Sales : +91-777 804 8217
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 11-03-2025 | AMENDMENT TO TTENDER DOCUMENTS | BOQ | 19-03-2025 |
| 2 | 06-03-2025 | AMENDMENT TO TENDER DOCUMENTS AND REVISED BOQ | BOQ | 19-03-2025 |
| Sl. No. | Item Description |
| 1 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.00, Air delivery minimum 210 Cum/Min , 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete all as specified and directed. |
| 2 | Supply & fix Air Circulator fans 230 volts single phase oscillating 450 mm sweep suitable for wall mounting complete all as specified and directed. |
| 3 | Supply, installation, commis-sioning of Water cooler fully stainless steel, electric driven single phase having approx storage and nominal cooling capacity 40/80 Ltrs complete all as specified and directed. |
| 4 | Supply and install inverter typehi wall split ACunits indoor & outdoor complete with cordless remote control unit and with in built air ioniser and Plasma filter for better indoor air quality with 5 star rating of capacity 1.0 TR , with and including MS wall mounted bracket complete all as specified and directed. |
| 5 | Supply and install inverter typehi wall split ACunits indoor & outdoor complete with cordless remote control unit and with in built air ioniser and Plasma filter for better indoor air quality with 5 star rating of capacity 1.5 TR , with and including MS wall mounted brackets, complete all as specified and directed. |
| 6 | Supply and install inverter typehi wall split ACunits indoor & outdoor complete with cordless remote control unit and with in built air ioniser and Plasma filter for better indoor air quality with 5 star rating of capacity 2.0 TR , with and including MS wall mounted brackets, complete all as specified and directed. |
| 7 | Supply and fix air conditioner towertype suitable for operational on three phase AC electric supply, including water pump Sets, cooling tower, ducting plumbing and electric connection, capacity 22500 K cal Per hour (4 ton) or nearest size, complete all as specified and directed. |
| 8 | Supply & fix Voltage stablizer for automatic operation ,single phase naturally air cooled indoor type & designedfor input variation between 170 to 250 V with output voltage stablized at 230 V with accuracy 2.5% and of capacity 4 KVA, complete all as specified and directed. |
| 9 | Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A \"C\" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and with connections, testing and commissioning etc. complete all as specified and directed. |
| 10 | M&L for wiring for circuit / submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit, complete all as specified and directed. |
| 11 | 2 X 4 Sqmm + 1 X 4 Sqmm earth wire |
| 12 | 2 X 6 Sqmm+ 1 X 6 Sqmm earth wire |
| 13 | 4 X 6 Sqmm + 2 X 6 Sqmm earth wire |
| 14 | Supply and Fix Monoblock pump set suitable for 415 V, 3 phase system having capacity 10 HP of pumping 1085 Ltrs/Hr of 30 Ft head including disconnecting the old pump and connecting and testing commissioning of the new pump complete all as specified and directed. |
| 15 | Supply and Fix Monoblock pump set suitable for 415 V, 3 phase system having capacity 12.5 HPof pumping 1085 Ltrs/Hr of 30 Ft headincluding disconnecting the old pump and connecting and testing commissioning of the new pump complete all as specified and directed. |
| 16 | Supply and fixng of Submersible pump, electric driven 415 V, TP suitable for 200/250 mm dia bore well (Casing pipe size 200/250 mm) supply and Install completesubmersible pumpp 12.5 HP including taking out the old pump and connetion of new submersible pump and testing commissioning complete all as specified and directed. |
| 17 | All as per item No. 13 above but submersible pump of 10 Hp capacity complete all as specified and directed. |
| 18 | Supply and fixing of DOL starter of 10 HP capacity pump complete all as sepcified and directed. |
| 19 | Supply and fixing of DOL starter of 15 HP capacity pump complete all as sepcified and directed. |
| 20 | Supply and lay 40mm dia GI pipe, “Medium grade”, including all fittings complete all as specfied and directed. |
| 21 | Supply,installation, testing and commissioning of silent Diesel Engine driven,generating set 415 volts, 125KVA /100 KW 3 phase0.8 power factor 50Hz, 1500 RPM, Liquid Cooled, With all complete all connected acessories in all respects for commissioning of the DG Set, with CPCB approved and latest MOEF guide line Accoustic enclosure IP 23,self excitedself regulated brushless AC generator installed including accoustic enclosure suitable for ambient condition at Hyderabad including AMF panel and confirming to condition under IS 4722/1460, BS 5514/2613/5000 ISO 8526/3046 with the following:- |
