| 1 | Supply and fix including commissioning of 16M high mast 360/150--3/3 shaft in two section suitable for 47 m/sec wind speed along with head frame, luminaires carriage suitable for 6-9 luminaires in symmetrical arrangement and other accessories manufactured in factory. Supply of raising lowering system comprising double drum winch, 4mm diameter SS wire rope, trailing cable, connector, integral power tool motor, manual handle, junction box, lightning finial. .(a) Supply and fix foundation bolts along with nuts, washers, anchor plate and common template.(b)Supply and fix LED type single dome aviation obstruction light.(c)Supply and fixoutdoor stand mounted feeder pillar with 32A TPN MCB incomer, single dial time switch, 25A TP contactor for the automatic switching of luminaries, power tool control with 2 no 9A contactors and raise lower push button, Incoming 35 sq. mm and out going 16 & 2.5 sq. mm terminals.Complete all as specified and as directed. |
| 2 | Supply and fix single arm GRP pole of 5 mtr cyclindrical/square with bracket having high impact strength, high bending strength, non conductive, electric insulator, shock proof and non effective from chemical, salt and smog with suitable size of GI nut bolts and taper including PCC work, complete all as specified and as directed |
| 3 | Supply and fix including commissioning and testing of 20 watt Solar integral AIO (All-in-One) street light with high pressure die-cast (LM6 Alloy) Aluminium housing, reliable & robust construction with IP65 & IK08 protection, suitable for OD 50/60mm bracket, having Min 4500 system lumens, suitable for 24hrs (2 Nights) Autonomy. The luminaire should work on Hybrid mode with priority for solar, in case solar charging is not available then it should automatically switch to AC grid supply for reliable operation. Dimming Profile: From Dusk – First 04 hours full brightness level • Next fixed at 30% Brightness level• Lithium Pherrophosphate Battery capacity min [email protected] or 256Wh & Battery Temp range -10 to +50℃. Panel capacity min 60Wp, CRI >=70, System Efficacy >150lm/W, & system wattage should not be more than 30W ± 2%, if wattages increases then the size of battery & panel shall also be increased in similar percentage to maintain equal autonomy of the system. The fixture should have designed for street light application & should have flexible angle of mounting from 0-15 Degree for divers geographical condition. Life class of LED System [email protected] :-Certified, charger efficiency >90% and standards IEC62109-1, IEC61547, CISPR15,IEC62093, IEC61347-2-13, EN50530, IEC62384 or equivalent BIS Standards. The PV module should be made up of crystalline silicon solar cells \"Mono-Crystalline\" and must have a certificate of testing conforming to IEC 61215 Edition II / BIS 14286 & IEC 61730-1,2 IEC60598, Operating temp -10 Degree C to 50 Degree C, certifying above given parameters all reports shall be from In-house NABL or IECQ or any international accredited Laboratory complete all as specified and directed. |
| 4 | Material and labour for construction of shallow foundation with concrete for the highmast considering the safe soil bearing capacity at site as 10 T/sqmtr at 2 metre depth with all materials and labour and including the erection of the high mast with the help of suitable tools and plants, wiring of luminaires with all wiring materials like PVC insulated PVC sheathed flexible cable of suitable copper conductor cores of 1.5 sq. mm, lugs, MCB and all labour and Installation of the mast feeder pillar by grouting the stand in concrete. |
| 5 | Supply and fixing LED flood light 120 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp, all as specified and directed. |
| 6 | Connecting /disconnecting of air-conditioner in married officers quarters, OTM, offrs Mess from the existing over head lines all as directed and specified (No service of ACs Involved in the item rate.(Cables and materials for connection will be provided by occupant /userof the accn) |
| 7 | Providing labour transport and T&Pfor locating the fault in HT/LT line in OH/UG Line/cable in by visual inspection recce of faulty area and repairs to the fault by means of replacement of Unservicible Jumpers / Fuse wires / Burnt lugs / MCCB etc.including restrain of broken/loose ACSR counductors / Earth wire. If required to make temporary connection for fault in HT/LT lines, the cable shall be given by the the AGE E/M store for temorary connection to resume the power supply urgently. Note : (i)Materials requried for fault repairs will be measured under relevant items included in BOQ. (ii)Contractor will depute the dedicated team and necessary transportation, he will completely responsible for all the safety aspects of his team. No dispute regarding safety of person would be entertain later on. If any mishappening occures during rectifaction of fault in HT/LT lines contractor will be fully liable to bear all the expenses of indls. Special Notes:- (for 66 KV Grid, Sub Stn No.3, Sub Stn No.9, AMN Dump Barsat and Baffle Range Dhablan)(a)Contractor will provide all set of T & P, communication device (Mobile Phone) to deployed persons,electrcian team for each sub station required for repair of HT/LT Electricalswitch gear system including safety equipment such as All type of T&Ps(Bamboo ladders, screw drivers, wire/cable cutters with blades, multi meters, cutting plairs, torch lights etc)for routine maintenance and protection of the trademan incl safety equipment such as Hand gloves, Rubber boots, Sefety belt and helmets etc.