| 1 | Excavation in trenches in not exceeding 1.5 m wide and not exceeding 1.5 M depth for foundation and getting out inhard / dense soil, all as specified & directed. |
| 2 | Returning, filling in including spreading leveling watering and well ramming in layers not exceeding 25 cm (soil),all as specified & directed. |
| 3 | Removing excavation materials not exceeding 50 Metre and deposition where directed at a level not exceeding 1.5 M above the starting point (soil),all as specified & directed. |
| 4 | Earth cushioning to UG cables using excavated soil riddled by using large sieve to separate the composite particles/roots etc and refilling in trenchesall as specified andas directed. Note :Punned thickness onlywill be considered for measurement and payment purpose. |
| 5 | Horizonal boring holes under road,pavement, hard standing by trncheles technology using ultra sounding technique and necessary machine including HDPE pipe of dia 80 mm suitable for 0.4 Mpa working pressure |
| 6 | Material and Labourfor dismantling / cutting of existing road / path / hard standing cement concrete (unreinforced) in ground floors and pavings not exceeding 15 cm thickness (below or above ground level) suitable for laying cable protection pipe 80 / 50 mm dia under the road / path / hard standing, completeall as specified and as directed. |
| 7 | Material and labour for PCC (1:2:4) type B-2 (using 40 mm graded crushed stone aggregate) for making good the disturbed surface of road/path/hard standing 0.45 mtr wide and 0.15 mtr thick complete all as specified and directed. including demolition of old PCC and removing the debris from site & upto a distance of 50 Mtr, complete all as specified and as directed. |
| 8 | Supply and lay burnt bricks sub-class \"B\" designation 75 for cable protection all as specified and as directed. |
| 9 | Supply and laying GI pipe light grade 80 mm bore including all type fitting such as bends, elbows, tee etc fixed on walls/to poles/laid in trenches as cable protection, all as specified and as directed. |
| 10 | Supply and laying GI pipe light grade 50 mm bore including all type fitting such as bends, elbows, tee etc fixed on walls/to poles/laid in trenches as cable protection, all as specified and as directed. |
| 11 | Supply, layig, connecting, testing and commissioning of 240 Sqmm 3.5 Core under ground LT cable XLPE insulated screened, PVC bedded, armoured heavy duty electric cable confirming to IS : 7098-1985 with stranded aluminium conductor 1100 volts laid in trenches, floor, fixed to walls/drawn through pipe, duct or along the pole and incl the disturbence surface of road making good with using PCC, fixing the cable with suitable size glands, crimping type lugs etc all as specified and directed. |
| 12 | Supply, layig, connecting, testing and commissioning of 120 Sqmm 3.5 Core under ground LT cable XLPE insulated screened, PVC bedded, armoured heavy duty electric cable confirming to IS : 7098-1985 with stranded aluminium conductor 1100 volts laid in trenches, floor, fixed to walls/drawn through pipe, duct or along the pole and incl the disturbence surface of road making good with using PCC, fixing the cable with suitable size glands, crimping type lugs etc all as specified and directed. |
| 13 | Supply, layig, connecting, testing and commissioning of 95 Sqmm 3.5 Core under ground LT cable XLPE insulated screened, PVC bedded, armoured heavy duty electric cable confirming to IS : 7098-1985 with stranded aluminium conductor 1100 volts laid in trenches, floor, fixed to walls/drawn through pipe, duct or along the pole and incl the disturbence surface of road making good with using PCC, fixing the cable with suitable size glands, crimping type lugs etc all as specified and directed. |
| 14 | Supply, layig, connecting, testing and commissioning of 70 Sqmm 3.5 Core under ground LT cable XLPE insulated screened, PVC bedded, armoured heavy duty electric cable confirming to IS : 7098-1985 with stranded aluminium conductor 1100 volts laid in trenches, floor, fixed to walls/drawn through pipe, duct or along the pole and incl the disturbence surface of road making good with using PCC, fixing the cable with suitable size glands, crimping type lugs etc all as specified and directed. |
| 15 | Supply, layig, connecting, testing and commissioning of 50 Sqmm 3.5 Core under ground LT cable XLPE insulated screened, PVC bedded, armoured heavy duty electric cable confirming to IS : 7098-1985 with stranded aluminium conductor 1100 volts laid in trenches, floor, fixed to walls/drawn through pipe, duct or along the pole and incl the disturbence surface of road making good with using PCC, fixing the cable with suitable size glands, crimping type lugs etc all as specified and directed. |
