| 1 | Medical services work |
| 2 | Medical Gas Pipe line System : Supply, Installation, Testing and Commissioning of Medical Gas Area Alarm should be digital and capable of monitoring : 1 Gas(Oxygen): - Medical gas area alarm panel shall be capable of monitoring medical gas services by means of pressure sensors, which detect deviations from the normal operating limits of either pressure or medical vacuum. The cover and backbox shall be polyester powder coated. A single tamperproof fastener shall be used to gain access to the hinged door. Each gas service shall be displayed by colored 7” LCD touch screen to display the pipeline pressure and status for normal and fault conditions. An audible warning shall sound simultaneously with any failure indication and a mute facility shall be provided. Following a mute selection the audible will resound after approximately 15 minutes, or shall operate simultaneously should a further alarm condition occur. A “Mute” switch shall be provided inside the panel for use during any maintenance resulting in prolonged pipeline or plant shutdown. This facility shall automatically reset when the gas service returns to normal. Pressure switches shall include a ¼” BSPP threaded pipeline connection. |
| 3 | Supply, Installation, Testing and Commissioning of Emergency Oxygen Inlet Station: It should have the source of supply outside the building and should have an inlet to connect a temporary, auxiliary source of supply for emergency or maintenance situations. This connection should include necessary valves and to allow for an emergency supply of oxygen and Isolation of the normal source of supply. The inlet connection should be a 1\" female npt connection and be provided with a plug to prevent entry of foreign matter into the oxygen system when not in use. Brass ball valve controls access to the Emergency supply, and the gauge indicates the pressure being introduced into oxygen pipeline. The enclosure door should be labelled “Emergency High Pressure Oxygen Inlet Station” and should be equipped with a staple for padlocking to allow entry only by authorized personnel. The interior of the enclosure should be clearly labelled with instructions for connection and operation of the emergency oxygen inlet. |
| 4 | Supply, Installation, Testing and Commissioning of Oxygen Switch over vie control panel : The Control panel is designed to accept a supply of gaseous oxygen from the VIE at 1050 kPa (10.5) bar or from the standby manifold at 850 kPa (8.5 bar) and to reduce the pressure to a nominal 420 kPa (4.2 bar) pipeline distribution system pressure.Control panels are designed to regulate line pressure 28mm, sized pipe line. Mounted on a light weight mild steel zinc plated and passivated back plate assembly. It should be light weightless the 70Kg. All components degreased for oxygen use. Mild steel powder coated enclosure with inlet and outlet pressure gauges.Pressure Sensors : Pressure switches monitor inlet pressure. Dual line pressure switch monitor (high and low pressure). Pressure Reduction Capacity : Maximum inlet pressure: 2,800 kPa (28 bar). Outlet pressure reduced to: 420 kPa (4.2 bar). Flow Rate : 28mm system 3,000 L/min. Relief Valve Settings : Nominal 4 bar manifold 550kPa (5.5 bar). |
| 5 | Supply, Installation, Testing and Commissioning of Oxygen Analyzer |
| 6 | Supply, Installation, Testing and Commissioning of Oil Free SCROLL Air Compressor (Total 6 air compressors) 3 air compressor having each of85cfm (2350lpm each) running to produce 7000lpm as working and 3 air compressor of 85cfm (2350lpm each) to produce 7000lpm as stand by (5% tolerance will be allowed) |
| 7 | Supply, Installation, Testing and Commissioning of Medical Breathing Air Dryer System -2 air dryer as working and 2 air dryer as stand by. It should have heatless desiccant air dryer type, with a minimum accuracy in a range from -20 deg.C to -40 degC with Purge Loss of 15±1%. It shall have Operating Voltage: 100-240 VAC 50/60 Hz 1 Phase. It shall have Maximum Operating Pressure: 16 kg/cm2(g) |
| 8 | Supply, Installation, Testing and Commissioning of Additional 4 Stage Air Filter for 4 Bar1no. Coarse coalescing filter with air quality standard ISO 8573-1: 2010. Element of E30612 grade1no. Fine coalescing filter with air quality standard ISO 8573-1: 2010. Element of E30612 grade1no. Fine Dust Filter with air quality standard ISO 8573-1: 2010. Element of E30612 grade 1no. Activated Carbon Filter with air quality standard ISO 8573-1: 2010. Element of E30612 grade |
| 9 | Supply, Installation, Testing and Commissioning of Additional 4 Stage Air Filter for 7 Bar1no. Coarse coalescing filter with air quality standard ISO 8573-1: 2010. Element of E30612 grade1no. Fine coalescing filter with air quality standard ISO 8573-1: 2010. Element of E30612 grade1no. Fine Dust Filter with air quality standard ISO 8573-1: 2010. Element of E30612 grade 1no. Activated Carbon Filter with air quality standard ISO 8573-1: 2010. Element of E30612 grade |