(b)On intimation of any type of repair/maintenance work of HT/LT switch gear incomer as well as out going feeder the contractor is responsible tolocate the fault by the dedicated team comprising tradesman helpers required numbersas per the gravity /nature of the work involved to restore the power supply andcommunicate with SBA on duty and getting permit card for working on HT lines and deposit the permit card after rectification of fault, all the activities shall be carried out within reasonable time as given by the Engineer-in-Charge.(c) Contractor will provide necessary complaint slip, complaint boook & permit book, contractor will direct the instructions to indls for lodgging the complaints duly marked the location, time and date for earlier rectifications.(d) After getting the complaints, team deployed by the contractor will rectify the complaints within stipulated time i.e within 2 hours from the time of receiving of complaints.(e)Contractor should also provide a dedicated supervisor for collection of complaints from SBA, JE, USER etc. He would be held responsible, in case complaints are not collected timely. |
| 8 | Supply only the HT fuse wire of size 5 Amps of capacity.all as directed and specified |
| 9 | Supply only the HT fuse wire of size 10 Amps of capacity.all as directed and specified |
| 10 | Supply only the HT fuse wire of size 20 Amps of capacity. all as directed and specified |
| 11 | Supply only the HT fuse wire of size 32 Amps of capacity. all as directed and specified |
| 12 | Supply only the HT fuse wire of size 40 Amps of capacity.all as directed and specified |
| 13 | Supply only the HT fuse wire of size 60 Amps of capacity.all as directed and specified |
| 14 | Supply only the HT fuse wire of size 100 Amps of capacity.all as directed and specified |
| 15 | Repair/replacement of LT Jumper all as directed and specified |
| 16 | Replacement of HT Jumper all as directed and specified |
| 17 | Supply only multi-jointed ACSR jumpers of HT over head lines with and inclXLPE/PVCinsulated 11000 volts multi stranded aluminium conductor single core cable of size 120 sqmm as per colour code in sequence Red, yellow, blue and black for neutralincl fixing with ACSR conductors with suitable size PG (Parellel Groove) clampcomplete all as specified and directed .(Length of one jumper not exceeding more than 3.0 mtrs) |
| 18 | All as per Srl item No.17.00 here-in-before but of size 240 Sqmm. all as specified and directed . |
| 19 | Replacement of HT Loop type insulator, vitreous porcelain, white, brown or green large size, with overall dimensions 90mmx140mm, clearance of hole 25.5mm insulator all as directed and specified |
| 20 | Supply only pin type porcelain, vitreous, white, brown or green insulator incl one galvanised mild steel spindle, two galvanised iron washers and one galvansied iron nut, 150mmheight, 150mm dia for 11000 volts grade complete all as specified and directed. |
| 21 | Supply only Disc type porcelain insulator, vitreous 145mm height and 255 dia ball and socket type, white, brown and green \" Two in series\" assembly for tension with tension clamps for conductor, working pressure 11000 volts grade complete all as specified and directed. |
| 22 | Laying only HT/LT cable for providing temporary supply to feeder of various sizes from MES store and deposited back to store yard after permanent rectification of fault all as directed and specified (Cost is inclusive of transport of cables from stores to fault sites, fixing arrangement /dismantling of old cables/refixing of new cables as required at site) |
| 23 | Supply and Fix cable lugs aluminium any typesuitable for cable up to 10 to 16 sqmm including necessary crimping with crimping tool complete all as specified and directed . |
| 24 | Supply and Fix cable lugs aluminium any typesuitable for cable for 25 sqmm including necessary crimping with crimping tool complete all as specified and directed . |
| 25 | Supply and Fix cable lugs aluminium any typesuitable for cable for 35 sqmm including necessary crimping with crimping tool complete all as specified and directed . |
| 26 | Supply and Fix cable lugs aluminium any typesuitable for cable for 50 sqmm including necessary crimping with crimping tool complete all as specified and directed . |