| 16 | Supply, layig, connecting, testing and commissioning of 35 Sqmm 3.5 Core under ground LT cable XLPE insulated screened, PVC bedded, armoured heavy duty electric cable confirming to IS : 7098-1985 with stranded aluminium conductor 1100 volts laid in trenches, floor, fixed to walls/drawn through pipe, duct or along the pole and incl the disturbence surface of road making good with using PCC, fixing the cable with suitable size glands, crimping type lugs etc all as specified and directed. |
| 17 | Supply and fixing 200 Amp, 4 Pole, 415 Volts, 50 Hz open executions on load mannual change over switch conforms to IEC-609473 with all accessories required for fixing in existing LT panel board complete all as specified and directed. |
| 18 | Supply and fixing quartz analog street light timer switch 20 Amp, complete all as specified and directed. |
| 19 | Supply and fix 3 pole contactor 440 volts 22 amps capacity, complete all as specified and directed. |
| 20 | Supply and fixingACB 800A, 4 Pole, 415 Volts, 50 Hz with thermal magnetic (Manual Drawout type) including fixing in existing LT panel board complete all as directed. |
| 21 | Supply and fixingMCCB 400 Amp, 4 Pole, Ics 50 KA, 415 Volts, 50 Hz with adjustable type with all accessories (such as nuts, bolts, washers, spider terminal link) including fixing in existing LT panel board complete all as directed. |
| 22 | Supply and fixingMCCB 350 Amp, 4 Pole, Ics 50 KA, 415 Volts, 50 Hz with adjustable type with all accessories (such as nuts, bolts, washers, spider terminal link) including fixing in existing LT panel board complete all as directed. |
| 23 | Supply and fixingMCCB 250 Amp, 4 Pole, Ics 50 KA, 415 Volts, 50 Hz with adjustable type with all accessories (such as nuts, bolts, washers, spider terminal link) including fixing in existing LT panel board complete all as directed. |
| 24 | Supply and fixingMCCB 200 Amp, 4 Pole, Ics 50 KA, 415 Volts, 50 Hz with adjustable type with all accessories (such as nuts, bolts, washers, spider terminal link) including fixing in existing LT panel board complete all as directed. |
| 25 | Supply and fixingMCCB 160 Amp, 4 Pole, Ics 50 KA, 415 Volts, 50 Hz with adjustable type with all accessories (such as nuts, bolts, washers, spider terminal link) including fixing in existing LT panel board complete all as directed. |
| 26 | Supply and fixingMCCB 125 Amp, 4 Pole, Ics 50 KA, 415 Volts, 50 Hz with adjustable type with all accessories (such as nuts, bolts, washers, spider terminal link) including fixing in existing LT panel board complete all as directed. |
| 27 | Supply and fixingMCCB 100 Amp, 4 Pole, Ics 50 KA, 415 Volts, 50 Hz with adjustable type with all accessories (such as nuts, bolts, washers, spider terminal link) including fixing in existing LT panel board complete all as directed. |
| 28 | Supply and fixingMCCB 63 Amp, 4 Pole, Ics 50 KA, 415 Volts, 50 Hz with adjustable type with all accessories (such as nuts, bolts, washers, spider terminal link) including fixing in existing LT panel board complete all as specified & directed. |
| 29 | Supply and fixing MCB TPN 32 Amp \"C\" Series of breaking capacity 10 KA, ISI marked, complete all as specified & directed. |
| 30 | Supply and fixing ly and fixing MCB 63 Amp, 4 Pole\"C\" Series of breaking capacity 10 KA, ISI marked, complete all as specified & directed. |
| 31 | Supply and fixing MCB 25 Amp, 4 Pole\"C\" Series of breaking capacity 10 KA, ISI marked, complete all as specified & directed. |
| 32 | Supply and fixing MCB 40 - 63Amp, 4 Pole\"C\" Series of breaking capacity 10 KA, ISI marked, complete all as specified & directed. |
