| 1 | ELECTRICAL WORKS |
| 2 | 1. FSD Shivpura, Kota |
| 3 | Supply,Installation, testing andcommissioning of 82.5 kVA Silent type Liquidcooleddieseldrivengenerating set conforming to CPCBIV+ normscomprisingofradiator,4strokemulti cylinder engine of minimum100 BHP to deliverratedkVAatprevailingsite conditions equipped with flywheel, residential type silencer, fuel governor, fuelpump/ CRDI,builtinfueltank,electric startingequipmentwithrequirednos. of suitable AH sealed maintenance free batteriesetc.,directlycoupledto82.5 kVA0.8PF (lag),alternatorsuitablefor3 phase, 4 wire 50Hz AC supply system with the entire system mounted on common base frame etc. on an existing foundation, exhaust piping with thermal insulation, control wiring from Alternatortocontrolpanel,acoustic enclosure, etc.as specified and consisting of the followings and AMF panel as per specification given in the detailed specifications sheet as attached in the DG set Specifications sectionetc. as required.; Diesel Engine: One number Diesel Engine multi-cylinder,four stroke, liquid cooled, electric start, turbo charged typeengine suitable for developingtheminimum 100BHPat1500 rpm, suitable for above output of alternatorat40ºC,50%RHandat 1000MetreMSLandconformingto BS 5514, BS 649, IS:10000, ISO 8528 Part I with upto date amendments/ norms, capable of taking 10%overloadingfor onehour after 12 hours of continuous operation completewith common baseframe, Anti vibration mountings, radiator, starting equipment,batteries, residential type silencer and other accessories etc. as required and as specifiedinthedetailedspecification enclosedin the DG set Specifications section. Governing Class (As per ISO 8528 part-V); Noise Level ≤ 75 dBA at a distance of 1m (IS 8528-10)/as per latest CPCB NORMS ; Fuel Tank Capacity-minimum 160L / to run minimum of 8hr in one time full refilling ; Weight of Gen Set with Canopy-Wet- minimum 1350 Kgs (or as per Manufacturer standards) ;Electrical Battery Starting Voltage-12 V DCEngine Specifications- Rated Output (Prime continuous Rating as per ISO 8528-1)-66 kW/ minimum 100 HP; No of Cylinders-3/4;Rated Speed at 1500 RPMAspiration - Turbo Aspiration; Lube Oil Sump Capacity- minimum 7L; Coolant Capacity- minimum 12LAlternator: Insulation-Class H; Efficiency at (100% Load)-0.8 pf (As per Standards IS 4722, IEC 34-1)-90% with voltage regulator ±1%; Max time to build Rated Voltage at Rated RPM-Voltage Recovery TIme-6 sec |
| 4 | Supplying, installation, testing and commissioning of automatic mains failure control suitable for 82.5kVA including auto By pass panel of 16SWG CRCA sheet floor mounted type, weather proof, corrosion resistance, water proof, Powder coated, powder painted, 7 tank process with suitable rating of 02 nos. FP MCCB, 02 nos. FP Contactors,aluminium bus bar for Grid, DG output and common output as approved by Engineer in Charge, suitable for required capacity of silent type DG site complete with relays, timers, set of CTs for metering & protection and energy analyser indicate currents, phase and line voltages, frequency, power factor, KWH, KVARH & provision for overload, short circuit, restricted earth fault, under frequency, control cabling from AMF Panelto diesel Engine and else where if required all complete and inter locking including all the required installations as mentioned in detailed specification sheet for DG setetc. as required. The AMF Panel may be placed inside the Canopy or at the suitable outdoor location as per latest norms and site conditions. |
| 5 | 2. FSD Bundi |
| 6 | Supply,Installation, testing andcommissioning of 35 kVA Silent type Liquidcooleddieseldrivengenerating set conforming to CPCBIV+ normscomprisingofradiator,4strokemulti cylinder engine of minimum40 BHP to deliverratedkVAatprevailingsite conditions equipped with flywheel, residential type silencer, fuel governor, fuelpump/ CRDI,builtinfueltank,electric startingequipmentwithrequirednos. of suitable AH sealed maintenance free batteriesetc.,directlycoupledto35 kVA0.8PF (lag),alternatorsuitablefor3 phase, 4 wire 50Hz AC supply system with the entire system mounted on common base frame etc. on an existing foundation, exhaust piping with thermal insulation, control