| 22 | Alternator - Standard design alternator, Power Rating 125 KVA/ 100 KW, 3 Phase 4 wire,415 Volts, 50 HZ, Power factor 0.8(lagging)Current 87 Amps,net output at site after considering derating for per site conditions at 0.8 (lagging) power factor, 1500 RPM, Cooling Liquid cooled, Aspiration Turbo charged, air cooled self regulated screen protected drip proof IP 23 enclosure brushless design with widing in pole faces, insulating class \"H\" and voltage regulation of +1% at rated voltage from no load to full load, A1 The alternator shall be conforming to BS 2613/5000 and shall be in position to generate supply with frequency regulation with in +1% tolerance. The alternator will be suitable for tropical climate and shall generally confirm to BS-2613/5000/IS-4722.Make of the Alternator : |
| 23 | Diesel Engine : Minimum 80 BHP capacity, multi stroke, 3 Cylinder,TurboChargedDiesel Engine suitable for 125 KVA coupled with alternator and after considering derating as per site conditions after generating and reducing power consumed by accessories, directly coupled through flexible coupling, multi cylinder, multi stroke direct injection, cold starting 1500 RPM, as per relevant ISI/BS-5514 with an overload capacity of 10% for one hour in 12 hours continous running complete with standard accessories all as specified and required for safe handling and operation salient features of accessoires shall be as under :- KIRLOSKAR/CUMMINS/GREAVES Insulation class - \"H\" , Temperature rise class - \"H\" ,Excitation- Self excited Regulation performance - The voltage is kept constant with + 1%, manual voltage adjustment with in + 5%. ,Frequency Regulation + 1% Suitable size & suitable number of runsof UG copper cable (Control cable) from Alternator to AMF & RAW Power to AMF Panel is deemed to be include is quoted rate. |
| 24 | (i)Flywheel with housing(ii) Cooling System : Mounted radiator with fan and belts(iii)Cooling Water Pump : Centrifugal type belt driven(iv) Exhaust System : As per OEM reccommendation/specification.(v)Starting System:- Electric Self Starter with maintenance free batteries including battery charging alternative belt driven.(vi)Batteries :- 12 Volts DC electrical batteries ofsuitableAH rating, complete connected with copper cable PVC sheathed conductor multistranded leads of suitbale length from self starter to the battery terminals complete with initial charge and initial fill of electrolite all as specified and directed.(vii)Fuel tank of adequate capacity :- As per OEM norms and specifications designed for above capacity of DG Set. |
| 25 | AMF Panel : Auto Main Failure (AMF) Panel made out 14/16 Gauge CRCAsheet weather proof powder coated conforming to IS 8623 totally enclosed dust and vermin proof with front and rear openings of 415 Volts, 3 Phase, 4 wireAC 50 HZ having aluminium bus bar of capacity required to carry current at 100% load of 125 KVA DG Set with three phase and half neutral colour coded pre-wired with copper flexible cable, all as specified with the following accessories, control cable from Gen Set to AMF Panel. Contactor of Suitable capacity 3 pole with required nos as per OEM, TP contactor for netural for both supplies Suitable capacity of MCCB, 4 Polefor both supplies CTs 150/5A for both the supplies Push buttons Indication Lamps2 over load + earth leakage relay Multi functional digital meter for KWH, KVA, KW, Amps, Volts, frequency, power factor etc. SMPS Battery charge 12V, with trickle and boost charging. ON/OFF Switch.Automatic/Manual Switch. Hooter. Voltage sensing relay.Six window anunciator for fault indications. |
| 26 | Acoustic Enclosure : Enclosure is free standing floor mounted factory built and modular in construction to facilitate easy assembly at work site and will be drop over housing type. It will consist of acoustically treated panel housed in sheet metal will provide easy access for maintenance, repairs and operation. The enclosure is custom to suit conditions, with the following features :-(i) Custom built product for various equipments, with ensure the optimum performance without duration.(ii) 16SWG (1.6mm) thick CRCA sheet to be used for enclosure panel to ensure longer life against weathing action. High quality acoustic insulation materials to be used as per IS 8183 for maximum sound absoption. Acoustic layers are supported by perforated sheets.(iii)Sheet metal component of the enclosure should undergo various stages of surface treatment prior to painting which leads to be better life of the enclosure against weathering action.(iv) Specialpaint treatment with pure polyster powder/epoxy to be provided for better weather resistance.(v)Well designed ventilation system to be provided to put out the heat from the chamber efficiently.(vi) For effective acoustic/weather sealinga special type weather sealing gaskets, new frame rubber gaskets to be used. |