| 33 | Supply, Installing, testing and commissioning, CPRI approved outdoor cubial type LT feeder pillar box suitable for 415V, 3 Phase, 4 wire, 50 Hz, AC supply system fabricated from stainless steel (SS 316) totally enclosed, dust, weather & vermin proof, front & back openable, double door system lockable / openable by keys from both sides having pattern fancy locks stainless steel in opening handle with louvers & air vent gasket for natural flow of air, the bottom of the outer shell contains a detacheable plate having provision for entry of adequate size with glands, 3.0 mm thick for outer shell and 2 mm thick for inner shell having TPN aluminium busbars of rating 1.5 times that of incoming MCCB supported on SMC insulators with short circuit withstand capacity 35 MVA for 1 second, bottom C type base channel of MS section not less than 100 mm, entire panel shall have a common aluminium earth bar of size 25 mm x 5 mm at the rear with 2 nos earth stud, solid bus bar connections from main bus bar to switchgears with required size and contrrol wiring with minimum 1.5 Sqmm FRLS insulated copper conductor wire, cable alleys, cable gland plates for Indicating lamp LED type, CT, selector switch,multifuction digital energy meter. The energy meter havingto measure voltage, current, PF KWH, KVAH, KVARH (Make - Secure / L&T / C&S / Schneider / Legrand), general construction confirming to IS : 8623 / 93 and mounted on suitable PCC foundation with followiing detailed specifications & controls and taking down the old panel board including disconnecting/reconnecting of all incoming and outgoing cable with new cable glande :- (Make - CPRI approved/certified manufacture) |
| 34 | (a) The size of panel is1.5 x 1.7 x 0.9 Mtr outdoor type having accomdoate 01 (one) NosIncoming 800 Amps ACB and 08 (Eight) Nosoutgoings. (Loc : Camp Area Sub Stn)Note : (i) The height of panel should be 0.45 to0.60 mtr from ground level with PCC foundation the cost of PCC foundation included in quated rate. (ii)Each MCCB\"s having seperate enclosures, marking with feeder name(iii) Switch gear\"s will be measure and paid seperately under relevent items . (iv) The minimu height of PCC is 30 CM andratio of PCC 1:3:6 (v) Earth work excavation, returing filling, removel for panel erection and cabling connection included in quated rate |
| 35 | Supply, Installing, testing and commissioning, CPRI approved outdoor cubial type LT feeder pillar box suitable for 415V, 3 Phase, 4 wire, 50 Hz, AC supply system fabricated from stainless steel (SS 316) totally enclosed, dust, weather & vermin proof, front & back openable, double door system lockable / openable by keys from both sides having pattern fancy locks stainless steel in opening handle with louvers & air vent gasket for natural flow of air, the bottom of the outer shell contains a detacheable plate having provision for entry of adequate size with glands, 3.0 mm thick for outer shell and 2 mm thick for inner shell having TPN aluminium busbars of rating 1.5 times that of incoming MCCB supported on SMC insulators with short circuit withstand capacity 35 MVA for 1 second, bottom C type base channel of MS section not less than 100 mm, entire panel shall have a common aluminium earth bar of size 25 mm x 5 mm at the rear with 2 nos earth stud, solid bus bar connections from main bus bar to switchgears with required size and contrrol wiring with minimum 1.5 Sqmm FRLS insulated copper conductor wire, cable alleys, cable gland plates for Indicating lamp LED type, CT, selector switch,multifuction digital energy meter. The energy meter havingto measure voltage, current, PF KWH, KVAH, KVARH (Make - Secure / L&T / C&S / Schneider / Legrand), general construction confirming to IS : 8623 / 93 and mounted on suitable PCC foundation with followiing detailed specifications & controls and taking down the old panel board including disconnecting/reconnecting of all incoming and outgoing cable with new cable glande :- (Make - CPRI approved/certified manufacture) |
| 36 | (a) The size of panel is1.1 x 1.0 x 0.4 Mtr outdoor type having accomdoate01 (one) Nos 350 Amps Incoming + 02 (Two) Nos Change over switch and 04 (Four) Nos outgoings for MCCB, 02 (Two) Nos outgoing for MCB Four Pole. (Loc : Near AFFWA)Note : (i) The height of panel should be 0.45 to0.60 mtr from ground level with PCC foundation the cost of PCC foundation included in quated rate. (ii)Each MCCB\"s having seperate enclosures, marking with feeder name(iii) Switch gear\"s will be measure and paid seperately under relevent items . (iv) The minimu height of PCC is 30 CM andratio of PCC 1:3:6 (v) Earth work excavation, returing filling, removel for panel erection and cabling connection included in quated rate |