wiring from Alternatortocontrolpanel,acoustic enclosure, etc.as specified and consisting of the followings and AMF panel as per specification given in the detailed specifications sheet as attached in the DG set Specifications sectionetc. as required.; Diesel Engine: One number Diesel Engine multi-cylinder,four stroke, liquid cooled, electric start, turbo charged typeengine suitable for developingtherequiredBHPat1500 rpm, suitable for above output of alternatorat40ºC,50%RHandat 1000MetreMSLandconformingto BS 5514, BS 649, IS:10000, ISO 8528 Part I with upto date amendments/ norms, capable of taking 10%overloadingfor onehour after 12 hours of continuous operation completewith common baseframe, Anti vibration mountings, radiator, starting equipment,batteries, residential type silencer and other accessories etc. as required and as specifiedinthedetailedspecification enclosedin the DG set Specifications section. Governing Class (As per ISO 8528 part-V); Noise Level ≤ 75 dBA at a distance of 1m (IS 8528-10)/as per latest CPCB NORMS ; Fuel Tank Capacity-minimum 80L / to run minimum of 8hr in one time full refilling ; Weight of Gen Set with Canopy-Wet- minimum 1050 Kgs (or as per Manufacturer standards) ;Electrical Battery Starting Voltage-12 V DCEngine Specifications- Rated Output (Prime continuous Rating as per ISO 8528-1)-28 kWe/ minimum 40 HP ; No of Cylinders-3/4;Rated Speed at 1500 RPMAspiration - Turbo Aspiration ;Lube Oil Sump Capacity- minimum 7L; Coolant Capacity- minimum 8LAlternator: Insulation-Class H ; Efficiency at (100% Load)-0.8 pf (As per Standards IS 4722, IEC 34-1)-86% with voltage regulator ±1% ;Max time to build Rated Voltage at Rated RPM-Voltage Recovery TIme-6 sec |
| 7 | Supplying, installation, testing and commissioning of automatic mains failure control suitable for 35kVA including auto By pass panel of 16SWG CRCA sheet floor mounted type, weather proof, corrosion resistance, water proof, Powder coated, powder painted, 7 tank process with suitable rating of 02 nos. FP MCCB, 02 nos. FP Contactors,aluminium bus bar for Grid, DG output and common output as approved by Engineer in Charge, suitable for required capacity of silent type DG site complete with relays, timers, set of CTs for metering & protection and energy analyser indicate currents, phase and line voltages, frequency, power factor, KWH, KVARH & provision for overload, short circuit, restricted earth fault, under frequency, control cabling from AMF Panelto diesel Engine and else where if required all complete and inter locking including all the required installations as mentioned in detailed specification sheet for DG setetc. as required. The AMF Panel may be placed inside the Canopy or at the suitable outdoor location as per latest norms and site conditions. |
| 8 | 3. FSD Baran |
| 9 | Supply,Installation, testing andcommissioning of 30 kVA Silent type Liquidcooleddieseldrivengenerating set conforming to CPCBIV+ normscomprisingofradiator,4strokemulti cylinder engine of minimum35 BHP to deliverratedkVAatprevailingsite conditions equipped with flywheel, residential type silencer, fuel governor, fuelpump/ CRDI,builtinfueltank,electric startingequipmentwithrequirednos. of suitable AH sealed maintenance free batteriesetc.,directlycoupledto30 kVA0.8PF (lag),alternatorsuitablefor3 phase, 4 wire 50Hz AC supply system with the entire system mounted on common base frame etc. on an existing foundation, exhaust piping with thermal insulation, control wiring from Alternatortocontrolpanel,acoustic enclosure, etc.as specified and consisting of the followings and AMF panel as per specification given in the detailed specifications sheet as attached in the DG set Specifications sectionetc. as required.; Diesel Engine: One number Diesel Engine multi-cylinder,four stroke, liquid cooled, electric start, turbo charged typeengine suitable for developingtherequiredBHPat1500 rpm, suitable for above output of alternatorat40ºC,50%RHandat 1000MetreMSLandconformingto BS 5514, BS 649, IS:10000, ISO 8528 Part I with upto date amendments/ norms, capable of taking 10%overloadingfor onehour after 12 hours of continuous operation completewith common baseframe, Anti vibration mountings, radiator, starting