| 27 | (vi) The batteries should be placed inside the enclosure inside the DG Set on a suitable insulated platform.(vii)The DG set should be provided with external emergency stop push button.(viiii)Provn of 2 Nos 11 Watts LED lamp fitting of approved Make incl wiring inside canopy with single switch controlled.(ix)Fuel gauge to be provided with the neck of fuel tank.(x) Tools as per manufacturers with the box.(xi)Inventory spares of suitable company be manufacture.(xii) The acoustic enclosure parts shall be of powder coated after pre treatment process. (xiii)The quotd rate to be includednecessary civil work for reqd alteration in existing DG plateform complete. |
| 28 | Supplyinstallation testing and commissioning of silent Diesel Engine driven , generating set 415 volts, 250KVA /200 KW 3 phase0.8 power factor 50Hz, 1500 RPM, Liquid Cooled, With all complete all connected acessories in all respects for commissioning of the DG Set, with CPCB approved and latest MOEF guide line Accoustic enclosure IP 23,self excitedself regulated brushless AC generator installed including accoustic enclosure suitable for ambient condition at Hyderabad including AMF panel and confirming to condition under IS 4722/1460, BS 5514/2613/5000 ISO 8526/3046 with the following:-Alternator - Standard design alternator, Power Rating 250 KVA/ 200 KW, 3 Phase 4 wire,415 Volts, 50 HZ, Power factor 0.8(lagging)Current 87 Amps,net output at site after considering derating for per site conditions at 0.8 (lagging) power factor, 1500 RPM, Cooling Liquid cooled, Aspiration Turbo charged, air cooled self regulated screen protected drip proof IP 23 enclosure brushless design with widing in pole faces, insulating class \"H\" and voltage regulation of +1% at rated voltage from no load to full load, A1 The alternator shall be conforming to BS 2613/5000 and shall be in position to generate supply with frequency regulation with in +1% tolerance. The alternator will be suitable for tropical climate and shall generally confirm to BS-2613/5000/IS-4722.Make of the Alternator : |
| 29 | Diesel Engine : Minimum 80 BHP capacity, multi stroke, 3 Cylinder,TurboChargedDiesel Engine suitable for 250 KVA coupled with alternator and after considering derating as per site conditions after generating and reducing power consumed by accessories, directly coupled through flexible coupling, multi cylinder, multi stroke direct injection, cold starting 1500 RPM, as per relevant ISI/BS-5514 with an overload capacity of 10% for one hour in 12 hours continous running complete with standard accessories all as specified and required for safe handling and operation salient features of accessoires shall be as under :- KIRLOSKAR/CUMMINS/GREAVESInsulation class - \"H\" , Temperature rise class - \"H\" ,Excitation- Self excitedRegulation performance - The voltage is kept constant with + 1%, manual voltage adjustment with in + 5%. ,Frequency Regulation + 1% Suitable size & suitable number of runsof UG copper cable (Control cable) from Alternator to AMF & RAW Power to AMF Panel is deemed to be include is quoted rate. |
| 30 | (i)Flywheel with housing.(ii) Cooling System : Mounted radiator with fan and belts.(iii)Cooling Water Pump : Centrifugal type belt driven.(iv) Exhaust System : As per OEM reccommendation/ specification.(v)Starting System:- Electric Self Starter with maintenance free batteries including battery charging alternative belt driven.(vi)Batteries :- 12 Volts DC electrical batteries ofsuitableAH rating, complete connected with copper cable PVC sheathed conductor. multistranded leads of suitbale length from self starter to the battery terminals complete with initial charge and initial fill of electrolite all as specified and directed.(vii)Fuel tank of adequate capacity :- As per OEM norms and specifications designed for above capacity of DG Set. |
