| 1 | Dismantling of existing unserviceable cables,junction boxes, panels,MS Pipes etc complete as reqd. |
| 2 | Dismantling of existing sewage submersible pumps i/c disconnection of pipes,nuts & bolts& Transportation of existing pumps to the site in 25KM range as directed by Engineer-in-Charge,i/c loading & unloading etc complete as reqd. |
| 3 | Providing, laying, testing & commissioning of \"C\" class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required. |
| 4 | 100 mm dia |
| 5 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required. |
| 6 | 100 mm dia |
| 7 | Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required: |
| 8 | 100 mm dia |
| 9 | Cutting holes up to 15x15 cm in R.C.C. floors and roofs and repairing the hole after insertion of drain pipes etc. with cement concrete (1:2:4). |
| 10 | Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars and disposal of unserviceable material within 50 metres lead as per direction of Engineer - in- charge. |
| 11 | Lifting & Lowering of existing sewage submersible pump of following capacity with the help of chain block & tripod set i/c disconnection & reconnection of pipes, testing etc. as reqd |
| 12 | 20 to 25 HP |
| 13 | Constructing masonry Chamber 30x30x50 cm inside, in brick work in cement mortar 1:4 (1 cement :4 coarse sand) for stop cock, with C. I. surface box 100x100 x75 mm (inside) with hinged cover fixed in cement concrete slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 ( 1 cement : 5 fine sand : 10 graded stone aggregate 40mm nominal size ) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12mm thick, finished with a floating coat of neat cement complete as per standard design :. |
| 14 | With common burnt clay F.P.S.(non modular) bricks of class designation 7.5 |
| 15 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level : |
| 16 | 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size). |
| 17 | Painting with Synthetic enamel paint of approved brand and manufacture to give even shade. |
| 18 | one or more coats on old work |
| 19 | Supplying, fabrication &installation of wall mounted outdoor type cubical feeder pillar of size not less than 0.68 sqmtrs.(face area) depth not less than25 cm, made out of M.S. sheet 2mm thick (14 SWG) duly compartmentalized having 4 strip aluminium busbar of 200 Amp capacity double door with locking arrangement for protection from rain, dust,andarrangement for fixing of following accessories mouted inside the cubical panel i/c making connection, inter connection with aluminium thimbles, earthing with two nos. earth studs duly Powder coated,cable entry provision from top & bottom both complete etc. as reqd. (Drawing of Feeder Pillar should be approved by Engineer-in-Charge before installation at site) i/c supplying & fixing of following accessorries in the existing cubical panel board/feeder pillar including connection testing etc. as reqd. |
| 20 | i. 160 Amp, 25 KAFPMCCB -1No.(Ics=100% Icu)63 Amp, TPMCCB, 18 KA - 4 Nos.(Ics=100% Icu)32 Amp, TPNMCB, 10 KA - 2Nos. iv. Digital Voltmeter 0-500 Volt 96 sqmm flush type with selector switch. -1No. v. Digital Ammeter 0-200 Amp 96 sqmm flush type with selector switch & 200/5 Amp ratio CT\"s. -1No.vi. LED Indication lamps (RYB) with 2 Amp. SPMCB fitting- 3 Nos.vii. Danger Notice plate- 2 Nos. viii. Godown Lock-3 Steps- in Front door- 2 Nos. |
| 21 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover platem having locking arrangement and watering pipe etc. with charcoal/coke and salt as required. |
| 22 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 23 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 24 | Supplying & fixing of chequered plate of 6 mm thick Mild Steel sheet including cutting the same in suitable size & Shape alongwith making provision for pull up to cover the existing open duct/shaft complete with support of 50X50X6 mm MS Angle, two coat of superior quality anti corrosive primer, black enamel paint and necessary masonary work i/c cutting,drilling etc as required. |