equipment,batteries, residential type silencer and other accessories etc. as required and as specifiedinthedetailedspecification enclosedin the DG set Specifications section. Governing Class (As per ISO 8528 part-V); Noise Level ≤ 75 dBA at a distance of 1m (IS 8528-10)/as per latest CPCB NORMS ; Fuel Tank Capacity-minimum 60L / to run minimum of 8hr in one time full refilling ; Weight of Gen Set with Canopy-Wet- minimum 750 Kgs (or as per Manufacturer standards) ;Electrical Battery Starting Voltage-12 V DCEngine Specifications- Rated Output (Prime continuous Rating as per ISO 8528-1)-24 kW/ minimum 35 HP ; No of Cylinders-3;Rated Speed at 1500 RPMAspiration - Turbo Aspiration ;Lube Oil Sump Capacity- minimum 4.5L; Coolant Capacity- minimum 9LAlternator: Insulation-Class H ; Efficiency at (100% Load)-0.8 pf (As per Standards IS 4722, IEC 34-1)-86% with voltage regulator ±1% ;Max time to build Rated Voltage at Rated RPM-Voltage Recovery TIme-6 sec |
| 10 | Supplying, installation, testing and commissioning of automatic mains failure control suitable for 30kVA including auto By pass panel of 16SWG CRCA sheet floor mounted type, weather proof, corrosion resistance, water proof, Powder coated, powder painted, 7 tank process with suitable rating of 02 nos. FP MCCB, 02 nos. FP Contactors,aluminium bus bar for Grid, DG output and common output as approved by Engineer in Charge, suitable for required capacity of silent type DG site complete with relays, timers, set of CTs for metering & protection and energy analyser indicate currents, phase and line voltages, frequency, power factor, KWH, KVARH & provision for overload, short circuit, restricted earth fault, under frequency, control cabling from AMF Panelto diesel Engine and else where if required all complete and inter locking including all the required installations as mentioned in detailed specification sheet for DG setetc. as required. The AMF Panel may be placed inside the Canopy or at the suitable outdoor location as per latest norms and site conditions. |
| 11 | 4. FSD Bhawani mandi |
| 12 | Supply,Installation, testing andcommissioning of 25 kVA Silent type Liquidcooleddieseldrivengenerating set conforming to CPCBIV+ normscomprisingofradiator,4strokemulti cylinder engine of minimum32 BHP to deliverratedkVAatprevailingsite conditions equipped with flywheel, residential type silencer, fuel governor, fuelpump/ CRDI,builtinfueltank,electric startingequipmentwithrequirednos. of suitable AH sealed maintenance free batteriesetc.,directlycoupledto25 kVA0.8PF (lag),alternatorsuitablefor3 phase, 4 wire 50Hz AC supply system with the entire system mounted on common base frame etc. on an existing foundation, exhaust piping with thermal insulation, control wiring from Alternatortocontrolpanel,acoustic enclosure, etc.as specified and consisting of the followings and AMF panel as per specification given in the detailed specifications sheet as attached in the DG set Specifications sectionetc. as required.; Diesel Engine: One number Diesel Engine multi-cylinder,four stroke, liquid cooled, electric start, turbo charged typeengine suitable for developingtheminimum 32BHPat1500 rpm, suitable for above output of alternatorat40ºC,50%RHandat 1000MetreMSLandconformingto BS 5514, BS 649, IS:10000, ISO 8528 Part I with upto date amendments/ norms, capable of taking 10%overloadingfor onehour after 12 hours of continuous operation completewith common baseframe, Anti vibration mountings, radiator, starting equipment,batteries, residential type silencer and other accessories etc. as required and as specified inthedetailedspecification enclosedin the DG set Specifications section. Governing Class (As per ISO 8528 part-V); Noise Level ≤ 75 dBA at a distance of 1m (IS 8528-10)/as per latest CPCB NORMS; Fuel Tank Capacity-minimum 50L / to run minimum of 8hr in one time full refilling; Weight of Gen Set with Canopy-Wet- minimum 750 Kgs (or as per Manufacturer standards) ;Electrical Battery Starting Voltage-12 V DCEngine Specifications- Rated Output (Prime continuous Rating as per ISO 8528-1)-20 kW/ minimum 32 HP; No of Cylinders-3;Rated Speed at 1500 RPMAspiration - Turbo Aspiration; Lube Oil Sump Capacity- minimum 4.5L; Coolant Capacity- minimum 5LAlternator: Insulation-Class H; Efficiency at (100% Load)-0.8 pf (As per Standards IS 4722, IEC 34-1)-86% with voltage regulator ±1%; Max time to build Rated Voltage at Rated RPM-Voltage Recovery TIme-6 sec |
