| 1 | HVAC ItemsDesign ,supply , installation, testing and commissioning of 4400 Cfm 11 TR Nominal capacity DX Air-cooled Condensing unit fixed with energy efficient R410A Refrigerant scroll compressor along with grooved copper tube/aluminium fins air cooled condensor coil with anticorrosion coatings,liquid ,accumulator, low noise alumimium propeller condenser fan with Fan motor etc all suitably assembled neatly in heavy duty GSS sheet metal cabinet and duly powdercoated as per specification .the unit to include built in safety controls like HP/LP switch power quality protector, in built thermal / temperature protection .(Carrier / Blue Star / Daikin) |
| 2 | Supply ,installation , testing and commissioning of 4400 Cfm 11 TR Nominal capacity factory assembled Double Skin AHUs Ceiling Mounted with 50mm-45kg/cum PUF Insulated detachable panels ,extruded thermal break aluminium profiles filled with PUF,panel external skin with 0.6 mm preplasticized sheet, panel internal skin with 0.6mm galvanized sheet, AMCA tested DIDW backward/forward curved centrifugal fan with EFF1 rating motor ,drive arrangement with taper lock pulleys for fan and motor ,vibration isolators out of heavy duty rubberized mounts, |
| 3 | prefilters with 3ply HDPE 50mm thick filters having an efficiency of 90% 10 mic, 6row /12FPI deep DX copper cooling coil with copper header and aluminium fins ,GI mist arrestor ,condensate coil trough with SS-304-20G insulated with 9mm closed cell elastomeric foam, guard for inspection door ,out let damper of aerofoil blades &PVC gears ,and flexible fire retardant canvass complete with galvanized hardware. (Carrier/Blue Star/Daikin) |
| 4 | Design, supply, installation, testing and commissioning of 3400 Cfm 8.5 TR Nominal capacity DX Air-cooled Condensing unit fixed with energy efficient R410A Refrigerant scroll compressor along with grooved copper tube/aluminium fins air cooled condensor coil with anticorrosion coatings,liquid ,accumulator, low noise alumimium propeller condenser fan with Fan motor etc all suitably assembled neatly in heavy duty GSS sheet metal cabinet and duly powdercoated as per specification .the unit to include built in safety controls like HP/LP switch power quality protector, in built thermal / temperature protection .(Carrier/Blue Star/Daikin) |
| 5 | Supply ,installation , testing and commissioning of 3400 Cfm 8.5 TR Nominal capacity factory assembled double skin ceiling mounted AHU with 50mm-45kg/cum PUF Insulated detachable panels ,extruded thermal break aluminium profiles filled with PUF,panel external skin with 0.6 mm preplasticized sheet, panel internal skin with 0.6mm galvanized sheet, AMCA tested DIDW backward/forward curved centrifugal fan with EFF1 rating motor ,drive arrangement with taper lock pulleys for fan and motor ,vibration isolators out of heavy duty rubberized mounts, |
| 6 | prefilters with 3ply HDPE 50mm thick filters having an efficiency of 90% 10 mic, 6row /12FPI deep DX copper cooling coil with copper header and aluminium fins ,GI mist arrestor ,condensate coil trough with SS-304-20G insulated with 9mm closed cell elastomeric foam, guard for inspection door ,out let damper of aerofoil blades &PVC gears ,and flexible fire retardant canvass complete with galvanized hardware. (Carrier/Blue Star/Daikin) |
| 7 | Supply, fabrication and fixing of MS channel for mounting the Airconditioning Indoor Unit. |
| 8 | Supply, fabrication and fixing of MS channel for mounting the Airconditioning Outdoor Unit. |
| 9 | Supply, installation, testing and commissioning of Laminar Flow arrangements with HEPA Filters,Frames, etc. 8 ft X 6 ft for OT Ceiling Suspended provides ultra clean sterile CLASS 100 clean air anddesigned as per CLASS 5 OF ISO 14644-1 standards with air plenum at Aluminium powder coated1mm thick casing with Aluminium pleat HEPA filters & 0.3 micron 99.97% efficiency and SS 304 perforated grill with 13 mm thickness XLP Insulation with Modular Housing, Frame: Aluminium, Flange type, Filter Media: Micro glass fibre, Sealant : Plolyurethanewith Air flow as per standards suitable for 11 TR. |
