onduct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required. |
| 136 | Acoustic insulation of duct with 12 MM thick CR-300 rigid board (Fiber Glass) covered with RP Tissue & 30 G perforated Aluminium cladding. |
| 137 | Installationof Motorised Fire Dampers with Linkage & dead weights / spring etc (Fire damper will be provided by C-DAC .All related work i.e fixing, wiring etc is in vendor scope) |
| 138 | CASSETTE AC WORK |
| 139 | Supply of Cassette AC of 2TR (2star non inverter model) with One year Comprehensive warranty. |
| 140 | Supply of Cassette AC of 1.5TR (2star non inverter model) with One year Comprehensive warranty. |
| 141 | LOW SIDE |
| 142 | Indoor and outdoor unit Installation,testing, commissioning charges |
| 143 | REFREGERENT PIPING,POWER/CONTROL CABLING FORCASSETTE AC:-Supply, Installation, Testing & Commissionin of copper piping complete with copper fittings & charge of refregerant gas for the above units(including drilling through wall), Piping associated with Cassette AC unitsshall be insulated with 13 mm thick closed cell elastomeric insulation .Quoted price shall be inclusive of UV protection paint for all exposed pipes.Price shall be comprise of copper power cabling from indoor to outdoor unit as required. |
| 144 | CONDENSATE DRAIN PIPING-Supply, Installation Testing and Commissioning of 25 mm dia.Chlorinated Polyvinyl Chloride (CPVC) pipes, including all CPVC plain fittings, including fixing the pipes with pipes clamps at 1.00 m spacings. This includes joints of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Supporting arrangement in accordance with the approved shop drawings and spacification. Pipes shall be insulated with 9mm thick closed cell elastometic insulation in tubing form. |
| 145 | MS FRAME FOR ODU OFCASSETTE AC\"S-Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. (MS base frame duly applied with red-oxide primer & followed by black enamel paint for mountingof outdoor units.) |
| 146 | In gratings, frames, guard bar, ladder, railings, brackets,gates and similar works |
| 147 | Dismantling of Rittal system( 2 cooling unit LCPs of10KW each +3 racks)from 4th floor ( south wing) and reinstallation of system on the 1 st floor (north wing) of CIP building including required material, labour, consumable etc complete to make the system functional in all respect.Scope of work includes-1) Dismantling of Rittal system with outdoor unit2)Shifting of dismantled equiments to 1st floor north wing3)Installation of entire Rack system ( with outdoor units as shown in the drawing) system including copper piping( 3/8\" & 5/8\"including R 410 gas charging,insulation), drain pump piping ,cable trays,MS stand for ODU, electrical connection (2.5 sq mm 4 Core etc) till electrical DB/panel and other require material to complete the installation, testing & commissioning of the system.Note;- The above work shall be get done from OEM of Rack considering warranty, AMC terms.Model number of LCP is SK3311.420 |
| 148 | Providing & Fixing Decorative Wall Cladding Perforated Facade Metal Panels for outdoor units of Cassette Acs |
| 149 | Shifting & positioning of AHU Plenum as per required orientation etc complete including necessary supports, tools ,tackles etc complete |
| 150 | FIRE FIGHTING WORK |
| 151 | Supplying and fixing air realease valve made of 25 mm dia on top and flanged connection to riser with required accessories, paintingwith synthetic enamel paint and after One coat of primer of approved shade as required. |
| 152 | Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories. |
| 153 | Pendent Sprinkler |
| 154 | Upright Sprinkler |
| 155 | Supplying, installation, testing & commissioning of sprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, support channel, stockbar of following sizes comolete as reauired. |
| 156 | 1500mm |
| 157 | Providing, installation, testing & commissioning of adjustable rosette plate for 15mm dia in white finish UL Listed or FM approved complete as required. |
| 158 | SLTC of M.S. pipe on surface |
| 159 | Providing, laying, testing & commissioning of \"C\" class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint after One coat of primer required shade complete as required : |
| 160 | 25 mm dia |
| 161 | 32 mm dia |
| 162 | 40 mm dia |
| 163 | 50 mm dia |
| 164 | 65 mm dia |
| 165 | 80 mm dia |
| 166 | 100 mm dia |
| 167 | 150 mm dia |
| 168 | Providing, Installation, Testing and Commissioning of Gun Metal / Bronze Ball Valves screwed ends of following sizes as required. (For sprinkler drain )as approved by architect and complete in all respect.(MAKE - ZOLOTO , SANT) |
| 169 | 25 mm dia |
| 170 | Draining out fire header line for sprinkler piping connection and refilling it after completion of work |
| 171 | Liasoning with Fire department and obtaining Fire NOC for the North wing of 1st floor by submitting require documents such as Form A, Form B ,Technical submittal etc complete. The statutary fees will be paid by CDAC but necessary steps is in vendor scope. |