| 1 | Taking out the ACB Panel and thorough inspection & take preventive care after discharging incl. taking out of its housing & refitting the same after attaining the desired IR value & re-fixing the ACB complete and testing and commissioning as per direction of E.I.C |
| 2 | Servicing & overhauling upto 1600A ACB incl. complete servicing of breaker, cleaning moving & fixed contacts and adjustment incl. mechanical lever, greasing,oiling etc. and disconnection of the armoured cable and cleaning the surfacewithCCl₄,marking cloth,emery papers and applying of petrolium jelly etc. to the socket terminals and taping with PVC tapes and re-connection of the same as per direction of E.I.C |
| 3 | Dismantling of existing defective C.T\"s from Bus Bars,fixing the newly supplied C.T\"s & making proper wiring termination on site |
| 4 | Supply & delivery of protection class C.T of ratio 500/5A,CL5P10,VA-15-Cast Resin (Make:-KAPPA/AE/Equivalent reputed manufacturer |
| 5 | Supply & delivery of Metering Class C.T of ratio 500/5A,CL-1, VA-15-Cast Resin (Make:-KAPPA/AE/Equivalent reputed manufacturer |
| 6 | Supply,delivery & fixing of Heavy duty 3ph 15 KVAR,440 V AC,50Hz Cylindrical Capacitor (Make: L&T/ABB/ Equivalent reputed manufacturer) |
| 7 | Supply,delivery & fixingof Heavy duty 3ph 5 KVAR,440 V AC,50Hz Cylindrical Capacitor (Make: L&T/ABB/ Equivalent repuded manufacturer) |
| 8 | Supply,delivery & fixingof Heavy duty 3ph 3 KVAR,440 V AC,50Hz Cylindrical Capacitor (Make: L&T/ABB/ Equivalent repuded manufacturer) |
| 9 | Supply,delivery & fixing of Heavy duty 3ph 2 KVAR,440 V AC,50Hz CylindricalCapacitor (Make: L&T/ABB/ Equivalent repuded manufacturer) |
| 10 | Supply,delivery,fixing, setting or programming of Digital EOCR with ground fault protection ,0.5-80A range, 100-240V Ac/DC Model no:-3DM2-WRDUWZ (Make:-Schneider or equivalent reputed manufacturer |
| 11 | Overall inspection & full check up LTMCC panel,with necessary tightness check of bus bar joints ofBuses,motor feeder, making necessary modification in power circuits of motor feeder for proper power transfer etc. on site |
| 12 | Supply,delivery & fixingof DIN Fuse 100A,Size 00 (Make: L&T/ABB/ Equivalent repuded manufacturer) |
| 13 | Supply ,delivery & fixingof DIN Fuse 32A,Size 00 (Make: L&T/ABB/ Equivalent repuded manufacturer) |
| 14 | Supply ,delivery & fixingof DIN Fuse 20A,Size 00 (Make: L&T/ABB/ Equivalent repuded manufacturer) |
| 15 | Cleaning,refilling,hydro testing of existing ABC type fire extinguishers of 6Kg capacity with change of damaged spares including removing from site, discharging existing dry powder and re-fixing after refilling |
| 16 | Servicing and overhauling,programming if necy the Soft starter for motor after opening all components, electric timer,o/c relay,semiconductor fuse etc. & fitting, fixing the same after same plate servicing and overhauling testingas required as per direction of EIC |
| 17 | Complete servicing and overhauling and necessary repairing of DTH 250 Amps MCCB |
| 18 | Supply,delivery & laying 1.5 sqmmFR PVC insulated flexible industrial cabel |
| 19 | Supply,delivery and laying1C 50Sq mm Unarmoured Cu Cable complete as per direction of EIC |
| 20 | Supply,delivery & fixing 440V,3Ph MO C5type capacitor duty contractor |
| 21 | Supply,delivery & fixing 440V,3Ph MO C15type capacitor duty contractor |
| 22 | Supply,delivery & fixing 440V,3Ph MO C3type capacitor duty contractor |
| 23 | Taking down the heavy duty exhaust fan 3ph 23 cm sweep to 60cm sweep with necessary tools and tackles and arrangement from top of the wall |
| 24 | Opening the 3ph 24\" or 60cm sweep exhaust fan,testing, checking,re-winding by supplying super enameled copper wire ofappropriate gauge,minalex paper,mica sheet,changing the loops,overhauling, becking,varnishing,re-fitting and testing and measuring r.p.m etc. |
| 25 | Add : GST@ 18.00% on Rs. 405904.00 i.e Total amount over item no. 1.00 to 24.00 |
| 26 | Add CESS @ 1.00% on Rs. 478967.00 i.e Total amount over item no. 1.00 to 25.00 |