| 10 | Supply and fixing of 10 kW Wall-mounted VFD Starter Panel complete set Vector control in steel enclosure with Dimension 800mm x 600mm x 300mm Operating Temperature of -10°C to +50°C. |
| 11 | Supply and filling of R410A Refrigerant Gas |
| 12 | Supply, Fabrication and Erection of fabricated ducting made up of GI sheets of 22 Gauge thickness. |
| 13 | Supply, Fabrication and Erection of fabricated ducting made up of GI sheets of 24 Gauge thickness. |
| 14 | Supply and providing Acoustic for initial portion of Ducting with 12mm thick fiber glass rigid board covered with Tissue Paper and Aluminium Perforated Sheet. |
| 15 | Supply and fixing of extruded Aluminium powder Coated, supply and return Air Grilles /Diffusers with volume control dampers. |
| 16 | Supply and fixing of flexible Canvas connection |
| 17 | Supply and fixing of Duct Mouth Dampers |
| 18 | Supply and fixing of 50 mm thick Anti Vibrating Rubber Pads |
| 19 | Supply and providing thermal insulation of 9 mm thick vidoflex with Aluminium Foil. |
| 20 | Supply and fixing of Refrigirant piping out of hard drawn copper pipe set of 28.60 mmsize |
| 21 | Supply and fixing of Refrigirant piping out of hard drawn copper pipe set of 15.9mmsize. |
| 22 | Supply and providing of pipeline nitrile rubber insulation for refrigerant and drain pipe lines |
| 23 | Supply and providing of 1.5sqmm copper flexible cable |
| 24 | Supply and providing of 0.5sqmm 4 core flexible signal cable |
| 25 | Supply and fixing of 1\" PVC water drain pipe line |
| 26 | Electrical Items:Wiring with 2 x1.5 sq.mm.PVC insulated single core unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigidpipe Concealed inwall and ceiling with PVC accessories with Module GIswitch box in flush with wallwith 6A one way module switch with module front plate with continuous earth wire connection of 1.5 sq.mm copper wireand making good of the concealed portion with suitable colourfor ConcealedPVC Light point / fan point (for electronic regulator) (5 points / Coil) Higher End ) |
| 27 | Supply and fixing of 42W 2x2 LED Clean Room Bottom Opening luminaire for hygienic facilities (Havells BOCR2X2R42WLED857SP CMSEXE / Eq) of IP65 rating, dust free & zero maintenance with 1.5 sqmm PVC unsheathead FRLS copper wire from terminals to the fitting and necessary connection complete. |
| 28 | Supply and Run of 4 of 10 sq.mm.PVC insulated SC unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigidpipe concealed inwall and ceiling with continuous earth wire connection of 10 sq.mm copper wire and making good of the concealed position. |
| 29 | Supplyandrunof2of1.5sq.mm. PVCinsulatedSCunsheathedFRLScopperconductorof1100Vgradeinrigidpipe concealedinwallandceilingwithcontinuousearthwireconnectionof1.5sq.mmcopperwireandmakinggoodofthe concealed portion with suitable colour (For LED Ceiling Lights) |
| 30 | Supplyandrunof2of4sq.mm. PVCinsulatedSCunsheathedFRLScopperconductorof1100VgradeinsuitablePVC rigidpipeconcealedinwallandceilingwithcontinuous earthwire connectionof 4sq.mm copperwire andmakinggood of the concealed portion with suitable colour (For Computer Set plug) |
| 31 | Supply and fixing of 63A, 10kA FP MCB in sheet enclosure in flush with wall and making good of the concealed portion with necessary earth connection. (The MCB and metal enclosure should be of Higher End). |
| 32 | Supply and clamping of 3-1/2 x 25sq.mm. aluminium PVC LTUG armoured cable on post or on wall with MS clamps. |
| 33 | Supply and fixing of brass cable gland for 3-1/2 x 25 sq.mm. aluminium PVC armoured LTUG cable with earth connection |
| 34 | Supply and providing cable end termination of 3-1/2 x 25 sq.mm. aluminium PVC LTUG aluminium armoured cable with necessary aluminium cable sockets by crimping etc with electrical connection complete. |
| 35 | Supply and fixing of 1 no.6/16A two modulesocket , 1 no.16A one module switch with module cover plate (plastic) onsuitable module concealedBox (GI ) in flush with wall with connections. Higher End |