| 37 | Supply, Installing, testing and commissioning, CPRI approved outdoor cubial type LT feeder pillar box suitable for 415V, 3 Phase, 4 wire, 50 Hz, AC supply system fabricated from stainless steel (SS 316) totally enclosed, dust, weather & vermin proof, front & back openable, double door system lockable / openable by keys from both sides having pattern fancy locks stainless steel in opening handle with louvers & air vent gasket for natural flow of air, the bottom of the outer shell contains a detacheable plate having provision for entry of adequate size with glands, 3.0 mm thick for outer shell and 2 mm thick for inner shell having TPN aluminium busbars of rating 1.5 times that of incoming MCCB supported on SMC insulators with short circuit withstand capacity 35 MVA for 1 second, bottom C type base channel of MS section not less than 100 mm, entire panel shall have a common aluminium earth bar of size 25 mm x 5 mm at the rear with 2 nos earth stud, solid bus bar connections from main bus bar to switchgears with required size and contrrol wiring with minimum 1.5 Sqmm FRLS insulated copper conductor wire, cable alleys, cable gland plates for Indicating lamp LED type, CT, selector switch,multifuction digital energy meter. The energy meter havingto measure voltage, current, PF KWH, KVAH, KVARH (Make - Secure / L&T / C&S / Schneider / Legrand), general construction confirming to IS : 8623 / 93 and mounted on suitable PCC foundation with followiing detailed specifications & controls and taking down the old panel board including disconnecting/reconnecting of all incoming and outgoing cable with new cable glande :- (Make - CPRI approved/certified manufacture) |
| 38 | (a) The size of panel is1.5 x 1.1 x 0.4 Mtr outdoor type having accomdoate 01 (one) NosIncoming MCCB 350 Amps and 08 (Eight) Nos outgoings for MCB FourPole, . (Loc : T-17, Officers Md Accn)Note : (i) The height of panel should be 0.45 to0.60 mtr from ground level with PCC foundation the cost of PCC foundation included in quated rate. (ii)Each MCCB\"s having seperate enclosures, marking with feeder name(iii) Switch gear\"s will be measure and paid seperately under relevent items . (iv) The minimu height of PCC is 30 CM andratio of PCC 1:3:6 (v) Earth work excavation, returing filling, removel for panel erection and cabling connection included in quated rate |
| 39 | Supply, Installing, testing and commissioning, CPRI approved outdoor cubial type LT feeder pillar box suitable for 415V, 3 Phase, 4 wire, 50 Hz, AC supply system fabricated from stainless steel (SS 316) totally enclosed, dust, weather & vermin proof, front & back openable, double door system lockable / openable by keys from both sides having pattern fancy locks stainless steel in opening handle with louvers & air vent gasket for natural flow of air, the bottom of the outer shell contains a detacheable plate having provision for entry of adequate size with glands, 3.0 mm thick for outer shell and 2 mm thick for inner shell having TPN aluminium busbars of rating 1.5 times that of incoming MCCB supported on SMC insulators with short circuit withstand capacity 35 MVA for 1 second, bottom C type base channel of MS section not less than 100 mm, entire panel shall have a common aluminium earth bar of size 25 mm x 5 mm at the rear with 2 nos earth stud, solid bus bar connections from main bus bar to switchgears with required size and contrrol wiring with minimum 1.5 Sqmm FRLS insulated copper conductor wire, cable alleys, cable gland plates for Indicating lamp LED type, CT, selector switch,multifuction digital energy meter. The energy meter havingto measure voltage, current, PF KWH, KVAH, KVARH (Make - Secure / L&T / C&S / Schneider / Legrand), general construction confirming to IS : 8623 / 93 and mounted on suitable PCC foundation with followiing detailed specifications & controls and taking down the old panel board including disconnecting/reconnecting of all incoming and outgoing cable with new cable glande :- (Make - CPRI approved/certified manufacture) |
| 40 | (a) The size of panel is1.5 x 1.5 x 0.4 Mtr outdoor type having accomdoate 01 (one) NosIncoming MCCB 400 Amps and 06 (Six) Nos outgoings for MCCB, 01 (One) No outgoing for MCB four Pole. (Loc : P-43 Sub Stn)Note : (i) The height of panel should be 0.45 to0.60 mtr from ground level with PCC foundation the cost of PCC foundation included in quated rate. (ii)Each MCCB\"s having seperate enclosures, marking with feeder name(iii) Switch gear\"s will be measure and paid seperately under relevent items . (iv) The minimu height of PCC is 30 CM andratio of PCC 1:3:6 (v) Earth work excavation, returing filling, removel for panel erection and cabling connection included in quated rate |