| 31 | AMF Panel : Auto Main Failure (AMF) Panel made out 14/16 Gauge CRCAsheet weather proof powder coated conforming to IS 8623 totally enclosed dust and vermin proof with front and rear openings of 415 Volts, 3 Phase, 4 wireAC 50 HZ having aluminium bus bar of capacity required to carry current at 100% load of 250 KVA DG Set with three phase and half neutral colour coded pre-wired with copper flexible cable, all as specified with the following accessories, control cable from Gen Set to AMF Panel. |
| 32 | Contactor of Suitable capacity 3 pole with required nos as per OEM, TP contactor for netural for both supplies Suitable capacity of MCCB, 4 Polefor both supplies CTs 150/5A for both the supplies Push buttons Indication Lamps.2 over load + earth leakage relay Multi functional digital meter for KWH, KVA, KW, Amps, Volts, frequency, power factor etc. SMPS Battery charge 12V, with trickle and boost charging. ON/OFF Switch.Automatic/Manual Switch. Hooter. Voltage sensing relay.Six window anunciator for fault indications.Acoustic Enclosure : Enclosure is free standing floor mounted factory built and modular in construction to facilitate easy assembly at work site and will be drop over housing type. It will consist of acoustically treated panel housed in sheet metal will provide easy access for maintenance, repairs and operation. The enclosure is custom to suit conditions, with the following features :- |
| 33 | (i) Custom built product for various equipments, with ensure the optimum performance without duration.(ii) 16SWG (1.6mm) thick CRCA sheet to be used for enclosure panel to ensure longer life against weathing action. High quality acoustic insulation materials to be used as per IS 8183 for maximum sound absoption. Acoustic layers are supported by perforated sheets.(iii)Sheet metal component of the enclosure should undergo various stages of surface treatment prior to painting which leads to be better life of the enclosure against weathering action. |
| 34 | (vi) The batteries should be placed inside the enclosure inside the DG Set on a suitable insulated platform.(vii)The DG set should be provided with external emergency stop push button.(viiii)Provn of 2 Nos 11 Watts LED lamp fitting of approved Make incl wiring inside canopy with single switch controlled.(ix)Fuel gauge to be provided with the neck of fuel tank.(x) Tools as per manufacturers with the box.(xi)Invents of suitable company be manufacture.(xii) The acoustic enclosure parts shall be of powder coated after pre treatment process. (xx)The coated rate to be includednecessary civil work for reqd alteration in existing DG plateform complete. |
| 35 | Supplyinstallation testing and commissioning of silent Diesel Engine driven , generating set 415 volts, 320KVA /256 KW 3 phase0.8 power factor 50Hz, 1500 RPM, Liquid Cooled, With all complete all connected acessories in all respects for commissioning of the DG Set, with CPCB approved and latest MOEF guide line Accoustic enclosure IP 23,self excitedself regulated brushless AC generator installed including accoustic enclosure suitable for ambient condition at Hyderabad including AMF panel and confirming to condition under IS 4722/1460, BS 5514/2613/5000 ISO 8526/3046 with the following:-Alternator - Standard design alternator, Power Rating 320 KVA/ 256 KW, 3 Phase 4 wire,415 Volts, 50 HZ, Power factor 0.8(lagging)Current 87 Amps,net output at site after considering derating for per site conditions at 0.8 (lagging) power factor, 1500 RPM, Cooling Liquid cooled, Aspiration Turbo charged, air cooled self regulated screen protected drip proof IP 23 enclosure brushless design with widing in pole faces, insulating class \"H\" and voltage regulation of +1% at rated voltage from no load to full load, A1 The alternator shall be conforming to BS 2613/5000 and shall be in position to generate supply with frequency regulation with in +1% tolerance. The alternator will be suitable for tropical climate and shall generally confirm to BS-2613/5000/IS-4722.Make of the Alternator : |
| 36 | Diesel Engine : Minimum 80 BHP capacity, multi stroke, 3 Cylinder,TurboChargedDiesel Engine suitable for 320 KVA coupled with alternator and after considering derating as per site conditions after generating and reducing power consumed by accessories, directly coupled through flexible coupling, multi cylinder, multi stroke direct injection, cold starting 1500 RPM, as per relevant ISI/BS-5514 with an overload capacity of 10% for one hour in 12 hours continous running complete with standard accessories all as specified and required for safe handling and operation salient features of accessoires shall be as under :- KIRLOSKAR/CUMMINS/GREAVESInsulation class - \"H\" , Temperature rise class - \"H\" ,Excitation- Self excited Regulation performance - The voltage is kept constant with + 1%, manual voltage adjustment with in + 5%. ,Frequency Regulation + 1% Suitable size & suitable number of runsof UG copper cable (Control cable) from Alternator to AMF & RAW Power to AMF Panel is deemed to be include is quoted rate. |
