| 1 | Supply and erection of P.C.C. pole as per REC manual no 15/1979 (ammended upto date) and as per latest Discom specifications with factor of safety 2.5including excavation of pit upto pole planting depth 1/6th of pole length. and back filling with stone aggregate/boulders and soil by ramming and watering etc complete as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR9.0 Mtr long PCC pole of 200 Kg Working Load |
| 2 | 9.0 Mtr long PCC pole of 400 Kg Working Load |
| 3 | Supply and erection of GI stay set confirming to pattern-1 of BS:16/1974 and as per latest Discom Specifications complete with stay rod with anchor plate fitted with cast iron cross head and steel bow, in cement concrete 1:3:6 including excavation of pit-re-filling etc complete as reqd. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSRStay set of dia 20mm, 2.4m long stay rod and anchor plate 380 x 380 x 4.0 mm |
| 4 | Supply and fixing of following LT Supporting accessories with nut bolt & Clamps made out as per standard Discom\"s specifications with two coats of Red oxide and two coats of Aluminium paint etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSRLT cross arm 600 mm long with clamp |
| 5 | Supply and fixing of LT porcelain pin insulator as per IS 1445-1997 and as per Discom\"s standard specifications,suitable for working voltage 1100 volts including all accessories like MS Forged GI LT Pin confirming toIS:7935/1975 (latest amended) Nut, Bolt etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR100 mm x 70 mm |
| 6 | Supply and fixing of LT porcelain shackle insulator as per IS:1443 1979 and as per Discom\"s standard specifications, suitable for working voltage 1100 volts including all accessories like GI Hardware fittings confirming toIS:7935/1975 (latest amended) Nut, Bolt etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR75mm x 90mm |
| 7 | Supplying and drawing overhead steel core Aluminium conductor (ACSR) ISI marked(IS 398 part II-1996) on existing cross arms through insulator with all necessary T&P required including binding and twisting etc. complete in all respect as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR50 Sqmm of (6+1) 3.35 mm (Insulated Rabbit) for LT |
| 8 | 100 sqmm of (6/4.72 mm+1/1.57 mm) (Dog) |
| 9 | Supply and fixing of \"V\" type cross arms with top hamper and clamps as per latest Discom specifications made of MS angle on the existing poles complete including all necessary nut and bolt, clamps with two coats of Red oxide and two coats of Aluminium paint etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 10 | Supply and fixing of top hamper on the existing pole as per latest Discom specifications complete including nut bolts with two coats of Red oxide and two coats of Aluminium paint etc as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSRVertical type11 kV (.7m long) (65 x 65 x6mm angle) |
| 11 | 11 kV(50 x 6 mm flat) |
| 12 | Horizontal type11 kV(65 x 65 x6mm angle) |
| 13 | 11 kV with double top hamper (65 x 65 x 6mm angle) |
| 14 | Supply and fixing of MS. Channel Bracket with clamp as per Discom Specifications including Nut, Bolt with two coats of Red oxide and two coats of Aluminium paint etc. as Required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR1.8 Mtr. Long |
| 15 | 1.4 Mtr. Long |
| 16 | Supply and fixing of 11 kV pin insulator confirming to IS:731:1971 with latest ammendmenton existing bracket including all accessories like MS forged hot dipped GI Pin confirming to IS 2486(Part-I)/1993 & IS:2486 (Part-II)/1989 with latest amendment, and as per latest Discom specs. etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 17 | Supply and fixing of 11kV Disc insulator and Hot dipped galvanized Hardware confirming to IS:731:1971 with latest ammendment and as per latest Discom Specs. on existing bracket including all accessories etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSRB & S type hardware 45 KN |
| 18 | B & S disc insulator 45 KN |
| 19 | Supply and fixing of PG / T clamps on overhead lines/jumpers, made of aluminium alloy 4600 of IS 617-1994 (with latest amendment if any) with steel nut and bolts conforming to IS 1363-1992 & IS 1367/1979-80 (with latest amendments if any) all ferrous metal parts intended for outdoor use except those made of stainless steel shall be protected by hotdip galvanising in accordance with IS 2633-1986 complete in all respect as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSRPG Clamp for Panther Conductor |
| 20 | PG Clamp for Rabbit Conductor |
| 21 | T Clamp for Panther Conductor |
| 22 | Supplying and layingof Hot dip galvanized steel stay wire of 550-900 N/mm Quality confirming to IS-2141/2000 in all respect Including chemical composition (Heavily coated Hard quality) of dia 7/3.15 mm(7/10 SWG) and as per latest Discom specs. etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 23 | Supply and fixing of 11 / 33. KV Stay insulator as per IS:5300/1969 and as per Discom\"s standard specifications etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR110 x 75 x 22mm 11 KV Stay Insulator |