| 41 | Supply, Installing, testing and commissioning, CPRI approved outdoor cubial type LT feeder pillar box suitable for 415V, 3 Phase, 4 wire, 50 Hz, AC supply system fabricated from stainless steel (SS 316) totally enclosed, dust, weather & vermin proof, front & back openable, double door system lockable / openable by keys from both sides having pattern fancy locks stainless steel in opening handle with louvers & air vent gasket for natural flow of air, the bottom of the outer shell contains a detacheable plate having provision for entry of adequate size with glands, 3.0 mm thick for outer shell and 2 mm thick for inner shell having TPN aluminium busbars of rating 1.5 times that of incoming MCCB supported on SMC insulators with short circuit withstand capacity 35 MVA for 1 second, bottom C type base channel of MS section not less than 100 mm, entire panel shall have a common aluminium earth bar of size 25 mm x 5 mm at the rear with 2 nos earth stud, solid bus bar connections from main bus bar to switchgears with required size and contrrol wiring with minimum 1.5 Sqmm FRLS insulated copper conductor wire, cable alleys, cable gland plates for Indicating lamp LED type, CT, selector switch,multifuction digital energy meter. The energy meter havingto measure voltage, current, PF KWH, KVAH, KVARH (Make - Secure / L&T / C&S / Schneider / Legrand), general construction confirming to IS : 8623 / 93 and mounted on suitable PCC foundation with followiing detailed specifications & controls and taking down the old panel board including disconnecting/reconnecting of all incoming and outgoing cable with new cable glande :- (Make - CPRI approved/certified manufacture) |
| 42 | (a) The size of panel is1.5 x 1.7 x 0.6 Mtr outdoor type having accomdoate 01 (one) NosIncoming MCCB 400 Amps and 08 (Eight) Nos outgoings for MCCB. (Loc : Officer\"s Mess DG Room)Note : (i) The height of panel should be 0.45 to0.60 mtr from ground level with PCC foundation the cost of PCC foundation included in quated rate. (ii)Each MCCB\"s having seperate enclosures, marking with feeder name(iii) Switch gear\"s will be measure and paid seperately under relevent items . (iv) The minimu height of PCC is 30 CM andratio of PCC 1:3:6 (v) Earth work excavation, returing filling, removel for panel erection and cabling connection included in quated rate |
| 43 | Supply, Installing, testing and commissioning, CPRI approved outdoor cubial type LT feeder pillar box suitable for 415V, 3 Phase, 4 wire, 50 Hz, AC supply system fabricated from stainless steel (SS 316) totally enclosed, dust, weather & vermin proof, front & back openable, double door system lockable / openable by keys from both sides having pattern fancy locks stainless steel in opening handle with louvers & air vent gasket for natural flow of air, the bottom of the outer shell contains a detacheable plate having provision for entry of adequate size with glands, 3.0 mm thick for outer shell and 2 mm thick for inner shell having TPN aluminium busbars of rating 1.5 times that of incoming MCCB supported on SMC insulators with short circuit withstand capacity 35 MVA for 1 second, bottom C type base channel of MS section not less than 100 mm, entire panel shall have a common aluminium earth bar of size 25 mm x 5 mm at the rear with 2 nos earth stud, solid bus bar connections from main bus bar to switchgears with required size and contrrol wiring with minimum 1.5 Sqmm FRLS insulated copper conductor wire, cable alleys, cable gland plates for Indicating lamp LED type, CT, selector switch,multifuction digital energy meter. The energy meter havingto measure voltage, current, PF KWH, KVAH, KVARH (Make - Secure / L&T / C&S / Schneider / Legrand), general construction confirming to IS : 8623 / 93 and mounted on suitable PCC foundation with followiing detailed specifications & controls and taking down the old panel board including disconnecting/reconnecting of all incoming and outgoing cable with new cable glande :- (Make - CPRI approved/certified manufacture) |
| 44 | (a) The size of panel is1.6 x 2.0 x 0.4 Mtr outdoor type having accomdoate 02 (Two) NosIncoming for MCCB 250 Amps + 02 Nos Incomming for Change over and 06 (Six) Nos outgoings for MCCB and 02 Nos for MCB SPN, Analog quartztimer switch and 3 pole cntactor. (Loc : Mukharjee Hall)Note : (i) The height of panel should be 0.45 to0.60 mtr from ground level with PCC foundation the cost of PCC foundation included in quated rate. (ii)Each MCCB\"s having seperate enclosures, marking with feeder name(iii) Switch gear\"s will be measure and paid seperately under relevent items . (iv) The minimu height of PCC is 30 CM andratio of PCC 1:3:6 (v) Earth work excavation, returing filling, removel for panel erection and cabling connection included in quated rate |