| 10 | Supply, Installation, Testing and Commissioning of Oxygen Smart Monitoring System (i) Alarm : The LCD alarm shall be microprocessor based with a 10\" (25.4 cm) screen and capable of monitoring oxygen medical gases. Oxygen gas service shall be provided with a digital read-out comprising of 0-249 psi (0-1,717 kPa) for pressure . The digital read-out shall provide a constant indication of each gas being measured, indicating a green “NORMAL” and a red “HIGH” or “LOW” alarm condition. (ii) Sensors : It shall be mounted locally (in the rough-in box) by installing the copper pipe provided or mounted remotely. Sensors will be automated for gas specific detection. Each sensor unit is gas specific, with an error message display for an incorrect connection. (iii) LED Screen 50\" or above size approx(iv) CPU with HDMI cable and Keyboard, mouse and networking switch(iv) UPS 1 KVA with battery back 10-15min(vi) Rack of 6 U for fixing CPU and accessories |
| 11 | Modular Operation Theater :Supply, Installation, Testing and Commissioning of Pressure Relief Damper: Pressure Relief Damper shall be provided in each room to prevent cross contamination of air from clean and dirty areas. Suitably sized air pressure relief damper shall be strategicallyplaced, enabling differential room pressure to be maintained and ensure that when doorsare opened between clean and dirty areas. Counter-weight balancing system should be provided in PRD to maintain positive pressure inside operation room.Air pressure stabilizers have unique capability of controlling differential pressure to close tolerance.The PRD remains closed at pressure below the set pressure and can open fully atpressure only fractionally above the threshold pressure. The body shall epoxy coated asper standard BS colors. First class electrolyzed steel plate should be used for body andwith high grade SS304 Stainless Steel for blades.It should have CE or as per applicable standard compliance under applicable standard medical devices directive. |
| 12 | Supply, Installation, Testing and Commissioning ofNIST Connection: The unit is connected to the Medical Gas main utilizing a first fix NIST connector with a gas specificcolour coded flexible hose providing the connection between the first fix NIST and theterminal unit. NIST Connection for each Gas to be supplied and installed on the Pendant except for AGSS. It shall be gas specific type in order to eliminate any risk of cross connection during initial installation and future maintenance.It shoud be mounted with standard make Pendants. |
| 13 | Supply, Installation, Testing and Commissioning ofDirty Linen Hatch Box 600mm x 600mm: It should be made up of Stainless Steel 304 grade of 1.5mm thk. HtachBox for Operation Theatre to exchange materials from the Operation Theatre to sterile store area just adjacent to operation theatre. Each hatch box should be equipped with two doors and the door shall be operated electronically having UV light. The hatch box shall be designed in such away that only one door should be opened one time. |
| 14 | Supply, Installation, Testing and Commissioning ofSMS Double Leaf manual Swing Door 2000 x 2100mm: Double leaf flushed swing door of 44 mm thick door blade material is made with 3-4 mm SMS Sheet on both side with PUF (polyurethane) as infill, with 2.5 mm thick Anodized Aluminum 6063 door frames totally flush with the wall panels, hardware like D type SS304 handles, door closure, double glazed view glass of size300 mm x300mm, hinges, door lock. |
| 15 | Supply, Installation, Testing and Commissioning ofSMS Double Leaf manual Swing Door 1800 x 2100mm: Double leaf flushed swing door of 44 mm thick door blade material is made with 3-4 mm SMS Sheet on both side with PUF (polyurethane) as infill, with 2.5 mm thick Anodized Aluminum 6063 door frames totally flush with the wall panels, hardware like D type SS304 handles, door closure, double glazed view glass of size300 mm x300mm, hinges, door lock. |
| 16 | Supply, Installation, Testing and Commissioning ofSMS Double Leaf manual Swing Door 1500 x 2100mm: Double leaf flushed swing door of 44 mm thick door blade material is made with 3-4 mm SMS Sheet on both side with PUF (polyurethane) as infill, with 2.5 mm thick Anodized Aluminum 6063 door frames totally flush with the wall panels, hardware like D type SS304 handles, door closure, double glazed view glass of size300 mm x300mm, hinges, door lock. |
| 17 | Supply, Installation, Testing and Commissioning ofSMS Single Leaf manual Swing Door 1200 x 2100mm: Single leaf flushed swing door of 44 mm thick door blade material is made with 3-4 mm SMS Sheet on both side with PUF (polyurethane) as infill, with 2.5 mm thick Anodized Aluminum 6063 door frames totally flush with the wall panels, hardware like D type SS304 handles, door closure, double glazed view glass of size300 mm x300mm, hinges, door lock. |