| 27 | Supply and Fix cable lugs aluminium any typesuitable for cable for 70 sqmm including necessary crimping with crimping tool complete all as specified and directed . |
| 28 | Supply and Fix cable lugs aluminium any typesuitable for cable for 95 sqmm including necessary crimping with crimping tool complete all as specified and directed . |
| 29 | Supply and Fix cable lugs aluminium any typesuitable for cable for 120 sqmm including necessary crimping with crimping tool complete all as specified and directed . |
| 30 | Supply and Fix cable lugs aluminium any typesuitable for cable for 150 sqmm including necessary crimping with crimping tool complete all as specified and directed . |
| 31 | Supply and Fix cable lugs aluminium any typesuitable for cable for 185 sqmm including necessary crimping with crimping tool complete all as specified and directed . |
| 32 | Supply and Fix cable lugs aluminium any typesuitable for cable for 240sqmm including necessary crimping with crimping tool complete all as specified and directed . |
| 33 | Supply and Fix cable lugs aluminium any typesuitable for cable for 300 sqmm including necessary crimping with crimping tool complete all as specified and directed . |
| 34 | Supply and Fix cable lugs aluminium any typesuitable for cable for 400 sqmm including necessary crimping with crimping tool complete all as specified and directed . |
| 35 | Taking out wornout MCCB of any size, any capacity and any rating including dismantling including fixing,complete all as specified and as directed |
| 36 | Supply and fix MCCB with adjustable thermal and magentic setting typeRelease Range 63 Amps 4 Pole breaking capacity at 415 volt AC 50 Hz, 16 kA complete all as specified and directed. |
| 37 | Supply and fix MCCB with adjustable thermal and magentic setting typeRelease Range 100 Amps 4 Pole breaking capacity at 415 volt AC 50 Hz, 16 kA complete all as specified and directed. |
| 38 | Supply and fix MCCB with adjustable thermal and magentic setting typeRelease Range 160 Amps 4 Pole breaking capacity at 415 volt AC 50 Hz 36 kA complete all as specified and directed. |
| 39 | Supply and fix MCCB with adjustable thermal and magentic setting typeRelease Range 200 Amps 4 Pole breaking capacity at 415 volt AC 50 Hz 36 kA complete all as specified and directed. |
| 40 | Supply and fix MCCB with adjustable thermal and magentic setting typeRelease Range 250 Amps 4 Pole breaking capacity at 415 volt AC 50 Hz 36 kA complete all as specified and directed. |
| 41 | Supply and fix MCCB with adjustable thermal and magentic setting typeRelease Range 400 Amps 4 Pole breaking capacity at 415 volt AC 50 Hz 36 kA complete all as specified and directed. |
| 42 | Supply, fix and in replacement of LT ACB 4 Pole, 415 V, 50 KA with thermal Magnetic Release (Manual Drawout type) of capacity 630 Amps all as specified and as directed. |
| 43 | Supply, fix and in replacement of LT ACB 4 Pole, 415 V, 50 KA with thermal Magnetic Release (Manual Drawout type) of capacity 800 Amps all as specified and as directed. |
| 44 | Material and labour for providing necessary following stationary require to lodge the complaint, as per requirement and as per existing sample for a minimum period of 06 Months from the date of commencement of contract to 66 KV Grid, sub stn No.9 and sub stn No.3:- (i) Complaint Register/books as per sample.(ii) Complaint Slip/job card as per sample.(iii) Permit book as per sample.(iv) Other materials ie glue stick,pen, pencil, carbon paper and stainless steel scale 1\". |
| 45 | Material & Labour for Periodical cutting of trees /trimming of branches along the HT /LT overhead lines in a girth of 03mtrs on either side of the conductors including removing the same and dumpingcomplete all as directed. Note : Expenditure for necessary tool and plants required for Periodical cutting of trees / trimming of branches along the HT / LT overhead lines are deemed to be included in rate quoted by the contractor. Complete all as specified and as directed.Note:- (i)Contractor will arrange the security boards/danger boards (Man at work)at the site, so that prevent from any damaged. (ii)Contractor will liable to cutting/trimming the branches within the day after of complaint received. |
| 46 | Material & Labour for Earthingcomplete with galvanized earth plate electrode60 cm x 60cm x 6mm thick buried directly in ground to the depth of not less than 2.25 mtr below ground level with top edge of earth plate or a depth not less than 1.50 m below ground levelconnected to GI strip 32 x 6mm as earth lead by means of galvanized bolts, nuts check nuts and washers and necessary excavation and earth work PCC 1:2:4 type B-1 using 20mm graded brick aggregate for earth pit RCC cover , charcoal & common salt filled in alternate layers funnel with 20mm bore light grade watering pipe, 40mm dia GI pipe light grade for protection of GI strip, wire mesh andconnected to earth point including testing on all as specified and shown in electric plate No 3 of SSR part I. |