| 24 | Supply and fixing of LT Distribution Kiosk confirming to IS:13947/1993/ IEC 60947 Pt.3 amended up-to-date and as per DISCOMspecifications made of 2 mm thick powder coated CRCA sheet of 415 volts 3 phase 4 wire triple pole and neutral type, complete in all respect as required. Including Incoming Switch Disconnector Fuse unit, Aluminium Busbar with copper one piece U contacts base, brass studs and nuts, copper busbar for main and interconnection, MS Channel frame of 75 mm x 40 mmgrouted with C.C. of M-10 grade to achieve the height of 1.5 feet above the road level suitable for required no.outgoing. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR200 Amp. LT Distribution Kiosk for 63/100 KVA Transformer |
| 25 | 400 Amp. LT Distribution Kiosk for 250/315 KVA Transformer |
| 26 | 100 Amp. Distribution Kiosk suitable for Underground cable of Size 500mm x 550 mm x 700 mm |
| 27 | Supply and fixing of 11 KV Outdoor 4 way feeder pillar Box confirming to Discom specifications and made of 3.15 mm thick powder coated CRCA sheet enclosure confirming to IS 14772/IEC 60670 (1989) of Size 1000 mm x 1000 mm x 1500 mm, Both front and rear doors should have 3 heavy duty M.S. hinges with Brass pin inserted inside and locking arrangements.The bottom foundation frame stand should be made from 65x65x6mm MS Angle with four legs of 200mm height provided with 150x150x6mm flatsgrouted with C.C. of M-10 grade to achieve the height of 2.0 feet above the road level suitable for four outgoing. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 28 | Supply and fixing of 100 Amp, 11kV Horn gap fuse set IS 9385 on existing DP structure with 6 nos 24kV/22kV post insulator (IS:5350 part III), hot dipped hard ware,fuse wire of required size etc. complete in all respect as per Discom specification etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 29 | Supply and fixing of 11kV, 400 Amp 3 pole, central pot rotating double break type isolator (IS:9921 part I toV) without earth blade operating mechanism with GI spring loaded reverse loop type fixed contact, solid hard drawn electolytic copper tubular moving contact with silver/ nickel plated at end points, 9 nos post insulator of 12 kV (IS:2554 & IS 5350 part III), hot dipped galvanising hard ware, nut, bolts etc complete in all respect as per Discom specification etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 30 | Supply and fixing of distribution type Lightening arrestor ( Set of 3 Nos.) 9 kV, 10 kA (IS:3070) with mounting breaking to be installed on existing DP structure etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 31 | Supply and fixing Substation structure for mounting 11/0.4 Kv Transformer on Double poleas per DISCOM specification complete in all respect as required including nuts and bolts etc (excluding the cost of poles) made of MS channel of 4 nos 100 x 50 x 6mm and 4 nos 75 x 40 x 6mm and MS flat 50 x 6mm etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 32 | Supply and fixing of 1.6 mm thick MS 11 kV Danger plates as per IS :2551-1982 & specification of Discom on the existing poles complete in all respectas as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 33 | Providing and fixing of single pole mounted substation structure set for isolator / single phase transformer as per DISCOM specification complete in all respect with nuts and bolts as required MS flat 50 x 6mm, MS angle 65 x 65 x6mm, MS channel 100 x 50 x 6mm. ( Excluding cost of pole ). Etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 34 | Supply and erection of RS joist of 116 x 100 mm, 11 Meter long with the welded/ bolted top hamper 65 x 65 x 6mm (0.7 Mtr long) making necessary arrangement for fixing 11 kV \"V\" cross arm, LT bracket and guard wire bracket, grouted in ground 1/6 th of its length and fixed with cement, coarse and grit in 1:3:6 ratio in 1/5th of its length (40cm dia) from the bottom including two coats of aluminium paint over the complete length of joistetc. as required.(Excavation of pit PCC and CC foundation as per Discom specs. to be Paid Extra) All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 35 | Supplying and drawing ofXLPE insulated LT Aerial bunched Aluminium conductor cable confirming to IS 14255/1995 and IS 398 (Pt-4)/ 1994 and as per Discom Specs. on existing cross arms through I hook with all necessary T&P required including binding and twisting etc. complete in all respect as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . 1 X 25 sq. mm. + 1X25 sq. mm. (insulated) |
| 36 | 3 X 25 sq. mm. + 1X25 sq. mm. (insulated) |