| 18 | Supply, Installation, Testing and Commissioning ofSMS Single Leaf manual Swing Door 1000 x 2100mm: Single leaf flushed swing door of 44 mm thick door blade material is made with 3-4 mm SMS Sheet on both side with PUF (polyurethane) as infill, with 2.5 mm thick Anodized Aluminum 6063 door frames totally flush with the wall panels, hardware like D type SS304 handles, door closure, double glazed view glass of size300 mm x300mm, hinges, door lock. |
| 19 | Supply, Installation, Testing and Commissioning ofSMS Single Leaf manual Swing Door 900 x 2100mm: Single leaf flushed swing door of 44 mm thick door blade material is made with 3-4 mm SMS Sheet on both side with PUF (polyurethane) as infill, with 2.5 mm thick Anodized Aluminum 6063 door frames totally flush with the wall panels, hardware like D type SS304 handles, door closure, double glazed view glass of size300 mm x300mm, hinges, door lock. |
| 20 | Supply, Installation, Testing and Commissioning ofSMS Single Leaf manual Swing Door 750 x 2100mm: Single leaf flushed swing door of 44 mm thick door blade material is made with 3-4 mm SMS Sheet on both side with PUF (polyurethane) as infill, with 2.5 mm thick Anodized Aluminum 6063 door frames totally flush with the wall panels, hardware like D type SS304 handles, door closure, double glazed view glass of size300 mm x300mm, hinges, door lock. |
| 21 | Supply, Installation, Testing and Commissioning ofAntibactirial Paint on Wall |
| 22 | Supply, Installation, Testing and Commissioning of Double Glass Windows with Motorized Blinds. Tentative Size is 1200 mm X 1800 mm |
| 23 | Supply, Installation, Testing and Commissioning of IV System with IV Hooks and Runner IV Track of 4feet with IV Hook ( both sides of the bed ) along with with mounting support and all accessories. It should be made from heavy Duty Aluminium Intravenous track of aluminium natural anodized to 15 microns complete with wall brackets with matching screws. 2 no. IV carrier to a set of IV support track complete with 5 points Telescopic Bottle Holder adjustable 600mm~900mm tree |
| 24 | Supply, Installation, Testing and Commissioning of Medical Curtains & Curtain Track: Curtain Track L shape Ceiling Cubical Partition Track Aluminium rail with plastic runner, rings and netted curtains. It is made from heavy Duty Aluminium cubicle track, made of aluminium natural anodized to 15 microns complete with nylon gliders and hooks, plastic end cap, overlapping joint connector, wall brackets with screws and securely fixed to above slab. |
| 25 | Supply, Installation, Testing and Commissioning of Hand Rail with Wall Guard System : Top Hand Rail Protection System with bottom wall guard protection system connected with SS Bracket alongwith 1.6mm aluminum thickness and PVC panel (size 4000mm x 180mm) |
| 26 | Supply, Installation, Testing and Commissioning of Corner Guard System : Coner Guard Protection System with 1.6mm and PVC panel (size 75mm x 75mm) |
| 27 | Supply, Installation, Testing and Commissioning of Glass Panels with Dugitally UV printed HD Image Backed with PPGI Sheet of 0.8mm thick filled with DOW PUF |
| 28 | Nurse Calling System :Supply, Installation, Testing and Commisoning of BED SIDE UNIT - WirelessFeatures : 1. Nurse call , 2. Code blue, 3. Maid call, 4. Extra support & RFID AlsoBedside Unit suitable for installation in the bed head Panel unit or for wall mounting.Adheres to the size standards of 6 modular. Dimensions: height 9.5 cm and width 22.5 cm. Device should be Germ-inhibiting membrane keypad with the following buttons: Nurse Call (left side top), Code Blue (left side bottom), Maid Call , Extra Support.Bedside unit should contain in-built unique staff identification with an RFID terminal. Every calling button should have its own reassuring light. Every device should work through wired, wireless & Hybrid. If wired, it should work through the LAN cable; if wireless, it should work through WiFi. Every device should be capable enough to work both wired and wireless simultaneously. If a wire gets disconnected, device should switch to WiFi automatically. Devices work through an AC or UPS power supply of 230 V and 0.2 Ames from the bed side unit. |
| 29 | Supply, Installation, Testing and Commisoning of Hand Held Device Hand held device - Nurse Call with a cable length of 3 meters & Versatile for bed rails only with Nurse Call Button. The hand-held device shall be connected to the bedside unit via a wire. Hand-held device cable thickness: 4.85mm. Device should be able to communicate on Ethernet switch. |
| 30 | Supply, Installation, Testing and Commisoning of PULL Cord Pull Cord - Restroom Unit : Nurse Call with waterproof design with antibacterial cord. Actuating the pull cord has the same effect as pressing a call button and equip with a reassurance light (Red) which gives the patient an immediate visual indication that help is on the way. In device design, it is necessary to mention \"SOS\" on the button. Should come with a 3 to 5 meter rope for activating the call. The pull cord shall be connected to the main call point, which activates the nurse\"s call when pulled. Call point shall have a unique software ID for identification in the server or nurse calling software. Dimension: Height 8.5 cm and width 8.5 cm & Rope length 45 cm to 180 cm. Nurse call with waterproof design with antibacterial cord |