| 36 | Supply and fixing of 4 way 7 segment triple pole neutral MCB distribution boardin sheet steel enclosure double door type with metal door with IP 42 protection with 63A 4 pole MCB as incoming and 3Nos 63A DP RCCB as sub incomer and 12Nos. 6 A to 32 A SP MCB as outgoing in flush with wall and making good of the concealed portion with earth connection. (Higher End) |
| 37 | Supply and fixing of 7.5kVAsingle Phase In & Single Phase out Online UPS of Microcontroller based High frequency and Double Conversion Online Technology with inbuilt isolation transformer system, LCD/ LED Display with suitable SMF battery to provide minimum 2 hour backup along with Powder coated MS Rack and interlink cables with following specifications: |
| 38 | 1. Output Voltage Range : 208V/220V/230V/240V AC2. Voltage THD (Linear Load) :≤2%3. Voltage THD (Non-Linear Load) : ≤4%4. Current THD : < 10%5. Overload: >110%, 30s turn to Bypass mode; >150% instant turn to Bypass mode6. Short Circuit protection : 5 cycles turn off inverter, no transfer to Bypass, provide Alarm (AC mode) ; 5cycles turn off inverter, provide Alarm (Battery mode), Input fuse blown or breaker action7. Waveform : Pure sinewave |
| 39 | 8. Transfer time : (AC mode to Battery mode - Zero) (Inverter to bypass - <4ms)9. Efficiency : 85% to 92%10. Noise Level : less than 50dBA @ 1meter (with fan speed control)11. Warranty : Two years on Electronics & one year on battery.(UPS make: Microtek / Numeric make), (Battery make : Exide) |
| 40 | Medical equipments of Modular OTSupply and Installation Single arm moveable pendant for Anesthetist to comply with NFPA 99C / HTM 02-01 / DIN / EN / ISO 7396-1. The support arms shall be extremely robustandrevolveonhighquality bearings, sothatthependantheadglides smoothlyand quicklytoanydesired position. |
| 41 | ItshallhaveSinglemoveablearmswith total coverage of minimum1800 mm and minimum 330˚ which can be easily adjusted to suit the desired mode of operation. Armshallhaveabilityofhorizontal movement. Vertical movement shall be motorized and the arm height shall remain at aheightgreaterthan6.5 feetabove floor level. |
| 42 | Weightcarryingcapacityofthearmshall not belessthan180kganditshallhave electromagnetic brakes. |
| 43 | The Pendant Service Heads shall be modular withminimum800mmhead.The heads shallbe capable of accepting a rangeof shelves,infusionpoles, electrical switch/sockets,gasoutletsandother required accessories. ThePendant Heads shallsupporttherangeofPhysiological Monitor Mounting Solutions. |
| 44 | The Pendant Service Heads shall be suppliedwithmedicalgasterminalunits and 6A/16 A hybrid sockets. |
| 45 | Pendant shall be supplied with outlets and probes as mentioned below. |
| 46 | Oxygen outlets: 2 number |
| 47 | Vacuum outlets: 2 number |
| 48 | Nitrous oxide outlet: 1 number |
| 49 | Air (4 bar) outlets: 2 number |
| 50 | AGSS outlet: 1 number |
| 51 | Electrical sockets: 10 number |
| 52 | Adjustable shelf with two rails one oneach side: 3 number |
| 53 | IV Fluid Pole with 4 hooks: 1 number |
| 54 | Data socket RJ-45: 2 number |
| 55 | Anesthetist pendant shall have NISTConnection for all gases to connect the MGPS system. (Make: LM Medical Division / Eq conforming to relevant standards technical specifications). The pendant should be CE certified or USFDA and should be approved by the department officers before execution. |
| 56 | Supply and Installation of Single arm moveable pendant for Surgeon to comply with NFPA 99C / HTM 02-01 / DIN / EN / ISO 7396-1. |
| 57 | The support arms shall be extremely robust and revolve on high quality bearings, so that the pendant head glides smoothly and quickly to any desired position. |
| 58 | Single moveable arm with total coverage ofmin 1800 mm and minimum 330˚. Arm shallhave ability of horizontal movement. Vertical movement shall be motorized and the arm height shall remain at a height greater than 6.5 feet above floor level. |
| 59 | Weight carrying capacity of the arm shall not be less than 180 kg. It shall have electromagnetic brakes. |
| 60 | Each arm shall be capable of minimum 330˚of rotation, which can be easily adjusted to suit the desired mode of operation. |
