| 1 | Retrofitting/Replace work of 800/1000 amp. ACB establish at LT panel siturated in Smarak Sthal |
| 2 | SITC of ACB 1000A 4P 50KA 415V with LSIG The ACB shall confirm the requirements of IEC 60947-2 & 3 type tested & certified forcompliance to standards from accredited national/ international lab. The circuit breaker shall be suitable for service voltage 690, 3 Phase 50 Hz supply system, suitable for utilization category B. Air Circuit Breakers shall be with mouldedhousing flush front, draw out type and shall be provided with a trip free manual operating mechanism with mechnicalon/off indication.The cradle shall be so designed and constructed as to permit smooth withdrawal and insertion of the breaker into it. The movements shall be free from jerks, easy to operate There shall be 4 distinct and separate position with self-locking arrangement of the circuit breaker on the cradle. Racking Interlock in Service/Test/Disconnected PositionSAFETY FEATURESa) The safety shutter shall prevent inadvertent contact with isolating contacts when breaker is withdrawn from the Cradle.b) There shall be provision of positive earth connection between fixed and moving portion of the ACB either through connectors plug or sliding solid earth mechanism. Earthing bolts shall be provided on the cradle or body of fixed ACB.c) It shall be possible to bolt the draw out frame not only in connected position but also in TEST and DISCONNECTED position to prevent dislocation due to vibration and shocks.d) Draw-out breakers should not close unless in distinct Service/Test/Isolated positions.e) The ACB shall provide in built electrical and mechanical anti-pumping.f) All ACB’s shall be having type tested design with combined sequence test as per IEC 60947.ACB Insulation voltage 1000V & 12KV Impulse with Min. Mech operation 20000, Electrical operation 8000 , Inbuilt Counter required for no. of operation , Protection Release shall be Microproccessor based having Touch Display for easy access , setting of all parameter of breaker , release shall be equiped with Over Load , Sort cicuit & earth FaultProtection , Release shall provide Date, time, fault current by phase and type of protection tripped over the last 30 trips;& Date, time and type of operation of the last 200 events (example: opening/closing of circuit-breaker, pre-alarms, editing of settings, ect. Zone Selective Interlocking , Release shall be Self Powered , Number of operations of the circuit-breaker: divided into mechanical operations (no current), electrical operations (with current) and protection function (trip), ACB Contact Wear estimated Function.All the information can be viewed directly from the display and from a Smartphone, Tablet (with Ekip Bluetooth) or PC using the front port of the trip unit or the system communicationMake ABB |
| 3 | S/F Cradle Make ABB |
| 4 | S/F Opening Coil 220-240 V AC/DC for conversion to EDO Model-YO E.1.2.E6.2-XT7-XT7M Make ABB |
| 5 | S/F Closing Coil 220-240 V AC/DC for conversion to EDO Model - YCE1.2.E6.2-XT71 Make ABB |
| 6 | S/F Spring Charge Motor Coil 220-250 V AC/DC for conversion to EDO Model- M E1.2 Make ABB |
| 7 | S/F Under Voltage Coil 380-400V AC/DC for electrical interlocking Model YU E1.2.E6.2-XT7-XT7M Make ABB |
| 8 | S/F Ready to Close Contact for indecation of breaker readiness to closeModel RTC250VACE1.2-XT7M Make ABB |
| 9 | SITC of ACB 800A 4P 50KA 415V with LSIG The ACB shall confirm the requirements of IEC 60947-2 & 3 type tested & certified for compliance to standards from accredited national/ international lab. The circuit breaker shall be suitable for service voltage 690, 3 Phase 50 Hz supply system, suitable for utilization category B. Air Circuit Breakers shall be with mouldedhousing flush front, draw out type and shall be provided with a trip free manual operating mechanism with mechnical on/off indication.The cradle shall be so designed and constructed as to permit smooth withdrawal and insertion of the breaker into it. The movements shall be free from jerks, easy to operate There shall be 4 distinct and separate position with self-locking arrangement of the circuit breaker on the cradle. Racking Interlock in Service/Test/Disconnected Position 4 SAFETY FEATURESa) The safety shutter shall prevent inadvertent contact with isolating contacts when