| 37 | (i)Flywheel with housing(ii) Cooling System : Mounted radiator with fan and belts(iii)Cooling Water Pump : Centrifugal type belt driven |
| 38 | (iv) Exhaust System : As per OEM reccommendation/specification.(v)Starting System:- Electric Self Starter with maintenance free batteries including battery charging alternative belt driven.(vi)Batteries :- 12 Volts DC electrical batteries ofsuitableAH rating, complete connected with copper cable PVC sheathed conductor multistranded leads of suitbale length from self starter to the battery terminals complete with initial charge and initial fill of electrolite all as specified and directed.(vii)Fuel tank of adequate capacity :- As per OEM norms and specifications designed for above capacity of DG Set. |
| 39 | AMF Panel : Auto Main Failure (AMF) Panel made out 14/16 Gauge CRCAsheet weather proof powder coated conforming to IS 8623 totally enclosed dust and vermin proof with front and rear openings of 415 Volts, 3 Phase, 4 wireAC 50 HZ having aluminium bus bar of capacity required to carry current at 100% load of 320 KVA DG Set with three phase and half neutral colour coded pre-wired with copper flexible cable, all as specified with the following accessories, control cable from Gen Set to AMF Panel.Contactor of Suitable capacity 3 pole with required nos as per OEM, TP contactor for netural for both supplies Suitable capacity of MCCB, 4 Polefor both supplies CTs 150/5A for both the supplies Push buttons Indication Lamps. 2 over load + earth leakage relay Multi functional digital meter for KWH, KVA, KW, Amps, Volts, frequency, power factor etc. SMPS Battery charge 12V, with trickle and boost charging. ON/OFF Switch.Automatic/Manual Switch. Hooter. Voltage sensing relay.Six window anunciator for fault indications.Acoustic Enclosure : Enclosure is free standing floor mounted factory built and modular in construction to facilitate easy assembly at work site and will be drop over housing type. It will consist of acoustically treated panel housed in sheet metal will provide easy access for maintenance, repairs and operation. The enclosure is custom to suit conditions, with the following features :- |
| 40 | (i) Custom built product for various equipments, with ensure the optimum performance without duration.(ii) 16SWG (1.6mm) thick CRCA sheet to be used for enclosure panel to ensure longer life against weathing action. High quality acoustic insulation materials to be used as per IS 8183 for maximum sound absoption. Acoustic layers are supported by perforated sheets.(iii)Sheet metal component of the enclosure should undergo various stages of surface treatment prior to painting which leads to be better life of the enclosure against weathering action.(iv) Specialpaint treatment with pure polyster powder/epoxy to be provided for better weather resistance.(v)Well designed ventilation system to be provided to put out the heat from the chamber efficiently.(vi) For effective acoustic/weather sealinga special type weather sealing gaskets, new frame rubber gaskets to be used. |
| 41 | (vii) The batteries should be placed inside the enclosure inside the DG Set on a suitable insulated platform.(viii)The DG set should be provided with external emergency stop push button.(ix)Provn of 2 Nos 11 Watts LED lamp fitting of approved Make incl wiring inside canopy with single switch controlled.(x)Fuel gauge to be provided with the neck of fuel tank.(xi) Tools as per manufacturers with the box.(xii)Invents of suitable company be manufacture.(xiii) The acoustic enclosure parts shall be of powder coated after pre treatment process. (xiv)The coated rate to be includednecessary civil work for reqd alteration in existing DG plateform complete. |
| 42 | Supplyinstallation testing and commissioning of silent Diesel Engine driven , generating set 415 volts, 82.5KVA /66 KW 3 phase0.8 power factor 50Hz, 1500 RPM, Liquid Cooled, With all complete all connected acessories in all respects for commissioning of the DG Set, with CPCB approved and latest MOEF guide line Accoustic enclosure IP 23,self excitedself regulated brushless AC generator installed including accoustic enclosure suitable for ambient condition at Hyderabad including AMF panel and confirming to condition under IS 4722/1460, BS 5514/2613/5000 ISO 8526/3046 with the following:- |