| 13 | Supplying, installation, testing and commissioning of automatic mains failure control suitable for 25kVA including auto By pass panel of 16SWG CRCA sheet floor mounted type, weather proof, corrosion resistance, water proof, Powder coated, powder painted, 7 tank process with suitable rating of 02 nos. FP MCCB, 02 nos. FP Contactors,aluminium bus bar for Grid, DG output and common output as approved by Engineer in Charge, suitable for required capacity of silent type DG site complete with relays, timers, set of CTs for metering & protection and energy analyser indicate currents, phase and line voltages, frequency, power factor, KWH, KVARH & provision for overload, short circuit, restricted earth fault, under frequency, control cabling from AMF Panelto diesel Engine and else where if required all complete and inter locking including all the required installations as mentioned in detailed specification sheet for DG setetc. as required. The AMF Panel may be placed inside the Canopy or at the suitable outdoor location as per latest norms and site conditions. |
| 14 | EARTHING WORK |
| 15 | Earthing with G.l. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/coke and salt as required. |
| 16 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of2.7 metre long etc. with charcoal/ coke and salt as required. |
| 17 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 18 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 19 | Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.l. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 20 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 21 | SUPPLY AND LAYING OF SERVICE CABLE |
| 22 | Supplying ofXLPE Armoured cable with aluminium conductor of 1.1 KV grade confirming to IS:7098 (Part- I) 1988 with up to date ammendments of the following sizeas required. |
| 23 | 3½ x 35 sq. mm |
| 24 | 3½ x 50sq. mm |
| 25 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 26 | 3½ X 35 sq. mm (32mm) |
| 27 | 3½ X 50 sq. mm (35mm) |
| 28 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. |
| 29 | upto 35 sq. mm |
| 30 | above 35 sq. mm and upto 95 sqmm |
| 31 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. |
| 32 | Above 35 sq. mm |
| 33 | above 35 sq. mm and upto 95 sqmm (clamped with 25*3 mm MS flat clamp) |
| 34 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. |
| 35 | upto 35 sq. mm |
| 36 | above 35 sq. mm and upto 95 sqmm |
| 37 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 38 | upto 35 sq. mm |
| 39 | above 35 sq. mm and upto 95 sqmm |
| 40 | Supplying and fixing of light class G.I. pipe of 50 mm dia. (nominal) 3 metres length along the pole for protection of under ground cable as required. |
| 41 | CIVIL WORKS |
| 42 | Providing foundation and platform for the 25 kVA Silent type DG set so as to place the above mentioned DGSet conforming to clause 2.5.1of General specifications for Electrical Works Part - VII DG Sets 2013 including PCC & suitable CC mix as recommended by OEM/ Manufacturer. |
| 43 | At FSD Bhawani Mandi |
| 44 | Providing foundation and platform for the 30 kVA Silent type DG set so as to place the above mentioned DGSet conforming to clause 2.5.1of General specifications for Electrical Works Part - VII DG Sets 2013 including PCC & suitable CC mix as recommended by OEM/ Manufacturer. |
| 45 | At FSD Baran |
| 46 | Providing foundation and platform for the 35 kVA Silent type DG set so as to place the above mentioned DGSet conforming to clause 2.5.1of General specifications for Electrical Works Part - VII DG Sets 2013 including PCC & suitable CC mix as recommended by OEM/ Manufacturer. |
| 47 | At FSD Bundi |
| 48 | Providing foundation and platform for the 82.5kVA Silent type DG set so as to place the above mentioned DGSet conforming to clause 2.5.1of General specifications for Electrical Works Part - VII DG Sets 2013 including PCC & suitable CC mix as recommended by OEM/ Manufacturer. |
| 49 | At FSD Shivpura,kota |