| 31 | Supply, Installation, Testing and Commisoning ofRFID Enabled Nurse Identity Card to cancel the call. |
| 32 | Supply, Installation, Testing and Commisoning ofDoor Light Door Light : 360° bright, eye-catching colors from long distances when calls are active. Three LED indication fields in the colors Green (Nurse Call), Blue (Code blue), and Red (Maid Call & Extra support). Door Light: Should come in a round shape, providing better visibility and aesthetic appeal. The call light should exhibit the alarm indications in different scenarios based on the priority of different alarms. Dimension: diameter 9 cm, top side with ABS transparent plastic & bottom holder should be made of aluminium. |
| 33 | Supply, Installation, Testing and Commisoning of Central Management System Fully pre-installed and ready to operate software interfaces seamlessly with external hardware and nurse station software, enhancing the reliability of central services and connections. The nurse station software includes several key features:Auto Fault Detection: •The system checks component status every 60 seconds, and notifies maintenance staff of anyproblems or disconnections. Support: A Local server placed at the hospital server room to process the nurse call application. •Auto Fault Detection: Should continuously checks the status of each device every second and notices maintenance staff if any problem or dis-connectivity is detected. •Built-in backup communication protocol: Provides access to a built-in backup communication protocol in order to connect to hospital Wi-Fi during service downtime for the wired system.•Strategic report generation. •Mobile application. • Up gradable to Smart OPD calling system. •Upgadable to Smart Queue management systemIntegration: Should be able to support the integration of the Hospital Information System (HIS) for all the nurse stations. Smart Dashboard: Can be able to monitor entire system functionality via a web applicationStrategic report generation: Should Generates detailed reports on call response times, frequency of calls, TAT, and peak usage periods to enhance operational efficiency. |
| 34 | Supply, Installation, Testing and Commisoning of Android Television (ATV1)Specifications: 32\"\" inches HD Ready LED Smart Android TV .Brightness: 250 nits, 75 Hz Refresh Rate. Aspect Ratio 16:09 3.Technology & Resolution: HD Ready, 1366 x 768. Wi-Fi Type: Dual Band WiFi: 2.4 GHz and 5 GHz, Ports: 2 x HDMI & 2 x USBPower Requirement: AC 100 - 240 V, 50/60 Hz |
| 35 | Supply, Installation, Testing and Commisoning of Smart Watch 1. General Description- The device is designed for triggering a nurse call with a simple button press.- Functions as a wireless call device integrated with theNurse Call System.- The watch connects to the Bedside Unit via Bluetooth for call transmission. 2. Key Features- Uses an nRF series chipset for efficient signal processing and communication.- Provides a reliable Bluetooth connection to the bedside unit, which relays the call.- IP66 protection, making it resistant to dust and water. 3. Technical Specifications- Operating Temperature Range: -20°C to 50°C- Battery Life: Up to 20 days (assuming fewer than 10 calls per day)- Color: Black- Communication Protocol: BLE 4. Applications- Nurse Call System: Used to alert nurses instantly when the button is pressed.- Hospital Emergency Response: Enables quick assistance for patients in need.- Healthcare Staff Communication: Enhances efficiency in hospitals by reducing response time. 5. User Interaction & Functionality- The device is worn as a watch for easy access.- A button press triggers the nurse call, which is relayed through the Bedside Unit to be displayed at the Nurse Station.- The call status updates in real-time on the Nurse Station display.- Can be integrated with mobile applications or cloud platforms for data analysis and reporting. 6. Durability & Maintenance- Designed with robust casing to withstand hospital environments.- Requires minimal maintenance with a replaceable battery system.- Ensures long-term reliability with power-efficient chipset design. 7. Regulatory Compliance- Meets IP66 standards for protection against dust and water.- Designed with compliance to BLE transmission standards. |
| 36 | Supply, Installation, Testing and Commisoning of Nurse Station Display Software : It should show every active call along with call types on a 32-inch display. Should be able to view every patient\"s information in detail through HIS integration. There shouldn\"t be no limit for the nurse station display count. It should be able to be used anywhere. Must be capable enough to configure more than 50 devices with a single nurse station display. Should display & notify according to the call priority with the room number (voice). Nurse Station Alert: Must specify the room number in the voice note. |