| 43 | Alternator - Standard design alternator, Power Rating 82.5 KVA/ 66 KW, 3 Phase 4 wire,415 Volts, 50 HZ, Power factor 0.8(lagging)Current 87 Amps,net output at site after considering derating for per site conditions at 0.8 (lagging) power factor, 1500 RPM, Cooling Liquid cooled, Aspiration Turbo charged, air cooled self regulated screen protected drip proof IP 23 enclosure brushless design with widing in pole faces, insulating class \"H\" and voltage regulation of +1% at rated voltage from no load to full load, A1 The alternator shall be conforming to BS 2613/5000 and shall be in position to generate supply with frequency regulation with in +1% tolerance. The alternator will be suitable for tropical climate and shall generally confirm to BS-2613/5000/IS-4722.Make of the Alternator : Diesel Engine : Minimum 80 BHP capacity, multi stroke, 3 Cylinder,TurboChargedDiesel Engine suitable for 82.5 KVA coupled with alternator and after considering derating as per site conditions after generating and reducing power consumed by accessories, directly coupled through flexible coupling, multi cylinder, multi stroke direct injection, cold starting 1500 RPM, as per relevant ISI/BS-5514 with an overload capacity of 10% for one hour in 12 hours continous running complete with standard accessories all as specified and required for safe handling and operation salient features of accessoires shall be as under :- KIRLOSKAR/CUMMINS/GREAVES Insulation class - \"H\" , Temperature rise class - \"H\" ,Excitation- Self excited Regulation performance - The voltage is kept constant with + 1%, manual voltage adjustment with in + 5%. ,Frequency Regulation + 1% Suitable size & suitable number of runsof UG copper cable (Control cable) from Alternator to AMF & RAW Power to AMF Panel is deemed to be include is quoted rate. |
| 44 | (i)Flywheel with housing(ii) Cooling System : Mounted radiator with fan and belts(iii)Cooling Water Pump : Centrifugal type belt driven(iv) Exhaust System : As per OEM reccommendation/specification.(v)Starting System:- Electric Self Starter with maintenance free batteries including battery charging alternative belt driven.(vi)Batteries :- 12 Volts DC electrical batteries ofsuitableAH rating, complete connected with copper cable PVC sheathed conductor multistranded leads of suitbale length from self starter to the battery terminals complete with initial charge and initial fill of electrolite all as specified and directed.(vii)Fuel tank of adequate capacity :- As per OEM norms and specifications designed for above capacity of DG Set. |
| 45 | AMF Panel : Auto Main Failure (AMF) Panel made out 14/16 Gauge CRCAsheet weather proof powder coated conforming to IS 8623 totally enclosed dust and vermin proof with front and rear openings of 415 Volts, 3 Phase, 4 wireAC 50 HZ having aluminium bus bar of capacity required to carry current at 100% load of 82.5 KVA DG Set with three phase and half neutral colour coded pre-wired with copper flexible cable, all as specified with the following accessories, control cable from Gen Set to AMF Panel. |
| 46 | Contactor of Suitable capacity 3 pole with required nos as per OEM, TP contactor for netural for both supplies Suitable capacity of MCCB, 4 Polefor both supplies CTs 150/5A for both the supplies Push buttons Indication Lamps. 2 over load + earth leakage relay Multi functional digital meter for KWH, KVA, KW, Amps, Volts, frequency, power factor etc. SMPS Battery charge 12V, with trickle and boost charging. ON/OFF Switch.Automatic/Manual Switch. Hooter. Voltage sensing relay.Six window anunciator for fault indications.Acoustic Enclosure : Enclosure is free standing floor mounted factory built and modular in construction to facilitate easy assembly at work site and will be drop over housing type. It will consist of acoustically treated panel housed in sheet metal will provide easy access for maintenance, repairs and operation. The enclosure is custom to suit conditions, with the following features :-(i) Custom built product for various equipments, with ensure the optimum performance without duration.(ii) 16SWG (1.6mm) thick CRCA sheet to be used for enclosure panel to ensure longer life against weathing action. High quality acoustic insulation materials to be used as per IS 8183 for maximum sound absoption. Acoustic layers are supported by perforated sheets.(iii)Sheet metal component of the enclosure should undergo various stages of surface treatment prior to painting which leads to be better life of the enclosure against weathering action. |