| 37 | Supply & Erection ofM S lattice structure of height 12.8 mtr as per DISCOMs approved design & details in alignment, including painting of tower of approved make two coat of red oxide paint and one coat of aluminium paint before installation and one coat of Aluminium paint after erection work completed as per technical specifications & drawing of DISCOM.(Excavation of pit PCC and CC foundation as per Discom specs. to be Paid Extra). All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 38 | Supply & Erection ofM S lattice structure of height 11.0 mtr as per DISCOMs approved design & details in alignment, including painting of tower of approved make two coat of red oxide paint and one coat of aluminium paint before installation and one coat of Aluminium paint after erection work completed as per technical specifications & drawing of DISCOM.(Excavation of pit PCC and CC foundation as per Discom specs. to be Paid Extra) All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 39 | Supply of Fabricated 33 KV of \"V\" type cross arms as per Discom specifications made of MS channel 100x50 ISMC (9.5Kg. Per Mtr.) on the existing poles complete including all necessary nut and bolt etc with clamps including two coats of Red oxide and two coats of Aluminium paint etc. as Required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 40 | Supply and fixing of top hamper as per Discom specifications on the existing pole complete including nut bolts etc as required. Vertical type 33 kV. 0.75mtr. IS 75x75x6mm as per tech specs. Of DISCOM (Steel weight 6.5Kg. Approx. per top hamper). All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 41 | Supply and fixing of 33kV Disc insulator and Hot dipped galvanized Hardware confirming to IS:731:1971 with latest ammendment and as per latest Discom Specs. on existing bracket including all accessories etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . B & S type hardware 120KN |
| 42 | B & S disc insulator 120KN |
| 43 | Supply and fixing M.S. channel (cut point) 100x50mm ISMC(9.5Kg. Per Mtr.) 2x1.8mtr. long with pilot patti 50x6mm thick necessary nuts and bolts etc. as per technical specification & drawingof DISCOM. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 44 | Supply and installation of spike of M.S. rod 20mm dia 3.0mtr. long for earthing of (tower/pole) drive into earth by mechanical means sturcture connection the spike with cross arm top hamper PCC pole, lattics tower to earth etc. completeas per technical specification of DISCOM. |
| 45 | Labour charges for Dismentling the structure with pole mounted transformer different capacity along with distribution boards and re- erecting the transformer in the structure to be newly erected along with distribution boards and erecting testing, testing and commissioning (as well as cabling) |
| 46 | Labour charges for Dismantling ofexisting electric poles (PCC poles, MS channel, Lattic tower 12.6mtr. , 11 mtr. along with the ACSR Conductors, 11KV/33KV/LT line etc. 11KV insulator LT insulatorguard wires, staywires and other electric items of the pole coming along the alignment of the road and removal and re- rollingPCC pole, MS channel different sizes as well as handing over the same to DISCOM store including transportation from site to store and stacking of dismantling material in store and as per the direction of Engineer Incharge and clean the site good as per the requirement and submit the receipt from DISCOM/ concering authority, including all complete works. |
| 47 | Labour charges for Dismantling of following existing street light electric poles with street light fixtures, underground cable, MS box and other electric items of the pole coming along the alignment of the road and removal and re- rolling MS poles/PCC poles of different sizes as well as handing over the same to DISCOM/UIT/MCstore and as per the direction of Engineer Incharge and clean the site good as per the requirementand submit the receipt from concering authority,all complete works. |
| 48 | Labour charges for Dismantling of service line connection of industrial/domestic connection, single phase supply/three phase supply system on existing cross armPCC pole, MS channel different sizes of poles along with the ACSR conductor/service line weather proof cable/ Armoured cable, guard wire, stay wire and other electrical item of the pole comming along the alignment of the road and removal and re-rolling as well as handing over the same to DISCOM store including transportation from site to store and stacking of dismantling material in store and temporary supply electrical connection to domestic/industrial connection to consumer where supply disconnected andas per the direction of Engineer Incharge and clean the site good as per the requirement , all complete works. |
| 49 | Labour charges for Trimming of tree branches/plants and prepairing route approaches for electric proposed line complete with prior permission of local authority in writing , taking proper shutdown from discom office and inform to DISCOM after complete the work. |