| 61 | The Pendant Service Heads shall be modular with minimum 800 mm head. The heads shallbe capable of accepting a rangeofshelves,infusionpoles, electrical switch/sockets,gasoutletsandother required accessories. The Pendant Heads shallsupporttherangeofPhysiologicalMonitor Mounting Solutions. |
| 62 | The Pendant Service Heads shall be suppliedwithmedicalgasterminalunits and 6A/16 A hybrid sockets. |
| 63 | Pendant shall be supplied with outlets and probes as mentioned below. |
| 64 | O2 and MA4: One each |
| 65 | Vacuum outlets: 2 number |
| 66 | Air (7 bar) outlet: 01 number |
| 67 | CO2 outlet: 01 number |
| 68 | Electrical sockets: 10 number |
| 69 | Adjustable shelf with two rails one on eachside: 3 number |
| 70 | Data socket RJ-45: 2 number |
| 71 | IV Fluid Pole with 2 hooks: 1 number |
| 72 | Nitrous oxide outlet: 1 number |
| 73 | Surgeon pendant shall have NIST connection for all gases to connect the MGPS system. (Make: LM Medical Division / Eq conforming to relevant standards technical specifications). The pendant should be CE certified or USFDA and should be approved by the department officers before execution. |
| 74 | Supply and Installation of surgeon control panel to control HVAC (Temperature and humidity), MOT Lights and ON/OFF Ceiling lights, instruction board, touch screen. It shall be CE / USFDA / ETL / UL / BIS certified or listed. It shall be wall mounted, stationed in the visibility line of the surgeon & MOT staff. The access height shall be convenient for the Nurse to operate. |
| 75 | The Control Panel shall be able to1) Indicate Medicalgasalarm forhighand low gaspressuresforeachgas service(except for vacuum, for vacuum it shall be normal or low) present in the MOT including vacuum, supported by audible alarm, digital clock and pressure switches. |
| 76 | 2)Temperature adjustment from the controller (temp adjustmentof+/- 5˚C to be achieved within 5 minutes) |
| 77 | 3) Display Digital Room pressure |
| 78 | 4) Display HEPA filter bank differential pressure indicator |
| 79 | 5) Hands free telephone with memory. 6) Display the MGPS Alarms.(Make: LM Medical Division / Eq conforming to relevant standards technical specifications). The control panel should be approved by the department officers before execution. |
| 80 | Supply and Installation of Pressure Relief Dampers with Frame, body and blade made of Grade SS 304 stainless steel. Counter-weight balancing system should be provided in the PRD to maintain positive pressure inside the operation room. (Make: MDD/ MPS / Eq conforming to relevant standards technical specifications) |
| 81 | Supply and Fixing of Germicidal UV Lights (40W) emitting ultraviolet light in the \"UV-C\" wavelength range (Make: MDD/ MPS / Eq conforming to relevant standards technical specifications) |
| 82 | Supply and installation of writing board of size 965 mm x 655 mm for a operation theatre. It should be made of ceramic having Magnetic properties and should be flushed to the wall. (Make: MDD/ MPS / Eq conforming to relevant standards technical specifications) |
| 83 | Supply and Fixing of twin plate X-ray viewing screen, designed to provide a high level of control luminance, without flicker from a unit that is easy to clean and maintain. |
| 84 | The X-ray Viewing screen is with LED illuminations , The front panel diffuser will be of a glare free type, sealed flush with the inside face of the operations theatre wall The LED lamp is providing a uniform level of illuminations across the entire front panel diffuser and controlled by electronic step-less dimming controls to provide flicker free dimming from maximum brightness to off. Access for maintenance and lamp changing is from front of the panel. All internal wire are terminate in connectors with screw all internal circuit. All internal wiring having high temperature and secured by property cabled, wall flush mounted . LED type flat panel viewing panel shall be flicker free. Mounting shall be flush with the wall to avoid dust accumulation & growth or organisms between wall and panel. |