| 47 | (iv) Specialpaint treatment with pure polyster powder/epoxy to be provided for better weather resistance.(v)Well designed ventilation system to be provided to put out the heat from the chamber efficiently.(vi) For effective acoustic/weather sealinga special type weather sealing gaskets, new frame rubber gaskets to be used.(vii) The batteries should be placed inside the enclosure inside the DG Set on a suitable insulated platform.(viii)The DG set should be provided with external emergency stop push button.(ix)Provn of 2 Nos 11 Watts LED lamp fitting of approved Make incl wiring inside canopy with single switch controlled.(x)Fuel gauge to be provided with the neck of fuel tank.(xi) Tools as per manufacturers with the box.(xii)Invents of suitable company be manufacture.(xiii) The acoustic enclosure parts shall be of powder coated after pre treatment process.(xiv)The coated rate to be includednecessary civil work for reqd alteration in existing DG plateform complete. |
| 48 | Supply,installation, testing and commissioning of silent Diesel Engine driven, generating set 415 volts, 25KVA /20 KW 3 phase0.8 power factor 50Hz, 1500 RPM, Liquid Cooled, With all complete all connected acessories in all respects for commissioning of the DG Set, with CPCB approved and latest MOEF guide line Accoustic enclosure IP 23,self excitedself regulated brushless AC generator installed including accoustic enclosure suitable for ambient condition at Hyderabad including AMF panel and confirming to condition under IS 4722/1460, BS 5514/2613/5000 ISO 8526/3046 with the following:-Alternator - Standard design alternator, Power Rating 25 KVA/ 50.4 KW, 3 Phase 4 wire,415 Volts, 50 HZ, Power factor 0.8(lagging)Current 87 Amps,net output at site after considering derating for per site conditions at 0.8 (lagging) power factor, 1500 RPM, Cooling Liquid cooled, Aspiration Turbo charged, air cooled self regulated screen protected drip proof IP 23 enclosure brushless design with widing in pole faces, insulating class \"H\" and voltage regulation of +1% at rated voltage from no load to full load, A1 The alternator shall be conforming to BS 2613/5000 and shall be in position to generate supply with frequency regulation with in +1% tolerance. The alternator will be suitable for tropical climate and shall generally confirm to BS-2613/5000/IS-4722.Make of the Alternator : |
| 49 | Diesel Engine : Minimum 80 BHP capacity, multi stroke, 3 Cylinder,TurboChargedDiesel Engine suitable for 25 KVA coupled with alternator and after considering derating as per site conditions after generating and reducing power consumed by accessories, directly coupled through flexible coupling, multi cylinder, multi stroke direct injection, cold starting 1500 RPM, as per relevant ISI/BS-5514 with an overload capacity of 10% for one hour in 12 hours continous running complete with standard accessories all as specified and required for safe handling and operation salient features of accessoires shall be as under :- KIRLOSKAR/CUMMINS/GREAVES Insulation class - \"H\" , Temperature rise class - \"H\" ,Excitation- Self excited Regulation performance - The voltage is kept constant with + 1%, manual voltage adjustment with in + 5%. ,Frequency Regulation + 1% Suitable size & suitable number of runsof UG copper cable (Control cable) from Alternator to AMF & RAW Power to AMF Panel is deemed to be include is quoted rate. |
| 50 | (i)Flywheel with housing(ii) Cooling System : Mounted radiator with fan and belts(iii)Cooling Water Pump : Centrifugal type belt driven(iv) Exhaust System : As per OEM reccommendation/specification.(v)Starting System:- Electric Self Starter with maintenance free batteries including battery charging alternative belt driven.(vi)Batteries :- 12 Volts DC electrical batteries ofsuitableAH rating, complete connected with copper cable PVC sheathed conductor multistranded leads of suitbale length from self starter to the battery terminals complete with initial charge and initial fill of electrolite all as specified and directed.(vii)Fuel tank of adequate capacity :- As per OEM norms and specifications designed for above capacity of DG Set. |