| 50 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed ArrmouredAluminiumcable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV withH4- Grade electrolyticaluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) includingtesting etc. as required of following size. OEM must have it\"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR25 sq.mm 3.5 core |
| 51 | 120 sq.mm 3.5 core |
| 52 | 185 sq.mm 3.5 core |
| 53 | 300 Sq.mm 3.5 core |
| 54 | Add Extra in Item no. 11.7 if Excavation done in Hard Rock / CC road / TAR Road and making Good the same |
| 55 | Add Extra for Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV gradedirect in ground in the same trench in one tier horizontal formation including excavation of trench of size additional 20 cm in width,with procedure as per following points :- (a) Make a river sand bed of height 125 mm along the trench, (b) Lay another cable in middle of trench in such manner that spacing between another cable is 20 cm., (c) Provide river sand bed of height 125 mm on top of the cable. (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 /Sand stone slabs of 50 mm thicknessand 225 mm widejust above the sand bed vertically across the cable ( Approx. 9 no. Bricks per Mtr.), (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth |
| 56 | Add extrain item no. 11.1 to 11.4 for Laying Charges for cable through Manual Boggi by making pit at regular interval and repairing the pit after laying of cable with PCC/ Bitumin as required. |
| 57 | Supplying and makingend termination with heavy aluminiumlugs ( Pin / ring type )confirming to IS 8309 -1993 & IS 8337-1976 duly crimped with crimping tool, PVC tape etc of following size.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR .25.0 Sq.mm |
| 58 | 120.0 Sq.mm |
| 59 | 185.0 Sq.mm |
| 60 | 300.0 Sq.mm |
| 61 | P / L of Double wall corrugated HDPE pipe confirming to IS : 16205 P-24, Stiffness Class750 N,Externally corrugated and having smooth surface insidewith HDPE Coupler, Elbow, Teeat required Depth below the ground for laying cable of followingNominal Outer dia.MFR Test reportfrom NABL accrediated is to be submitted.(Excavation of Earth& Back filling with compaction is to be Paid Extra)All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR .50 mm |
| 62 | Providing & Laying XLPE insulated three core ArmouredAluminiumcable for working voltage 11 K.V.(E) confirming IS :7098 P - 2withH4- Grade electrolyticaluminium conductor confirming to IS: 8130 class-2 of purity >99.6 %, Insulation Screening: Extruded Semiconducting Compound followed by helically wrapped Copper Tape, round / flat strip armouring of cables , Inner / outer sheath PVC type ST-2 confirming to IS:5831in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray includingtesting etc. as required of following size. OEM must have it\"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810 All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR .3 core 185.0 Sq.mm |
| 63 | Add Extra for Laying of one number additional XLPE power cable of 11/33 KV (Earthed) voltage grade direct in ground in the same trench in one tier horizontal formation including excavation of trench of size additional 20 cm in width,with procedure as per following points:-(a) Make a river sand bed of height 125 mm along the trench, (b) Lay another cable in middle of trench in such manner that spacing between another cable is 20 cm, (c) Provide sand bed of height 125 mm on top of the cable. (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mm thicknessand 225 mm wide just above the sand bed vertically across the cable ( Approx. 9 no. Bricks per Mtr.) (e) Backfill the excavated soil leaving 300 mm from the Ground level.(f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth |
| 64 | Add Extra in Item no. 13.5 if Excavation done in Hard Rock / CC road / TAR Road and making Good the same |
| 65 | Providing & making heat shrinkable type indoor/outdoor/straight through terminations/ joint kitsuitable for11 KV / 33 KV (Earthed) cable with required components, prepration of cable ends. Type test report should be as per IS13573:2011 which covered all sequence for table 2 for termination kit and table 3 for streightthrough joint inclusive thermal & dynamic short circuit test, humidity test, soil fog test. Crosslinking shall be done out side factory with E- beam/ peroxide technology. Extrusion process shall be in house OEM within same vicinity. includingtesting etc. as required of following sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR .11 KV End Termination Kit Outdoor type3 core 120/150/185 Sq.mm |
| 66 | 33 KV End Termination Kit Outdoor type3 core120/150/185 Sq.mm |
| 67 | Erection of transformer including pole erection and feeder piller box installation , testing commsiisong of all type of work , fencing, installtion of all capacity of distribution transformer ( as per JVVNL) |
| 68 | Providing of fencing of DTR as per IEC with material and menpower( as per JVVNL) |