Design, Engineering And Supply Of Lt Power Cables And Emergency Mldb Alongwith Accessories Etc. Required For Coal Handling Plant And Rapid Loading System With Surge Bin Near Kaniha Wharfwall Siding (10 Mty) Of Mcl Kaniha Odisha Design, Engineering And Supply Of Lt Power Cables And Emergency Mldb Alongwith Accessories Etc. Required For Coal Handling Plant And Rapid Loading System With Surge Bin Near Kaniha Wharfwall Siding (10 Mty) Of Mcl Kaniha Odisha , Lt Power Cables 1.1 Kv Grade Pvc Insulated (Heavy Duty) Round Wire Armoured Aluminium Conductor Electric Cables With Frls Properties As Per Ts. , 3C X 35 Sq.Mm,Al , 3C X 150 Sq.Mm, Al , 3.5C X 185 Sq.Mm, Al , 3.5C X 240 Sq.Mm, Al , Lt Power Cables 1.1 Kv Grade, Un-Armoured, Extruded, Single Core, Pvc Insulated, Pvc Inner Sheath And Frls Pvc Outer Sheath, Stranded Copper Wire Of Size 1.0 Sq. Mm Conforming To Ts 1C X 1 Sq.Mm , Cu Cable , Emergency Main Lighting Distribution Board Design ,Engineering, Manufacture, Shop Testing ,Inspection, Packaging, Forwarding, To Mcl Site For The Following Items Along With Commissioning Spares As And When Required For Successfulcommissioningas Per Ts & Sld. Emldb 230V(L-L), 10Ka For 1Sec, 125 Amp, 50 Hz, Tpn, Aluminium Busbar, Ip-42 Enclosure, Single Front, Fixed Type, Compartmentalized, Multitier,Self Supporting, Indoor, Floor Mounted, Bottom Cable Entry, Dust And Vermin Proof, Cubicle Type, Emergency Main Lighting Distribution Board (Emldbs) As Per Technical Specification And Sld, With The Incomer -125A, Tp, 230V, Mccb-2 Nos., Buscoupler-1 No. Mccb And Outgoing Feeders 12 Nos.63A, Tp Mccbs.