| 51 | AMF Panel : Auto Main Failure (AMF) Panel made out 14/16 Gauge CRCAsheet weather proof powder coated conforming to IS 8623 totally enclosed dust and vermin proof with front and rear openings of 415 Volts, 3 Phase, 4 wireAC 50 HZ having aluminium bus bar of capacity required to carry current at 100% load of 25 KVA DG Set with three phase and half neutral colour coded pre-wired with copper flexible cable, all as specified with the following accessories, control cable from Gen Set to AMF Panel.Contactor of Suitable capacity 3 pole with required nos as per OEM, TP contactor for netural for both supplies Suitable capacity of MCCB, 4 Polefor both supplies CTs 150/5A for both the supplies Push buttons Indication Lamps. 2 over load + earth leakage relay Multi functional digital meter for KWH, KVA, KW, Amps, Volts, frequency, power factor etc. SMPS Battery charge 12V, with trickle and boost charging. ON/OFF Switch.Automatic/Manual Switch. Hooter. Voltage sensing relay.Six window anunciator for fault indications. |
| 52 | Acoustic Enclosure : Enclosure is free standing floor mounted factory built and modular in construction to facilitate easy assembly at work site and will be drop over housing type. It will consist of acoustically treated panel housed in sheet metal will provide easy access for maintenance, repairs and operation. The enclosure is custom to suit conditions, with the following features :-(i) Custom built product for various equipments, with ensure the optimum performance without duration.(ii) 16SWG (1.6mm) thick CRCA sheet to be used for enclosure panel to ensure longer life against weathing action. High quality acoustic insulation materials to be used as per IS 8183 for maximum sound absoption. Acoustic layers are supported by perforated sheets.(iii)Sheet metal component of the enclosure should undergo various stages of surface treatment prior to painting which leads to be better life of the enclosure against weathering action.(iv) Specialpaint treatment with pure polyster powder/epoxy to be provided for better weather resistance.(v)Well designed ventilation system to be provided to put out the heat from the chamber efficiently.(vi) For effective acoustic/weather sealinga special type weather sealing gaskets, new frame rubber gaskets to be used. |
| 53 | (vii) The batteries should be placed inside the enclosure inside the DG Set on a suitable insulated platform.(viii)The DG set should be provided with external emergency stop push button.(ix)Provn of 2 Nos 11 Watts LED lamp fitting of approved Make incl wiring inside canopy with single switch controlled.(x)Fuel gauge to be provided with the neck of fuel tank.(xi) Tools as per manufacturers with the box.(xii)Invents of suitable company be manufacture.(xiii) The acoustic enclosure parts shall be of powder coated after pre treatment process. (xiv)The coated rate to be includednecessary civil work for reqd alteration in existing DG plateform complete. |
| 54 | M&L for taking down, dismantling of unserviceable oldDG sets 16 KVA to 63 KVA after dismantling of all components/ cables etc tranpoting to AGE E/M store yard to a distance of upto 5 km complete all as specified and directed. |
| 55 | M&L for taking down, dismantling of unserviceableoldDG sets 110 KVA to 320 KVA after dismantling of all components/ cables etc tranpoting to AGE E/M store yard to a distance of upto 5 km complete all as specified and directed. |
| 56 | M&L for earthing complete with galvanised steel,earth plate electrode 600mmx600mmx6mm thick burried directly in ground verticaly (earth pit not less than 2.25 m belowground level ) with top edge of the plate not less than 1.5 m below normal ground level connected to galvanised iron 32 x 6 mm strip as earth lead by means of bolts, nuts, check nuts and washers of galvanised iron/steel allconnected to main switch board/main DBs/earthing test point including all necessary excavation and earth work in hard/dense soil common salt and charcoal dust mixed and packed 150mm thick all round the GI earth plate, watering pipe 20mm dia GI medium grade. GI sheet 0.63 mm thick funnel, wire gauge, 50mm thick RCC cover in PCC 1:2:4 type B1 duly reinforced with MS round bars 6mm dia @ 150mm c/c both ways and pit/chamber in PCC 1:3:6 type C1 with suitable lifting handleto cover, GI protection pipe 40mm dia light grade up to 7.5m from electrode GI pipe to be fixed with complete all as specified and directed. |
| 57 | M&L forProviding and fixing 25mmx5mm GI strip in & including 40mm dia GI pipe from earth electrode, connection with GI nuts, bolts, spring, washers, excavation and refilling etc complete all as specified and directed. |
| 58 | M&L for25mmx5mm GI strip at 0.5m below ground as earth strip including connnection/termination with GI nuts, bolts, spring, washers,etc (jointing shall be done by over laping and with 02 sets of GI nut bolt washer,spaced at 50mm) complete all as specified and directed. |