| 85 | The body shall be of extruded aluminium powder coated with bacteria resistant and disinfectant resistant finish. Proper spring - loaded film clip with rollers / holding button shall be provided to hold the films firmly and to remove the film without scratches. It shall consists of dual panel viewing screen. This should comply with relevant electrical safety codes.The visible part of the frame should be SS 304. (Make: MPS/ MDD/ Eq confirming to technical specification) |
| 86 | Supply and fixing of MOT surgical lighting system with provision of ideal combination of brightness, manoeuvrability and shawdow resolution without sacrificing colour and accuracy through a consistent LED technology and shall have the following technical specifications:1.DoubleDomeSurgicalLightincorporatingthelatestLED technologyonly, to get a HomogenousLight. a. Colour temperature range : 3800K -5000K (+/- 10%) - variable colour temperature. Field size diameter : 20 to 28 cm (+/- 10%)b. Working range : 750 to 1100mm (+/-10%) c. Illumination level : Minimum 160,000 lux (both for major dome & minor dome seperately) d. Controls : Control panel (two : one on the wall and other on dome) |
| 87 | 2. Light dome shall be compatible with laminar air flow, irrespective of the lime dome shape, to have shadow less operating light field with the following specifications. |
| 88 | a.The Surgical O.T.Light should haveLED‘s to developcool and homogenouslight field.b.Each dome should have 160000 lux and equal number of LEDs to offer homogenouslighting.c.Eachdomeshouldhave30ormoreLEDstooffershadow freehomogenous lighting. d.Shall be able to work in Modular OT with Laminar Air Flow3. The main light and satellite shall havethe followingspecifications:- |
| 89 | a. Electronic Illuminationadjustment 10% to 100% Depth of illumination (L1 + L2) of 110 cms and aboveb. Remaining illuminationwith two masks of40-60 %c. Illuminationenergy- 550 W/m2 or lessd. Operating / storage humidity : 10 to 95% |
| 90 | 4. Should have Latest Generation Single Bright White LED‘s & they should have minimum life of 50,000 to 60,000 hours.Shallhave ElectronicswhichavoidsvariationinLight Intensityoutputdue to loss ofillumination,duetoLEDtechnology to achievestable&constantillumination (Flux Stability)throughout the Surgical Procedures.5. Shall have warm and cool LED for long term maintenance and ease of replacement. |
| 91 | 6. 3rd Suspensionfor display with Flat Screen Holder shall be provided.7. OT light should have an endoscopic mode to dim the light for endoscopic procedures.8. Average radiant energyof the lights shall be less than 3.6 mW / m2 |
| 92 | 9. Shall have facility to attach latest detachable/fixed mounted HD camerawhich shall be mounted on the centre of the light dome & shall be able to be mounted on either main or satellite dome, without use in tools (plug & play)(Make: KLS martin / Eq confirming to relevant standard technical specification). The surgicial light should be approved by the department officers before execution. |
| 93 | Supply and installation of HD LED Flat Panel Monitor of 32” medical grade high-definition progressive scan flat-panel monitors with ceiling mountedspringarmsuspensiontosupporthighdefinition/HDTVprogressivescanimages andshallbeabletosupportanddisplayDVI/HDTV,RGBHV,S-video,compositevideo signals.Aspectratio16:9/16:10.Resolution:1920X1080orbetter.ItshallmeetIP54 regulations. |
| 94 | The flat panel suspension shall be ready with the cables for integration ofhigh-definition digital (DVI/HDTV), RGBHV (high resolution), SVHS(S-video), composite video signals to travelfromthevarioussourcesofvideolikeendoscopiccamera,roomcamera,in-light camera, high definition flat panel monitors, while assuring apivore solution/signal.Monitor shall be capable of displaying from other sources like endoscope, microscope etc. Necessary provision for the same shall be made.(Make: KLS martin / Eq confirming to relevant standard technical specification).The HD LED flat panel monitor should be approved by the department officers before execution. |