breaker is withdrawn from the Cradle.b) There shall be provision of positive earth connection between fixed and moving portion of the ACB either through connectors plug or sliding solid earth mechanism. Earthing bolts shall be provided on the cradle or body of fixed ACB.c) It shall be possible to bolt the draw out frame not only in connected position but also in TEST and DISCONNECTED position to prevent dislocation due to vibration and shocks.d) Draw-out breakers should not close unless in distinct Service/Test/Isolated positions.e) The ACB shall provide in built electrical and mechanical anti-pumping.f) All ACB’s shall be having type tested design with combined sequence test as per IEC 60947.ACB Insulation voltage 1000V & 12KV Impulse with Min. Mech operation 20000, Electrical operation 8000 , Inbuilt Counter required for no. of operation , Protection Release shall be Microproccessor based having Touch Display for easy access , setting of all parameter of breaker , release shall be equiped with Over Load , Sort cicuit & earth FaultProtection , Release shall provide Date, time, fault current by phase and type of protection tripped over the last 30 trips;& Date, time and type of operation of the last 200 events (example: opening/closing of circuit-breaker, pre-alarms, editing of settings, ect. Zone Selective Interlocking , Release shall be Self Powered , Number of operations of the circuit-breaker: divided into mechanical operations (no current), electrical operations (with current) and protection function (trip), ACB Contact Wear estimated Function.All the information can be viewed directly from the display and from a Smartphone, Tablet (with Ekip Bluetooth) or PC using the front port of the trip unit or the system communication ModelMake ABB |
| 10 | S/F CradleMake ABB |
| 11 | S/F Opening Coil 220-240 V AC/DC for conversion to EDO Model-YO E.1.2.E6.2-XT7-XT7M Make ABB |
| 12 | S/F Closing Coil 220-240 V AC/DC for conversion to EDO Model - YCE1.2.E6.2-XT71 Make ABB |
| 13 | S/F Spring Charge Motor Coil 220-250 V AC/DC for conversion to EDO Model- M E1.2 Make ABB |
| 14 | S/F Under Voltage Coil 380-400V AC/DC for electrical interlocking Model YU E1.2.E6.2-XT7-XT7M Make ABB |
| 15 | S/F Ready to Close Contact for indecation of breaker readiness to closeModel RTC250VACE1.2-XT7M Make ABB |
| 16 | Discunnected power supply 440 v removing 400sq mm 3.5 core power LT cable lugh then Dismentling old busbar andRYBN busbar sleeving, nutbolt, fastner, suspender, busbar supporter, FRP seat and suitable size as per site requirement retrofit 1000 amp busbar kit with help of hydrolic based busbar cutting machine labour T &P complete in all respect |
| 17 | Discunnected power supply 440 v removing 400sq mm 3.5 core power LT cable lugh then Dismentling old busbar andRYBN busbar sleeving, nutbolt, fastner, suspender, busbar supporter, FRP seat and suitable size as per site requirement retrofit 800 amp busbar kit with help of hydrolic based busbar cutting machine labour T &P complete in all respect |
| 18 | S/F of 3Ph Amp. Meter with inbuilt Selector Accu. Cl.1 M1A 3-1 Ammeter 3Ph (Cl 1.0) Make ABB |
| 19 | S/F of 3Ph Volt. Meter with inbuilt Selector Accu. Cl.1 M1V 3-1 Volt Meter 3Ph Make ABB |
| 20 | S/F of 3Ph 4Wire Multifinction Meter with RS 485 M1M 12-1 Modbus Make ABB |
| 21 | S/F of LED Indicating Lamp 220V AC RED CL2-523R Make ABB |
| 22 | S/F of LED Indicating Lamp 220V AC GREEN CL2-523G Make ABB |
| 23 | S/F of LED Indicating Lamp 220V AC YELLOW CL2-523iY Make ABB |
| 24 | S/F of LED Indicating Lamp 220V AC BLUE CL2-523L Make ABB |
| 25 | S/F of LED Indicating Lamp 220V AC Amber CL2-523A Make ABB |
| 26 | Cutting Welding Finishing Fixing Rubber Gasket , Door Modification & removing OLD Powder Coated Paint Manual / Mechnical and Powder coating with heavy duty sparey machine inner / outer Side of ACB Panel Body Complete Rate with Labour and T&P Modification. |
| 27 | Removing Old control wiring and S/F new suitable size control wirng ACB to all Ammeter , Voltmeter , Indication Lam , Selector switch Opning Coil, Closing Coil, Spring Charg Motor & Under Voltage Coil , ready to close contact coil. And all required points in ACB electrical complete with material T&P all control wire using heavy duty FRLS Copper flexible wire Make KEI/Polycab/RR/Havells only |