| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bellpoint with 1.5 sq.mm FRLS PVC insulated copper conductorsingle core cable in surface / recessed medium class PVC conduit, withmodular switch, modular plate, suitable GI box and earthing the pointwith 1.5 sq.mm FRLS PVC insulated copper conductor single core cableetc. as required. (i/c rebate of replaced item).a) Group C (DSR-2022,1.10.3) |
| 2 | Wiring for group controlled (looped) light point/fanpoint/exhaust fan point/ call bell point ( without independentswitch etc.) with 1.5 sq. mm FRLS PVC insulated copperconductor single core cable in surface/ recessed PVC conduit,and earthing the point with 1.5 sq. mm Fcopper conductor single core cable etc. as required. (i/c rebate ofreplaced items)a) Group C (DSR2022, 1.55.3) |
| 3 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVCinsulated copper conductor single core cable in surface/recessed meduim class PVC conduit alongwith 1 No. 4 sq. mm FRLSPVC insulated copper conductor single core cable for loop earthing (i/crebate of replaced items)as required. (DSR-2022,1.12) |
| 4 | Wiring for light/ power plug with 4X4 sq. mm FRLS PVCinsulated copper conductor single core cable in surface/recessed medium class PVC conduit alongwith 2 Nos. 4 sq. mm FRLSPVC insulated copper conductor single core cable for loop earthing asrequired. (i/c rebate of replaced items)(DSR-2022,1.13) |
| 5 | Wiring for circuit/ submain wiring alongwith earth wire with thefollowing sizes of FRLS PVC insulated copper conductor, singlecore cable in surface/ recessed medium class PVC conduit as required.(i/c rebate of replaced items)a) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire (DSR-2022,1.14.1) |
| 6 | b) 4 X 16 sq. mm + 2 X 6 sq. mm earth wire (DSR-2022,1.14.11) |
| 7 | Supplying and drawing following pair 0.5 mm dia FRLS PVCinsulated annealed copper conductor, unarmored telephonecable in the existing surface/ recessed steel/ PVC conduit asrequired. (i/c rebate of replaced item).1 Pair (DSR-2022,1.18) |
| 8 | Supplying and fixing following size. Modules. GI box along withmodular base cover plate for modualr switches in recess etc. as reqd.(i/c rebate of replaced items)(a) 1 or 2 Module (75mm x 75mm) (DSR-2022,1.27) |
| 9 | Supplying and fixing following modular switch/ socket on theexisting modular plate & switch box including connections butexcluding modular plate etc. as required. (i/c rebate of replaced items)a) Telephone socket outlet (DSR-2022,1.24.6) |
| 10 | Supplying and fixing two module stepped type electronic fanregulator on the existing modular plate switch box includingconnections but excluding modular plate etc. as required. (i/c rebate ofreplaced items) (DSR-2022,1.25) |
| 11 | Supplying and fixing suitable size GI box with modular plate andcover in front on surface or in recess, including providing andfixing 3 pin 5/6 A modular socket outlet and 5/6 A modularswitch, connections etc. as required. (i/c rebate of replaced items) (DSR2022,1.31) |
| 12 | Supplying and fixing suitable size GI box with modular plate andcover in front on surface or in recess, including providing andfixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 Amodular switch, connections etc. as required. (i/c rebate of replaceditems) (DSR-2022,1.32) |
| 13 | Supplying and fixing following way, horizontal type three pole andneutral, sheet steel, MCB distribution board, 415 V, on surface/ recess,complete with tinned copper bus bar, neutralbus bar, earth bar, din bar, interconnections, powder painted includingearthing etc. as required. (But without MCB/RCCB/Isolator) (i/c rebateof replaced items) (DSR_2022)a) 4 way (4 + 12), Double door |
| 14 | b) 6 way (4 + 18), Double door |
| 15 | c) 8 way (4 + 24), Double door |
| 16 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\"curve, miniature circuit breaker suitable for inductive load offollowing poles in the existing MCB DB complete withconnections, testing and commissioning etc. as required. (i/c rebate ofreplaced items)a) Single pole (DSR-2022,2.10) |
| 17 | b) Double pole |
| 18 | c) Triple pole and neutral |
| 19 | Supplying and fixing single pole blanking plate in the existingMCB DB complete etc. as required. (i/c rebate of replaced items) (DSR-2022,2.11) |
| 20 | Supplying and fixing following rating, four pole, 415 V, isolatorin the existing MCB DB complete with connections, testing andcommissioning etc. as required.a) 40 amps (i/c rebate of replaced items) (DSR-2022,2.13) |
| 21 | b) 63 amps |
| 22 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface / recess including cutting the wall and making good the same in case of recessed conduit as reuired. (DSR- 2022,1.21.2) (i/c rebate of replaced item). a) 25 mm |
| 23 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. (DSR_2022_5.18) |
| 24 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/METAL pipe as required (DSR_2022_7.5.1)Upto 35 Sq mm |
| 25 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 26 | Supply and replacement of Plastic ventilation Fan size 250 mm singlephase, fixing the same on existing opening with suitable nut bolt fixtureand plywood after cutting making hole in plywood, connection, testingetc. as reqd. (i/c rebate of replaced items) |
| 27 | Supply and replacement of Heavy duty exhaust Fan single phase, fixingthe same on existing opening with suitable nut bolt fixture and plywoodafter cutting making hole in plywood, connection, testing etc. as reqd.(i/c rebate of replaced items) a) 300 mm |
| 28 | b) 450 mm (1400 RPM) |
| 29 | Supply and replacement of Wall Fan of size 400 mmsingle phase, fixingthe same on wall with suitable nut bolt fixture, connection, testing etc. as reqd.(i/c rebate of replaced items) |
| 30 | Supply and replacement of Wall Fan of size 400 mmsingle phase, fixingthe same on wall with suitable nut bolt fixture, connection, testing etc. as reqd.(i/c rebate of replaced items) |
| 31 | Supplying of following sizes of multicore aluminum conductor XLPEinsulated armoured cable 1.1 KV grade confirming to IS:7098 (Part-I)complete with all amendments etc as required. 2X16 SQ MM |
| 32 | Supply and replacement of LED batten minimum 24 wa (i/c rebate of replaced item).tt made out of engineering plastic connection testing etc as required. (i/c rebate of replaced item) |
| 33 | Supply and replacement of high efficiency surface mounting not more than 30 watt and not lesser than 3600 Lux, LED panel complete with accessories of 600 x 600 mm size deep drawn CRCA sheet steal housing duly powder coated with high efficient LED & Glare free full opal diffuser (IP20) to accommodate into existing fall ceiling including connection testing and fixing the same in fall ceiling etc as required. (i/c rebate of replaced item). |
| 34 | SITC of minimum 15 Watt LED based bollard with aluminium extruded housing with glare free opal diffuser. IP65 i/c making of foundation, nut bolts, erection etc. complete as required. |
| 35 | Supply and replacement of LED Down lighter minimum 12 Watt surface/ Recessed type powder coated aluminium housing and white poly carbonate ring.etc complete as reuired. (i/c rebate of replaced item). |
| 36 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/ PVC conduit as required.(DSR: 2022 1.17)a) 3x1.5 sq mm |
| 37 | b) 6x1.5 sq mm |