| 95 | Supply and Installation of Integrated in-light camera system(HD Camera System – 1080p/i ) shall be integrated at the centre of one of thedomesofthislightingsystem/thirdarminordertocaptureimagesandvideo sequences of the open cases.Such a autofocus–lockable camera shall have the following specifications –a. Sensor:1/2.8\" to1/3\" CMOSb. Signal System:1080pc. Picture elements:23,80,000d. Aspect Ratio:16: 09e. Lensf. Diameter(mm):25-30g. Zoom:Zoom optical 10X and above/digital 12Xand aboveh. Focal length :3.8 to 144 mmi. Aperture:F1.8 to F3.4j. Digital Zoom:12X and above |
| 96 | k. Angleof view: 57 or above degree (Wide)and approx.7.6 degree (Tele) l. Min.workingdistance(mm/inch):Camerashouldfunctionwith minimumworking distance m. It should be a good sensitivitycamera. |
| 97 | n. Electronicshutter speed:1/25 to 1/30000so. S/N ratio (dB): > 50p. Antiflicker:Yesq. White balance:Auto / Manualr. Focus:Autos. Exposure:Auto |
| 98 | t. Integrated Camera shall have a control through Control panel of the control equipment placed inside the operating room.u. Location of Camera: Center of light headv. Video Signal outputs: HD -2XHD-SDI or HDMIw. Serial link interface:RS-232g.(Make: KLS martin / / Eq confirming to relevant standard technical specification). The HD camera system should be approved by the department officers before execution. |
| 99 | Supply and Installation of Recording system of one TB storage space and Data cable for communication from both pendants and monitor Patch panel for power and signal shall be laid down for 48-inch LED monitor at wall of MOT.Recorder shall be capable of recording video from other sources like microscopes, endoscopes etc., suitable provision for the same shall be made. |
| 100 | Monitor:Itshallbefull HD medicalgrademonitor.Itssizeshallbeminimum48inch.Monitorshall beflush mountedwithsuitable frameinMOTwall.Frameshall be openable/serviceable for service.(Make:KLS martin / Eq confirming to relevant standard technical specification).The recording system should be approved by the department officers before execution. |
| 101 | Supply and painting of wall and Ceiling with Anti-bacterial and Anti-fungus sterile coating will be applied on the SS finished walls & ceiling with at least 2-3 coats to achieve a thickness of minimum 200 micron. Before application of sterile allocating an appropriate primer will be applied. The Primer will be supplied along with the paint. |
| 102 | Sterile coating and primer will be applied on the surface by air-less spray gun. |
| 103 | Sterile coating will be to withstand with commonly used cleaners in the operation rooms and even withstanding with regular steam cleaning.(Make: SSK / LIQUID PLASTIC / Eq) |
| 104 | Civil Works:Supplying and fixing of Stainless Steel Wall Cladding - Wall Paneling System - Stainless Steel 304 Panel: - The inner surface walls should be fixed to the brick wall with essential supports. All joints will be filled with Silicon Sealent. |
| 105 | Coving:- Extruded SS 304 profile coving R80 for wall to Wall and wall to ceiling and column with anodized profile. |
| 106 | Reverse Coving:- Extruded SS 304 profile coving R80 for wall to Wall and wall to floor and column with anodized profile. |
| 107 | Supplying and fixing of HATCH BOX to be provided in each operation theartre to remove waste materials from the operation theatre to dirty linen area/corridor just adjacent to MOT. Each hatch box shall be equipped with two doors and the doors shall be operated electrically / motorized. The hatch Box shall be designed in such way that only one door shall be openable at one time. Hatch box material shall be SS 304 grade. Length and wldth of the hatch box shall be minimum 600mm x 600mm |
| 108 | Supply and Instalation of storage shelves and shall be made with at least 0.8mm thick SS 304 stainless steel panels. The shelves shall be of SS 304 stainless steel and removable for cleaning .The storage unit shall be divided in 2 or more parts and each parts shall have individual glass doors with high quality locking system. |
| 109 | GST |